Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

Similar documents
64 Series Pressure Reducing Regulators

1805 Series Relief Valves

1301 Series High-Pressure Regulators

1305 Series Pressure Reducing Regulators

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

MEGR-1912 Instruction Manual

61 Series Pilots for Pilot-Operated Pressure Reducing Regulators

1805 Series Relief Valves

Type R622 Pressure Reducing Regulator

Types S100K and S102K Pressure Regulators

Types 749B and R130 Changeover Manifolds

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

Type EZH Relief or Backpressure Regulator

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators

MEGR-1627 Instruction Manual

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

T208VR Series Tank Blanketing Vacuum Regulator

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

61 Series Pilots for Pilot-Operated Pressure Reducing Regulators

Type CT88 Backpressure Regulator

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

630 Series Regulators and Relief Valves

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

Type FEQ Slam-Shut Valve

CP200 Series Commercial / Industrial Pressure- Loaded Pressure Reducing Regulator

Y692VB Series Vacuum Breaker

T208 Series Tank Blanketing Vapor Recovery Regulators

627 Series Pressure Reducing Regulators

Types 95L and 95H Pressure Regulators

Type ACE95jr Tank Blanketing Valve

PRO-50 Instrument Supply Regulator

Types 627W and 627WH Direct-Operated Pressure Reducing Liquid Regulators

Type EZL Pressure Reducing Regulator for Low Differential Pressure Applications

Type HSR Pressure Reducing Regulator for Residential, Commercial or Industrial Applications

Type 92S Pilot-Operated Steam Regulator

299H Series Pressure Reducing Regulators

R122H, R222, R232A, and R232E Series Instruction Manual

1301 Series High-Pressure Regulators

Type 1190 Low-Pressure Gas Blanketing Regulator

R600 and HSRL Series Instruction Manual

299H Series Pressure Reducing Regulators

OPERATING AND MAINTENANCE MANUAL

V DGX Series. Direct-Operated Regulators Manual D103834X012

RB Series Regulating System

299H Series Pressure Reducing Regulators

Fisher DVI Desuperheater Venturi Inline

Types ACE95 and ACE95Sr Tank Blanketing Valves

INJECTION ODORIZING SYSTEMS : DOSAODOR TYPE

Types ACE95 and ACE95Sr Tank Blanketing Valves

SLAM-SHUT VALVE. Type OSE CONTENTS INTRODUCTION CHARACTERISTICS. Scope of Manual. Material. Product Description. Connections

Type 63EG Relief Valve or Backpressure Regulator

Types S100C and S102C Pressure

Fisher Lever Lock Handlever Actuators for POSI SEAL A81 Rotary Valves

Fisher and Whisper Disk Diffusers

Fisher Lever-Lock Handlever Actuators for POSI-SEAL A81 Rotary Valves

Mooney * Noise Controller Installation, Operation, and Maintenance Manual

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

Type 99 Pressure Reducing Regulators

Types ACE95 and ACE95Sr Tank Blanketing Valves

66 Series Direct-Operated Regulators and Vacuum Service Equipment

Fisher DSA Steam-Atomized Desuperheater

Design DSA Steam-Atomized Desuperheater

Float Operated Level Controllers

Type EZL Pressure Reducing Regulator for Low Differential Pressure Applications

627 Series Pressure Reducing Regulators

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

CS800 Series Commercial / Industrial Pressure Reducing Regulators

Fisher 2625 and 2625NS Volume Boosters

ANDERSON GREENWOOD SERIES 9000 POSRV INSTALLATION AND MAINTENANCE INSTRUCTIONS

Avenger Model 33M Installation & Operation Instructions

Type ACE95jr Tank Blanketing Valve

CS200 Series Commercial / Industrial Pressure Reducing Regulators

Anti-flood device Model B-1

VS100 Series Slam-Shut Device

ERNG-X TESCOM Product Manual

1200B2 Series Service Regulators. Instruction Manual

PRESSURE REGULATORS. Type B/240. Process Management TM

V DFX Series. Direct-Operated Tank Blanketing Regulator Manual D103808X012

Type 4660 High-Low Pressure Pilot

Pressure Reducing Regulator Manual

RESIDENTIAL REGULATORS

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

INSTRUCTION MANUAL. CVS P37 LP Gas Reducing Regulator

S300 Series. Valve Link. Features. Fisher Controls

Type 299 Pressure Reducing Regulators

English. Safety Instructions Form /2007 WARNING. All Products. How to Get Safe-Use Guides. Inspection and Maintenance Schedules

R600 and HSRL Series Instruction Manual

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER FILTER DRYER

INSTRUCTIONS FOR MODEL SSC LOW DELIVERY PRESSURE GAS REGULATORS

Speed control assembly model A-1

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

TECHNICAL DATA CAUTION

Pressure Regulators. Operating Instructions. Instrumentation

TECHNICAL DATA. Page 1 of 12

Transcription:

Instruction Manual D100343X012 Type 1367 November 2017 Type 1367 High-Pressure Instrument Supply System with Overpressure Protection TYPE 252 FILTER 2ND-STAGE TYPE 67CF FILTER-STYLE REGULATOR INLET TYPE H800 RELIEF VALVE 1ST-STAGE TYPE 1301F REGULATOR W8649 Figure 1. Type 1367 High-Pressure Instrument Supply System! Warning Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion, fire and/or chemical contamination causing property damage and personal injury or death. Fisher regulators must be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies Inc. instructions. If the regulator vents gas or a leak develops in the system, service to the unit may be required. Failure to correct trouble could result in a hazardous condition. Installation, operation and maintenance procedures performed by unqualified personnel may result in improper adjustment and unsafe operation. Either condition may result in equipment damage or personal injury. Use qualified personnel when installing, operating and maintaining the Type 1367 regulator.

Specifications The Specifications table lists general Type 1367 instrument supply system specifications, while a nameplate wired to one of the pipe nipples gives the maximum inlet pressure and date of manufacture. Connection Size Inlet and Outlet: 1/4 NPT Type H800 Vent: 1/2 NPT with removable screen Maximum Inlet Pressure (1) 2000 psig / 138 bar Fixed Relief Setting of Type H120 Relief Valve 150 psig / 10.3 bar Outlet (Supply) Pressure Range 5 to 90 psig / 0.34 to 6.2 bar Maximum Outlet (Supply) Pressure with Type 67CF Regulator Failed Wide-Open with: Type H800 Relief Valve Relieving: 50 psig / 3.4 bar Type H120 (Second Stage) Relief Valve Relieving: 5 psig / 0.34 bar over Type H120 set point Temperature Capabilities (1) -20 to 150 F / -29 to 66 C Approximate Weight 12 lbs / 5.4 kg 1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded. Introduction Scope of the Manual This manual provides installation information on the Type 1367 high-pressure instrument supply system. For complete adjustment, maintenance and parts information on the individual components of this system, refer to separate manuals for the Types 67CF and 1301F regulators, Type 252 filter and Type H800 relief valve. Refer to other manuals for actuator, valve body and instrument information. Note No instruction manual exists for the Type H120 relief valve, as this relief valve cannot be adjusted or repaired. Any maintenance on the Type H120 relief valve must be accomplished by replacing it as a complete unit. Product Description The Type 1367 high-pressure instrument supply system takes a pressure of up to 2000 psig / 138 bar and reduces it to a controlled pressure to be used for supplying a pneumatic instrument. This system consists of the following filters, regulators and relief valves: A Type 252 extended body filter with drain valve. A first-stage Type 1301F regulator with mounting bracket for an actuator yoke or casing. A Type H120 relief valve mounted in the side outlet of the Type 1301F regulator. A second-stage Type 67CF filter-style regulator, mounted on the Type 1301F regulator. A Type H800 or H120 relief valve nipple-mounted in the outlet of the Type 67CF regulator. Principle of Operation The Type 252 filter helps remove dirt, rust, chips, scale and moisture from the incoming high-pressure supply before it enters the Type 1301F regulator. The Type 1301F regulator is set to reduce this incoming high-pressure to 100 psig / 6.9 bar. The reduced pressure from the Type 1301F regulator is then further reduced to the required outlet (supply) pressure. The Type 67CF regulator is normally set between 20 to 90 psig / 1.4 to 6.2 bar. The first stage Type H120 relief valve serves to protect the Type 67CF regulator by relieving if the reduced pressure from the Type 1301F regulator exceeds 150 psig / 10.3 bar. The Type H800 or H120 relief valve serves to protect downstream equipment from overpressure by relieving if the reduced pressure from the Type 67CF regulator exceeds the relief setpoint. Air or gas flowing from one or both of the relief valves indicates that one or both of the regulators are worn or damaged and must be repaired or replaced immediately. 2

TYPE H800 TYPE 1301F TYPE 67CF TYPE 252 TYPE H120 RELIEF VALVE NOT SHOWN HIGH INLET PRESSURE ATMOSPHERIC PRESSURE INITIAL STEP-DOWN PRESSURE, 100 psig / 6.9 bar FINAL OUTLET PRESSURE, 5 TO 90 psig / 0.34 TO SS6.2 bar RELIEF PRESSURE TYPE 1301F TYPE H120 TYPE 67CF TYPE 252 FIRST STAGE TYPE H120 RELIEF VALVE NOT SHOWN HIGH INLET PRESSURE ATMOSPHERIC PRESSURE INITIAL STEP-DOWN PRESSURE, 100 psig / 6.9 bar FINAL OUTLET PRESSURE, 5 TO 90 psig / 0.34 TO 6.2 bar RELIEF PRESSURE Figure 2. Type 1367 Operational Schematic 3

Installation All key numbers mentioned in this section appear in Figure 3.! Warning Installing a Type 1367 instrument supply system where its capabilities can be exceeded or where proper operation might be impaired may cause personal injury, property damage or leakage due to bursting of pressure-containing parts or explosion of accumulated gas. To avoid such conditions: Use qualified service person to install the Type 1367 instrument supply system. Install the Type 1367 instrument supply system where it is protected from exposure to physical damage and/or corrosive substances. Install the instrument supply system where service conditions are within the unit capabilities specified in Specifications. Consult your local Sales Office if service conditions exceed Specifications capabilities. Consult local Sales Office if service conditions exceed Specifications capabilities. Impairment of proper operation includes permanently removing the Types H120 and H800 relief valves from their respective regulators and plugging the side outlet of the Type 1301F regulator. Note If the Type 1367 instrument supply system is shipped mounted on another unit, install that unit according to the appropriate instruction manuals. With an instrument supply system that is shipped separately: 1. Make sure that there is no damage to the components. 2. Mount the bracket of the Type 1301F regulator (key 2) on the actuator yoke or casing. Note If using pipe in the following steps, apply thread tape or pipe compound to the pipe threads before making the connections. 3. Install tubing or piping into the 1/4 NPT inlet connection of the Type 252 filter (key 1) so that flow is in the proper direction as indicated on the filter head. 4. Install tubing or piping from the 1/4 NPT outlet (or side) connection of the Type H800 or tee of the Type H120 relief valve (key 5) to the pneumatic instrument.! Warning An instrument supply system may vent some gas to the atmosphere. In hazardous or flammable gas service, vented gas may accumulate, causing personal injury, death or property damage due to fire or explosion. Vent a supply system in hazardous gas service to a remote, safe location away from air intakes or any hazardous location. The vent lines in both of the following steps must be protected against condensation or clogging. 5. To remotely vent gas from the 1/2 NPT vent (or bottom) connection of the Type H800 relief valve (key 5), remove the screen from the Type H800 vent. Then install the appropriate size piping or tubing into the Type H800 vent connection. The piping or tubing should vent the gas to a safe location, be as short and have as few bends as possible to minimize backpressure during relief valve operation and have a screened vent on its exhaust end. Install any remote vent piping or tubing so that the vent is protected from condensation, freezing or any substance that could clog it. 6. To remotely vent gas from the 1/4 NPT connection of the street elbow (key 7) or the pipe tee (key 10), remove the Type H120 relief valve (key 3 and/ or key 5) from the elbow or tee. Then install the appropriate size piping or tubing into the elbow. 4

The piping or tubing should vent the gas to a safe location and be as short as possible and have as few bends as possible to minimize backpressure during relief valve operation. Reinstall the Type H120 relief on the remote end of the piping or tubing installed in the elbow. Startup With installation completed and downstream equipment adjusted, slowly open the upstream and downstream block valves while using pressure gauges to monitor pressure. Adjustments Each instrument supply system is factory-set per the requirements in the order. Consult the Types 67CF and 67CFR regulators instruction manual for the procedure to adjust the Type 67CF regulator (key 4, Figure 3) anywhere within its 5 to 90 psig / 0.34 to 6.2 bar outlet pressure range. Shutdown First, close the upstream shutoff valve and then, close the downstream shutoff valve. Next, open the vent valve between the regulator and the downstream shutoff valve and open the vent valve between the regulator and the upstream shutoff valve. If vent valves are not installed, safely bleed off both inlet and outlet pressures and check that the regulator contains no pressure. Maintenance All key numbers mentioned in this section appear in Figure 3. Type 1367 instrument supply systems parts are subject to normal wear and must be inspected and replaced as necessary. The frequency of inspection and parts replacement depends on the severity of service conditions and the requirements of local, state and federal rules and regulations. The drain valves of both the Types 252 and 67CF regulators (keys 1 and 4) should be opened periodically to empty accumulated moisture. Consult the appropriate instruction manual for maintenance procedures on each of the components of the Type 1367 instrument supply system.! Warning To avoid personal injury or equipment damage from sudden release of pressure or explosion of accumulated gas, do not attempt any maintenance or disassembly without first isolating the instrument supply system and associated equipment from system pressure and relieving all internal pressure from the instrument supply system and associated equipment. To avoid personal injury or equipment damage due to impaired operation, make sure that the relief valves (keys 3 and 5) are directly or remotely installed into the appropriate outlets of the regulators (keys 2 and 4) after maintenance is completed. Parts Ordering When corresponding with your local Sales Office about this unit, include the date of manufacture from the nameplate and the type numbers and all other pertinent information from the nameplates and other identification appearing on each of the components. Specify the appropriate part number when ordering any new parts from the following list. Parts List To Provide Sour Gas Corrosion Resistance Capability (1) Key Description Part Number 1 Type 252 Filter FS252-8S (2) 2 Type 1301F Regulator For yoke mounting FS1301F-N5/M1 (2) For casing mounting FS1301F-N5/M3 (2) 3 Type H120 Relief Valve FSH120-N150 4 Type 67CF Regulator (0 to 35 psig / 0 to 2.4 bar) FS67CF-N206 (2) 5 Type H800 Relief Valve FSH800-1 (2) 6 Pipe Nipple, Plated Carbon steel (3 required) - - - - - - - - - - - 7 Street Elbow, Heat-treated steel - - - - - - - - - - - 8 Nameplate, Stainless steel (not shown) - - - - - - - - - - - 9 Wire, Monel with Lead seal (not shown) T12315T0012 Monel is a mark owned by Special Metals Corporation. 1. Detailed in NACE international standard MR0175. 2. For entire assembly. See separate manual for individual part numbers. 5

For Other Than Sour Gas Corrosion Resistance Applications With Type H800 Key Description Part Number 1 Type 252 Filter FS252-8S (2) 2 Type 1301F Regulator For yoke mounting FS1301F-2/M1 (2) For casing mounting FS1301F-2/M3 (2) 3 Type H120 Relief Valve FSH120-150 4 Type 67CF Regulator (0 to 35 psig / 0 to 2.4 bar) FS67CF-206 (2) 5 Type H800 Relief Valve FSH800-1 (2) 6 Pipe Nipple, Zinc-plated Galvanized steel (3 required) - - - - - - - - - - - 7 Street Elbow, Galvanized plated Malleable iron - - - - - - - - - - - 8 Nameplate, Stainless steel (not shown) - - - - - - - - - - - 9 Wire, Monel with Lead seal (not shown) T12315T0012 With Type H120 Key Description Part Number 1 Type 252 Filter FS252-4S 2 Type 1301F Regulator For yoke mounting FS1301F-N5/M1 (2) For casing mounting FS1301F-N5/M3 (2) 3 Type H120 Relief Valve FSH120-SS150 4 Type 67CFS Regulator (0 to 35 psig / 0 to 2.4 bar) FS67CFS-226 5 Type H120 Relief Valve FSH120-40 FSH120-50 FSH120-60 FSH120-70 FSH120-75 6 Pipe nipple, Stainless steel (3 required) - - - - - - - - - - - 7 Street Elbow, Stainless steel - - - - - - - - - - - 8 Nameplate, Stainless steel (not shown) - - - - - - - - - - - 9 Wire, Monel with lead seal (not shown) - - - - - - - - - - - 10 Pipe tee, Stainless steel - - - - - - - - - - - Monel is a mark owned by Special Metals Corporation. 2. For entire assembly. See separate manual for individual part numbers. 6

8 9 2 4 5 7 1 3 6 a7036 TYPE H120 RELIEF VALVE NOT SHOWN 8 9 4 2 7 10 1 3 6 5 FIRST STAGE TYPE H120 RELIEF VALVE NOT SHOWN Figure 3. Type 1367 Instrument Supply System Assembly 7

Webadmin.Regulators@emerson.com Fisher.com Facebook.com/EmersonAutomationSolutions LinkedIn.com/company/emerson-automation-solutions Twitter.com/emr_automation Emerson Automation Solutions Americas McKinney, Texas 75070 USA T +1 800 558 5853 +1 972 548 3574 Europe Bologna 40013, Italy T +39 051 419 0611 Asia Pacific Singapore 128461, Singapore T +65 6770 8337 Middle East and Africa Dubai, United Arab Emirates T +971 4 811 8100 D100343X012 1984, 2017 Emerson Process Management Regulator Technologies, Inc. All rights reserved. 11/17. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC, a business of Emerson Automation Solutions. The contents of this publication are presented for information purposes only, and while effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice. Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.