RP920A-D Modular Pneumatic Controller BEFORE INSTALLATION INSTALLATION INSTRUCTIONS Note the following dimensions in Figure 1 when installing an RP920 Modular Pneumatic Controller ( Controller ). RC171 3 (7) MINIMUM CLEARANCE RP90A: 1-7/8 (48) RP920B-D: 3-13/16 (96) 1/8 (3) MINIMUM SPACING 4 (102) -7/8 (148) /16 (8) RP920A: 2 (1) RP920B-D: 3-7/8 (98) RP920A: 1-1/2 (36) RP920B-D: 3-1/4 (83) Fig. 1. RP920 Dimensions in Inches (Millimeters). C400 Copyright 199 Honeywell Inc. All Rights Reserved 9-7392
Fig. 2. Module and Port Locations. 9-7392 2
INSTALLATION Before Mounting Adjustments If a connection to Port 4, 6, 7, or 8 (Fig. 2) is required, remove the self-tapping screw from Port 8 and use the screw to tap the appropriate port. Install 1037-001 Barb Fitting and O-ring fingertight in the appropriate port. Reinstall the screw in Port 8 if not used. If a remote restriction is used for the primary sensor, block the internal air supply (adjustable after gage installation, but easier to adjust before installation): a. Loosen the screw one turn (Fig. 3) and rotate the switchplate (light grey) 90 degrees counterclockwise to the sensor supply blocked position. b. Retighten the screw and check for leaks. If a leak is found, reposition the switchplate. NOTES: 1. The switchplate screw must be tightened securely to prevent a false inoperative sensor condition. 2. The compensation sensor on Port requires an external restricted main air supply. Device Mounting Mark and drill two mounting holes for No. 8 fasteners using the Controller as a template or the dimensions in Figure 1. Mount the Controller with two No. 8 fasteners. Connections Push the tubing on the barb fittings according to the job drawings. See Figure 2 for port locations. Install the gage or plug: a. If a gage is not used, tighten the gage plugs finger-tight. If a gage is used, remove the plug and by hand, screw the gage into the gage port three turns. b. A soft rubber, factory-installed seal allows the plug or gage to be rotated (for alignment) without leakage. c. If the gage is not oriented for correct viewing, rotate the gage counterclockwise until correct. Connector Block Module 2 3 1 After Mounting Adjustments and Changes Controller Action Change SUPPLY OPEN SWITCHPLATE POSITION INDICATOR OPEN POSITION BLOCKED POSITION SUPPLY BLOCKED (EXTERNAL RESTRICTOR) SCREW SWITCHPLATE C102 Fig. 3. Primary Sensor Air Supply. Loosen the four screws (Fig. 4) on the Proportional Module. Remove the module. Rotate the module and its gasket 180 degrees, and reinstall. Ensure that the notch on the module lines up with the proper indication on the Controller label (base). Retighten the four screws. Recalibrate, if required. CAPTIVE SCREW (4) Proprotional Module 20 10 Xp (%) DO NOT ADJUST SCREW 4 Xp (%) 30 20 30 4 10 DIR. REV. DIRECT ACTING CONTROLLER LABEL NOTE LOCATION OF NOTCH DIR. REV. Fig. 4. Changing Controller Action. REVERSE ACTING C103 3 9-7392
Negative (Winter) to Positive (Summer) Compensation (RP920B and D only) Change Loosen the four screws (Fig. ) on the Compensation Module. Remove the module. Rotate the module and its gasket 180 degrees, and reinstall. Ensure that the notch on the module lines up with the proper indication on the Controller label (base). Retighten the four screws. Recalibrate, if required. Check the position of the gasket tab (Fig. 6, front). Loosen the three screws on the Switch Block Module and remove the module. Remove the gasket and note the letters (B, B+, C, C+) embossed on the back of the module. Rotate and/or flip the gasket until the gasket position matches the functions desired (Fig. 6, back). When correct, only the desired letter shows. Install the gasket on the back of the Switch Block Module, reinstall the module, and tighten the three screws. Connect the integral action cut-off switching components to Ports 6 and 7, if used. Gage Function and Intergral Action Cut-off (RP920C and D) Adjustment The position of the gasket located under the Switch Block Module (Fig. 2) determines the function of the field-installed gage on the Switch Block Module and determines if integral action cut-off function is enabled or disabled. See Table 1 for factory and field settings. All devices manufactured in Arlington Heights are supplied with the gasket in the B (Branch Line Gage) position. Table 1. Switch Block Gasket Position. Factory Model Field Setting Options RP920B B C RP920C B B+ RP920D B C, C+, B+ B = Branch Line Gage. C = Compensation Sensor Gage. + = Integral Action Cut-Off Enabled. Fig. 6. Integral Action Cut-Off and Gage Function Gasket Position. Compensation Module CAPTIVE SCREW (4) Ac (%) 300 20 200 DO NOT ADJUST SCREW 10 0 0 10 200 Ac (%) 20 300 POS.NEG. POS.NEG. NEGATIVE COMP. (FACTORY SET) NOTE LOCATION OF NOTCH Fig.. Changing from Negative to Positive Compensation. POSITIVE COMP. C104 9-7392 4
Setpoint (W 1 ) Adjustment The Setpoint (W 1 ) knob is embossed with a 0 to percent scale which correlates with the values listed in Table 2. Scaleplate overlays are included to directly match various sensor ranges. Three methods of controlling Setpoint (W 1 ) are available: Local Setpoint Setpoint (W 1 ) adjusted directly on the Controller. Adjustments: If a scaleplate overlay is used, insert the overlay between the Setpoint (W 1 ) knob and the transparent overlay retainer. Note the position of the key and noncoded scaleplate overlay notch (Fig. 7). Adjust the Setpoint (W 1 ), according to the job drawings, using the Setpoint (W 1 ) knob. Calibrate only if the control point deviates excessively from the Setpoint (W 1 ), taking into consideration the throttling range. Remote Setpoint Setpoint (W 1 ) controlled from 0 to percent of primary sensor span from a remote 3 to 1 psi (21 to 104 kpa) bleed-type signal. Adjustments: Adjust the Setpoint (W 1 ) knob to percent (Fig. 7) or to the maximum limit to be applied to the remote setpoint. Install the 1037-001 Barb Fitting and O-ring to Port 8 and connect to a bleed-type remote setpoint device (e.g., SP970) and a remote setpoint gage. Control Point Adjustment (CPA) Available on specific models. Local (baseline) Setpoint (W 1 ) adjusted on the Controller and can be varied ±1 percent of the primary sensor span from a remote 3 to 1 psi (21 to 104 kpa) signal. Adjustments: Pipe CPA to Port 9. Select the proper scaleplate overlay, if used. Note the position of key on the Setpoint (W 1 ) knob and the non-coded scaleplate overlay notch (Fig. 7) for Controllers with U.S.A. labels. Controllers (RP920B, C, D) with German labels must use R coded scaleplate overlay notch when using a CPA device. Insert the scaleplate overlay between the Setpoint (W 1 ) knob and the transparent overlay retainer. Adjust the Setpoint (W 1 ) according to the job drawings using the Setpoint (W 1 ) knob. Fig. 7. Setpoint (W 1 ) Adjustment. 9-7392
60 0 RP920A-D MODULAR PNEUMATIC CONTROLLER Proporational Band (X p ) Adjustment Adjust the Proportional Band (Xp), according to the job drawings, using the Proportional Band Adjustment (Xp) knob on the Proportional Module (Fig. 8). Do not loosen the module knob screw. Authority (Ac) Adjustment (RP920B and D only) Adjust the Authority (A c ), according to the job drawings, using the Authority Adjustment (A c ) knob on the Compensation Module (Fig. 8). Do not loosen the module knob screw. CAUTION The Proportional Band Adjustment (Xp) knob may be difficult to rotate. Use CCT819 RP920 PB and Authority Setting Adjustment Tool or a narrow, stiffblade putty knife to rotate the knob. Loosening the knob screw may induce a Controller leak and cause loss of control until it is retightened. CAUTION The Authority Adjustment (A c ) knob may be difficult to rotate. Use CCT819 RP920 PB and Authority Setting Adjustment Tool or a narrow, stiff-blade putty knife to rotate the knob. Loosening the knob screw may induce a Controller leak and cause loss of control until it is retightened. 2 3 1 7 Connector Block Module 80 % Wc 20 Switch Block Module STARTPOINT ADJUSTMENT KNOB TR Setpoint Module 60 0. 20 80 Proportional Module 20 0 30 10 W 1 % Xp (%) 4 Ac (%) 1 1. 0 300 AUTHORITY ADJUSTMENT KNOB PROPORTIONAL BAND ADJUSTMENT KNOB DIR. REV. POS RP920 MODULE KNOB SCREWS (DO NOT LOOSEN KNOB SCREWS) Fig. 8. Adjustments. C107 Compensation Startpoint (W c ) Adjustment (RP920B and D only) Adjust the Compensation Startpoint (W c ), according to the job drawings (reset schedule), using the Compensation Startpoint Adjustment (W c ) knob (Fig. 8). For direct-acting sensors, the knob setting is equal to the compensation value corresponding to the lowest value given for the primary sensor (from the reset schedule). See Figure 9 for an example of this adjustment. If the value given is not in percent, convert it to a percentage of the compensation sensor range using Table 2. To use Table 2: Find the correct sensor range column. Find the desired temperature in the column. Read the equivalent pressure in the far right column. Read the equivalent percentage in the far left column. Reset Time (T r ) Adjustment (RP920C and D only) Adjust the Reset Time (T r ), according to the job drawings, using the Reset Time Adjustment (T r ) knob (Fig. 8). Decrease the setting until the system becomes unstable. Increase the setting slightly until the system becomes stable. Cover If a cover is used, snap the cover straight on from the front. The cover may be further secured by tightening the self-taping screw in the lower right corner of the cover. 9-7392 6
POSITIVE % PRIMARY Wc ( STARTPOINT) LOWEST PRIMARY VALUE GRAPHICAL NEGATIVE % PRIMARY Wc ( STARTPOINT) LOWEST PRIMARY VALUE 0% 0% POINT 0% % 0% % RESET SCHEDULE VALUES PRIMARY (DISCHARGE) (OUTDOOR AIR) START 120F (48C) (%) 60F (1C) (0%) FULL 160F (71C) (60%) 0F ( 18C) (20%) RANGE TO 2F (4 TO 11C) TO 160F ( TO 71C) % Span STARTPOINT Fig. 9. Compensation Startpoint (W c ) Adjustment (RP920B & D Only) Example. Table 2. Sensor Value to Equivalent Percentage or Equivalent Pressure Conversion Chart. C108 TP92 LP91A TP92, Dew- Humidity Sensors LP914 1077 108 TP974 probe %RH deg F (deg C) deg F psi (kpa) 6/9 1/8 1/7 0 3 (20.68) 1 3.12 (21.1) 2 3.24 (22.34) 3 3.36 (23.17) 4 3.48 (23.99) 3.6 (24.82) 6 3.72 (2.6) 7 3.84 (26.48) 8 3.96 (27.30) 9 4.08 (28.13) 10 4.2 (28.96) -/160 (-/71) 6 1 1 - (-.00) 6.4 1.8 1.8-38 (-38.89) 6.8 16. 16. -36 (-37.78) 66.2 17.3 17.3-34 (-36.67) 66.6 18.1 18-32 (-3.6) 67 18.8 18.8-30 (-34.44) 67.4 19.6 19. -28 (-33.33) 67.8 20.4 20.3-26 (-32.22) 68.2 21.2 21-24 (-31.11) 68.6 21.9 21.8-22 (-30.00) 68.9 22.7 22. -20 (-28.89) /2 (/11) (4.44) 42 (.6) 44 (6.67) 46 (7.78) 48 (8.89) 0 (10.00) 2 (11.11) 4 (12.22) 6 (13.33) 8 (14.44) 60 (1.6) -20/80 (-30/30) -20 (-28.89) -19 (-28.33) -18 (-27.78) -17 (-27.22) -16 (-26.67) -1 (-26.11) -14 (-2.6) -13 (-2.00) -12 (-24.44) -11 (-23.89) -10 (-23.33) 0/200 2/12 (-18/93) (-4/2) 2/12 (-4/2) 30 (-1.11) 30.9 (-0.61) 31.8 (-0.11) 2 (-3.89) 0 (-17.78) 2. (-16.39) (-1.00) 7. (-13.61) 10 (-12.22) 12. (-10.83) 1 (-9.44) 26.3 (-3.17) 27. (-2.0) 28.8 (-1.78) 30 (-1.11) 31.1 (-0.0) 32.2 (0.11) 33.3 (0.72) 32.7 (0.39) 33.6 (0.89) 34. (1.39) 3. (1.94) 36.4 (2.44) 37.3 (2.94) 38.2 (3.44) 39.9 (4.39) 0/ (10/38) 0 (10.00) 0. (10.28) 1 (10.6) 1. (10.83) 2 (11.11) 2. (11.39) 3 (11.67) 3. (11.94) 4 (12.22) 4. (12.0) (12.78) 103/ 13 103 103. 104 104. 10 10. 106 106. 107 107. 108 7 9-7392
% Span 11 4.32 (29.79) 12 4.44 (30.61) 13 4.6 (31.44) 14 4.68 (32.27) 1 4.8 (33.10) 16 4.92 (33.92) 17.04 (34.7) 18.16 (3.8) 19.28 (36.) 20.4 (37.23) 21.2 (38.06) 22.64 (38.89) 23.76 (39.71) 24.88 (.4) 2 6 (41.37) 26 6.12 (42.20) 27 6.24 (43.02) 28 6.36 (43.8) 29 6.48 (44.68) 30 6.6 (4.1) 31 6.72 (46.33) 32 6.84 (47.16) Table 2. Sensor Value to Equivalent Percentage or Equivalent Pressure Conversion Chart (Continued). TP92 LP91A TP92, Dew- Humidity Sensors LP914 1077 108 TP974 probe %RH deg F (deg C) deg F psi (kpa) 6/9 1/8 1/7 -/160 (-/71) 69.3 23. 23.3-18 (-27.78) 69.7 24.2 24-16 (-26.67) 70.1 2 24.8-14 (-2.6) 70. 2.8 2. -12 (-24.44) 70.9 26. 26.3-10 (-23.33) 71.3 27.3 27-8 (-22.22) 71.7 28.1 27.8-6 (-21.11) 72.1 28.8 28. -4 (-20.00) 72. 29.6 29.3-2 (-18.89) 72.9 30.4 30 0 (-17.78) 73.8 31.2 30.8 2 (-16.67) 73.7 31.9 31. 4 (-1.6) 74.1 32.7 32.3 6 (-14.44) 74. 33. 33 8 (-13.33) 74.9 34.2 33.8 10 (-12.22) 7.3 3 34. 12 (-11.11) 7.7 3.8 3.3 14 (-10.00) 76.1 36. 36 16 (-8.89) 76.4 37.3 36.8 18 (-7.78) 76.8 38.1 37. 20 (-6.67) 77.2 38.8 38.3 22 (-.6) 77.6 39.6 39 24 (-4.44) /2 (/11) 62 (16.67) 64 (17.78) 66 (18.89) 68 (20.00) 70 (21.11) 72 (22.22) 74 (23.33) 76 (24.44) 78 (2.6) 80 (26.67) 82 (27.78) 84 (28.89) 86 (30.00) 88 (31.11) 90 (32.22) 92 (33.33) 94 (34.44) 96 (3.6) 98 (36.67) (37.78) 102 (38.89) 104 (.00) -20/80 (-30/30) -9 (-22.78) -8 (-22.22) -7 (-21.67) -6 (-21.11) - (-20.6) -4 (-20.00) -3 (-19.44) -2 (-18.89) -1 (-18.33) 0 (-17.78) 1 (-17.22) 2 (-16.67) 3 (-16.11) 4 (-1.6) (-1.00) 6 (-14.44) 7 (-13.89) 8 (-13.33) 9 (-12.78) 10 (-12.22) 11 (-11.67) 12 (-11.11) 0/200 2/12 (-18/93) (-4/2) 17. (-8.06) 20 (-6.67) 22. (-.28) 2 (-3.89) 27.1 (-2.72) 29.3 (-1.0) 31.4 (-0.33) 33.6 (0.89) 3.7 (2.06) 37.9 (3.28) (4.44) 42.2 (.67) 44.4 (6.89) 46.7 (8.17) 48.9 (9.39) 1.1 (10.61) 3.3 (11.83).6 (13.11) 7.8 (14.33) 60 (1.6) 62.1 (16.72) 64.3 (17.94) 34.4 (1.33) 3.6 (2.00) 36.7 (2.61) 37.8 (3.22) 38.9 (3.83) (4.44) 41 (.00) 42 (.6) 43 (6.11) 44 (6.67) 4 (7.22) 46 (7.78) 47 (8.33) 48 (8.89) 49 (9.44) 0 (10.00) 1.1 (10.61) 2.2 (11.22) 3.3 (11.83) 4.4 (12.44).6 (13.11) 6.7 (13.72) 2/12 (-4/2) (4.44).8 (4.89) 41.7 (.39) 42.8 (6.00) 43.3 (6.28) 44.2 (6.78) 4 (7.22) 4.8 (7.67) 46.7 (8.17) 47. (8.61) 48.3 (9.06) 49.2 (9.6) 0 (10.00) 0.9 (10.0) 1.8 (11.00) 2.7 (11.0) 3.6 (12.00) 4. (12.0). (13.06) 6.4 (13.6) 7.3 (14.06) 8.2 (14.6) 0/ (10/38). (13.06) 6 (13.33) 6. (13.61) 7 (13.89) 7. (14.17) 8 (14.44) 8. (14.72) 9 (1.00) 9. (1.28) 60 (1.6) 60. (1.83) 61 (16.11) 61. (16.39) 62 (16.67) 62. (16.94) 63 (17.22) 63. (17.0) 64 (17.78) 64. (18.06) 6 (18.33) 6. (18.61) 66 (18.89) 103/ 13 108. 109 109. 110 110. 111 111. 112 112. 113 113. 114 114. 11 11. 116 116. 117 117. 118 118. 119 9-7392 8
% Span Table 2. Sensor Value to Equivalent Percentage or Equivalent Pressure Conversion Chart (Continued). 33 6.96 (47.99) 34 7.08 (48.82) 3 7.2 (49.64) 36 7.32 (0.47) 37 7.44 (1.30) 38 7.6 (2.12) 39 7.68 (2.9) 7.8 (3.78) 41 7.92 (4.61) 42 8.04 (.43) 43 8.16 (6.26) 44 8.28 (7.09) 4 8.4 (7.92) 46 8.2 (8.74) 47 8.64 (9.7) 48 8.76 (60.) 49 8.88 (61.23) 0 9 (62.0) 1 9.12 (62.88) 2 9.24 (63.71) 3 9.36 (64.4) 4 9.48 (6.36) TP92 LP91A TP92, Dew- Humidity Sensors LP914 1077 108 TP974 probe %RH deg F (deg C) deg F psi (kpa) 6/9 1/8 1/7 -/160 (-/71) 78.4 39.8 26 (-3.33) 78.4 41.2. 28 (-2.22) 78.8 41.9 41.3 30 (-1.11) 79.2 42.7 42 32 (0.00) 79.6 43. 42.8 34 (1.11) 80 44.2 43. 36 (2.22) 80.2 4 44.3 38 (3.33) 80. 4.7 4 (4.44) 80.7 46.3 4. 42 (.6) 81 47 46 44 (6.67) 81.2 47.6 46. 46 (7.78) 81.3 48.3 47 48 (8.89) 81.7 48.9 47. 0 (10.00) 81.9 49.6 48 2 (11.11) 82.2 0.2 48. 4 (12.22) 82.4 0.9 49 6 (13.33) 82.7 1.6 49. 8 (14.44) 82.9 2.2 0 60 (1.6) 83.1 2.9 0. 62 (16.67) 83.4 3. 1 64 (17.78) 83.6 4.2 1. 66 (18.89) 83.9 4.8 2 68 (20.00) /2 (/11) 106 (41.11) 108 (42.22) 110 (43.33) 112 (44.44) 114 (4.6) 116 (46.67) 118 (47.78) 120 (48.89) 122 (0.00) 124 (1.11) 126 (2.22) 128 (3.33) 130 (4.44) 132 (.6) 134 (6.67) 136 (7.78) 138 (8.89) 1 (60.00) 142 (61.11) 144 (62.22) 146 (63.33) 148 (64.44) -20/80 (-30/30) 13 (-10.6) 14 (-10.00) 1 (-9.44) 16 (-8.89) 17 (-8.33) 18 (-7.78) 19 (-7.22) 20 (-6.67) 21 (-6.11) 22 (-.6) 23 (-.00) 24 (-4.44) 2 (-3.89) 26 (-3.33) 27 (-2.78) 28 (-2.22) 29 (-1.67) 30 (-1.11) 31 (-0.6) 32 (0.00) 33 (0.6) 34 (1.11) 0/200 2/12 (-18/93) (-4/2) 66.4 (19.11) 68.6 (20.33) 70.7 (21.0) 72.9 (22.72) 7 (23.89) 76.7 (24.83) 78.3 (2.72) 80 (26.67) 82.2 (27.89) 84.4 (29.11) 86.7 (30.39) 88.9 (31.61) 91.1 (32.83) 93.3 (34.06) 9.6 (3.33) 97.8 (36.6) (37.78) 102 (38.89) 104 (.00) 106 (41.11) 108 (42.22) 110 (43.33) 7.8 (14.33) 8.9 (14.94) 60 (1.6) 61.1 (16.17) 62.2 (16.78) 63.3 (17.39) 64.4 (18.00) 6.6 (18.67) 66.7 (19.28) 67.8 (19.89) 68.9 (20.0) 70 (21.11) 71 (21.67) 72 (22.22) 73 (22.78) 74 (23.33) 7 (23.89) 76 (24.44) 77 (2.00) 78 (2.6) 79 (26.11) 80 (26.67) 2/12 (-4/2) 9.1 (1.06) 60 (1.6) 60.9 (16.06) 61.8 (16.6) 62.7 (17.06) 63.6 (17.6) 64. (18.06) 6. (18.61) 66.4 (19.11) 67.3 (19.61) 68.2 (20.11) 69.1 (20.61) 70 (21.11) 71 (21.67) 72 (22.22) 73 (22.78) 74 (23.33) 7 (23.89) 7.8 (24.33) 76.7 (24.83) 77. (2.28) 78.3 (2.72) 0/ (10/38) 66. (19.17) 67 (19.44) 67. (19.72) 68 (20.00) 68.8 (20.44) 69 (20.6) 69. (20.83) 70 (21.11) 70. (21.39) 71 (21.67) 71. (21.94) 72 (22.22) 72. (22.0) 73 (22.78) 73. (23.06) 74 (23.33) 74. (23.61) 7 (23.89) 7. (24.17) 76 (24.44) 76. (24.72) 77 (2.00) 103/ 13 119. 120 120. 121 121. 122 122. 123 123. 124 124. 12 12. 126 126. 127 127. 128 128. 129 129. 130 9 9-7392
% Span 9.6 (66.19) 6 9.72 (67.02) 7 9.74 (67.16) 8 9.96 (68.67) 9 10.08 (69.0) 60 10.2 (70.33) 61 10.32 (71.1) 62 10.44 (71.98) 63 10.6 (72.81) 64 10.68 (73.64) 6 10.8 (74.46) 66 10.92 (7.29) 67 11.04 (76.12) 68 11.16 (76.9) 69 11.28 (77.77) 70 11.4 (78.60) 71 11.2 (79.43) 72 11.64 (80.26) 73 11.76 (81.08) 74 11.88 (81.91) 7 12 (82.74) 76 12.12 (83.6) Table 2. Sensor Value to Equivalent Percentage or Equivalent Pressure Conversion Chart (Continued). TP92 LP91A TP92, Dew- Humidity Sensors LP914 1077 108 TP974 probe %RH deg F (deg C) deg F psi (kpa) 6/9 1/8 1/7 -/160 (-/71) 84.1. 2. 70 (21.11) 84.4 6.1 3 72 (22.22) 84.6 6.8 3. 74 (23.33) 84.8 7. 4 76 (24.44) 8.1 8.1 4. 78 (2.6) 8.3 8.8 80 (26.67) 8.6 9.4. 82 (27.78) 8.8 60.1 6 84 (28.89) 86 60.7 6. 86 (30.00) 86.3 61.4 7 88 (31.11) 86. 62 7. 90 (32.22) 86.8 62.7 8 92 (33.33) 87 63.4 8. 94 (34.44) 87.3 64 9 96 (3.6) 87. 64.7 9. 98 (36.67) 87.7 6.3 60 (37.78) 88 66 60. 102 (38.89) 88.2 66.6 61 104 (.00) 88. 67.3 61. 106 (41.11) 88.7 68 62 108 (42.22) 89 68.6 62. 110 (43.33) 89.2 69.3 63 112 (44.44) /2 (/11) 10 (6.6) 12 (66.67) 14 (67.78) 16 (68.89) 18 (70.00) 160 (71.11) 162 (72.22) 164 (73.33) 166 (74.44) 168 (7.6) 170 (76.67) 172 (77.78) 174 (78.89) 176 (80.00) 178 (81.11) 180 (82.22) 182 (83.33) 184 (84.44) 186 (8.6) 188 (86.67) 190 (87.78) 192 (88.89) -20/80 (-30/30) 3 (1.67) 36 (2.22) 37 (2.78) 38 (3.33) 39 (3.89) (4.44) 41 (.00) 42 (.6) 43 (6.11) 44 (6.67) 4 (7.22) 46 (7.78) 47 (8.33) 48 (8.89) 49 (9.44) 0 (10.00) 1 (10.6) 2 (11.11) 3 (11.67) 4 (12.22 (12.78) 6 (13.33) 0/200 2/12 (-18/93) (-4/2) 112 (44.44) 114 (4.6) 116 (46.67) 118 (47.78) 120 (48.89) 121.8 (49.89) 123.6 (0.89) 12. (1.94) 127.3 (2.94) 129.1 (3.94) 130.9 (4.94) 132.7 (.94) 134. (6.94) 136.4 (8.00) 138.2 (9.00) 1 (60.00) 141.8 (61.00) 143.6 (62.00) 14. (63.06) 147.3 (64.06) 149.1 (6.06) 10.9 (66.06) 81 (27.22) 82 (27.78) 83 (28.33) 84 (28.89) 8 (29.44) 86 (30.00) 87 (30.6) 88 (31.11) 89 (31.67) 90 (32.22) 91 (32.78) 92 (33.33) 93 (33.89) 94 (34.44) 9 (3.00) 96 (3.6) 97 (36.11) 98 (36.67) 99 (37.22) (37.78) 101 (38.33) 102 (38.89) 2/12 (-4/2) 79.2 (26.22) 80 (26.67) 81 (27.22) 82 (27.78) 83 (28.33) 84 (28.89) 8 (29.44) 86 (30.00) 87 (30.6) 88 (31.11) 89 (31.67) 90 (32.22) 90.9 (32.72) 91.8 (33.22) 92.7 (33.72) 93.3 (34.06) 94. (34.72) 9. (3.28) 96.4 (3.78) 97.3 (36.28) 98.2 (36.78) 99.1 (37.28) 0/ (10/38) 77. (2.28) 78 (2.6) 78.8 (26.00) 79 (26.11) 79. (26.39) 80 (26.67) 80. (26.94) 81 (27.22) 81. (27.0) 82 (27.78) 82. (28.06) 83 (28.33) 83. (28.61) 84 (28.89) 84. (29.17) 8 (29.44) 8. (29.72) 86 (30.00) 86. (30.28) 87 (30.6) 87. (30.83) 88 (31.11) 103/ 13 130. 131 131. 132 132. 133 133. 134 134. 13 13. 136 136. 137 137. 138 138. 139 139. 1 1. 141 9-7392 10
% Span 77 12.24 (84.39) 78 12.36 (8.22) 79 12.48 (86.0) 80 12.6 (86.87) 81 12.72 (87.70) 82 12.84 (88.3) 83 12.96 (89.36) 84 13.08 (90.18) 8 13.2 (91.01) 86 13.32 (91.84) 87 13.44 (92.67) 88 13.6 (93.49) 89 13.68 (94.32) 90 13.8 (9.1) 91 13.92 (9.98) 92 14.04 (96.80) 93 14.16 (97.63) 94 14.28 (98.46) 9 14.4 (99.29) Table 2. Sensor Value to Equivalent Percentage or Equivalent Pressure Conversion Chart (Continued). TP92 LP91A TP92, Dew- Humidity Sensors LP914 1077 108 TP974 probe %RH deg F (deg C) deg F psi (kpa) 6/9 1/8 1/7 96 14.2 (.11) 97 14.64 (.94) 98 14.76 (101.77) -/160 (-/71) 89.4 69.9 63. 114 (4.6) 89.7 70.6 64 116 (46.67) 90 71.2 64. 118 (47.78) 90.2 71.9 6 120 (48.89) 90.4 72. 6. 122 (0.00) 90.6 73.2 66 124 (1.11) 90.9 73.9 66. 126 (2.22) 91.1 74. 67 128 (3.33) 91.4 7.2 67. 130 (4.44) 91.6 7.8 68 132 (.6) 91.9 76. 68. 134 (6.67) 92.1 77.1 69 136 (7.78) 92.3 77.8 69. 138 (8.89) 92.6 78.4 70 1 (60.00) 92.8 79.1 70. 142 (61.11) 93.1 79.8 71 144 (62.22) 93.3 80.4 71. 146 (63.33) 93. 81.1 72 148 (64.44) 93.8 81.7 72. 10 (6.6) 94 82.4 73 12 (66.67) 94.3 83 73. 14 (67.78) 94. 83.7 74 16 (68.89) /2 (/11) 194 (90.00) 196 (91.11) 198 (92.22) 200 (93.33) 202 (94.44) 204 (9.6) 206 (96.67) 208 (97.78) 210 (98.89) 212 (.00) 214 (101.11) 216 (102.22) 218 (103.33) 220 (104.44) 222 (10.6) 224 (106.67) 226 (107.78) 228 (108.89) 230 (110.00) 232 (111.11) 234 (112.22) 236 (113.33) -20/80 (-30/30) 7 (13.89) 8 (14.44) 9 (1.00) 60 (1.6) 61 (16.11) 62 (16.67) 63 (17.22) 64 (17.78) 6 (18.33) 66 (18.89) 67 (19.44) 68 (20.00) 69 (20.6) 70 (21.11) 71 (21.67) 72 (22.22) 73 (22.78) 74 (23.33) 7 (23.89) 76 (24.44) 77 (2.00) 78 (2.6) 0/200 2/12 (-18/93) (-4/2) 12.7 (67.06) 14. (68.06) 16.4 (69.11) 18.2 (70.11) 160 (71.11) 161.8 (72.11) 163.6 (73.11) 16. (74.17) 167.3 (7.17) 169.1 (76.17) 170.9 (77.17) 172.7 (78.17) 174. (79.17) 176.4 (80.22) 178.2 (81.22) 180 (82.22) 181.7 (83.17) 183.3 (84.06) 18 (8.00) 186.7 (8.94) 188.3 (86.83) 190 (87.78) 103 (39.44) 104 (.00) 10 (.6) 106 (41.11) 107 (41.67) 108 (42.22) 109 (42.78) 110 (43.33) 111 (43.89) 112 (44.44) 113 (4.00) 114 (4.6) 11 (46.11) 116 (46.67) 117 (47.22) 118 (47.78) 119 (48.33) 120 (48.89) 121 (49.44) 122 (0.00) 123 (0.6) 124 (1.11) 2/12 (-4/2) (37.78) 101 (38.33) 102 (38.89) 103 (39.44) 104 (.00) 10 (.6) 106 (41.11) 107 (41.67) 108 (42.22) 109 (42.78) 110 (43.33) 110.9 (43.83) 111.8 (44.33) 112.7 (44.83) 113.6 (4.33) 114. (4.83) 11. (46.39) 116.4 (46.89) 117.3 (47.39) 118.2 (47.89) 119.1 (48.39 120 (48.89) 0/ (10/38) 88. (31.39) 89 (31.67) 89. (31.94) 90 (32.22) 90. (32.0) 91 (32.78) 91. (33.06) 92 (33.33) 92. (33.61) 93 (33.89) 93. (34.17) 94 (34.44) 94. (34.72) 9 (3.00) 9. (3.28) 96 (3.6) 96. (3.83) 97 (36.11) 97. (36.39) 98 (36.67) 98. (36.94) 99 (37.22) 103/ 13 141. 142 142. 143 143. 144 144. 14 14. 146 146. 147 147. 148 148. 149 149. 10 10. 11 11. 12 11 9-7392
% Span Table 2. Sensor Value to Equivalent Percentage or Equivalent Pressure Conversion Chart (Continued). TP92 LP91A TP92, Dew- Humidity Sensors LP914 1077 108 TP974 probe %RH deg F (deg C) deg F psi (kpa) 6/9 1/8 1/7 99 14.88 (102.9) 1 (103.42) 101 1.12 (104.2) 102 1.24 (10.08) 103 1.36 (10.90) 104 1.48 (106.73) -/160 (-/71) 94.8 84.3 74. 18 (70.00) 9 8 7 160 (71.11) /2 (/11) 238 (114.44) 2 (11.6) -20/80 (-30/30) 79 (26.11) 80 (26.67) 0/200 2/12 (-18/93) (-4/2) 191.7 (88.72) 193.3 (89.61) 19 (90.6) 196.7 (91.0) 198.3 (92.39) 200 (93.33) 12 (1.67) 2/12 (-4/2) 121 (49.44) 122 (0.00) 123 (0.6) 124 (1.11) 12 (1.67) 0/ (10/38) 99. (37.0) (37.78) 103/ 13 12. 13 CALLIBRATION Sensors Sensors need no separate calibration as they are calibrated to the system. Systems All RP920 Controllers are factory calibrated. It is intended that the Controller be adjusted to the field-calculated values listed on the job drawing. This approach to Controller startup will be adequate for most systems. If it is determined that closer calibration is required, use the following procedures: NOTE: The Controller design allows all adjustments to be made independent of each other. For example, changing the Proportional Band (X p ) setting does not affect the calibration of the Setpoint (W 1 ), the Compensation Startpoint (W c ), or the Authority (A c ) adjustment. If a CPA device is used, apply 9 psi (62 kpa) to Port 9. If a remote setpoint is used, block Port 8. RP920A System Install a temporary receiver gage (matching the primary sensor) or a 0 to 30 psi (0 to 207 kpa) gage in the primary sensor gage port if one is not permanently installed or install a tee gage into the sensor line (Port 3). Apply mainline pressure (MLP) to the system. Install a 0 to 30 psi (0 to 207 kpa) gage in the branchline pressure (BLP) test tap (moisten the needle before inserting). If the sensor reading is greater than ±10 percent of the expected setpoint, remove the sensor tubing from Port 3 and apply a pressure equivalent (expected setpoint) using a CCT816B Calibration Unit. NOTE: For the most accurate calibration, the actual measured variable at the sensor must be ±10 percent of the expected setpoint. With the sensor at or near the desired control point, adjust the Setpoint (W1) knob until the BLP equals the center of the controlled device throttling range, e.g., 8 psi ( kpa) for a 3 to 13 psi (21 to 90 kpa) range device. If the Setpoint (W 1 ) and primary sensor gage do not match, remove the Setpoint (W 1 ) knob and replace it so the setpoint matches the actual primary sensor gage reading. Readjust the Setpoint (W 1 ) to the desired setpoint, if required. Calibration is complete. RP920B Systems Install a receiver gage matching the compensation sensor or a 0 to 30 psi (0 to 207 kpa) gage in Port as shown in Figure 10. NOTE: If the Controller is setup for a compensation gage in the right gage port, plug Port and use the existing gage. 9-7392 12
THE GAGE RANGE MUST MATCH THE RANGE OF THE FEEDING PORT FULL COMP 4 8 9 7 2 3 1 6 M PRIMARY SETPOINT (W 1 ) COMP START PRIMARY C109 Fig. 10. Piping for RP920B Compensation Startpoint (W c ) Setting. Install a 0 to 30 psi (0 to 207 kpa) gage in BLP test tap or in BLP gage port if one is not permanently installed. Apply MLP to the system. Adjust the Authority knob to minimum. Adjust the Compensation Startpoint (W c ) knob until the receiver gage (Port ) reads the pressure equivalent of the Compensation Startpoint (W c ) (Fig. 11 or 12). If the Compensation Startpoint (W c ) and desired startpoint do not match, remove the knob and replace it so they do match. The Compensation Startpoint (W c ) is now calibrated. NOTE: The response of the receiver gage may be slow (up to one minute). The Controller is not defective under these conditions. Set up the CCT816B Calibration Unit (Fig. 13) to connect to Port 3 (primary sensor). NOTE: Sensors are not connected. Apply a pressure equivalent of the primary sensor value corresponding to the Compensation (Comp) Start on the reset schedule (Fig. 11 or 12). Adjust the Setpoint (W 1 ) knob until the BLP equals the expected pressure of the controlled device at Comp Start conditions. If needed, remove the Setpoint (W 1 ) knob and replace it so the setpoint matches the primary sensor value at Comp Start. The Setpoint (W 1 ) is now calibrated. Set up the CCT816B Calibration Unit (Fig. 14) to connect to Port 3 (primary sensor) and Port (compensation sensor). Apply sensor input pressures equivalent to the full compensation on the building schedule. Adjust the Authority (Ac) knob until the BLP equals the expected pressure of the controlled device at full compensation conditions. Calibration is complete. Changing Compensation Startpoint (W c ) or Setpoint (W 1 ) affects only the one corresponding value of the reset schedule, while changing Authority (A c ) affects only the slope of the reset schedule. NOTE: See Compensation Startpoint (W c ) Adjustment (RP920B and D only) for more information. Remove the CCT816B Calibration Unit and pipe sensors. PRIMARY SETPOINT (W ) COMP 1 START STARTPOINT (W ) c FULL COMP C111 Fig. 12. Positive Compensation Calibration Reset Schedule. PRIMARY PRIMARY RESTRICTION SWITCH M BLOCKED NO CONNECTION 4 8 9 7 2 3 1 6 M CCT816B CALIBRATION UNIT NO CONNECTION (BLOCKED RESTRICTION ALTERNATE OK) C112 Fig. 13. RP920B Setpoint (W 1 ) CCT816B Calibration Unit Piping. 3 STARTPOINT (W c ) C110 Fig. 11. Negative Compensation Calibration Reset Schedule. 13 9-7392
INSTALL 1037-001 BARB FITTING AND APPLY 8.0 PSI ( kpa) M 4 8 9 7 2 3 1 6 M CCT816B CALIBRATION UNIT M TR 0. 1 1. 2 Min 20 1 10 7 4 3 INTEGRAL MODULE C114 Fig. 1. Integral Module Piping. NO CONNECTION RP920B Calibration Example: PRIMARY PRIMARY RESTRICTION SWITCH BLOCKED M NO CONNECTION 3 Assume the following reset schedule: Compensation Range Primary Sensor (Discharge) Compensation Sensor (OA) Start 120F (48C) 60F (1C) Full 160F (71C) 0F ( 18C) Operating Span F (23K) 60F (33K) Sensor Range to 2F (4 to 11C) to 160F (4 to 71C) (BLOCKED RESTRICTION ALTERNATE OK) C113 Fig. 14. RP920B Authority (A c ) CCT816B Calibration Unit Piping. RP920C and D Systems Remove the screw from Integral Module (Fig. 1) and install the 1037-001 Barb Fitting and O-ring in its place. Apply 8 psi ( kpa) to the Integral Module. Calibrate the RP920C following the procedure for the RP920A. Calibrate the RP920D following the procedure for the RP920B except that the calibration value of the BLP for Steps 8 and 12 should both be 8 psi ( kpa). When calibration is complete, remove the Barb Fitting from the Integral Module and replace the screw. Assume a 10K (.6K) Throttling Range. Using a 2. to 6. psi (17. to 4. kpa) operator with a n.o. valve where 6. psi (4. kpa) is the no load condition and 2. psi (17. kpa) is the full load condition. See Figure 16 for schedule graph. Initial Settings: Setpoint (W1) = 120F (48C) = percent = 7.8 psi (4.6 kpa). For Calibration Step : Compensation sensor at Start = Compensation Startpoint (Wc). (W c ) = 60F (1C) = 0 percent = 9.0 psi (62 kpa). For Calibration Step 7: Primary sensor at Start = 120F (48C) or 7.8 psi (4.6 kpa). For Calibration Step 8: Desired BLP = 6. psi (4. kpa). 9-7392 14
For Calibration Step 12: Primary sensor at Full Compensation = 160F (71C) = 10.2 psi (71.4 kpa). Compensation sensor at Full Compensation = 0F ( 18C) =.4 psi (37.8 kpa). Expected BLP = 2. psi (17. kpa). 160F (71C) PRIMARY 120F (48C) FULL COMP SETPOINT (W 1 ) COMP START 2. PSI (17. kpa) EXPECTED BLP 6. PSI (4. kpa) 0F ( 18C) STARTPOINT (W ) c C11 Fig. 16. Calibration Example Reset Schedule. 1 9-7392
Home and Building Control Honeywell Inc. Honeywell Plaza P.O. Box 24 Minneapolis MN 8-024 Honeywell Latin American Division Miami Lakes Headquarters 140 Commerce Way Suite 00 Miami Lakes FL 33016 Home and Building Control Honeywell Limited-Honeywell Limitée 7 Ellesmere Road Scarborough Ontario M1P 2V9 Honeywell Europe S.A. 3 Avenue du Bourget B-11 Brussels Belgium Honeywell Asia Pacific Inc. Room 3213-322 Sun Hung kai Centre No. 30 Harbour Road Wanchai Hong Kong 9-7392 Rev. 9-9 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers Helping You Control Your World