Fisher DVI Desuperheater Venturi Inline

Similar documents
Fisher DSA Steam-Atomized Desuperheater

Design DSA Steam-Atomized Desuperheater

Fisher and Whisper Disk Diffusers

Fisher Lever Lock Handlever Actuators for POSI SEAL A81 Rotary Valves

Fisher Lever-Lock Handlever Actuators for POSI-SEAL A81 Rotary Valves

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

Safety manual for Fisher GX Control Valve and Actuator

This manual provides necessary requirements for meeting the IEC or IEC functional safety standards.

Fisher 2625 and 2625NS Volume Boosters

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

Fisher L2sj Low Emission Liquid Level Controller

Float Operated Level Controllers

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

English. Safety Instructions Form /2007 WARNING. All Products. How to Get Safe-Use Guides. Inspection and Maintenance Schedules

OPERATING AND MAINTENANCE MANUAL

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

WW-730. Pressure Sustaining/Relief Control Valve

1305 Series Pressure Reducing Regulators

Type ACE95jr Tank Blanketing Valve

1805 Series Relief Valves

WW-720. Pressure Reducing Control Valve

Temperature Controllers

Fisher 4660 High-Low Pressure Pilot

Fisher FIELDVUE DVC6200f Digital Valve Controller PST Calibration and Testing using ValveLink Software

Types S100K and S102K Pressure Regulators

Fisher 4660 High-Low Pressure Pilot

1301 Series High-Pressure Regulators

WW-720. Pressure Reducing Control Valve

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

Fisher 4194 Differential Pressure Indicating Controllers

ANDERSON GREENWOOD SERIES 9000 POSRV INSTALLATION AND MAINTENANCE INSTRUCTIONS

PENBERTHY SUBMERSIBLE AUTOMATIC SUMP DRAINER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems.

Type 4660 High-Low Pressure Pilot

Types 95L and 95H Pressure Regulators

Installation, Operation, and Maintenance Manual

Bermad Model:

Type R622 Pressure Reducing Regulator

Bermad Pressure Reducing. Model: 42T

V DGX Series. Direct-Operated Regulators Manual D103834X012

4194 Series Differential Pressure Indicating Controllers

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

MEGR-1912 Instruction Manual

Installation, Operation and Maintenance Manual for Back Pressure Regulator

MEGR-1627 Instruction Manual

Types 749B and R130 Changeover Manifolds

64 Series Pressure Reducing Regulators

Pressure Reducing & Desuperheating (PRDS) Station Pressure Reducing (PRS) Station Desuperheating (DSH) Station. Ver. 1.1 (2016)

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device

TITAN FLOW CONTROL, INC.

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

CLASS DH - PNEUMATIC TESTING - GREATER THAN 1 BAR (15 PSIG)

Eaton Filtration, LLC

Installation, Operation, and Maintenance Manual

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

Type EZH Relief or Backpressure Regulator

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

Type FEQ Slam-Shut Valve

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h)

Discharge Relief Valve Operation & Maint.

PRO-50 Instrument Supply Regulator

Type CT88 Backpressure Regulator

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

Bray/ VAAS O-Ported Series Knife Gate Valve 770/780 Series Operation and Maintenance Manual

COMPARING PLUG & SEAT REGULATORS & CONTROL VALVES. Lamar Jones. Equipment Controls Company 4555 South Berkeley Lake Road Norcross, GA 30071

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

C1 Series Pneumatic Controllers and Transmitters

Fisher 8532 High-Performance Butterfly Valve

Mooney * Noise Controller Installation, Operation, and Maintenance Manual

T208VR Series Tank Blanketing Vacuum Regulator

Type 92S Pilot-Operated Steam Regulator

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

V DFX Series. Direct-Operated Tank Blanketing Regulator Manual D103808X012

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

WHEATLEY Series 500 Swing Check Valve

Type 299 Pressure Reducing Regulators

SIL Safety Manual for Fisherr ED, ES, ET, EZ, HP, or HPA Valves with 657 / 667 Actuator

Model GPR Primary Pressure Regulating Valve. Instruction Manual

Waterous Relief Valve

Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve

SCA Series Inverted Bucket Steam Traps

Eaton Filtration, LLC

Oxygen Usage Best Practice Guide

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

1200B2 Series Service Regulators. Instruction Manual

DelVal Flow Controls Private limited

Masoneilan* 78 Model Air Filter Regulator

Fisher C1 Pneumatic Controllers and Transmitters

BUTTERFLY VALVES Series 800

VAD Variable Area Desuperheaters

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

1805 Series Relief Valves

Transcription:

Instruction Manual DVI Desuperheater Fisher DVI Desuperheater Venturi Inline Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 3 Operating Instructions... 4 Verification of Control Instrumentation... 4 Maintenance Instructions... 5 Servicing... 6 Troubleshooting... 7 Parts Ordering... 7 Parts List... 8 Figure 1. Fisher DVI Desuperheater Venturi Inline W5365 1 Introduction Scope of Manual This instruction manual includes installation and operation information for the Fisher DVI desuperheater venturi inline. Do not install, operate, or maintain a DVI desuperheater without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is important to carefully read, understand, and follow all the contents of this manual, including all safety cautions and warnings. If you have any questions about these instructions, contact your Emerson sales office or LocaL Business Partner before proceeding. Description The DVI desuperheater venturi inline (figure 1) offers efficient desuperheating in steam pipelines of NPS 24 and less. It is particularly designed for rugged service conditions and can maintain final temperatures to within 6 to 8 C (10 to 15 F) of saturation. By utilizing a compact design and unique flow path, the desuperheater provides even distribution of spraywater with good turndown for a fixed orifice desuperheater. It is easily installed between any two ASME flanges up to CL1500 and NPS 24. The simple design of the desuperheater allows for virtually maintenance free operation. www.fisher.com

DVI Desuperheater Instruction Manual Table 1. Specifications Steam Line Sizes NPS 1 through 24 Steam Line Connection Sizes Designed for water connection with NPS 1 through 24 CL150, 300, 600, 900, and 1500 raised face and ring type joint flanges Spraywater Connection Sizes NPS 1/2, 3/4, 1, and 2 CL150, 300, 600, 900, and 1500 raised face and ring type joint flanges Maximum Inlet Pressures (1) Consistent with applicable CL150, 300, 600, 900, or 1500 pressure temperature ratings per ASME B16.34 Inherent Rangeability (2) Up to 10:1 Spraywater Pressure Required 3.5 to 35 bar (50 to 500 psi) greater than steam line pressure depending on nozzle design Minimum Steam Velocity 6.1 m/s (20 feet per second) depending on conditions 1. Do not exceed the pressure or temperature limits in this instruction manual, nor any applicable code or standard limitations. 2. Ratio of maximum to minimum controllable C v. Figure 2. Detail of Fisher DVI Desuperheater WATER TUBE DISTRIBUTION CHAMBER INJECTION ORIFICE INJECTION POINT STEAM FLOW DESUPERHEATER VENTURI W5370 1* Principle of Operation The operation of the DVI desuperheater is quite simple. Spraywater flow is throttled by a control valve that responds to the signal generated by the temperature control loop. The spraywater enters the desuperheater water tube and then continues into the distribution chamber (see figure 2). As the chamber fills, the spraywater is forced into the injection orifices. As the flow area is reduced, the spraywater accelerates to the injection point. The accelerated flow results in a fine spray for efficient and rapid vaporization. At the same time, the steam flow is entering the desuperheater venturi. The reduction in flow area continues until the point of water injection. This results in a higher velocity and turbulent steam flow, thus improving the mixing of the spraywater with the steam and increasing overall system turndown. 2

Instruction Manual DVI Desuperheater Installation Always wear protective gloves, clothing, and eyewear when performing any installation operations to avoid personal injury. Avoid personal injury from sudden release of process pressure. Before performing any maintenance operations: Use bypass valves or completely shut off the process to isolate the line from process pressure. Relieve process pressure on both sides of the valve. Drain the process media from both sides of the valve. Use lock out procedures to be sure that the above measures stay in effect while you work on the equipment. Check with your process or safety engineer for any additional measures that must be taken to protect against process media. If installing into an existing application, also refer to the at the beginning of the Maintenance section in this instruction manual. Personal injury or equipment damage caused by sudden release of pressure may result if the desuperheater is installed where service conditions could exceed the limits given in table 1 or on the nameplate. To avoid such injury or damage, provide a relief valve for over pressure protection as required by government or accepted industry codes and good engineering practices. CAUTION When ordered, the desuperheater configuration and construction materials were selected to meet particular pressure, temperature, pressure drop, and fluid conditions. Do not apply any other conditions to the desuperheater without first contacting your Emerson sales office or Local Business Partner. 1. Mount the DVI desuperheater between two flanges with gaskets and bolt the desuperheater to the pipe in accordance with standard piping practice. 2. Clean and flush out the cooling water line before connection to the desuperheater. Use only clean sources of cooling water. Use of clean water decreases wear and prevents clogging of the desuperheater by solid particles. Note Installation of a strainer and isolating valve on the water line leading to the desuperheater is recommended. Failure to do so may result in clogging of the desuperheater by solid particles, thus hampering temperature control of the steam. Please consult the factory for the minimum diameter of the nozzles and recommended strainer size to assure debris will not disrupt the flow by blocking the nozzles. 3. A straight run of pipe is required downstream of the desuperheater to ensure complete vaporization of the cooling water. Consult the desuperheater sizing sheet for installation recommendations including the exact straight pipe distance required. 3

DVI Desuperheater Instruction Manual Figure 3. Typical Control Loop with Fisher DVI Desuperheater TC B2318-1 4. A temperature sensor should be mounted in accordance with the manufacturer's instructions. The recommended distance from the desuperheater to the temperature sensor changes with the velocity and percentage of spraywater required. Consult the desuperheater sizing sheet for installation recommendations including the exact distance required before the temperature sensor. 5. Allow no branching out from the steam line, to divide the steam flow, between the temperature sensor and the desuperheater. A typical control loop is illustrated in figure 3. A temperature sensor generates a signal (pneumatic or digital) through a transmitter. This signal is transmitted to the positioner on the spraywater control valve. The positioner output signal is piped to the actuator, which strokes the spraywater control valve governing the amount of spraywater flow. Operating Instructions Verification of Control Instrumentation 1. Connect the appropriate signal lines to the temperature transmitter, indicating control station, and valve positioner in accordance with the instrumentation manufacturer's instructions. 4

Instruction Manual DVI Desuperheater 2. Switch the controller to manual control. 3. This instruction manual assumes a pneumatic signal of 0.2 to 1.0 bar (3 to 15 psig). If 0.4 to 2.0 bar (6 to 30 psig) or another range is used, adjust the instrument signal referenced in the following steps accordingly. Adjust the instrument signal to 0.2 bar (3 psig). Check that the water valve is completely closed. Adjust the positioner, if necessary. 4. Now adjust the instrument signal to 1.0 bar (15 psig). Check that the control valve opens to its full travel. Adjust the positioner to correct the range and re zero if needed, by referring to step 3. 5. Thereafter, check that the controller is responding so that rising steam temperature gives an increasing instrument signal. 6. Adjust the instrument signal to 0.6 bar (9 psig). 7. Open the water supply. 8. Observe the downstream steam temperature. 9. Increase the instrument signal to 0.8 bar (11 psig). Check that the steam temperature decreases. 10. Adjust the instrument signal to 0.5 bar (7 psig) and check that the steam temperature rises. Note If the temperature does not fall when the instrument signal is increased, the cause may be that either the water valve has not been opened or that the steam temperature is close to saturation. If the latter is the case, set the instrument signal to 0.3 bar (4 psig) [water valve slightly open] and increase the signal to 0.4 bar (6 psig). Check if the temperature decreases. 11. When satisfactory coordination between the instrument signal and steam temperature is reached, adjust the controller in accordance with the manufacturer's instructions. 12. Switch the controller to automatic for automatic positioning. Note For more detailed calibration information, refer to the instrument manufacturer's operating instructions. Maintenance Instructions Avoid personal injury from sudden release of process pressure. Before performing any maintenance operations: Do not remove the actuator from the valve while the valve is still pressurized. Always wear protective gloves, clothing, and eyewear when performing any maintenance operations to avoid personal injury. Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator for the spraywater control valve. Be sure the actuator cannot suddenly open the valve. Completely shut off the process to isolate the DVI desuperheater from process pressure. Relieve process pressure on both sides of the desuperheater. Drain the process media from the desuperheater. Use lock out procedures to be sure that the above measures stay in effect while you work on the equipment. Check with your process or safety engineer for any additional measures that must be taken to protect against process media. 5

DVI Desuperheater Instruction Manual Figure 4. Fisher DVI Desuperheater with Nozzle Cross Section 4 3 1 5 2 B2710 Servicing Although the DVI desuperheater is a simple design requiring very little maintenance, in the event that the spray nozzles become clogged by debris, it may be necessary to service the unit. Prior to removal of the unit from the line, ensure that the necessary gaskets and spare nozzles (if applicable) are available for rebuild if turnaround time for the repair is critical. Review the drawing and specification sheet for clarification. If in doubt as to the construction, advise your Emerson sales office or Local Business Partner of the serial number and model number and ask for further clarification. Residual system pressure may be released during the following steps if the system was improperly isolated or vented. Use extreme care to prevent personal injury while loosening any fasteners in the pressure boundary. Ensure that the weight of the unit is sufficiently supported to avoid personal injury. 1. Slowly loosen the flange stud bolts retaining the DVI desuperheater in line taking care to ensure that there is no residual pressure and that the weight of the unit is sufficiently supported to avoid personal injury. Normally the lower flange bolts will be left loosely in place during removal of the desuperheater from the line unless the location or design requires their complete removal. 2. Remove the DVI desuperheater from the line. 3. Inspect the desuperheater for cuts on the flange mating facing and repair if needed. If there is damage on the gasket surfaces that is too large for field repair, the unit may require replacement. 4. Inspect the nozzles or spray orifices. If the desuperheater has drilled holes for water injection, ream out the holes with a small drill bit or welding rod to clear all obstructions. If the desuperheater has a screwed in nozzle(s) (key 5, figure 4), cut the tack weld(s) and unscrew the nozzle(s). 5. Thoroughly flush the DVI desuperheater after cleaning. For desuperheaters using screwed in nozzles, it is recommended that the nozzles be replaced if the unit has required cleaning. 6. After cleaning the unit including all gasket surfaces, screw in the new nozzles (key 5), if applicable, and tack weld the new nozzles in place with ER309 or similar weld rod taking care not to damage any gasket surface or other nozzles. 6

Instruction Manual DVI Desuperheater 7. When reinstalling the unit in line, take care to center the desuperheater between the steam line flanges as evenly as possible. This will help avoid leakage as well as making sure that the steam flow is not disrupted by not having the desuperheater installed evenly in the piping. Tighten the steam line flanges in accordance with good piping practice. 8. After installing the DVI desuperheater in the steam line, reconnect the water line flange connection. 9. After ensuring that the desuperheater is properly reinstalled in the pipeline, the unit may be returned to service. The desuperheater should be monitored as the unit is brought on line to ensure that there are no leaks in the connections. Troubleshooting The following guide (table 2) is a basic first line troubleshooting guide. Contact your Emerson sales office or Local Business Partner for assistance if you are unable to resolve your field operation problem. Table 2. Troubleshooting Guide Problem Temperature setpoint is not reached Temperature setpoint is not reached Temperature setpoint is not reached Temperature setpoint is not reached Temperature is below setpoint Temperature is below setpoint Temperature is below setpoint Temperature oscillates around setpoint Temperature oscillates around setpoint Water in steam line Water in steam line when steam line isolated Water in steam line Possible Solution Check water source availability and pressure Check nozzle(s) for plugging Make sure that steam saturation pressure is not above setpoint Check to ensure full actuator stroke is reached Check temperature control loop reset Check nozzle for fouling/poor spray pattern clean/replace Check temperature sensor location relocate per guidelines Tune control system parameters Temperature setpoint may be too close to saturation Check that steam traps are functioning properly Check for leakage of spraywater control valve Review piping configuration for downstream tees and elbows Parts Ordering Each DVI desuperheater is assigned a serial number that can be found on the DVI desuperheater body or on a tag attached to the water pipe. Refer to the serial number when contacting your Emerson sales office or Local Business Partner for technical assistance. When ordering a replacement nozzle, refer to the serial number and key number. The key numbers in figure 4 can be used to help in part identification. Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Automation Solutions should not, under any circumstances, be used in any Fisher valve, because they may void your warranty, might adversely affect the performance of the valve, and could cause personal injury and property damage. 7

DVI Desuperheater Instruction Manual Parts List Key Description Note For part numbers not shown, contact your Emerson sales office or Local Business Partner. 1 Body 2 Venturi 3 Water Pipe 4 Water Flange 5* Spray Nozzle *Recommended spare parts Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business division of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Emerson Automation Solutions Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore www.fisher.com Fisher 8 Controls International LLC 1990, 2017; All Rights Reserved