Air Sensor. FCS Ex. Manual. AQ Elteknik AB

Similar documents
Air Sensor. SAC Ex. Manual ATEX. AQ Elteknik AB

Ultrasound Controller

Ultrasound Controller

ULTRASOUND CONTROLLER

OSAT Series. Intrinsically Safe Infrared Temperature Sensor Operator's Guide

I/P Transducer Positioner Module

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Pressure control, differental pressure control and thermostat Type RT

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Magnetic level switch type MR783 Instruction Manual

SITRANS P measuring instruments for pressure

High-performance submersible pressure transmitter For level measurement Model LH-20

Pressure switch, Differential pressure switch and Thermostat RT-E

Electro-Pneumatic Converter YT-940 SERIES

Target disk flowmeter Series DP. Instructions manual DP65 DP500. R-MI-DP Rev.: 4 English version

High-performance submersible pressure transmitter For level measurement Model LH-10

Sensor for Air Bubble Detection at Liquid Filled Tubes. SONOCHECK Type ABD06.xx. Operating Manual

IA CERTIFICATE (Annual review required by MASC covered by an additional letter) (Revision 2- Review & Review)

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765

2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

Pressure switch KP-E. Data sheet

High-performance submersible pressure transmitter For level measurement Model LH-20

High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20

BA307C & BA308C Intrinsically safe loop-powered 3½ digit panel mounting indicators issue 9

User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] IM 01C25A00-12E

High-performance submersible pressure transmitter For level measurement Model LH-10

DMK 458. Pressure Transmitter for Marine and Offshore. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.25 % FSO option: 0.

MJK Expert 700 / 800 / 900 / 7070 / 7060 MJK Expert 1400 / 3400

Model PDT Dewpoint Transmitter

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition

1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure

J21K Series DIFFERENTIAL PRESSURE SWITCH. features

Pressure Measurement Single-range transmitters for general applications

Liquid level instruments BM 24 /BM 51

SITRANS. Pressure transmitter SITRANS P, Z series for gauge and absolute pressure. Introduction. Safety instructions 2.

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI

Operating Instructions of BROSA tension load cells, types 0111, 0113

Electropneumatic Transducer (I/P) Installation, Operation and

High-performance submersible pressure transmitter For level measurement Model LH-20

9700 Transmitter Submersible hydrostatic level transmitter

Level switches Series LD Vibrating fork level switch for liquids and solids

Technical Data. Dimensions

O3 3E 1 F Gas Sensor Module

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Instruction Manual for Intrinsically Safe - Reed Switches

T EK-COR 1100A Coriolis Mass Flowmeter

Expert Hydrostatic Level Transmitters

LEVEL Transmitters. ) of the liquid column above it and the atmospheric pressure (P atm

Operating Instructions for Intrinsically Safe Pressure Transmitters Series DMG/******** for Hazardous Application in Coal Mining Industry

Level switches Series LD Vibrating fork level switch for liquids and solids

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

Pressure Switches Application Guideline

Pressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview

Technical Data. General specifications. Rated operating distance s n 2 mm

Autocalibration Systems For In Situ Oxygen Analyzers

Two-Wire In Situ Oxygen Analyzer (550 to 1400 C)

LMP 307. Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % / 0.

MASS-STREAM TM Instruction Manual. D-6200 Analog Mass Flow Meters / Controllers

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

Instruction Manual AD 1000 / BA 1000 Absolute Pressure Sensor

Coriolis Mass Flow Meter

Technical Data. General specifications. Rated operating distance s n 5 mm

Pressure Measurement Single-range transmitters for general applications

XMPA12B2142 pressure sensor XMP - 12 bar - G 1/4 female - 2 NC - without control type

Product information. Capacitive. Level detection in liquid VEGACAP 62 VEGACAP 63 VEGACAP 64 VEGACAP 66 VEGACAP 69. Document ID: 29983

Technical Data. General specifications Switching element function Rated operating distance s n 2 mm

LTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.

IA CERTIFICATE (Revision 3 Revised for Annual Review) Hazel Grove Stockport Cheshire SK14 6NG United Kingdom

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING

Miniature flowmeters DK 46, DKR 46 DK 47, DK 48, DK 800

Level transmitter LT 100

Manual Power relay SR853

sitrans p Operating Instructions (de/en) Edition 03/2004

3000 Series OPTIMASS Mass Flowmeter. Stainless Steel Hastelloy

Technical Data. General specifications Switching element function Rated operating distance s n 1.5 mm

Transmitter CS 21 Operation Manual

Transmitter CS 21 Operation Manual

Instruction Manual Differential Pressure Transmitter

DK46 - DK800 Supplementary instructions

Pressure & Temperature Switches

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition

Intrinsically safe solenoid valves on/off controls - ATEX certification

Coriolis MASS Flowmeters SITRANS FC300 DN 4. Operating Instructions 07/2010 SITRANS F

Types and approvals. Page 1/6. Data Sheet

SPECIFICATIONS APCEPH1

T EK-COR 1100A. Coriolis Mass Flowmeter. FLOW. Technology Solutions

PyroCouple Series Operators Guide

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05

Technical Data. Dimensions

x act i Precision- Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor

C-Flow Coriolis Mass Flow Meters

SITRANS F I Gardex. Flowmeter. SITRANS F I Intra/Prima. Flap Flowmeter. Contents. English. General 1. SITRANS F I Gardex 2. SITRANS F I Intra/Prima 3

HBLT-A1 LIQUID LEVEL SENSOR

Monitoring device NTS 30

Proportional pressure regulators VPPE

VPPC02, VPPC08 3-way proportional pressure control valve, electronic closed loop control

Hydrostatic Level Measurement waterpilot FMX 160

Transcription:

Air Sensor FCS Ex Manual AQ Elteknik AB

Air Sensor Model FCS Ex Manual version 2.0 Oct 2010 AQ Elteknik AB AQ Elteknik AB Air Sensor Manual 2

Table of contents 1. Manufacturer information... 4 Manufacture Declaration of Conformity... 4 Limited Warranty... 4 Warning... 4 Manufacturer information... 4 2. Introduction... 5 Air Sensor... 5 Ultrasound Controller D72 / DP72... 5 3. Functional Description... 5 Principle of Bubble Detection... 5 Sensitivity... 5 4. Installing the Air Sensor... 6 Cable... 6 Vertical or Horizontal Installation... 6 5. Connecting the Air Sensor... 6 Connecting the Air Sensor Ex using barriers... 6 Choosing a barrier... 6 Ex-barriershields... 7 Connecting Air Sensor FCS via barriers to Ultrasound Controller D72 or DP72... 8 6. Ex description... 9 Label information written on Air Sensor Ex... 9 7. Air Sensor settings... 9 Setting the Filter (Integration and delay time)... 9 Sensitivity and Measurement Accuracy... 9 8. Calibration... 10 Calibration... 10 9. Troubleshooting... 10 10. Technical specifications... 11 Air Sensor FCS Ex dimensions... 11 AQ Elteknik AB Air Sensor Manual 3

1. Manufacturer information AQ Elteknik AB operates a policy of on-going development and reserves the right to make changes and improvements to any of the products described in this users guide without prior notice. Under no circumstances shall AQ Elteknik be held responsible for any loss or indirect damage howsoever caused. The contents of this document are provided as it is. AQ Elteknik AB reserves the right to revise this document or withdraw it at any time without prior notice. Manufacture Declaration of Conformity Manufacturer: AQ Elteknik AB Sweden declares, that the product: Air Sensor marked with CE-label conforms with the following standards: EN 61000-6-2:2001, EN 61000-6-4:2001, EN55011 (Group 1, Class B). The Air Sensor is RoHS Compliant, directive 2002/95/EC. Air Sensor marked with conforms to WEEE. When the Air Sensor is to be discarded it shall be sent back to AQ Elteknik AB for safe disposal. See Manufacturer Information for return address. Before sending the Air Sensor to AQ Elteknik AB it must be clean and without any harmful contaminations. A certificate shall be attached with the Air Sensor that confirms the cleaning and shows information: Who has cleaned the Air Sensor (company if other than sender) Who has checked and confirmed that the Air Sensor is clean (company and person) Who is sending back the Air Sensor (company) Limited Warranty AQ Elteknik AB warrants to the original end user that the Air Sensor is free from any defects in materials or workmanship for a period of one year from the date of purchase. During the warranty period, should the Air Sensor have indications of failure due to faulty workmanship or materials, AQ Elteknik AB will replace it with no charge. This warranty shall not apply if the Air Sensor is modified, misused or subjected to abnormal working conditions. Replacement as provided under this warranty is the only remedy of the purchaser. The purchaser pays freight to AQ Elteknik AB. AQ Elteknik AB shall in no event be held liable for indirect or consequential damages of any kind or character to the purchaser. Warning The Air Sensor is intended to be used with the Ultrasound Controller manufactured by AQ Elteknik AB. AQ Elteknik AB takes no responsibility for any possible damage that could happen if the Air Sensor is connected to any equipment not manufactured by AQ Elteknik AB. Manufacturer information Manufacturer: AQ Elteknik AB address: Alsikegatan 4 SE-753 23 Uppsala Sweden phone: +46 (0)18-18 34 30 fax: +46 (0)18-10 50 04 web: www.aqelteknik.com e-mail: info@aqelteknik.se AQ Elteknik AB Air Sensor Manual 4

2. Introduction Air Sensor Liquid flowing through the Air Sensor is monitored with ultrasound and the presence of gas or particles is detected by the connected Ultrasound Controller. The Air Sensor is reliable and easy to use. It is turned from one piece and the inside is completely smooth with low Ra-value Ultrasound Controller D72 / DP72 Ultrasound Controller D72 / DP72 are recommended for use with the Air Sensors. It mounts on a DIN-rail and can be connected to two Air Sensors. 3. Functional Description Principle of Bubble Detection Bubbles in the liquid flowing through the Air Sensor are monitored by the use of ultrasound. Inside the Air Sensor two low intensity beams of ultrasound are transmitted across the liquid-path in directions perpendicular to the liquid flow. If a bubble moves into one of the ultrasound-beams the ultrasound will be partially reflected and the intensity of the ultrasound will decrease. The controller constantly measures the intensity of the ultrasound and if the intensity becomes lower than the threshold it detects a bubble. Also dense material can reflect the ultrasound in a similar way as bubbles and will be detected. Sensitivity The sensitivity for bubbles can be set to high, medium, low, very low and very very low. (How to set it, see the users guide for the D72 / DP72 ultrasound controller.) With sensitivity set to high (threshold 40%) a single bubble of approximately 2mm diameter or larger can be detected passing trough the Air Sensor. With sensitivity set to medium (threshold 25%) a single bubble of approximately 3mm diameter or larger can be detected. With sensitivity set to low (threshold 25%) a single bubble of approximately 10mm diameter or two smaller bubbles (3mm) can be detected. Low sensitivity is achieved in the Air Sensor by requiring both ultrasound-beams to detect bubbles at the same time. Since the two ultrasound-beams are separated by a short distance in the direction of the liquid-flow, there must either come a very big bubble or two smaller bubbles in order to achieve a bubble-detection. Tiny (microscopic) bubbles are usually evenly distributed in the flowing liquid and will be detected with sensitivity set to high, medium or low if the amount of bubbles are high enough. With sensitivity set to very low or very very low sensitivity a different measuring technique is used making the Air Sensor very insensitive for bubbles of any size, even tiny (microscopic) bubbles. However the Air Sensor detects when it is empty. When using very low sensitivity the Air Sensor should preferably be installed with vertical liquid flow since otherwise lingering liquid lying inside the horizontal Air Sensor could be detected as liquid. AQ Elteknik AB Air Sensor Manual 5

4. Installing the Air Sensor One or two Air Sensors can be connected to one Ultrasound Controller D72 or DP72. The Air Sensor should be installed in accordance with national regulations. A person with the required knowledge should perform installation. Cable The cable from the Air Sensor connects to the barriers (hazardous side). The maximum cable length is 10m. A similar cable connects the barrier (safe side) to the Ultrasound Controller D72 / DP72. The cable-screen is important because it prevents external noise from entering. Therefore all cables must be screened and the screen connected to ground. The inner screen of the cable is connected to ground at the barrier. In addition to that the outer screen may be connected to ground via a screened cable gland. NOTE! The unscreened part of the cable should be kept very short. Vertical or Horizontal Installation Although the Air Sensor can be installed horizontally it is better to install it vertically because then bubbles will be drawn to the center where sensitivity is highest and when the flow stops bubbles will not linger inside the Air Sensor. 5. Connecting the Air Sensor Connecting the Air Sensor Ex using barriers The Ultrasound Controller D72 or DP72 is not ex-certified and intrinsically safe barriers must be used to connect the Air Sensor Ex. The diagram below shows how to connect two Air Sensors FCS Ex via four barriers. It is important to install the barriers and the sensors according to EN 60079-14 and to summarize the voltage and current according to appendix B. Two zener barriers are needed for each Air Sensor. In the diagrams, the cable type between D72 / DP72 and the barriers is the same type as between the barriers and the Air Sensors. Choosing a barrier The barrier must be chosen according to EN 60079-14, but there are also measurement considerations for choosing the barrier: 1. The barrier must use resistive current limitation. 2. The barrier must be made for AC current. 3. The barrier voltage should be as high as can be allowed. (minimum ±8V AC) 4. The barrier resistance should be as low as can be allowed. (maximum 110Ω) 5. The barrier must attenuate 2MHz as little as possible. The barrier capacitance to ground should be as low as possible. Recommended barrier: Pepperl+Fuchs Z960. AQ Elteknik AB Air Sensor Manual 6

Ex-barriershields The zener barriers are not shielded so noise can interfere when weak signals are being measured. To reduce noise interference, shielding aluminum plates must be placed outside each group of barriers belonging to each Ultrasound Controller D72 / DP72, see picture. Shielding aluminum plate must be ordered separately, item no: Ex-barriershield. The Ex-barriershield snaps on to the DIN-rail next to the intrinsically safe zener barriers. AQ Elteknik AB Air Sensor Manual 7

Connecting Air Sensor FCS via barriers to Ultrasound Controller D72 or DP72 AQ Elteknik AB Air Sensor Manual 8

6. Ex description The Air Sensor - Ex is made to be used in Apparatus-group IIB and Equipment-group 1/2G. The inside of the conduit of the sensor is designed to be exposed to zone 0 and the remaining parts to zone 1. The sensor is transmitting ultrasound into zone 0. Notice that Ultrasound Controller D72 is not Ex certified and barriers must be used to connect the Air Sensors. Common regulations for installation and maintenance of explosive protected electrical equipment shall be observed. (EN 60079-14 and EN 60079-17 in European countries connected to CENELEC). Special conditions for use according to certificate SP 04ATEX3622X concerning the Air Sensor: 1. The cable from the barrier to the Air Sensor shall be permanently installed, mechanically protected and protected from other environmental stress in order to ensure explosion protection. A person with the required knowledge should perform installation. 2. The current limitation of the intrinsically safe barriers connected to the Air Sensor must be resistive with linear characteristic 3. The enclosure of the Air Sensor must be connected to earth via the mounting in the conduit system. Label information written on Air Sensor Ex Air Sensor Made in Sweden Type see Technical specifications Inner diameter see Technical Specifications Ex Class II 1/2 G EEx ia IIB T4 SP No. SP 04ATEX3622X Transport temp. Tamb: -20 to +60 C Max input voltage Ui: 9,0V Max current input Ii: 480mA Max power input Pi: 1,1W Inner capacitance Ci: 200nF Inner inductance Li: 0,05mH 7. Air Sensor settings Setting the Filter (Integration and delay time) In order to avoid detection of single small bubbles or to avoid unnecessary bubble detections when some amount of bubbles can be accepted there is a filter. The filter can be set to different integration times and also different delay times. Setting the filter to integration means the duration of each bubble detected is added to the integration-sum and when the sum becomes higher than the set value the controller indicates air (for a minimum of 1s). The integration-sum is then reset to zero as soon as liquid is again detected. The speed by which the integration-sum increases depends both on the amount of bubbles and on the flow-rate. Setting the filter to delay means the controller indicates air only after bubbles has been detected continuously for duration of the set time. Sensitivity and Measurement Accuracy The measurement accuracy depend on how well the Air Sensor is calibrated, the flow-rate, the type of liquid, how the Air Sensor is mounted and weather there is a single bubble or many bubbles. Set higher SENSITIVITY and set shorter FILTER-integrate-time if too many bubbles pass the Air Sensor without being detected. Set lower SENSITIVITY, set longer FILTER-time and change from FILTER-integrate-time to FILTER-delay-time if too few bubbles pass the Air Sensor before being detected. AQ Elteknik AB Air Sensor Manual 9

8. Calibration Calibration Make sure there is liquid inside the Air Sensor and calibrate it according to the manual for the controller used. The calibration adjusts the intensity of the ultrasound-beams to 100%. Each Air Sensor should be calibrated after installation. After the first calibration it is advisable also to check the detection of air. A new calibration may be required if the liquid properties has changed significantly since the last calibration With air in the Air Sensor some sound also travels along the walls producing an error signal. This error signal should be less than 15%. 9. Troubleshooting Problem Possible cause Corrective action Air Sensor does not indicate Air Sensor type setting is wrong Change Air Sensor type setting liquid or air when it should Air Sensor is connected wrong Make correct connection DATA db with liquid Air Sensor is not calibrated Calibrate Air Sensor shows too high value relative DATA shows too high value with air Air or Liquid is indicated on the display but the relay does not move Bubble is lingering inside Air Sensor Air Sensor is faulty Ultrasound Controller D72 / DP72 is faulty Relay setting is wrong Remove bubble Replace Air Sensor Replace Ultrasound Controller D72 / DP72 Change relay setting AQ Elteknik AB Air Sensor Manual 10

10. Technical specifications Operating temperature range 0 C to 60 C Maximum temperature range* -20 C to 60 C Maximum pressure Protection class Finish in pipe (Ra-value) FCS: 1Mpa / 10 bar g at operating temperature range IP67 <0,375 µm / <15 micro inch *Proper indication of bubbles is not guaranteed at temperatures outside operating temperature range FCS Ex Air Sensor FCS Ex dimensions Model number Inner diameter (mm) Outer diameter (mm) Tri Clamp diameter (mm) Material FCS10-25 Ex 10 51 25 Stainless steel 316L FCS16-25 Ex 16 51 25 Stainless steel 316L FCS16-50 Ex 16 64 50 Stainless steel 316L FCS22-50 Ex 22 64 50 Stainless steel 316L FCS35-50 Ex 35 64 50 Stainless steel 316L FCS46-64 Ex 46 76 64 Stainless steel 316L AQ Elteknik AB Air Sensor Manual 11