VA FLOWMETERS Supplementary Instructions

Similar documents
DK46 - DK800 Supplementary instructions

Supplementary Installation and Operating Instructions. Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex. Category: II 2G Ex IIC II 3G Ex IIC

VG5 Supplementary instructions

VS18/26 with PROFINET and EtherNet/IP Interface. ATEX Installation Instructions

DK48 - DK800. Quick Start. Variable area flowmeter

RTD temperature probes

OPTIBAR P 1010 C Technical Datasheet

OPERATION MANUAL PNEUMATIC VALVES

Hafner-Pneumatik presents: General information on ATEX 95 & Products for explosion hazardous environment from the Hafner range

Technical Data. Dimensions

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS

IECEx certification of Non-Electrical Ex Equipment

Temperature gauge Installation Guide

Technical Data. Dimensions

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

Type 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies

ATEX installation and service instruction

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.

(Certification N:o VTT 08 ATEX 066 or IECEx VTT )

FV Flash Vessel Installation and Maintenance Instructions

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

BETTIS RPE Series Rack and Pinion Pneumatic Actuators. Safety Guide DOC.SG.BRPE.EN Rev. 1 November 2015

Technical Data. Dimensions

Declaration of Conformity as per Directive 97/23/EC

Instruction Manual Contact Pressure Vacuum Gauge

Safety Guide DOC.SG.EF.EN Rev. 0 March EL-O-Matic F-Series Rack and Pinion Pneumatic Actuators

Magnetic level switch type MR783 Instruction Manual

VALFONTA INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL PRV44

VALFONTA INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL M2

Declaration of Conformity as per Directive 97/23/EC

Technical Data. General specifications. Rated operating distance s n 5 mm

Declaration of Conformity as per Directive 97/23/EC and Manufacturer s Declaration as per Directive 98/37/EC

Level transmitter LT 100

Technical Data. General specifications. Rated operating distance s n 2 mm

Technical Data. Dimensions

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

Type BBS-03, BBS-05, BBS-06, BBS-25

GA24. GA24 Handbook. Variable-area flowmeter. KROHNE 02/ MA GA24 R01 en

Further technical information is available on

II 2G EEx ia IIC T6. Ignition protection class

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

4/2 way Pneumatic Solenoid Valve

Electro-Pneumatic Converter YT-940 SERIES

ELECTRIC ACTUATORS for continuous underwater use

3-PIECE BALL VALVE, 3600 PSI/ PN 248, WITH ISO DIRECT MOUNTING PAD 306M SERIES/ PED Category II

CVS10 Sanitary Check Valves

Type 2080 FALTENBALGVENTIL BELLOWS VALVE VANNE A SOUFFLET. Operating Instructions. Bedienungsanleitung Manuel d utilisation

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Brass Check Valve RDL

DK32 - DK34 - DK37 Technical Datasheet

Technical Data. Dimensions

Declaration of Conformity as per Directive 97/23/EC

Technical Data. Dimensions

Technical Data. Dimensions

Glass tube flowmeters Series 2000 Variable area flowmeter for low flows of liquids and gases

Glass tube flowmeters Series 2000

Operating Manual FSV, FSÖV, SSVF

ATEX VACUUM PUMPS AND GAUGES CHEMICALLY RESISTANT, OIL-FREE AND SAFE

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar

Type 0404 / /2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

GA24 Technical Datasheet

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Instructions for Safe Use

Certificate of Compliance

Centrifugal Gas Separator ZGA. Operating Manual. Dimensions, weights and other technical data are subject to changes.

Pressure Relief Valves. SPV, SPVF direct operated

Technical Data. General specifications Switching element function Rated operating distance s n 2 mm

Safety Instructions Liquiphant FailSafe FTL80, FTL81, FTL85

7000 Series OPTIMASS Mass Flowmeters. Titanium Hastelloy Stainless Steel

The evolution of the Ex-proof flame path

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

Manual Actuated Boiler Blowdown Valves

Telefon (+45) Telefax (+45)

IOM Manual Installation and Operation Manual.

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] IM 01C25A00-12E

Technical Data Sheet. OPTIMASS 7000 Custody Transfer Mass Flowmeter

Hand pump type CH. Product documentation. 300 bar 8.3 cm 3 /stroke. Operating pressure p max : Displacement volume V max stroke :

Rocker valve. Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

OPTIMASS 1000 Handbook

Pressure relief valve

T R A N S L A T I O N Declaration of Conformity as per Directive 2014/68/EU

CP10 Sensor Installation and Maintenance Instructions

INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Model Sanitary Vent SECTION I

Operating Instructions

TSS21 Sealed Thermostatic Steam Tracer Trap

AVM7 Stainless Steel Thermostatic Air Vent

Instruction manual. for. high purity gas pigtails 200 bar / 300 bar

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 5 mm

Safety Relief Valve HON 832

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI

Instruction Manual. LKHSP Self-Priming Centrifugal Pump (Appendix) ESE02222-EN

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Straight-Way Valve with Packing Gland

MAINTENANCE & ASSEMBLY INSTRUCTIONS FUSIBLE LINK. Inline Thermal Check Valve

DK 37 M8. All-metal miniature flowmeters. For hazardous-duty devices, please refer to Supplementary Installation and Operating Instructions:

Operating instructions for variable area flow meter with needle valve. Model: UVR/UTR

Gas Pressure Regulator HON 200

Transcription:

VA FLOWMETERS Supplementary Instructions Variable area flowmeters without electrical built-ins Equipment category II 2 G, II 2 D KROHNE

CONTENTS VA FLOWMETERS 1 General notes 3 2 Safety instructions 4 2.1 Flammable products... 4 2.2 Equipment category...4 2.3 Protection types... 5 2.4 Surface temperature...5 2.5 Static electricity... 6 2.5.1 Process dependent charging... 6 2.5.2 Charging non-conductive external parts by cleaning... 6 2.6 Device-specific notes... 7 3 Description 11 3.1 Safety description code... 11 3.2 Marking... 11 4 Installation 13 4.1 Mounting... 13 4.2 Special conditions... 13 5 Operation 14 5.1 Start-up... 14 5.2 Operation... 14 6 Service 15 6.1 Maintenance... 15 6.2 Dismantling... 16 7 Notes 17 2

VA FLOWMETERS GENERAL NOTES 1 INFORMATION! These supplementary instructions apply to explosion-protected versions of variable area flowmeters without electrical built-ins: DK32, DK34 DK37/M8M, DK37/M8M/R H250/M8MG, H250/M8MG/R H250/M9 H250/M40 DK46, DK47, DK48, DK800 GA24 VA40 In the categories II 2 G II 2 D They complete the standard manual for the non-explosion protected versions. The information given in these supplementary instructions contain only the data relevant to explosion protection. The technical details given in the standard manual for the non-explosion protected versions remain unchanged unless they will be excluded or replaced by these instructions. The series of the non-electrical versions of variable area flowmeters listed above have been tested by the manufacturer in accordance with: EN ISO 80079-36:2016 EN ISO 80079-37:2016 Non-electrical devices for use in hazardous areas The testing documentation has been stored in accordance with item 13, section 1b (ii) of the directive 2014/34/EU (ATEX) at the Physikalisch- Technischen Bundesanstalt (PTB), Braunschweig, Germany under the registration number: PTB 03 ATEX D127 The devices have identical designs in categories II 2 G and II 2 D. 3

2 SAFETY INSTRUCTIONS VA FLOWMETERS 2.1 Flammable products Atmospheric conditions: The ATEX directive does not stipulate values for atmospheric conditions. However, for determining the explosion characteristic parameters of temperature and pressure range, the following is assumed as a basis: T atm = -20...+60 C / -4...+140 F and P atm = 0.8...1.1 bar / 11.6...15.9 psi Outside of these ranges, for most mixtures no key figures are available for the ignition behaviour. Operating conditions: Variable area flowmeters operate outside of atmospheric conditions, which means that explosion protection according to the ATEX directive, regardless of the zone assignment, is fundamentally not applicable due to the lack of key safety data for the interior of the measuring unit. WARNING! Operation with flammable products is only permitted as long as no explosive fuel/air mixture builds up on the inside of the flowmeter under operating conditions. The operator is responsible to ensure that the flowmeter is operated safely in terms of the temperature and pressure of the products used. In case of operation with flammable products the measuring units must be included in the periodic pressure tests of the system. When using the device version H250/C... (PTFE version, non-conductive) the minimum conductivity of the media must be 10-8 S/m, in order to avoid danger from electrostatic charge. 2.2 Equipment category Variable area flowmeters are designed in category II 2 G / II 2 D for use in zone 1 or zone 2 or zone 21 or zone 22. The inside of the measuring unit is also approved for zone 1. INFORMATION! Definition of zone 1 acc. to EN 1127-1, Appendix B: An area in which an explosive atmosphere, as a result of the mixture of flammable substances in the form of gas, steam or mist with air, under normal operation may occasionally occur. Definition of zone 21 acc. to EN 1127-1, Appendix B: An area in which an explosive atmosphere may occasionally occur in the form of a cloud of flammable dust in the air under normal operation. 4

VA FLOWMETERS SAFETY INSTRUCTIONS 2 2.3 Protection types Non-electrical variable area flowmeters are designed in the protection type "design safety c" in accordance with EN ISO 80079-37. The marking of the non-electrical versions for the device type is: Device type Gas range Dust range DK32 / DK34 / DK37 II 2G Ex h IIC T6...T3 Gb II 2D Ex h IIIC T150 C Db H250/M8M II 2G Ex h IIC T6...T3 Gb II 2D Ex h IIIC T200 C Db DK46 / DK47 / DK48 / DK800 / VA40 II 2G Ex h IIC T6...T5 Gb II 2D Ex h IIIC T100 C Db H250/M9 or H250/M40 II 2G Ex h IIC T6...T2 Gb II 2D Ex h IIIC T300 C Db GA24 II 2G Ex h IIC T6...T4 Gb II 2D Ex h IIIC T120 C Db The marking contains the following information: II 2.4 Surface temperature Explosion protection, group II 2 Equipment category 2 G D Ex h IIC IIIC T6...T2 T300 C Gas explosion protection Dust ignition protection Non-electrical device - Protection through design safety Gas group, suitable for gas groups IIC, IIB and IIA Dust areas, suitable for groups IIIC, IIIB and IIIA Temperature class range, suitable for temperature class T6...T1 Maximum surface temperature of measuring unit Gb EPL, suitable for zone 1 and zone 2 Db EPL, suitable for zone 21 and zone 22 It is to be assumed that a combustible fuel / air mixture can be in contact with the outer wall of the measuring tube and process connections. Any temperature gradient between the internal wall in contact with the product (product temperature) and the outer surface is not taken into consideration. The actual maximum surface temperature does not depend on the device itself, but instead on the operating conditions. The device itself does not generate heat and, for this reason, the surface temperature is determined by the product temperature and, in versions with heating jackets, by the heating medium temperature as well. The nameplate shows the maximum values of the temperature classes and the maximum surface temperature. Depending on the device version, these values may not be reached. The maximum permitted ambient and product temperatures can be found in the standard manual. 5

2 SAFETY INSTRUCTIONS VA FLOWMETERS 2.5 Static electricity 2.5.1 Process dependent charging In variable area flowmeters, it is possible under field conditions for charge separation to occur in the measuring tube due to the transport of non-conductive fluids and/or when the flow comes into contact with non-conductive built-ins (e.g. liners, floats). For all metal devices, the measuring tube and the welded on process connections form a shield (Faraday cage) from which the electrical field cannot escape. In glass devices, it is basically possible for the electrostatic field generated inside the measuring tube to "punch through" to the outside of the device. For that reason, variable area flowmeters need to be permanently grounded by the operator by way of the process connections in order to allow discharge of electrostatic charges. The operator is also responsible for extending the ground continuity of the process pipeline. If grounding cannot be made via the process connections (plastic process connections or undefined connections), the measuring device should be connected to the described ground potential via the connection to ground. This connection only ensures the electrostatic grounding of the device and does not meet the requirements for equipotential bonding. CAUTION! Use of the equipment is not permitted in areas where the following occur: processes that generate strong charges, machine grinding and separation processes, electron spraying (e.g. near electrostatic painting systems) or pneumatically conveyed dust. 2.5.2 Charging non-conductive external parts by cleaning Area limits are taken into consideration with respect to the chargeability of non-conductive external parts under atmospheric conditions. Devices for which it can be expected that combustible electrostatic charging will occur due to cleaning are marked with an adhesive label: CAUTION! Achtung! Gefahr elektrostatischer Aufladung! Nicht reiben! Caution! Risk of electrostatic charge! Do not rub! A cleaning cloth moistened with water, for example, should be use to clean surfaces that could be loaded with a charge. 6

VA FLOWMETERS SAFETY INSTRUCTIONS 2 2.6 Device-specific notes If the device is not sufficiently electrostatically grounded via the process pipes, an additional ground connection must be established using the grounding screw 1. DK32 - DK34 DK37/M8M - DK37/M8M/R INFORMATION! The indicator housing is made of conductive plastic. Friction cannot cause electrostatic charge. 7

2 SAFETY INSTRUCTIONS VA FLOWMETERS H250/M9 In hazardous areas, only operate the indicator with a closed cover. CAUTION! When using a sight glass made of Polycarbonate, note the label information: Achtung! Gefahr elektrostatischer Aufladung! Nicht reiben! Caution! Risk of electrostatic charge! Do not rub! H250/M40 In hazardous areas, only operate the indicator with a closed cover. 1 Grounding in the indicator 2 Grounding outside INFORMATION! Grounding 1 and 2 are equivalent. 8

VA FLOWMETERS SAFETY INSTRUCTIONS 2 H250/M8MG - H250/M8MG/R INFORMATION! The indicator housing is made of conductive plastic. Friction cannot cause electrostatic charge. DK46 - DK47 - DK48 - DK800 When measuring gases or liquids that are not contaminated, risk of combustion due to electrostatic charge is not be expected if the flow rate does not exceed 20 times the nominal flow rate. The max. allowable operating pressure PS printed on the nameplate may not be exceeded! 9

2 SAFETY INSTRUCTIONS VA FLOWMETERS GA24 When measuring gases or liquids that are not contaminated, risk of combustion due to electrostatic charge is not be expected if the flow rate does not exceed 10 times the nominal flow rate. The max. allowable operating pressure PS printed on the nameplate may not be exceeded! VA40 When measuring gases or liquids that are not contaminated, risk of combustion due to electrostatic charge is not be expected, if the liquid does not have a conductivity of less than 1000 ps/m and the flow rate does not exceed 10 times the nominal flow rate. The max. allowable operating pressure PS printed on the nameplate may not be exceeded! CAUTION! The sight glass is made of Polycarbonate. Note the label information. Achtung! Gefahr elektrostatischer Aufladung! Nicht reiben! Caution! Risk of electrostatic charge! Do not rub! 10

VA FLOWMETERS DESCRIPTION 3 3.1 Safety description code 3.2 Marking The description code stated in the standard manual applies. The flowmeters are identified by the following nameplates: (examples are not to scale) Nameplate DK32 - DK34 XXXXXXXXX 40 70 Example for DK3x Nameplate H250/M9 - H250/M40 - DK37/M8M - DK37/M8M/R - H250/M8MG - H250/M8MG/R 00XX H250/RR/XXX P/A: XXXXXXXXX.XXX SN: XXXXXXXXX MD: 20XX PED/XX/XX/XX PTmax: XX bar PS: XX bar TS: XX C Tag-No.: XXXXXXXXX Reg.No. PTB 03 ATEX D127X II2G Ex h IIC T6...T2 Gb II2D Ex h IIIC T300 C Db T - 40 C...+ 90 C amb Example for H250/M40 11

3 DESCRIPTION VA FLOWMETERS Nameplate VA40 - GA24 - DK46 - DK47 - DK48 - DK800 20 100 XXXXXXXXXX XXXXXXXXX/XXX XXXXXXXXX XX XXXXXXXXXXXXXX XXXXXXXXXXXXXX XXXXXXXXX /XX/XX/XX XXX XXX XXX Example for VA40 CAUTION! The values stated on the nameplates (indicated with xxx) vary according to the individual device versions and can be found on the respective nameplate or standard manual for the device. 0035 - identification number of the PED supervisory body SN - serial number and/or PA - production order number MD - manufacturing date PS - max. operating pressure (Pressure Specified) PT max. - max. test pressure (Pressure Test max.) TS - max. operating temperature (Temperature Specified) PED - Pressure Equipment Directive key Tag-No. - tag identifier Reg.No. - registration number of notified body Tamb. - max. ambient temperature VG - V number, Germany SO - order number PA - production order number AC - article code 12

VA FLOWMETERS INSTALLATION 4 4.1 Mounting Mounting and setup must be carried out according to the applicable installation standards for hazardous areas by qualified personnel trained in explosion protection. The information given in the manual and these supplementary instructions must be observed at all times. Check the nameplate to ensure that the variable area flowmeters are suitable for the field of application. Check that the product is compatible with the wetted parts using the order information. 4.2 Special conditions Mechanical tests The flowmeters were subject to a shock test in accordance with EN ISO 80079-36. Equipment group - II Degree of mechanical risk - low Additional marking - X If the degree of mechanical risk is greater, additional protective measures must be taken. Device Measuring units, valves, regulators Impact energy (Joule) DK32, DK34 4 not applicable DK37/M8M, DK37/M8M/R 4 not applicable H250/M8MG, H250/M8MG/R 4 not applicable H250/M9 4 not applicable H250/M40 4 not applicable DK46, DK47, DK48, DK800 4 2 GA24 4 2 VA40 4 2 Sight glass, Protective cover, transparent INFORMATION! Testing is not required for the sight glass for all metal variable area flowmeters. With regard to explosion protection for these devices, the integrity of the sight glass is not important. 13

5 OPERATION VA FLOWMETERS 5.1 Start-up Start-up is only permitted when the variable area flowmeter: is correctly installed in the system and connected. has been checked for the proper state with regard to its installation requirements. has been tested to determine the suitability of the materials used for the measuring unit and for the gaskets for adequate resistance to corrosion from the process product. 5.2 Operation The operator of the system has to check prior to start-up, if the start-up was in compliance with the national regulations for checks. Variable area flowmeters must be operated in such a way that they remain within the maximum and minimum permissible temperatures and pressures and the electrical limit values. Variable area flowmeters may only be operated if the equipment parts necessary for safety are effective in the long run, and are not rendered inoperable during operation. When it comes to flammable products, the measuring sections must be included in the periodic pressure tests of the system. Opening the housing of the electronics compartment (equipment protection by flameproof enclosure or dustproof housing) in hazardous areas is only permitted in a de-energised state. WARNING! Ignition risks caused by pressure surges, impact or friction must particularly be avoided when titanium measuring units are used. 14

VA FLOWMETERS SERVICE 6 6.1 Maintenance Display The indication unit requires no maintenance under normal operating conditions and when used for the intended purpose. Measuring unit The measuring unit requires no maintenance under normal operating conditions and when used for the intended purpose. Depending on the application, worst-case operating conditions may lead to reduced measuring performance as a result of fouling of the measuring cone and/or float. Clean the measuring unit in accordance with the standard manual for non-explosion protected versions. The measuring unit must be dismantled for cleaning. To do this, follow the instructions for exchanging the entire device. The following visual checks should be carried out at regular intervals in conjunction with the system inspections required in hazardous areas to keep equipment in good operating condition: Inspection of the measuring unit for leakage. Include the flowmeter in the regular pressure testing of the process line. Preventive maintenance Maintenance work of a safety-relevant nature within the meaning of explosion protection may only be carried out by the manufacturer, his authorised representative or under the supervision of authorised inspectors. 15

6 SERVICE VA FLOWMETERS 6.2 Dismantling Replacing the indication unit Due to the modular design of the variable area flowmeters, from a safety perspective the indication can be replaced with identical KROHNE spare parts. In this case, the measuring tube can remain in the pipeline. This also applies for pressurised pipes. CAUTION! There may be a loss of measuring accuracy! Exchanging the entire device CAUTION! Pressurised pipes have to be depressurised before removing the measuring unit. Avoid uncontrolled discharge of residual fluid from the measuring unit. Where environmentally critical products are concerned, carefully decontaminate the wetted parts of the measuring tube after dismantling. The dismantling and installation is within the responsibility of the operator. 16

VA FLOWMETERS NOTES 7 17

7 NOTES VA FLOWMETERS 18

VA FLOWMETERS NOTES 7 19

KROHNE Process instrumentation and measurement solutions KROHNE - Subject to change without notice. Flow Level Temperature Pressure Process Analysis Services Head Office KROHNE Messtechnik GmbH Ludwig-Krohne-Str. 5 47058 Duisburg (Germany) Tel.: +49 203 301 0 Fax: +49 203 301 10389 info@krohne.com The current list of all KROHNE contacts and addresses can be found at: