FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

Similar documents
IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

TSS21 Sealed Thermostatic Steam Tracer Trap

DF1 and DF2 Diffusers

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

AVC32 Carbon Steel Air Vent for Steam Systems

PV4 and PV6 Piston Valves

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

AVM7 Stainless Steel Thermostatic Air Vent

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

CA44, CA44S, CA46 and CA46S Air and Gas Traps

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

TP1 and TP2 Temporary Cone Shaped Strainers

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

DCV6 Disc Check Valve

CA10S, CA14 and CA14S Air and Gas Traps

Dri-Line Mk3 Monnier Compressed Air Drain Trap

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

S and SF Inverted Bucket Steam Traps

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

CVS10 Sanitary Check Valves

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

Airodyn, BRair and BRoil Compressed Air Drain Traps

CP10 Sensor Installation and Maintenance Instructions

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

SCA Series Inverted Bucket Steam Traps

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

BPT13 Balanced Pressure Thermostatic Steam Traps

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

MF2M Monnier Miniature Compressed Air Filter

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

FV Flash Vessel Installation and Maintenance Instructions

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

APT14, APT14HC and APT14SHC Spares 2

Manual Actuated Boiler Blowdown Valves

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

PC10HP Pipeline Connector (ASME 600)

CS10-1 Stainless Steel Clean Steam Separator

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

SRV2S Pressure Reducing Valve

BCV31 DN40 - Blowdown Control Valve

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

SRV66 Sanitary Pressure Reducing Valve

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

Thermocirc Installation and Maintenance Instructions

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

TW Temperature Control Valve

ML3M Monnier Miniature Compressed Air Lubricator

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

MFP14-PPU (Vented) Automatic Packaged Pump Units

BCV31 DN20 - Blowdown Control Valve

BDV1 and BDV2 Blowdown / Depressurisation Valves

BRV71 and BRV73 Pressure Reducing Valves

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

Spirax Compact FREME Flash Recovery Energy Management Equipment

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

BCVi43 Blowdown Control Valve

Vane Flow Switches Colima FLU Series

BSA and BSAT Bellows Sealed Stop Valves Installation and Maintenance Instructions

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

M111 Spiraflo Transducer

QuickHeat TM Packaged Heat Exchanger Solutions

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

CA46S Austenitic Stainless Steel Air and Gas Trap DN40 and DN50

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

CA44 and CA44S Carbon Steel Air and Gas Traps Flanged DN15 to DN25

CA14 SG Iron Air and Gas Trap ½" and ¾" (Screwed)

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

Transcription:

1458050/5 IM-P145-12 ST Issue 5 FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1") Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Operation 6. Maintenance 7. Spare parts Printed IM-P145-12 in the ST UK Issue 5 Copyright 20091

1. Safety information Safe operation of this product can only be guaranteed if it is properly installed, commissioned, used and maintained by qualified personnel (see Section 1.11) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. 1.1 Intended use Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended use/application. The product listed below complies with the requirements of the European Pressure Equipment Directive 97/23/EC and carries the mark when so required. The product falls within the following Pressure Equipment Directive categories: Group 2 Group 2 Product Gases Liquids FTGS14 SEP SEP i) The product has been specifically designed for use on steam, air or water/ condensate which is in Group 2 of the above mentioned Pressure Equipment Directive. The products use on other fluids may be possible but, if this is contemplated, Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered. ii) Check material suitability, pressure and temperature and their maximum and minimum values. If the maximum operating limits of the product are lower than those of the system in which it is being fitted, or if malfunction of the product could result in a dangerous overpressure or overtemperature occurrence, ensure a safety device is included in the system to prevent such over-limit situations. iii) Determine the correct installation situation and direction of fluid flow. iv) Spirax Sarco products are not intended to withstand external stresses that may be induced by any system to which they are fitted. It is the responsibility of the installer to consider these stresses and take adequate precautions to minimise them. v) Remove protection covers from all connections and protective film from all name-plates, where appropriate, before installation on steam or other high temperature applications. 1.2 Access Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting to work on the product. Arrange suitable lifting gear if required. 1.3 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. 1.4 Hazardous liquids or gases in the pipeline Consider what is in the pipeline or what may have been in the pipeline at some previous time. Consider: flammable materials, substances hazardous to health, extremes of temperature. 2 IM-P145-12 ST Issue 5

1.5 Hazardous environment around the product Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive noise, moving machinery. 1.6 The system Consider the effect on the complete system of the work proposed. Will any proposed action (e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel at risk? Dangers might include isolation of vents or protective devices or the rendering ineffective of controls or alarms. Ensure isolation valves are turned on and off in a gradual way to avoid system shocks. 1.7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that the system has depressurised even when the pressure gauge indicates zero. 1.8 Temperature Allow time for temperature to normalise after isolation to avoid the danger of burns. 1.9 Tools and consumables Before starting work ensure that you have suitable tools and/or consumables available. Use only genuine Spirax Sarco replacement parts. 1.10 Protective clothing Consider whether you and/or others in the vicinity require any protective clothing to protect against the hazards of, for example, chemicals, high/low temperature, radiation, noise, falling objects, and dangers to eyes and face. 1.11 Permits to work All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to the Installation and Maintenance Instructions. Where a formal 'permit to work' system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibility is safety. Post 'warning notices' if necessary. 1.12 Handling Manual handling of large and/or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. IM-P145-12 ST Issue 5 3

1.13 Residual hazards In normal use the external surface of the product may be very hot. If used at the maximum permitted operating conditions the surface temperature of some products may reach temperatures in excess of 250 C (482 F). Many products are not self-draining. Take due care when dismantling or removing the product from an installation (refer to 'Maintenance instructions'). 1.14 Freezing Provision must be made to protect products which are not self-draining against frost damage in environments where they may be exposed to temperatures below freezing point. 1.15 Disposal Unless otherwise stated in the Installation and Maintenance Instructions, this product is recyclable and no ecological hazard is anticipated with its disposal providing due care is taken. 1.16 Returning products Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination residues or mechanical damage which may present a health, safety or environmental risk. This information must be provided in writing including Health and Safety data sheets relating to any substances identified as hazardous or potentially hazardous. 4 IM-P145-12 ST Issue 5

2. General product information 2.1 General description The FTGS14 ball float steam trap has an austenitic stainless steel body, stainless steel working internals and integral automatic air venting facility. The SG iron cover is electroless nickel-plated offering increased resistance to erosion. The trap can be supplied with either screwed or flanged horizontal connections and can be maintained without disturbing the pipework. Available options FTGS14 (R-L) Horizontal connections with flow from right to left FTGS14 (L-R) Horizontal connections with flow from left to right Capsule The BP99/32 capsule which is used in the FTGS14 is suitable for use on: 150 C superheat @ 0 bar g and 50 C superheat @ 32 bar g. Optional extras A manually adjustable needle valve (designated 'C' on the nomenclature i.e. FTGS14-C) can be fitted to the trap. This option provides a steam lock release (SLR) feature in addition to the standard air vent. For further information please consult Spirax Sarco. An integral strainer screen (designated 'X' on the nomenclature i.e. FTGS14X) can be fitted to the trap. For further information please consult Spirax Sarco. Standards This product fully complies with the requirements of the European Pressure Equipment Directive 97 / 23 / EC. Certification This product is available with a manufacturers Typical Test Report. Note: All certification/ inspection requirements must be stated at the time of order placement. Note: For further information see the following Technical Information Sheets: TI-P145-11 for the FTGS14 screwed and TI-P145-18 for the FTGS14 flanged. 2.2 Sizes and pipe connections ½", ¾" and 1" screwed BSP and NPT. DN15, DN20 and DN25 flanged EN 1092 PN16, ASME (ANSI) 150 and JIS / KS 10. Fig. 1 FTGS14 (R-L) Fig. 2 FTGS14-C (R-L) IM-P145-12 ST Issue 5 5

2.3 Pressure/temperature limits (ISO 6552) Pressure psi g Steam saturation curve The product must not be used in this region. Body design conditions PN16 PMA Maximum allowable pressure 16 bar g @ 120 C (232 psi g @ 248 F) TMA Maximum allowable temperature 250 C (482 F) Minimum allowable temperature -10 C (14 F) PMO Temperature C Maximum operating pressure for saturated steam service 14.6 bar g (211.7 psi g) TMO Maximum operating temperature 250 C @ 13.8 bar g (482 F @ 200 psi g) Minimum operating temperature 0 C (32 F) Maximum FTGS14-4.5 4.5 bar (65.25 psi g) PMX differential FTGS14-10 10 bar (145 psi g) pressure FTGS14-14 14 bar (203 psi g) Designed for a maximum cold hydraulic test pressure of: Pressure bar g 24 bar g (348 psi g) Temperature F 6 IM-P145-12 ST Issue 5

3. Installation Note: Before actioning any installation observe the 'Safety information' in Section 1. Warning The cover gasket contains a thin stainless steel support ring which may cause physical injury if not handled and disposed of carefully. Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended installation. 3.1 Check materials, pressure and temperature and their maximum values. If the maximum operating limit of the product is lower than that of the system in which it is being fitted, ensure that a safety device is included in the system to prevent overpressurisation. 3.2 Determine the correct installation situation and the direction of fluid flow. Please note that the FTGS14 is designed for horizontal flow only. 3.3 Remove protective covers from all connections and protective film from all name-plates, where appropriate, before installation on steam or other high temperature applications. Installation notes: - If the trap is to discharge to atmosphere ensure it is to a safe place, the discharging fluid may be at a temperature of 100 C (212 F). - The trap must be fitted with the float arm in a horizontal plane so that it rises and falls vertically, therefore the arrow on the name-plate must point downwards. - Unless specified, traps will be supplied with R-L (right to left) flow. Traps can be supplied with left to right (L-R) flow but must be specified at the time of order placement. - The connection orientation can be changed on site by undoing the four cover bolts and moving the cover to the preferred orientation. Please note that the FTGS14 is not designed for vertical flow. A new gasket must always be fitted before reassembly. - Minimum withdrawal distance to remove the cover is 105 mm (4.13"). 3.4 Open the isolation valves slowly until normal operating conditions are achieved. 3.5 Check for leaks. Installation of the manually adjustable needle valve (SLR assembly): 3.6 The SLR assembly is fitted to all float traps with the suffix 'C'. e.g. FTGS14-10C. 'C' = Combined steam lock release and thermostatic air vent. 3.7 Check if the application requires the SLR assembly for correct operation. The SLR should only be used to prevent 'steam locking' and therefore is designed to pass only a small amount of steam. 3.8 The SLR assembly will be dispatched, pre-set to a partial bleed condition. The unit should be screwed clockwise to close and anticlockwise to open. When required the SLR should be used as a controlled continuous bleed, it is not recommended that the SLR be left in the fully open condition as this may lead to premature trap failure and more frequent maintenance schedules. Please consult Spirax Sarco should further information be required. IM-P145-12 ST Issue 5 7

4. Commissioning After installation or maintenance ensure that the system is fully functioning. Carry out tests on any alarms or protective devices. 5. Operation The float trap is a continuous discharge trap, removing condensate the instant it forms. On start-up, the thermostatic air vent allows air to bypass the main valve preventing the system air binding. Hot condensate will close the air vent tightly, but as soon as it enters the main chamber of the trap, the float rises and the lever mechanism attached to it opens the main valve - keeping the system drained of condensate at all times. When steam arrives, the float drops and closes the main valve. Float traps are renown for their high start-up load handling capability, clean tight shut-off and resistance to waterhammer and vibration. 6. Maintenance Note: Before actioning any maintenance programme observe the 'Safety information' in Section 1. Warning The cover gasket contains a thin stainless steel support ring which may cause physical injury if not handled and disposed of carefully. 6.1 General information Before undertaking any maintenance on the trap it must be isolated from both the supply line and return line and any pressure allowed to safely normalise to atmosphere. The trap should then be allowed to cool. When reassembling, ensure that all joint faces are clean. 6.2 How to fit the main valve assembly: - Undo the cover bolts (2) and lift off the body (1). - Remove the complete float assembly (7, 8, 10 and 11) by undoing the two screws (7). - Remove the main valve seat (5) and replace with a new one supplied with new gasket (6). Note: A valve spring (Item 28) is fitted to the DN25 (1") traps only. - Fit a complete new float assembly by tightening the assembly set screws (7) to the recommended torque (see Table 1). - Refit the body (1) using a new gasket (3). 6.3 How to fit the air vent assembly: - Remove the spring clip, element and spacer plate (17). - Unscrew the seat. - Fit a new gasket (18), seat and frame. - Assemble the spacer plate, fit element and clips. - Align the complete air vent (17) horizontally so that the frame clears the cover. - Refit the body (1) using a new gasket (3). 8 IM-P145-12 ST Issue 5

6.4 How to fit the manually adjustable needle valve (SLR assembly): - Unscrew the complete SLR assembly (19 and 21). - Remove the SLR gasket (20). - Replace the SLR assembly (19 and 21) and gasket (20) with new ones. - Tighten the SLR assembly to the recommended torque (see Table 1). - To provide the maximum steam bleed turn the slotted SLR stem anticlockwise until the limit is reached. The amount of bleed can be adjusted by turning the SLR stem clockwise to close. The steam bleed will be fully closed within ¾ of a turn from fully open. Steam lock release assembly Air vent assembly SLR gland nut 19 + 21 20 1 18 17 Frame Seat 3 SLR body 2 6 5 11 10 7 28 8 3 Fig. 5 Main valve assembly Note: Item 28 is required for DN25 (1") size only Table 1 Recommended tightening torques Item Part or mm N m (lbf ft) 2 Cover bolts 17 A/F M10 x 30 47-50 (35-37) 5 Main valve seat 17 A/F 50-55 (37-40) 7 Main valve assembly screws Pozidrive M4 x 6 2.5-3.0 (1.8-2.2) 17 Air vent assembly 17 A/F 50-55 (37-40) 19 SLR body 19 A/F 57-63 (42-46) SLR gland nut 13 A /F 3-5 (2.2-3.7) 29 19 A/F M14 x 1.5 57-63 (42-46) IM-P145-12 ST Issue 5 9

7. Spare parts Spare parts The spare parts available are shown in solid outline. Parts drawn in broken line are not supplied as spares. Available spares Maintenance kit Main valve assembly with float 3, 5, 6, 7 (2 off), 8, 10, 11, 17, 18, 28 (DN25 / 1" only) 3, 5, 6, 7 (2 off), 8, 10, 11, 28 (DN25 / 1" only) Air vent assembly 3, 17, 18 Manually adjustable needle valve (FTGS14-C only) 19 + 21, 20 Cover gasket (packet of 3) 3 Plug and gasket 20, 29 How to order spares Always order spares by using the description given in the column headed 'Available spares' and state the size, type of trap and pressure range. Example: 1 - Main valve assembly for a Spirax Sarco ½" FTGS14-10 ball float steam trap. Manually adjustable needle valve Air vent assembly 19 + 21 20 18 17 3 11 10 6 5 7 28 8 3 Fig. 6 Main valve assembly Note: Item 28 is required for the DN25 (1") size only 10 IM-P145-12 ST Issue 5

IM-P145-12 ST Issue 5 11

12 IM-P145-12 ST Issue 5