Installation and maintenance of twin 45kg LPG cylinder systems

Similar documents
Types 749B and R130 Changeover Manifolds

First Stage Regulators

About. providing superior performance and reliability. Bromic regulators are AGA or UL144 approved.

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*

REGISTRATION EXAMINATION, NOVEMBER 2017 TRADESMAN GASFITTER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

Wilkins Safety Group

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Using propane cylinders safely

Smart Water Application Technologies (SWAT) TM

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

TECHNICAL DATA Q= C. Table 1 - Specifications

Manifolds & pressure reducing sets

Pressure Regulators. Operating Instructions. Instrumentation

ACS.CoNGLP1 SAFETY ASSESSMENT CRITERIA INITIAL & RE-ASSESSMENT DOMESTIC NATURAL GAS TO LPG GENERIC

CERTIFYING GASFITTER

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

ST/SG/AC.10/C.3/2016/8. Secretariat. United Nations. Transport of gas tanks for motor vehicles. Introduction

ISO INTERNATIONAL STANDARD. Small craft Liquefied petroleum gas (LPG) systems

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

MAINTENANCE AND SAFETY OF CNG REFUELLING STATIONS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

Transport of gas tanks for motor vehicles

Thank You for Attending Today s Webinar. Today s Featured Speaker

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

LIVE STEAMERS GAS FIRING CODE OF PRACTICE GAS FIRING OF AMBSC BOILERS AUSTRALIAN ASSOCIATION OF

Vaporizer Piping Liquid Chlorine Manifolds

G96 Series BASOTROL Dual Operator Valve

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

KFI Approved. High Pressure CO2 System Technical Datasheets

NZQA registered unit standard version 1 Page 1 of 5. Meet requirements for Approved Filler Test Certificate for refrigerants

What is LPG? Released Energy in the narrowest area. Clean and sure in the practise

CAPITAL CONTROLS SERIES NXT3000

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

PRESSURE TEST PUMP OPERATING & MAINTENANCE INSTRUCTIONS. Model No: PTP100. Part No: GC01/09

User Information Sheet 013

Compiled by: B Beard. Approved by: SH Carstens. Description of requirements and procedures for compact provers to be used as verification standards.

Summary of the MRA LPG Codes of Practice

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability.

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

ENERGY BLADE 3K4. Energy Blade Installation Instructions

Handling and Storage of Gases

CERTIFYING GASFITTER

LPG TANK INFORMATION An energy company that puts

Model: AT-1000 L.P.G. FREEZE VALVE

Installation & Maintenance Manual. Economy Manifold

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

TECHNICAL DATA. Table 1 - Specifications

BCGA GUIDANCE NOTE 17

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

Chlorine Supply Containers And Piping

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Compressed Gas Safety Standard

R600 and HSRL Series Instruction Manual

ARCHIVED. Compliance Document for New Zealand Building Code Clause G11 Gas as an Energy Source. Prepared by the Department of Building and Housing

R122H, R222, R232A, and R232E Series Instruction Manual

TRADESMAN DRAINLAYER

INSPECTION, TESTING AND CERTIFICATION OF GASFITTING WORK DONE UNDER SUPERVISION

OPERATING INSTRUCTIONS AND PARTS LIST AUTOMATIC FILLING MACHINE DE-401-GB-AUTO

Oxygen Usage Best Practice Guide

1 Exam Prep. Tabs and Highlights

LP GAS PRODUCTS HIGH QUALITY GAS PRODUCTS SINCE 1957

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Natural Gas to L.P. Gas Conversion Kit

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device

Types S100K and S102K Pressure Regulators

CRAFTSMAN EXAMINATION, NOVEMBER 2007 GASFITTING ANSWER SCHEDULE

Network Regulator Maintenance Operatives LS (Non-Accredited)

GW DRY PIPE VALVE INSTALLATION & OPERATION 100mm (4 ) 150mm (6 )

Your safety and the safety of others are very important.

OPERATING INSTRUCTIONS AND OWNER S MANUAL READ AND FOLLOW ALL INSTRUCTIONS

627 Series Pressure Reducing Regulators

Needle valve. Contents. User s Manual. (1) Be sure to read the following warranty clauses of our product 1. (2) General operating instructions 2

SERVICE MANUAL MODEL BA200AMST-S1 BREATHING AIR PANEL

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

BGA158 Series CE Approved Class A Shutoff Gas Valve

Bermad Model:

BRITISH STANDARD BS 341-4: Transportable gas container valves. Part 4: Pressure relief devices ICS

Transport of gas tanks for motor vehicles

SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

RTG 25. Introduction

AS/NZS 1596:2014. The storage and handling of LP Gas AS/NZS 1596:2014. Australian/New Zealand Standard. Superseding AS/NZS 1596:2008

Bermad Pressure Reducing. Model: 42T

Model: AT-1000 L.P.G. FREEZE VALVE

OPERATING INSTRUCTIONS

Draft. Not yet Approved

CERTIFYING GASFITTER

GUIDELINES. Systems. Pressure

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Natural Gas to L.P. Gas Conversion Kit

SERVICE MANUAL MODEL BA020AMST BREATHING AIR PANEL

Installation Instructions

Drum / cylinder handling

CASH VALVE TYPE KP BACK PRESSURE VALVES

FIRE PROTECTION PRODUCTS

Transcription:

LPG Association Code of Practice LPGA COP No 2 Installation and maintenance of twin 45kg LPG cylinder systems July 2014 LPG Association of New Zealand Inc PO Box 1776 Wellington New Zealand

2 Foreword The performance of LPG cylinder installations is a critical element in ensuring that gas is supplied to appliances reliably and safely. This Code of Practice has been compiled with advice and input from across the industry in New Zealand and from international authorities. The Code of Practice captures the latest knowledge and design features gained from operating experience and investigative work conducted by the LPG Association. The purpose of this Code of Practice is to: Assist with the reduction of phthalates from LPG systems. Assist with the removal of condensate at the regulator. Assist with the selection of suitable equipment and fittings. Assist with recommendations on equipment maintenance. It should be read in conjunction with AS/NZS 5601.1. It is intended that gas fitters will use this Code as a best practice guide for the installation and maintenance of domestic and commercial twin pack installations.

3 Table of Contents Foreword...2 Section 1: Scope, Interpretation, Definition and General...5 1.1 Scope...5 1.2 Definitions...5 Section 2: Selection criteria for LPG Cylinders, Pigtails, Change-over valves and Regulators...7 2.1 Cylinders...7 2.2 Pigtails...7 2.3 Changeover Valves...7 2.4 Regulators...7 2.5 Condensate Trap...8 2.6 Non-return valves...8 2.7 Excess flow valves...8 Section 3: Location of Cylinders...9 3.1 Location of Cylinders...9 3.2 Requirements for cylinder deliveries...9 Section 4: Location and Installation of Cylinders...10 4.7 Clearances around Cylinder...10 4.8 Cylinder Safety Valve Discharge...10 4.9 Regulators...10 4.10 Test Points...10

4 Section 5: Maintenance of twin LPG Cylinder Installations...11 5.1 Cylinders... 11 5.2 Flexible Pigtails manufactured to AS/NZS 1869... 11 5.3 Change-over Valves... 11 5.4 First Stage Regulators... 11 5.5 Second Stage Regulators... 11 5.6 Condensate Traps... 11

5 Section 1: Scope, Interpretation, Definition and General 1.1 Scope This Code of Practice sets out the requirements for installation and servicing of domestic and commercial 45kg twin cylinder LPG installations. 1.2 Definitions For the purposes of this code the following definitions shall apply: Accessible: Access can be gained without hazard or undue difficulty for inspection, repairs, testing, maintenance, renewal or operational purposes. Breather vent: An orifice or opening designed to permit atmospheric pressure to act on the diaphragm of a regulator. Condensate: The liquid that separates from the gas down stream of any regulator due to the reduction in temperature resulting from pressure reduction. Condensate trap (also known as a drip leg or tailpipe): A device installed in a gas line to trap the condensate liquid. EPA: Meaning the Environmental Protection Authority. Gasfitting: Has the same meaning as in the Plumbers, Gasfitters and Drainlayers Act 2006. Gas load: The total gas consumption of all downstream appliances. Gas Pressure Regulator: A device that automatically regulates the outlet pressure of the gas passing through it to a predetermined value. Automatic Change-Over Regulator: Combination valve / first stage gas pressure regulator, fitted to a LPG multiple-cylinder installation which will automatically change over from a cylinder in use to a reserve cylinder at a predetermined pressure. May be included in a one piece automatic changeover valve assembly comprised of automatic changeover valve, first and second stage regulators and may incorporate pressure relief or over pressure shut off capability.

6 HSNO: Hazardous Substances and New Organisms Act 1996. LAB number: Number allocated by EPA when a cylinder is approved. Lock-up pressure: The maximum pressure in an installation when the regulator has closed and all appliances are shut down. Non Return Valve: A valve designed to operate automatically to prevent reversal flow in a pipe or fitting. Phthalates: Plasticisers mainly DOP (DiOctyl Phthalates) predominantly found in hose inner liners. POL fitting (Prest-O-Lite): The common name given for a standard union with left hand thread, used for connection to a 45 Kg cylinder. Pigtail: A short length of flexible tube or copper pipe completed with end couplings. Use for connecting the cylinder to the manifold or the changeover valve. Pressure: Pressure as measured above atmospheric pressure, also called gauge pressure. Twin cylinder installation: A cylinder installation where the cylinders are connected separately to the system. Each cylinder is connected to a change over valve that can be operated manually or automatically, to change over the cylinder which is supplying LPG to the installation. Connection may be made using flexible rubber or copper pigtails, or pipe fittings. REFERENCED DOCUMENTS AS/NZS 5601.1 AS/NZS 1596 AS/NZS 1869 UL144 Gas Installations The storage and handling of LPG Hose and hose assemblies for liquefied petroleum gases (LP Gas), natural gas and town gas LP- Gas regulators UL252, AGA 205 Compressed gas regulators NF M 88-769 1977 Commercial Propane Installations In Movable Containers Coupling And Automatic Changeover Device Construction Operation Tests

7 Section 2: Selection criteria for LPG Cylinders, Pigtails, Change-over valves and Regulators 2.1 Cylinders (c) All cylinders must comply with the requirements of the EPA s Guide to Gas Cylinders. Cylinders filled for use in LPG installations must be stamped with an LAB or LABSP number and a current test date. Consideration should be given to ensure that the demand of the appliances to be connected to the system can be supplied by a 45kg cylinder. As a guide on NZ LPG mix, a 45kg cylinder is capable of supplying a duty cycle of 1kg/50MJ over the period of 1 hour. The instantaneous demand can exceed this rate for short periods. Table J2 of As/NZS 5601.1 provides more guidance on withdrawal rates for propane. 2.2 Pigtails Refer to clause 4.6 of AS/NZS 5601.1 2.3 Changeover Valves Changeover valves can be manual or automatic, and may include a non-return valve on each pigtail connection. The valve must comply with the requirements of the Authority. Changeover valves may be comprised of a first & second stage regulator system in a single body, or as a combination of separate component items. 2.4 Regulators Regulators shall comply with the requirements of the EPA Guide to Gas Cylinders. Regulators shall comply with the requirements of section J6 of AS/NZS 5601. (c) (d) Consideration must be given to the total expected gas load when sizing the regulator. A single stage regulator or the first stage of a mult-stage regulator shall be located so that the length of the piping that is subject to cylinder pressure is as short as practicable.

8 2.5 Condensate Trap Condensate traps remove condensate and prevent transfer downstream of most condensates present in the LPG. A condensate trap should be installed between the first and second stage regulator if they are separate items. If the regulator is the combined type then a condensate trap should be installed immediately after the regulator. Condensate traps must have a vertical limb in a direct line to the first stage regulator and be of a minimum volume of V=N X 5.5 where: V The volume of the vertical limb in Milliliters (ml) N The number of 45kg cylinders. The trap must have a plug or other means of removing the condensate. Examples of length of condensate trap tube for 10 and 13 mm pipe and various numbers of cylinders. Number of 45 kg cylinders Length 10 mm pipe Length 13 mm pipe Two 140 mm 88 mm Four 280 mm 180 mm Six 370 mm 240 mm Eight 560 mm 350 mm 2.6 Non-return valves Where the regulator does not prevent LPG flowing across the changeover system, a non-return valve shall be fitted either in each pigtail connection of the changeover valve, or as part of each pigtail. 2.7 Excess flow valves For flexible pigtails manufactured to AS/NZS 1869 an appropriately sized excess flow valve must be fitted immediately after the outlet of each cylinder valve. The excess flow valve can be an integral part of the pigtail assembly.

9 Section 3: Location of Cylinders 3.1 Location of Cylinders Refer to section J3 of AS/NZS 5601.1 3.2 Requirements for cylinder deliveries Cylinder installations should be located such that the delivery of gas can be made safely by one person without excessive manual handling or risk to customers property. In situations where the following conditions cannot be satisfied, other options such as locating the cylinders remotely and piping to the installation should be considered. (c) (d) (e) (f) (g) (h) (i) (j) (k) Cylinder installation must be designed to be capable of accommodating the size of cylinder intended for use, for either exchange or insitu fill applications. A minimum distance of 600mm should be provided between front of the cylinder installation and other structures to allow adequate access for the cylinder delivery to be made. The cylinder compound should be accessible by cylinder trolley. Paths should have a minimum width of 600mm. Steps should have a minimum of 2: 1 tread depth to tread rise. Maximum tread rise should be 125mm. Steps should not exceed 1.5m total rise. Paths should not exceed 20 deg gradients. Total distance from cylinder delivery truck parking area and cylinder installation should not exceed 75m. It must be possible to legally and safely park the truck while making the delivery. Access route should be firm and compact with adequate grip even in wet conditions. The access route should not be over delicate or decorative surfaces such as terracotta.

10 Section 4: Location and Installation of Cylinders Refer to section J4 of AS/NZS 5601.1. 4.7 Clearances around Cylinder Refer to section J5 of AS/NZS 5601.1 4.8 Cylinder Safety Valve Discharge Refer to section J6 of AS/NZS 5601.1 4.9 Regulators Refer to section J6 of AS/NZS 5601.1 4.10 Test Points Refer to section J6 of AS/NZS 5601.1

11 Section 5: Maintenance of twin LPG Cylinder Installations 5.1 Cylinders Cylinders should not be filled unless they have been tested and certified within the last ten years. 5.2 Flexible Pigtails manufactured to AS/NZS 1869 (c) Pigtails should be inspected visually for cracks and deterioration every time the cylinder is exchanged or filled. Pigtail connections should be checked with a soapy solution every time the cylinder is changed or filled. Pigtails should be replaced six years from the date of manufacture. 5.3 Change-over Valves Changeover valves should be checked for correct operation in accordance with manufacturers recommendations or in the absence of any recommendation, at least every ten years. 5.4 First Stage Regulators The first stage regulator to be checked for correct operation in accordance with the manufacturers recommendations, or in the absence of any recommendation at least every ten years. The condensate trap to be drained by removing the drain plug provided) at intervals not exceeding two years, and at every visit of the Gas fitter. 5.5 Second Stage Regulators The second stage regulator to be checked for correct operation in accordance with the manufacturers recommendations, or in the absence of any recommendation, at least every ten years. The rubber diaphragm and rubber seat must be inspected for deterioration and replaced if necessary. 5.6 Condensate Traps Condensate traps should be emptied whenever any work is carried out on the installation and at least every 2 years. NOTE For the quantities of residue expected to be found in the condensate traps, between 2 to 3 ml maximum, use disposable gloves when emptying the residue into absorbent material. The used absorbent material and the gloves can then be disposed of in general waste.