Inert Air (N2) Systems Manual

Similar documents
Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series

OPERATION MANUAL NTF-15

OPERATION MANUAL NTF-60 Plus

NGP-250/500 Nitrogen Generator Quick Start Guide

Tri-Tech Medical Inc.

Best Practice Guide, Servomex 2700

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS

Installation Instructions for NP100 Series Nitrogen Control Panels

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

Valve Proving System VDK 200 A S06*

SPECIFICATIONS ATTENTION

Pressure Regulators. Operating Instructions. Instrumentation

TECHNICAL DATA. Q = C v P S

CAPITAL CONTROLS SERIES NXT3000

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS

TECHNICAL DATA. Q = C v P S

Valve Proving System VDK 200 A S02

Pressure Differential Automatic Manifold For LPG. PDH1000 Series. LPG Installation & Operations Instructions

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel

MEDICAL EQUIPMENT CATALOG

ECS Protector Nitrogen Inerting Vent (PAV-WN)

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

S & M Water Consultants

TECHNICAL INFORMATION

TECHNICAL DATA. Q = C v P S

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

GM Series Dual-Block Multi-Function Gas Control Valves

TEST BENCH FOR SAFETY VALVES

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide

Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability.

BUBBLER CONTROL SYSTEM

Tank Blanketing Pressure Regulators RHPS Series

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

DESIGN DATA. Dry 105a. September 5, 2008

APPS-160 Gen 2 User Manual

ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E)

Installation & Maintenance Manual. Economy Manifold

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

OPERATING INSTRUCTIONS

TECHNICAL DATA. Q= Cv S

553 Series.

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S

Installation & Operating Instructions for Genesys Analog Series Manifolds

Operation Manual. Diaphragm Sensed Gas Pressure Regulators

Operator: Save these instructions for future use!

Types 749B and R130 Changeover Manifolds

Exhibit 4. Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N)

N2 Blanketing Valve DST100 / DST200 TYPE INSTRUCTION MANUAL CONTENTS K.S.P.C. General Description Operation. Installation Maintenance

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction.

Unimatic II Manifolds for Oxygen, Nitrous Oxide & Nitrogen Service Manual

Installation & Operating Instructions for Genesys Analog Series Manifolds

Data Sheet Issue A

Pressure on Demand. Air Pressure Amplifiers

Purge Star & Ring Purge Systems

Installing a Probe. Typical Installation

Distribution Transformer Instruction Manual

R E D I C O N T R O L S

Model 10E Enviro-Line Environmental Pressurization System Installation & Operation Manual

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

TECHNICAL DATA CAUTION

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

Hi-Force Limited Prospect Way Daventry Northants NN11 8PL United Kingdom Tel: +44(0) : Fax: +44(0) : Website:

Oxford Instruments Plasma Technology. PlasmaPro NGP80. Installation Data Sheet. Original Instructions.

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

SERIES 10. Pilot Operated Tank Blanketing Valve, 2" PROTECTOSEAL.

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

Tank Blanketing. Application Jordan Valve Product Offering Competition

O.K. Safety first CDN USA. Table of Contents. Approvals. Attention IFGC CSA UL ANSI NFPA

Nitrogen Tyre Inflator Owner s Manual

System Pressure Manager Standard & System Pressure Manager Plus

Information Sheet. About this information sheet. Floor and wall loadings. Attachment of process module to floor. PlasmaPro Estrelas100

Hydraulic Reliability & Preventive Maintenance Report

HP/UHP Spring-Loaded Regulator

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

TotalPac X Single interlock Preaction system Electric release

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

G96 Series BASOTROL Dual Operator Valve

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

Anti-flood device Model B-1

ACCU-PULSE Installation and Operation Instructions

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

TECHNICAL DATA OBSOLETE

TECHNICAL DATA. Q = C v P S

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

Storage Systems and Accessories

ACV-10 Automatic Control Valve

Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve

NTF-230 OPERATION MANUAL

1200B2 Series Service Regulators. Instruction Manual

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual

Automatic Valve Proving Control

Transcription:

INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT.

GENERAL INFORMATION Positive pressure nitrogen gas pressurizing systems protect transformer oil in the main tank from exposure to both oxidation and moisture, thereby maintaining the highest quality insulating oil. DESCRIPTION The nitrogen regulation system (see Figure 1 on page 4) consists of a nitrogen gas supply cylinder with its own control valve, a supply pressure gauge, a three stage pressure reducing assembly and the piping and valves which control the flow of gas to and from the tank. The system includes electrical connection points for low gas supply, high tank pressure and low tank pressure alarms. Provisions for pressure transmitters for bottle supply and tank pressures are included as well. When the nitrogen regulation system is correctly set-up and operating, it will maintain transformer tank pressure at 0.5 psi minimum and 5.0 psi maximum. During periods of transformer cooling, the overall tank pressure will decrease. If the tank pressure drops below 0.5 psi, nitrogen gas flows from the bottle supply cylinder through the reducing valve assembly and into the tank until the 0.5 psi pressure is restored. During periods of transformer heating, tank pressure will increase. If tank pressure exceeds 5.0 psi, the regulator assembly will vent the excess nitrogen to atmosphere to prevent tank damage or PRD operation. The 3 rd stage regulator supplying nitrogen to the transformer tank has an adjustable range of 0 2 psi and is set to a slight positive pressure (0.5 psi standard) at the factory. A 0.5 psi nitrogen supply pressure and a relief valve breaking pressure of 5.0 psi are chosen in order to provide a 4.5 psi tank regulation band. Increasing the nitrogen supply pressure will decrease the regulation band for the transformer tank and may increase nitrogen use during periods of heavy thermal cycling. Adjustable alarm contacts are provided to indicate max/min tank pressures selected by user. Typical alarm points would be set just outside of the selected regulation band. For example, user alarms are normally recommended to be set for 0.2 psi and 5.5 psi for a 0.5 to 5.0 regulation band. Nitrogen regulation systems are available in several configurations, as shown in Figures 2, 3 and 4 on pages 5 and 6. INSTALLATION The N2 system is easy to install and maintain. The following should be noted during installation: Mount the cabinet so that the bottom is at least 4 above grade. Use 3/8 diameter mounting hardware to mount the cabinet securely to the side of the transformer. Use sealed fittings for the electrical connections to avoid water accumulation inside the enclosure. Electrical connection points are provided on either side of the box and are sized for standard 1/2 conduit fittings. Ensure piping to the transformer is clean and free from corrosion or rust. The N2 system is designed to accept 1/4 NPT female connections for both the transformer tank inlet (left side of cabinet) and outlet (right side of cabinet) points. Valves located inside the cabinet walls allow the user to control the inlet and outlet flow for the tank piping. 2

SETTINGS SUMMARY N2 SYSTEM SETTINGS SUMMARY BYPASS REGULATOR PRESSURE STANDARD TANK REGULATION PRESS. PRESSURE RELIEF SET POINT VACUUM RELIEF SET POINT +7.0 PSI +0.5 PSI +5.0 PSI -3.0 PSI HIGH PRESSURE ALARM LOW PRESSURE ALARM EMPTY CYLINDER ALARM +5.5 PSI +0.2 PSI +200.0 PSI 3

TERMINAL BLOCK HIGH & LOW TANK PRESSURE ALARM ADJUSTMENT POINTS (TWO) ALARM ENABLE SWITCH 60 WATT PTC HEATER LOCATION (OPTIONAL) COMPOUND PRESSURE GAUGE W / ALARMS PRESSURE VACUUM BLEEDER NITROGEN SUPPLY POINT BYPASS VALVE THIRD STAGE REGULATOR TWO STAGE REGULATOR LOW NITROGEN CYLINDER PRESSURE GAUGE LOW NITROGEN CYLINDER PRESSURE SWITCH (PRESET TO 200 PSIG AT FACTORY) NITROGEN CYLINDER CONNECTION Figure 1 Regulator Panel Assembly 4

SYSTEM CONFIGURATIONS N2 SUPPLY PORT N2 RETURN PORT Figure 2 N2-0 System (External Bottle) N2 SUPPLY PORT Figure 3 N2-1 System (One Internal Bottle) 5

SYSTEM CONFIGURATIONS (continued) N2 RETURN PORT N2 SUPPLY PORT N2 SUPPLY PORT Figure 4 N2-2 System (Two Internal Bottles) CAUTON For ALL system configurations (Figures 2, 3 and 4), verify weekly during first 4 weeks and every 90 days thereafter that the oxygen content remains below one percent (1%). An increase in oxygen content indicates that purging of the tank is required (see page 9 under Tank Purging ). 6

TANK PRESSURE ALARM SETTINGS The compound pressure gauge monitors the gas pressure in the tank (see Figure 1 on page 4 for location of this gauge).the gauge is graduated from a negative 15.0 psi to a positive 15.0 psi ( 15.0 psi to +15.0 psi) and is equipped with two sets of adjustable alarm contacts. Alarm contacts are shipped with these alarms at 0. Upon receipt of the unit, these alarm points must be adjusted outside of the normal regulation band. Typical settings would be 0.2 psi and 5.5 psi. ELECTRICAL CONTACTS NOTE: ALL CONTACTS IN THE DIAGRAM ARE SHOWN WITH THE SYSTEM DE-ENERGIZED AT ATMOSPHERIC PRESSURE SW#1 TRANSFORMER TANK PRESSURE ALARMS CONTACT RED-WHT RECOMMENDED FACTORY SETTING TO CLOSE AT A PRESSURE OF 0.2 PSIG OR BELOW SENDING AN ALARM, IF MONITORED CONTACT BLK-WHT RECOMMENDED FACTORY SETTING TO CLOSE AT A PRESSURE OF 5.5 PSIG OR ABOVE SENDING AN ALARM, IF MONITORED SW#2, LOW NITROGEN STORAGE ALARM CONTACT BLU-BLK NORMALLY CLOSED SET TO OPEN AT 200 PSIG OR HIGHER CONTACT RED-BLK NORMALLY OPEN SET TO CLOSE AT 200 PSIG OR HIGHER Figure 5 Typical Alarm Connections for Pressure Gauge (PG1) and Bottle Switch (PS1) NOTE: PG1 switch contacts shown are in deactivated state. Contacts are open when tank pressure is between the recommended settings of 0.2 and 5.5 psi. PS1 contacts are shown in deactivated state (zero bottle pressure, factory set alarm is 200 PSIG). COMPOUND PRESSURE GAUGE IS RATED 1A, 125 VAC; 2A, 30V AC/DC. The Low Bottle Alarm Enable Switch is used during bottle changes. See N2 bottle change procedure on page 10. 7

HEATER POWER CONNECTIONS Heaters for the N2 systems are the Positive Temperature Coefficient (PTC) self-regulating type. Heater power requirements are 120V AC (50 60 Hz) and should be powered with a standard 20A feed. N2-0 systems use a standard 60 watt radiant heater type while the N2-1 and N2-2 systems use a 200 watt forced convection type heater. A terminal block is provided for easy customer power termination (see Figure 6 below). Figure 6 Typical Power Connections for N2 System Heaters 8

OPERATION Tank Purging The nitrogen gas pressurizing system may be used to purge transformer tanks of contaminated gas or air. During purging, gas does not flow through the 3rd stage pressure regulator. Instead, the gas flows from the 2nd stage regulator through a bypass line directly to the tank inlet pipe. NOTE: During bypass operation, the pressure-vacuum bleeder device may operate when feed nitrogen to static pressure is in excess of 5 psi. To Purge the Tank 1) Open the transformer outlet purge valve. 2) Turn the By-Pass-Reg. to By-Pass position for purging. This increases pressure going into the transformer from 0.5 to 7 psi. When Purging Is Completed 1. Return the By-Pass-Reg. valve to Reg. position. 2. Close the transformer outlet purge valve. Figure 7 By-Pass Regulation Valve THREE STAGE PRESSURE REDUCER ADJUSTMENTS The three-stage pressure reducer assembly regulates the flow of gas from the supply cylinder to the transformer tank. Stage one reduces the pressure of the gas flowing from the supply cylinder from 2200 to 100 psi. The regulator at stage two reduces the pressure of the gas flowing from 100 to 7 psi (see Figure 1 on page 4). The third stage reduces the pressure of the gas flowing from 7 to 0.5 psi (adjustable) and controls the flow of gas to the tank, admitting gas into the tank whenever the tank pressure drops below 0.5 psi. The third stage also includes a pressure vacuum device, which opens if tank pressure rises beyond 5.0 psi or a vacuum below 3.0 psi. P-V adjustable range is 3 12 psig. The three stages are factory set. 9

MAINTENANCE Inert air systems are shipped with the system tested and fully operational. To make certain that all components are functioning properly, the system should be checked according to the following schedule: First Week Check daily (minimum) Second through Fourth Week Check once per week (minimum) After Fourth Week Check as required by utility maintenance program and record with dates and times noted. Readings showing consistency indicate the equipment is operating properly. Parameters to be checked include supply cylinder pressure, transformer tank pressure, transformer oil temperature and ambient temperature. Nitrogen Gas Cylinder Replacement The cylinder that should be used is a standard, commercially available, 244 cu. ft. nitrogen gas cylinder pressurized to 2000 psi. Replacement cylinders should meet all required pressure vessel specifications and be filled with oil pumped nitrogen or nitrogen with a certified moisture content of less than 0.03 percent by weight. The impurity content must be less than 7.5 parts per million. Nitrogen consumption is dependent on transformer load variations and on the condition of the gas pressurizing equipment. Cylinder must be replaced when the supply pressure gauge reads 200 psi or below. (The factory set point for the Low Bottle Alarm is 200 PSIG) To Replace the Cylinder 1) Close transformer inlet valve. 2) Turn the Low Bottle Alarm Enable Switch to the OFF position. 3) Close the supply cylinder shutoff valve. 4) Release the union connection and remove the empty cylinder. 5) Position the replacement cylinder and make the connection. Do not tighten more than finger tight. 6) Open the shut-off valve on the replacement cylinder very slightly. Allow escaping gas to leak past the loose union connection and blow away any loose dirt, and then tighten the connection with a wrench until leakage stops. 7) Open transformer inlet valve. 8) Turn the Low Bottle Alarm Enable Switch to the ON Position. REPLACEMENT PARTS AND SERVICE Please contact us at 800-338-5526 for replacement parts and/or service. Or visit us online at www.waukeshacomponents.com. 10