S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

Similar documents
COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

S Surge Arresters

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

Effective May 2017 Supersedes August 2005 (S )

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

Inspection Recommendations

32374 R. Jazowski 4/4/ D. W. Mudge G. Sivik 1 of 8 ODN TITLE: Installation & Operation Manual for Nautilus G2 Connectors

Installation. S&C Vista Underground Distribution Switchgear. UnderCover, Vault-Mounted, and Pad-Mounted Styles. Instruction Sheet

Fiber Cable Puller with Tuf-Lugger lite

BUTTERFLY VALVES Series 800

S Loadbreak Apparatus Connectors WARNING: WARNING:

INSTALLATION COMMISSIONING, OPERATION & MAINTENANCE MANUAL

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Installation and Operation

MODELS (2 foot Version) (4 foot Version)

User Instructions 1789 Parapet Wall Anchor

ELECTRIC OPERATING PROCEDURES Date: 11/01/06

AC1810 / AC1810-A TECHNICAL SPECIFICATIONS. Operating Pressure psi ( kgs/cm²) [AC1810] Displacement. Net Weight

SPECIFICATIONS ATTENTION

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

Selection of Electrical PPE Tables

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

Teledyne Oil & Gas North Williamson Blvd. Daytona Beach, FL USA (phone) (fax)

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

COOPER POWER SERIES. Type VFI, Fluid-insulated Switchgear; Installation, Operation and Maintenance Instructions

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

100C Air Compressor Kit

UltraLo 1800 Alpha Particle Counter

OPERATIONS MANUAL RIGHT ANGLE CAPSTAN

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell:

Sub-Base Assembly For Type-ML 32 & VR-1 Step Voltage Regulator Single-Phase Liquid-Filled Part # GEK 35171

CP10K. 10,000 lb. Cable Puller Instruction Sheet. SAFETY ISSUES

OEM Manual MODEL 2305 ECONOMICAL DIGITAL SINGLE CYLINDER SCALE

MUELLER. A Wall Type. Indicator Post. Reliable Connections. General Information 2. Technical Data/ Dimensions 3. Installation 4-5.

3/8" Dr. Air Butterfly Impact Wrench

INSTRUCTION BOOK CARE AND MAINTENANCE OF OIL-IMMERSED (R-TEMP-OR SILICONE IMMERSED) TRANSFORMERS

200 PSI COMPRESSORS - MODEL NUMBERS

Operating Instructions

Ground Fault Circuit Interrupter(GFCI) Policy

Type CAP. CapSwitcher. Capacitor Switching Device kv 38 kv INSTALLATION & INSTRUCTION MANUAL

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

Single-Phase Pad-Mounted Distribution. Single-Phase Pad-Mounted Distribution Transformers KVA

Socket P2RF-05-S P2RF-08-S Clip & Release Lever Nameplate R99-11

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

TECHNICAL INFORMATION

Instructions for Installing and Operating Clark Reliance EA101 Series Levalarm

IMPORTANT SAFETY INSTRUCTIONS

GAS FUEL VALVE FORM AGV5 OM 8-03

60 Drum Style Spike Aerator

I.H.S INSTALLATION INSTRUCTIONS

! Warning, refer to accompanying documents.

Vertical Lifeline. Ladder Climb. User Instructions. 3M Occupational Health and Environmental Safety. Fall Protection Equipment

MUELLER. Xp, & Lineseal 350 Butterfly Valves

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

Bray/ VAAS O-Ported Series Knife Gate Valve 770/780 Series Operation and Maintenance Manual

LTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.

R E D I C O N T R O L S

Arran LED Floodlight Luminaire

GATOR Battery-powered Pistol Grip Cable Cutters

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Type Vector manual group-operated switch instruction manual. Installation operation maintenance E50001-F710-A420-X-4A00. Answers for energy.

Original Date of Issue: 04/09

Misaligned Folds Paper Feed Problems Double Feeds Won t Feed FLYER Won t Run iii

It is essential that the maintenance staff is qualified for electrical works and follows safety procedures.

WINCH USER GUIDE WARN 3000ACI Utility Winch Part Number: 93000

Transcription:

Vacuum Switches Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions Service Information S260-15-1 Figure 1 Type VCS-1 Vacuum Capacitor Switch 010065KM Contents Safety Information 2 Hazard Statement Definitions 2 Safety Instructions 2 Product Information 3 Introduction 3 Acceptance and Initial Inspection 3 Handling and Storage 3 Description of Operation 3 atings and Specifications 4 and Current atings 4 Installation Procedure 5 Check-out Procedure 5 High- Connections 5 Control Wiring 5 Wiring Diagrams 6 Switch Operation 8 Electrical Operation 8 Manual Hotstick Operation 8 Dimensions 9 Service Information 10 Service equirements 10 Frequency of Inspection 10 High-Potential Withstand Tests 10 Inspection of VCS-1 Module 10 eplacement Parts 10 Factory-Authorized Service Centers 10 September 2003 Supersedes 3/00 Printed in USA 1

Type VCS-1 Capacitor Switch Installation and Operation Instructions FO LIFE FO LIFE Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our Safety For Life mission FO LIFE The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described Only competent technicians, who are familiar with this equipment should install, operate, and service it A competent technician has these qualifications: Is thoroughly familiar with these instructions Is trained in industry-accepted high- and low-voltage safe operating practices and procedures Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc Following is important safety information For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings INFOMATION Safety Instructions Following are general caution and warning statements that apply to this equipment Additional statements, related to specific tasks and procedures, are located throughout the manual DANGE: Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low voltage lines and equipment G1033 WANING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage G1010 Hazard Statement Definitions This manual may contain four types of hazard statements: DANGE: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury WANING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only WANING: This equipment is not intended to protect human life Follow all locally approved procedures and safety practices when installing or operating this equipment Failure to comply can result in death, severe personal injury and equipment damage G1021 WANING: Power distribution equipment must be properly selected for the intended application It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures Failure to properly select, install or maintain power distribution equipment can result in death, severe personal injury, and equipment damage G1222 2

FO LIFE S260-15-1 Introduction Service Information S260-15-1 provides installation instructions, operation information, and maintenance information for Kyle Type VCS-1 capacitor switches The information contained in this manual is organized into the following major categories: Safety Information, Product Information, atings and Specifications, Installation Procedure, Switch Operation, Dimensions, and Service Information efer to the table of contents for page numbers ead This Manual First ead and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance When additional information is desired to satisfy a problem not covered sufficiently for the user's purpose, please contact your Cooper Power Systems Division sales representative Acceptance and Initial Inspection Each switch is completely assembled, inspected, tested, and adjusted at the factory It is in good condition when accepted by the carrier for shipment Upon receipt of a switch, inspect the switch thoroughly for damage and loss of parts incurred during shipment If damage or loss is discovered, file a claim with the carrier immediately PODUCT INFOMATION Handling and Storage If the switch is to be stored for an appreciable time before installation, provide a clean, dry storage area Locate the switch so as to minimize the possibility of mechanical damage ANSI Standards Kyle switches are designed and tested in accordance with ANSI standard C3766 Quality Standards The Quality System at the Cooper Power Systems, Kyle Distribution Switchgear plant is certified to the ISO 9001 standard Description of Operation The Kyle Type VCS-1 Vacuum Capacitor Switch is a singlephase, motor-operated vacuum switch that includes close and latch capability for either electrical or manual operation The solid polymer insulation system does not rely on gas, foam, or liquid dielectrics Highly resistant to ozone, oxygen, moisture, contamination, and ultraviolet light, it is an environmentally safe capacitor switch The VCS-1 switch has a single solid polymer bushing and is suitable for operation through a temperature range of -40 C to +65 C 3

Type VCS-1 Capacitor Switch Installation and Operation Instructions Check Switch atings Before Installation The switch must be applied within its specified ratings Check data plate ratings and compare with the system characteristics at the point of application prior to installation Tables 1 4 list the specifications and ratings for the VCS-1 switch atings All ratings meet or exceed values in ANSI C3766 for a distribution class switch, where applicable TABLE 1 atings Maximum, solidly grounded capacitor banks, phase-to-ground voltage 18 kv Maximum, ungrounded capacitor banks, phase-to-phase voltage 15 kv Basic Insulation Level (BIL) line-to-ground 95 or 125 kv Basic Insulation Level (BIL) open contact 95 kv Max IV @ 94 kv 1000 µv 60 Hz Withstand dry, 1 minute 50 kv wet, 10 seconds 45 kv TABLE 2 General Specifications TABLE 4 Current atings ated Asymmetrical Making Current 9000 A ated Continuous Current 200 A Load Interrupting Ability (Inductive) 10 to 100% Power Factor 200 A Capacitive Current (Max) 200 A Short-Time Current Momentary Asymmetric (10 cycles) 9000 A Symmetrical (05 second) 6000 A Symmetric (1 second) 4500 A ated High Frequency Peak Transient Making Current 12000 A ated Transient Inrush Frequency 6000 Hz Duty Cycle Operations at 40 A 400 Operations at 100 A 400 Operations at 200 A 400 TABLE 5 Control Wiring Specifications ACCESSOY PLUG Catalog Number Cable ange MaxWire Size Number of Pins OD AWG KA48N 5 11 14 mm 12 (0437 0562 in) KA98N 6 13 16 mm 16 (0500 0625 in) Mass (Weight) [kg (lb)] 18 (40) Operating Temperature ange ( C) -40 to +65 ated Frequency (Hz) 50/60 Mechanical Operations (close/open without maintenance) 30,000 TABLE 3 Electrical Specifications Operating, Nominal, 120 Vac Operating ange 95 127 Vac Current (nominal, ac) 14 A Motor run time - Opening (typical) 23 sec Motor run time - Closing (typical) 18 sec 4

FO LIFE S260-15-1 INSTALLATION POCEDUE CAUTION: Personal Injury Bushings have sharp edges Wear protective gloves when handling the unit Failure to do so can result in cuts and abrasions T2580 Check-out Procedure 1 Check data plate Make sure that ratings on the data plate are correct for the planned installation 2 Test mechanical operation Close and open the switch contacts manually, using the yellow operating handle Confirm that the contacts have closed and opened by listening for the sound of operation or by a continuity check between the switch terminals Transport unit with contacts in the closed position 3 Perform high-potential withstand tests Prior to installing the VCS-1 Switch, perform high-potential withstand tests efer to the Service Information section for high-potential withstand test procedures 4 eorient switch terminals if required for installation Loosen the head-to-tank mounting fasteners only if it is necessary to reorient the the position of the switch terminals to make high-voltage line connections Do not position the manual operating handle over the pole-mounting bracket After reorienting the terminals, immediately retorque the head-to-tank mounting fasteners in an alternating pattern to 13 20 N m (10 15 ft lbs) to prevent dust, dirt, or other contaminants from entering the unit 5 Install the switch Follow locally approved installation procedures Mounting hardware is available for pole mounting as an accessory WANING: Hazardous voltage Solidly ground all equipment Failure to comply can result in death, severe personal injury, and equipment damage T2232 WANING: This equipment is not intended to protect human life Follow all locally approved procedures and safety practices when installing or operating this equipment Failure to comply can result in death, severe personal injury and equipment damage High- Connections G1021 1 Ground the switch Make the ground connection to the ground connector located on the switch as shown in Figure 6 Do not rely on a ground connection to the tank 2 eorient bushing terminals if required for installation The bushing terminals are factory torqued to assure proper continuous current requirements and should not be adjusted or rotated without using the following procedure Should adjustment be required, maintain the position of the jam nut and loosen the terminal Next, realign the terminal and jam nut to the desired orientation Then, while maintaining the jam nut, tighten the terminal and retorque to 12 14 N m (9 10 ft lbs) 3 Make line connections Connect the primary leads to the switch terminalsthe universal clamp-type terminals accommodate AWG No 8 solid through 2/0 stranded conductor Control Wiring Connections to the actuating mechanism are made through the standard five-pin (or optional six-pin) receptacle on the head casting Mating plugs for the receptacle must be ordered separately Maximum cable and wire sizes accommodated by the plugs are indicated in Table 5 Pin orientation diagrams for the accessory receptacles are shown in Figure 2 D C E B A KEY 5-pin eceptacle Figure 2 eceptacle pin orientation Three-Wire Control emote control of the VCS-1 switch is supplied by a single-pole, double-throw switch (three-wire control) supplied by the customer Any manual switch, relay contact, time switch, voltage-, current- or photo-electric-controlled switch, or similar device can be used, provided the control circuit is energized for a minimum of 30 seconds (at - 40 ) for each operation A connection diagram for a standard three-wire control is shown in Figure 3 Two-Wire Control Accessory The control can also be operated by an SPST device (two-wire control), applicable voltage 120 Vac only A factory-installed SPDT relay accessory is required for twowire control operation A connection diagram for a twowire control is shown in Figure 3 Holding Switch Accessory If the controlling switch is energized for less than the required time, a factory-installed holding switch accessory is required However, the control circuit must be energized for at least one second for each operation to ensure operation of the holding switch A connection diagram for a two- or three-wire control with holding switch is shown in Figure 3 E D F C A B 6-pin eceptacle 5

Type VCS-1 Capacitor Switch Installation and Operation Instructions Wiring Diagrams Schematic diagrams of switch actuators wired for twoand three-wire controls are shown in Figure 3 Accessories are shown with dashed lines Three-wire Control with Auxiliary Switch accessory M SEL SW b a Three-wire Control with Holding Switch and Auxiliary Switch accessories Hold SW M SEL SW b a A B C D E F A B C D E F Close Control Open Close Control Open Two-wire Control with Auxiliary Switch accessory Two-wire Control with Holding Switch and Auxiliary Switch accessories SPDT SEL elay SW elay Coil b M a Hold SW elay Coil SPDT elay M SEL SW b a A D C B E F A D C B E F Control Control Control Control Figure 3 Typical connection diagrams (switch shown in OPEN position) 6

FO LIFE S260-15-1 Wiring Table A wiring table for various combinations of accessories is shown in Table 6 TABLE 6 Wiring Table eceptacle Pin Description Applicable eceptacle Unit Description A B C D E F Standard 3-wire control M SS-NC SS-NO 120, 240 Vac 5-pin 3-wire control, Holding Switch HS-NO M SS-NC SS-NO 120, 240 Vac 5-pin 3-wire control, Aux-Com M SS-NC SS-NO Aux-NO Aux-NC 120, 240 Vac 6-pin SPDT Aux Switch 3-wire control, Holding Switch, Aux-Com M SS-NC SS-NO Aux-NO Aux-NC 120, 240 Vac 6-pin SPDT Aux Switch 3-wire control, Surge Arrestor M SS-NC SS-NO 120 Vac 5-pin 3-wire control, Holding Switch, HS-NO M SS-NC SS-NO 120 Vac 5-pin Surge Arrestor 3-wire control, SPDT Aux, Aux-Com M SS-NC SS-NO Aux-NO Aux-NC 120 Vac 6-pin Surge Arrestor 3-wire control, Holding Switch, Aux-Com M SS-NC SS-NO Aux-NO Aux-NC 120 Vac 6-pin SPDT Aux Switch, Surge Arrestor Standard 2-wire control -B M -A 120 Vac only 5-pin 2-wire control, Holding Switch -B M HS-NO -A 120 Vac only 5-pin 2-wire control, SPDT Aux Switch -B M Aux-Com -A Aux-NO Aux-NC 120 Vac only 6-pin 2-wire control, Holding Switch, -B M HS-NO -A Aux-Com Aux-NO 120 Vac only 6-pin SPST Aux Switch (b contact) 2-wire control, SPDT elay, -B M -A 120 Vac only 5-pin Surge Arrestor 2-wire control, Holding Switch, -B M HS-NO -A 120 Vac only 5-pin Surge Arrestor 2-wire control, SPDT Aux Switch, -B M Aux-Com -A Aux-NO Aux-NC 120 Vac only 6-pin Surge Arrestor 2-wire control, Holding Switch, -B M HS-NO -A Aux-Com Aux-NO 120 Vac only 6-pin SPST Aux Switch (b contact), Surge Arrestor M: Motor Common SS: Selector Switch NC: Normally Closed NO : Normally Open HS: Holding Switch Aux: Auxiliary Switch Com: Common -B: elay Contact B -A: elay Contact A : SPDT elay 7

Type VCS-1 Capacitor Switch Installation and Operation Instructions INSTALLATION POCEDUE Electrical Operation The switch may be opened and closed electrically by applying rated control voltage to the proper terminals of the actuator receptacle efer to the Installation Procedure section of this manual for electrical connections and operating time Note: Main contacts and auxiliary switch operate before the motor has completed its operation IMPOTANT: If the switch does not respond to an electrical operating signal, it may be that the main switch contacts are not synchronized with the electrical control For example, if the switch is manually opened, an electrical OPEN signal must be transmitted to bring the control into synchronism with the switch contacts before an electrical CLOSE signal will close the switch The converse is also true Manual Hotstick Operation WANING: Hazardous voltage This device is not a substitute for a visible disconnect Follow all locally approved safety practices Failure to follow proper safety practices can result in contact with high voltage, which will cause death or severe personal injury G1121 IMPOTANT: The hotstick tip must be placed in the groove under the eyelet of the manual operating handle when closing the switch The switch may be manually opened and closed by using a hotstick to operate the yellow manual operating handle under the sleet hood as shown in Figures 4 and 5 WANING: Hazardous voltage Do not rely on the open position of the yellow operating handle; it does not ensure that the line has been de-energized Always establish a visible disconnect Failure to follow proper safety practices can result in contact with high voltage, which will cause death or severe personal injury G1160 To open the switch contacts, insert the hotstick tip into the eyelet of the manual operating handle and pull downward to the OPEN position See Figure 4 To close the switch contacts, place the hotstick tip against the manual operating handle and push upward to the CLOSE position See Figure 5 Incorrect placement of the hotstick during closing (placing the hotstick hook into the eyelet) causes the hook to catch on the sleet hood before the complete motion to fully close the switch can be accomplished This incorrect closing method can also cause damage to the sleet hood Contact Position Indication The yellow operating handle is also used as a contact position indicator The switch is closed when the operating handle is in the up position and is open when the operating handle is in the down position To open, insert hotstick tip into eyelet of manual operating handle and pull downward To close, place hotstick tip against manual operating handle and push upward 961019KM Figure 4 Correct placement of the hotstick to open the switch 961018KM Figure 5 Correct placement of the hotstick to close the switch 8

FO LIFE S260-15-1 DIMENSIONS 314 (1225) 166 (65) D C BUSHING CONNECTO CABLE ANGE #10 SOLID TO 350 MCM STANDED D A B GOUND CONNECTO #8 SOLID TO 2/0 AWG STANDED CABLE ANGE CLOSED O P E N Hole [4] 11 (5) ECEPTACLE MOUNTING HOLE FO 16 (0625) BOLT 70 (275) 52 (2) 205 (8) 32 (125) 35 (15) 32 (125) 181 (7) 121 (475) 106 (425) 147 (575) 212 (825) Dimensions A B C VCS-1, 95 kv BIL 316 (125) 752 (295) 195 (775) VCS-1, 125 kv BIL 377 (1475) 813 (320) 195 (775) Terminal Option Dimension D Creepage VCS-1 VCS-1 95 kv BIL 125 kv BIL Terminal to Terminal 675 (265) 675 (265) Terminal to Ground 669 (2625) 836 (330) Eyebolt 70 (275) Flat Pad, 2-Hole 114 (45) Note: Dimensions, given in mm (in), are approximate Figure 6 Dimensions of Type VCS-1 switch 9

Type VCS-1 Capacitor Switch Installation and Operation Instructions SEVICE INFOMATION Service equirements The Kyle Type VCS-1 switch has been designed with a minimum mechanical life of 30,000 operations The switch requires no routine maintenance; however, the switch should be inspected on a regular basis to check for physical damage and to verify operation Frequency of Inspection Because these switches are applied under widely varying operation and climatic conditions, maintenance intervals are best determined by the user based upon actual operating experience WANING: Hazardous voltage The switchgear and high voltage transformer must be in a test cage or similar protective device to prevent accidental contact with the high voltage parts Solidly ground all equipment Failure to comply can result in death, severe personal injury, and equipment damage T2213 CAUTION: adiation At voltages up to the specified test voltages, the radiation emitted by the vacuum interrupter is negligible However, above these voltages, radiation injurious to personnel can be emitted See Service Information S280-90-1, Vacuum Interrupter Withstand Test atings Information for further information G1092 High-Potential Withstand Testing Use the following procedures to perform high-potential withstand tests The VCS-1 capacitor switch should be tested at 375 kvac Closed Contacts Test 1 Close the switch contacts 2 Ground the switch 3 Apply proper test voltage to one of the bushing terminals The switch should withstand the test voltage for 60 seconds Open Contacts Test 1 Open the switch contacts 2 Ground the switch 3 Ground the bushing on one side of the switch 4 Apply proper test voltage to the ungrounded bushing The switch should withstand the test voltage for 60 seconds 5 everse the test and ground connections to the bushings 6 Apply proper test voltage to the ungrounded bushing The switch should withstand the voltage for 60 seconds Withstand Test esults The high-potential withstand tests provide information on the dielectric condition of the switch If the switch passes the closed-contacts test and fails the open-contacts test, the cause is likely to be in the interrupter assembly If the switch fails the closed contacts test, the cause is likely to be a diminished electrical clearance or insulation that has been damaged Causes of insulation damage include failure, abuse, and overvoltage surges Inspection of VCS-1 Module If the VCS-1 module was exposed to an external flashover, an inspection process is recommended to assure proper operation of the switch Should the VCS-1 exhibit external flashover attributes (carbon tracking or discoloration), the following procedure is recommended to restore the encapsulation back to its original condition: 1 emove device from service 2 Inspect module for damage to the terminals emove any damaged terminals and replace 3 Inspect module for damage to the module rods If there is damage to the module rods, the module must be replaced 4 Verify through careful inspection that there is no damage to the housing or head casting that could inhibit proper operation 5 Clean the damaged module with isopropyl alcohol and a scratch-free, nylon scouring pad to remove any carbon deposit 6 With a clean rag, apply a thin coat of dielectric silicone grease to the cleaned areas 7 Confirm the dielectric strength of the module by performing high-potential withstand testing Confirm both phase-to-ground and phase-to-phase conditions See the High-Potential Withstand Testing section of this manual eplacement Parts eplacement parts for Kyle switches are available through the factory Service Department Only factoryauthorized parts are to be used To order replacement parts, refer to the current eplacement Parts Price List for catalog numbers and pricing Contact your Cooper Power Systems representative for additional information and ordering procedures Factory-Authorized Service Centers Factory-authorized service centers are located throughout North America to provide maintenance, repair, and testing services for Kyle switches For further information, contact your Cooper Power Systems representative 10

FO LIFE S260-15-1 11

Type VCS-1 Capacitor Switch Installation and Operation Instructions FO LIFE 2003 Cooper Power Systems, Inc Kyle is a registered trademark of Cooper Power Systems or its affiliates KA2048-411 ev: 01 1045 Hickory St Pewaukee, WI 53072 wwwcooperpowercom KMW 8/04