EMA and Other Dynamic Testing of a 2-Span Prestressed Concrete Floor. Tuan Nguyen, Nicholas Haritos, Emad Gad and John Wilson

Similar documents
Evaluation of footfall induced vibration in building floor

Vibration of floors and footfall analysis

GEA FOR ADVANCED STRUCTURAL DYNAMIC ANALYSIS

Dynamic investigations of the Solferino footbridge

Application of pushover analysis in estimating seismic demands for large-span spatial structure

Experimental Investigation of Reykjavik City Footbridge

Vibration response of long cable-stayed timber footbridge case study

INSTRUMENT INSTRUMENTAL ERROR (of full scale) INSTRUMENTAL RESOLUTION. Tutorial simulation. Tutorial simulation

APPLICATION OF PUSHOVER ANALYSIS ON EARTHQUAKE RESPONSE PREDICATION OF COMPLEX LARGE-SPAN STEEL STRUCTURES

PHYS 102 Quiz Problems Chapter 16 : Waves I Dr. M. F. Al-Kuhaili

Performance of single pedestrian load models in predicting dynamic behaviour of flexible aluminum footbridges

Finite Element Modeling for Prediction of Low Frequency Floor Vibrations Due to Walking. Douglas Bradley Davis

Safety Assessment of Coastal Infrastructure via Vibration Monitoring and Simplified Model

Chapter 16. Waves-I Types of Waves

Vibrations of table tennis racket composite wood blades: modeling and experiments

Equivalent SDOF Systems to Simulate MDOF System Behavior

Waves Practice Problems AP Physics In a wave, the distance traveled by a wave during one period is called:

EMPIRICAL FORMULA OF DISPERSION RELATION OF WAVES IN SEA ICE

Footbridge Response on Single Pedestrian Induced Vibration Analysis

Rudder Investigation. By Harish M

Waves Chapter Problems

Slope Bottom Tuned Liquid Dampers for Suppressing Horizontal Motion of Structures

Development of a load model for men-induced loads on stairs

MODEL OF A PERSON WALKING AS A STRUCTURE BORNE SOUND SOURCE

PHYSICS - GIANCOLI CALC 4E CH 15: WAVE MOTION.

Vibration Analysis and Test of Backup Roll in Temper Mill

The Adequacy of Pushover Analysis to Evaluate Vulnerability of Masonry Infilled Steel Frames Subjected to Bi-Directional Earthquake Loading

Dynamic response of composite caissonpiles

Dynamic Analysis of the Rotterdam Central Station Footbridge Breman, C.; Stuit, H.G.; Snijder, H.H.

PHYSICS - CLUTCH CH 16: WAVES & SOUND.

Scanning Laser Vibrometry Assessment of Sports Equipment

FLOW RATES IN A SHORT LENGTH WET (BUBBLY) SEAL AND TEST RIG RE-DESIGN

Bending Vibration Analysis of Pipes and Shafts Arranged in Fluid Filled Tubular Spaces Using FEM

Dynamic Investigation of a Suspension Timber Footbridge

Pre AP Physics: Unit 7 Vibrations, Waves, and Sound. Clear Creek High School

HUMAN INDUCED VIBRATIONS ON FOOTBRIDGES

Seismic Response of Skewed RC Box-Girder Bridges

PEDESTRIAN-INDUCED BRIDGE RESPONSE. periodic pedestrian loads SAMUEL DAVID ROGERS. A thesis submitted to the Department of Civil Engineering

Finite Element Modal Analysis of Twin Ball Screw Driving Linear Guide Feed Unit Table

Footbridge 2005 Second International Conference

An experimental study on tuned liquid damper for mitigation of structural response

AN31E Application Note

MEASUREMENT OF ACCELERATIONS AND KEEL LOADS ON CANTING KEEL RACE YACHTS

Dynamic Characteristics of the End-effector of a Drilling Robot for Aviation

Learn more at

A New Approach to Modeling Vertical Stiffness in Heel-Toe Distance Runners

VORTEX SHEDDING INDUCED VIBRATIONS OF A LIGHT MAST

Chapter 11 Waves. Waves transport energy without transporting matter. The intensity is the average power per unit area. It is measured in W/m 2.

THE TACOMA NARROWS BRIDGE FAILURE Revision A

ITTC Recommended Procedures and Guidelines

Presented to the International Technical Rescue Symposium, November Abstract

DYNAMIC RESPONSE ANALYSIS OF THE SECOND SAIKAI BRIDGE A CONCRETE FILLED TUBULAR (CFT) ARCH BRIDGE-

Special edition paper

Chapter # 08 Waves. [WAVES] Chapter # 08

Chapter 11 Waves. Waves transport energy without transporting matter. The intensity is the average power per unit area. It is measured in W/m 2.

Inertial compensation for belt acceleration in an instrumented treadmill

Full scale VIV response measurements of a drill pipe in Gulf of Mexico loop currents (OMAE )

Available online at ScienceDirect. The 2014 Conference of the International Sports Engineering Association

Developing FE-Tire Model Library for Durability and Crash Simulations

API 618 Forced Response Studies by Brian Howes, Derrick Derksen, Kelly Eberle

Harmonics and Sound Exam Review

LEAP CO 2 Laboratory CO 2 mixtures test facility

G.C.E (A/L) Examination March In collaboration with

Quantification of dynamic excitation potential of pedestrian population crossing footbridges

How Do You Swing? You should be working with new lab partners starting with this lab.

Lesson 14: Simple harmonic motion, Waves (Sections )

The Estimation Of Compressor Performance Using A Theoretical Analysis Of The Gas Flow Through the Muffler Combined With Valve Motion

The influence of structural response on ballast performance on a high speed railway

A MODEL FOR ANALYSIS OF THE IMPACT BETWEEN A TENNIS RACKET AND A BALL

Analytical model of a rope and karabiner system

Malta Survey activities

Superposition of waves on a string

Reinforced Soil Retaining Walls-Design and Construction

A Physics Based Link Model for Tree Vibrations

Vibration Related Failures of Small-Bore Attachments

Along and Across Wind Loads Acting on Tall Buildings

TLP Minimum tendon tension design and tendon down-stroke investigation

Ch16Lectures Page 1. Ch16Lectures Thursday, April 16, :22 PM

Offshore Wind Turbine monopile in 50 year storm conditions

Vibration Characteristics of Offshore Wind Turbine Tower with Caisson Foundation under Wave Excitation

Modal Analysis of Barrels for Assault Rifles

Development of Human Body Model for the Dynamic Analysis of Footbridges under Pedestrian Induced Excitation

Less Interior Squeak and Rattle Noise Using a Simu lation Driven Design Approach

[Barve, 4(7): July, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

EFFECTS OF SIDEWALL OPENINGS ON THE WIND LOADS ON PIPE-FRAMED GREENHOUSES

Displacement-based calculation method on soil-pile interaction of PHC pipe-piles

Experimental research on instability fault of high-speed aerostatic bearing-rotor system

g L Agenda Chapter 13 Problem 28 Equations of Motion for SHM: What if we have friction or drag? Driven Oscillations; Resonance 4/30/14 k m f = 1 2π

Modal Analysis of Propulsion Shafting of a 48,000 tons Bulk Carrier

DYNAMIC BEHAVIOUR AND OPTIMISATION OF FRAMES FOR ROAD AND MOUNTAIN BIKES

Users Group Conference 2018

EXPERIMENTAL MEASUREMENT OF THE WASH CHARACTERISTICS OF A FAST DISPLACEMENT CATAMARAN IN DEEP WATER

Aerodynamic Measures for the Vortex-induced Vibration of π-shape Composite Girder in Cable-stayed Bridge

Vortex Induced Line Vibration

Lab 2: Superposition of waves on a string

SYSTEM IDENTIFICATION AND RESPONSE ANALYSIS OF RC HIGH-RISE BUILDINGS UNDER SUCCESSIVE EARTHQUAKES

HURRICANE SANDY LIMITED REEVALUATION REPORT UNION BEACH, NEW JERSEY DRAFT ENGINEERING APPENDIX SUB APPENDIX D SBEACH MODELING

Statnamic Load Testing Using Water as Reaction Mass

AIRMOUNT VIBRATION ISOLATION

Seakeeping Tests (with ships) Experimental Methods in Marine Hydrodynamics Lecture in week 43

Transcription:

EMA and Other Dynamic Testing of a 2-Span Prestressed Concrete Floor Tuan Nguyen, Nicholas Haritos, Emad Gad and John Wilson

INTRODUCTION This paper discusses experimental modal analysis (EMA) using swept sine wave forcing from a shaker, heel drop tests and walking tests performed on two bays of a prestressed concrete floor of a building under construction. Modal properties Response to walking (single persons and people in pair) Calibrate FE models movement joint

INTRODUCTION Notebook PC Controlled Data Acquisition System and Signal Generator Controlled Shaker System APS400 Shaker

INTRODUCTION Adhering grid-point location plates for accelerometers on test floor View of test setup from Eastern to Western test spans (EMA testing)

MODAL TESTING WITH SHAKER Swept sine signals, frequency range 5-13 Hz over a 64 second period. Dytran seismic accelerometers, 1-5 V/g sensitivity, 128 Hz sampling rate 43 measurement points on floor Plan view of floor showing EMA test setup with measurement points

MODAL TESTING WITH SHAKER 7 test setups (each with 1 reference sensor + 6 roving sensors) 5 repeat tests in each setup averaging ALL TEST POINTS SETUP 1 SETUP 2 SETUP 3 SETUP 4 SETUP 5 SETUP 6 SETUP 7

MODAL TESTING WITH SHAKER A typical floor response to shaker excitation measured by at the reference accelerometer (near the centre of the Western bay)

MODAL TESTING WITH SHAKER To obtain the modal properties including mode shapes, natural frequencies and damping ratios; an extensive analysis of the data obtained from all 43 measurement channels was performed using the ARTeMIS experimental modal analysis program

MODAL TESTING WITH SHAKER The temporary movement joints between the two floor bays did not fully prevent the transmission of vibration from the forced bay to the other bay The damping ratio of the test floor in bare condition without fittings and services is relatively low at approximately 1.1%. As the fundamental mode had a natural frequency of 7.6 Hz, i.e. less than 9 10Hz, the floor can be considered as a low-frequency floor which may be prone to resonant vibrations induced by human activities. WHY RESONANCE? F( t) = P 4 i= 1 α sin i if p = f n f p : footstep frequency f n : floor frequency ( 2πif t + φ ) p i

HEEL DROP TEST A standard heel drop impact is created by an 86-kg person rising onto their toes with their heels about 63 mm off the floor and suddenly dropping their heels to the floor. Only simple unreferenced heel drop tests were performed on the test floor (only the floor response is measured, rather than both the floor response and the impact force).

HEEL DROP TEST Relocation of accelerometers to cover the whole test area was not made and the floor response was recorded at only some locations close to the centre of the forced bay. A Random decrement (RANDEC) analysis was used to acquire an averaged acceleration history from the measured acceleration histories. Floor response due to heel drop

HEEL DROP TEST The modal frequencies and damping ratios acquired from the simple un-instrumented heel drop test compared well with those resulted from the shaker test ( f n 7.6 Hz, ζ 1.1%) A slight non-linearity was observed in the damping ratio whereby damping values can vary slightly with different levels of vibration

WALKING TESTS The floor response to footfall was evaluated in three conditions: single persons walking, two persons attempting to walk in-phase and two persons attempting to walk out-of-phase; at a pacing rate of about 1.8 2.0 Hz along the Western test bay. The filtered floor response was mass-weighted, assuming a typical body mass of 80-kg for an adult. 0.32% g a typical test 18 repeat tests One 80-kg person walking

WALKING TESTS a typical test 12 repeat tests 0.43% g Two 80-kg persons walking in-phase 0.40% g 10 repeat tests a typical test Two 80-kg persons walking out-of-phase

WALKING TESTS Peak floor response due to walking On average, the peak acceleration due to two persons walking (either inphase or out-of-phase) was found to be about 1.43 times of that due to one person walking. Perfect synchronization was unlikely to be achieved even when the walkers attempted to deliberately walk in-phase. Although the maximum peak acceleration from the two person walking in-phase scenario was 1.28 times greater than that from the out-of-phase scenario, the average values of peak acceleration were almost the same.

FE MODELLING Two modelling features were investigated: - Continuity conditions at movement joint: ideal hinge vs partial fixity - Use of Young modulus of elasticity of concrete in dynamic analysis of floor systems. A displacement constraint was assigned to each pair of joints at the two edges of the gap slab Movement joint Band beam slab Ideal-hinge: all vertical-displacement constraints with no bending stiffness Partial-fixity: some vertical-displacement constraints were replaced by rigid-body constraints which allows for the transmission of bending moment

FE MODELLING The mode shapes resultant from the FE models with partial fixity are more consistent with the measured mode shapes. The mode shapes acquired from the models with ideal hinges do not show a considerable transmission of vibration between the two bays, which is somewhat different from what was observed in the EMA testing.

FE MODELLING Floor natural frequencies (Hz) AS3600-2009: for 40 MPa concrete, E c = 32800 MPa Floor vibration guide lines (e.g. AISC DG11): E c, dyn = (1.1 1.35)E c The FE-predicted natural frequencies given in the table above were based on E c = 32800 MPa and E c,dyn = 44000MPa

FE MODELLING FLOOR RESPONSE TO SINGLE PERSONS WALKING (using FE model with partial fixity and concrete dynamic modulus E c,dyn ) a peak = 0.20% g a peak = 0.42% g a peak = 0.39% g 1.8 Hz pacing rate 1.88 Hz pacing rate 2.15 Hz pacing rate ARBITRARY NORMAL PACING RATE NORMAL PACING RATE WHOSE 4 TH HARMONIC MATCHES FLOOR FIRST FREQUENCY (7.53 Hz) FAST PACING RATE WHOSE 4 TH HARMONIC MATCHES FLOOR SECOND FREQUENCY (8.58 Hz)

CONCLUDING REMARKS Whilst sophisticated modal testing with shaker excitations and accelerometer relocation can provide valuable information about the floor modal properties including the mode shapes, adoption of a much simpler heel drop test requiring only one or a few response measurement points can be very instructive. Whilst most current guidelines provide calculation methods for floors subjected to single persons walking, an opportunity to investigate people walking in pairs has been presented in this paper. People walking in pairs were found to increase the footfall response due to single persons by a factor of about 1.43 An FE model that accounts for an increase in the concrete modulus of elasticity and the presence of partial bending stiffness at the movement joint appears to agree well with measurements.