NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC.

Similar documents
CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT. Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window

ASTM E1886 and ASTM E1996 TEST REPORT. Report No.: E Rendered to: 3M COMPANY St. Paul, Minnesota 55144

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO:

QUANEX BUILDING PRODUCTS TEST REPORT

PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E Rendered to: BAUTEX SYSTEMS

FEATURES. Welded Sash and Main Frame. Swiggle or DuraSeal Spacer System on Fixed Units. 3-1/4" Frame Depth. True Sloped Sill. Integral J Channel

Perma-Shield Gliding Windows (1971 to 1992)

Perma-Shield Gliding Windows

Residential Energy Tax Credit

U-Factor, SHGC & VT Simulated Values with SuperLite II-XL and GPX Framing by SAFTI FIRST

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or

IGUMA - IGU Design Limitations

Beauty-Line Windows (1957 to 1979)

everest efficiency weather tightness durability er tightness durability energy efficiency royalplast.ca

Code Compliance Research Report CCRR-0145

Product information VELUX INTEGRA flat roof window CVP

Kestrel Aluminium Systems Limited. Product Manual Section 10 Thermal Framing System. Manual Version

Test Report. Test Report Smart Systems Limited Incorporating Smart Extrusions. Page 1 of 78

1688 Jean-Berchmans-Michaud Drummondville, Quebec. J2C 8E9. Mr. Marc-Etienne Mathieu,ing.

Argonomics. Low emissivity coatings Argon gas fills Warm edge design FIGURE 1 ADD ARGON ADD INTERCEPT SPACER ADD SINGLE STACK LOW E COATING

CE conform applications according to EN Windows without thermal break Systems Forster presto and Forster norm

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA

Less bars, more light Maxilite Aluminium Roof Lanterns

OS2 F R A M E S E R I E S

SOLAR ENERGY. solutions. adhesives, sealants, and Potting encapsulants For solar energy applications

Report No. 371/ This report consists of 6 pages

CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7

BS EN ISO : 1999

P STYLE 6 LH 5 RH 4 LRH

Energy Performance Data for Krestmark Windows

Evidence of Performance. Class 4. Class 5A. Class C5 / B5. Test Report No PR01. ift Rosenheim

Data Sheet VELUX INTEGRA Roller Blind

Bomb Blast Mitigation Test

Code Compliance Research Report CCRR-0145

P STYLE 6 LH 5 RH 4 LRH

SINGLE HUNG. Operator Units INTEGRITY FROM MARVIN ALL ULTREX SERIES

Product information VELUX Mini Dormer

Product information VELUX Mini Dormer / Takfönsterkupa Mini

Intertek Testing Services Taiwan Ltd.

Appendix A Bridge Deck Section Images

Contents. Miscellaneous Standards. Architectural Systems. Extrusions Australia Pty Ltd Ph: Andretti Court Fx:

Statesville, NC. Results of AM ASHRAE 110 Laboratory Fume Hood Performance Evaluations Venturi Hood

Slide and Turn System SF25

BOAT WINDOWS AND SHOWERS Price List June 2017 Tel/Fax:

Vortrags(kurz)titel EXPORT BUILDING INFORMATION MODELING INTO PROJECT DESCRIPTION

TABLE OF CONTENTS International Racquetball Federation officially approved specifications. Copyright 01/13/1983; rev.

Vertical and Horizontal Bladder Tanks

SAR COMPLIANCE REPORT

TS1. Ultrasonic Tank Sender. Installation and Operating Instructions. For TS1 Firmware v3.8. Page 1 INST-TS1-V13 18/11/10

Surface Test Report. IMPORTANT NOTE: This report does not constitute an ITF Court Pace Classification.

P STYLE 6 LH 5 RH 4 LRH

IEC Test Report for mini-box.com Report No. NF September 29, Test Report

400 Series Circle & Oval Windows (1991 to Present)

DOUBLE HUNG. Operator Units

Intertek Testing Services Building Products. Enterdoor AB ubv

SECTION BUTTERFLY VALVES

CRL COMMERCIAL PATCH HARDWARE WEDGE LOCK STYLE FOR 5/8"-3/4" GLASS TYPICAL HURCULITE WEDGE-LOCK GLASS DOOR ELEVATIONS P STYLE

Banyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL

TESTING APPLICATION STANDARD (TAS)

NFRC Product Certification Authorization Report

GV Standard X-Vent. Setup, Commissioning & Installation Guide

ITF Court Surface Classification Scheme. ISSS Technical Meeting Nyon, October 2002

IDEM Indiana Department of Environmental Management Office of Land Quality P.O. Box 6015 Indianapolis, IN OLQ PH: (317)

TO THE DRAWINGS AND THE PROJECT MANUAL

The following drawings are concerned of this measure, which will be considered in the next revision of the documents as well as in LogiKal.

TOWNSHIP OF DOURO-DUMMER BY-LAW NO

SECTION SHOWER AND BATH ENCLOSURES. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

IN-PLACE DENSITY OF BITUMINOUS MIXES USING THE NUCLEAR MOISTURE-DENSITY GAUGE FOP FOR WAQTC TM 8

TEST REPORT. Solamatrix Inc. GLASS-GARD GGL1200 Multi-ply Window Film and Wetglaze Anchoring System on Single 6mm (1/4 ) Annealed Glass.

FAQs For Board of Outfitters Issues

Technical Report. Title: Product weathertightness testing of a sample of W.G.Ltd 500 series Curtain Walling for The Window Glass Company Limited

MSA Cairns FIRE HELMET PRODUCT SPECIFICATION

Duralite and Duraseal Gas Filling Manual

PRECISION ESTIMATES OF AASHTO T324, HAMBURG WHEEL-TRACK TESTING OFCOMPACTED HOT MIX ASPHALT (HMA) APPENDICES FOR FINAL REPORT

BRANDING OPPORTUNITIES AND GUIDELINES

EN1279 part 3 assessment of insulating glass: IGU with Duralite sealant

Reg No: 1999/027771/07 ACCREDITED AND APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS

Area of existing house. Gross Flr. area excluding parking. (+1,657 basement) Gross Flr. area inc. covered parking & accessory bldg.

24 HOUR CUSTOMER SERVICE

BOTTOM HINGED FLOOD BARRIER

SPECIFICATION FOR RAISED PAVEMENT MARKERS

B ADDENDUM # 1

Architectural Railing Systems

PUBLISHED PROJECT REPORT PPR850. Optimisation of water flow depth for SCRIM. S Brittain, P Sanders and H Viner

Gas Cylinder Cabinets

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Tel: +44 (0) Fax: +44 (0)

David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute 9.0 Appendix: 91

Product information VELUX INTEGRA centre-pivot pine roof window GGL

PROVIDING QUALITY SOLUTIONS FOR THE AUDIOMETRIC INDUSTRY

Installation Instructions

Product information VELUX INTEGRA Solar centre-pivot roof window GGL

Horizontal Bladder Tanks

Table of Contents. Lens Processing Service Lens Processing Service Glass 1 Hard Resin 1 Hi Index 1 Polycarbonate 1

CHANGE RECORDS TABLE OF CONTENTS

INDEPENDENT TESTING OF SPARKLIKE LASER NON-DESTRUCTIVE INSULATING GLASS GAS FILL ANALYZER

CERTIFICATE OF APPROVAL No ME 5088

WRO University Regular Category WRO Bowling Game rules

VER SPORTS PROTECTION VER

THREE-YEAR RE-INSPECTION and ASBESTOS MANAGEMENT PLAN for the

Transcription:

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC. SERIES/MODEL: DH990 Double Hung Report Number: Original Report Date: Revised Report Date: F4008.01-116-45 02/01/16 06/22/16 130 Derry Court York, PA 17406 www.archtest.com www.intertek.com/building p. 717.764.7700 f. 717.764.4129

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC. One Kees Place Merrick, New York 11566 Report Number: Simulation Date: Original Report Date: Revised Report Date: F4008.01-116-45 02/01/16 02/01/16 06/22/16 Project Summary: Architectural Testing, Inc., an Intertek Company (Intertek-ATI) was contracted to perform U- Factor, Solar Heat Gain Coefficient, Visible Transmittance, and Condensation Resistance* computer simulations in accordance with the National Fenestration Rating Council (NFRC). The products were evaluated in full compliance with NFRC requirements to the standards listed *NFRC's Condensation Resistance rating is NOT equivalent to a Condensation Resistance Factor (CRF) determined in accordance with AAMA 1503. Standards: ANSI/NFRC 100-2014: ANSI/NFRC 200-2014: NFRC 500-2014: Procedure for Determining Fenestration Product U-Factors Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence Procedure for Determining Fenestration Product Condensation Resistance Values Software: Frame and Edge Modeling: THERM 6.3.46 Center-of-Glass Modeling: WINDOW 6.3.74 Total Product Calculations: WINDOW 6.3.74 Spectral Data Library: IGDB 47.0 Simulations Specimen Description: Series/Model: DH990 Double Hung Type: Vertical Slider, Double Hung Frame Material: VY Vinyl Sash Material: VY Vinyl Standard Size: 1200mm x 1500mm 130 Derry Court York, PA 17406 www.archtest.com www.intertek.com/building p. 717.764.7700 f. 717.764.4129

F4008.01-116-45 Page 2 of 8 Revised Report Date: 06/22/16 Modeling Assumptions/Technical Interpretations: 1) To prevent air infiltration, tape was applied to all interior sash crack locations. 2) The j-channel and nailing flange for sill 3015 were not modeled because they are deemed removable by the manufacturer. 3) Sills 3012 and 3015 were grouped according to ANSI/NFRC 100-2014, Section 4.2.1.H.i. Specialty Products Table: The specialty products method allow the manufacturer to determine the overall product SHGC and VT for any glazing option. The center of glass SHGC and/or VT must be determined using WINDOW 7.4.8. The method gives overall product SHGC and VT indexed on center of glass properties. All values used in the calculations are truncated to six decimal place precision. No Dividers Dividers < 1 Dividers > 1 SHGC0 0.003115 0.005760 0.008247 SHGC1 0.722331 0.643891 0.570132 VT0 0.000000 0.000000 0.000000 VT1 0.719216 0.638131 0.561885 SHGC = SHGC0 + SHGCc (SHGC1 - SHGC0) VT = VT0 + VTc (VT1 - VT0) Validation Matrix: The following products are part of a validation matrix. Only one is required for validation testing. Product Line Report Number None -

F4008.01-116-45 Page 3 of 8 Revised Report Date: 06/22/16 Spacer Option Description Sealant Spacer Type Primary Secondary Code Quanex Duaraseal Spacer Butyl Rubber - A8-S Quanex Duralite Spacer Butyl Rubber - P1-S Grid Option Description Grid Size Grid Type Grid Pattern None - - Reinforcement Option Description Location Material None - Gas Filling Technique Description Fill Type Method 90% Argon Two-probe with concentration sensor 95% Argon Two-probe with concentration sensor Edge-of-Glass Construction Interior Condition Silicone between rigid PVC sash and glass Exterior Condition Rigid PVC glazing bead with flexible vinyl fin against glass Weatherstripping Type Quantity Location Finpile 2 rows Jamb Stiles Finpile 1 row Top, Lock and Keeper Rails; Sill Adapter Flexible vinyl gasket 1 row Bottom Rail Frame/Sash Materials Finish Interior Vinyl Exterior Vinyl

F4008.01-116-45 Page 4 of 8 Revised Report Date: 06/22/16 NFRC 100/200/500 Summary Sheet DH990 Double Hung ID Pane Thickness 1 Gap Width 1 U-Factor Pane Thickness 2 Gap Width 2 Pane Thickness 3 Gap Width 3 Pane Thickness 4 Gap Fill Solar Heat Gain Coefficient (SHGC) Grids (None / <1 / >=1) 1 NO FOAM: CLR/AIR/CLR (SS/SS) 7/8" 0.090 0.678 0.090 Low-e (Surface#) Tint Visible Transmittance (VT) Grids (None / <1 / >=1) Spacer Grid Type Condensation Resistance AIR CL A8-S N U-Factor 0.46 SHGC (N) 0.58 VT (N) 0.59 2 NO FOAM: CLR/AIR/CS36 (SS/SS) 7/8" 0.090 0.678 0.090 CR 45 AIR 0.027(#3) CL A8-S N U-Factor 0.33 SHGC (N) 0.34 VT (N) 0.48 3 NO FOAM: CLR/AIR/CLR (DS/DS) 7/8" 0.117 0.639 0.117 CR 54 AIR CL A8-S N U-Factor 0.46 SHGC (N) 0.57 VT (N) 0.59 4 NO FOAM: CLR/AIR/CS36 (DS/DS) 7/8" 0.117 0.639 0.128 CR 45 AIR 0.027(#3) CL A8-S N U-Factor 0.33 SHGC (N) 0.34 VT (N) 0.48 5 NO FOAM: CLR/ARG90/CS36 (SS/SS) 7/8" 0.090 0.678 0.090 CR 56 ARG90 0.027(#3) CL A8-S N U-Factor 0.30 SHGC (N) 0.35 VT (N) 0.48 6 NO FOAM: CLR/ARG90/CS36 (DS/DS) 7/8" 0.117 0.639 0.128 CR 57 ARG90 0.027(#3) CL A8-S N U-Factor 0.30 SHGC (N) 0.34 VT (N) 0.48 7 NO FOAM: CS36/AIR/CLR (SS/SS) 7/8" 0.090 0.678 0.090 CR 57 AIR 0.027(#2) CL A8-S N U-Factor 0.33 SHGC (N) 0.26 VT (N) 0.48 8 NO FOAM: CS36/AIR/CLR (DS/DS) 7/8" 0.128 0.639 0.117 CR 54 AIR 0.027(#2) CL A8-S N U-Factor 0.33 SHGC (N) 0.26 VT (N) 0.48 9 NO FOAM: CS36/ARG90/CLR (SS/SS) 7/8" 0.090 0.678 0.090 CR 56 ARG90 0.027(#2) CL A8-S N U-Factor 0.30 SHGC (N) 0.26 VT (N) 0.48 10 NO FOAM: CS36/ARG90/CLR (DS/DS) 7/8" 0.128 0.639 0.117 CR 57 ARG90 0.027(#2) CL A8-S N U-Factor 0.30 SHGC (N) 0.26 VT (N) 0.48 CR 57

F4008.01-116-45 Page 5 of 8 Revised Report Date: 06/22/16 NFRC 100/200/500 Summary Sheet DH990 Double Hung ID Pane Thickness 1 Gap Width 1 Pane Thickness 2 Gap Width 2 Pane Thickness 3 Gap Width 3 Pane Thickness 4 Gap Fill Low-e (Surface#) Tint Spacer Grid Type U-Factor 11 NO FOAM: SB70/ARG95/CS73 (SS/SS) 7/8" Solar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance 0.089 0.678 0.087 ARG95 0.018(#2) / 0.148(#4) CL A8-S N U-Factor 0.25 SHGC (N) 0.19 VT (N) 0.44 12 NO FOAM: E366/ARG95/CS73 (SS/SS) 7/8" 0.087 0.678 0.087 CR 46 ARG95 0.022(#2) / 0.148(#4) CL A8-S N U-Factor 0.26 SHGC (N) 0.19 VT (N) 0.44 13 NO FOAM: CS28/AIR/CS73 (DS/DS) 7/8" 0.125 0.639 0.123 CR 46 AIR 0.021(#2) / 0.148(#4) CL A8-S N U-Factor 0.28 SHGC (N) 0.20 VT (N) 0.41 14 NO FOAM: CLR/AIR/CLR (SS/SS) 7/8" 0.090 0.678 0.090 CR 45 AIR CL P1-S N U-Factor 0.45 SHGC (N) 0.58 VT (N) 0.59 15 NO FOAM: CLR/AIR/CS36 (SS/SS) 7/8" 0.090 0.678 0.090 CR 46 AIR 0.027(#3) CL P1-S N U-Factor 0.32 SHGC (N) 0.34 VT (N) 0.48 16 NO FOAM: CLR/AIR/CLR (DS/DS) 7/8" 0.117 0.639 0.117 CR 57 AIR CL P1-S N U-Factor 0.45 SHGC (N) 0.57 VT (N) 0.59 17 NO FOAM: CLR/AIR/CS36 (DS/DS) 7/8" 0.117 0.639 0.128 CR 46 AIR 0.027(#3) CL P1-S N U-Factor 0.32 SHGC (N) 0.34 VT (N) 0.48 18 NO FOAM: CLR/ARG90/CS36 (SS/SS) 7/8" 0.090 0.678 0.090 CR 59 ARG90 0.027(#3) CL P1-S N U-Factor 0.28 SHGC (N) 0.35 VT (N) 0.48 19 NO FOAM: CLR/ARG90/CS36 (DS/DS) 7/8" 0.117 0.639 0.128 CR 60 ARG90 0.027(#3) CL P1-S N U-Factor 0.28 SHGC (N) 0.34 VT (N) 0.48 20 NO FOAM: CS36/AIR/CLR (SS/SS) 7/8" 0.090 0.678 0.090 CR 60 AIR 0.027(#2) CL P1-S N U-Factor 0.32 SHGC (N) 0.26 VT (N) 0.48 CR 56

F4008.01-116-45 Page 6 of 8 Revised Report Date: 06/22/16 NFRC 100/200/500 Summary Sheet DH990 Double Hung ID Pane Thickness 1 Gap Width 1 Pane Thickness 2 Gap Width 2 Pane Thickness 3 Gap Width 3 Pane Thickness 4 Gap Fill Low-e (Surface#) Tint Spacer Grid Type U-Factor 21 NO FOAM: CS36/AIR/CLR (DS/DS) 7/8" Solar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance 0.128 0.639 0.117 AIR U-Factor 0.32 SHGC (N) 0.26 VT (N) 0.48 22 NO FOAM: CS36/ARG90/CLR (SS/SS) 7/8" 0.090 0.678 0.090 0.027(#2) CL P1-S N CR 59 ARG90 0.027(#2) CL P1-S N U-Factor 0.28 SHGC (N) 0.26 VT (N) 0.48 23 NO FOAM: CS36/ARG90/CLR (DS/DS) 7/8" 0.128 0.639 0.117 CR 60 ARG90 0.027(#2) CL P1-S N U-Factor 0.28 SHGC (N) 0.26 VT (N) 0.48 24 NO FOAM: SB70/ARG95/CS73 (SS/SS) 7/8" 0.089 0.678 0.087 CR 60 ARG95 0.018(#2) / 0.148(#4) CL P1-S N U-Factor 0.24 SHGC (N) 0.19 VT (N) 0.44 25 NO FOAM: E366/ARG95/CS73 (SS/SS) 7/8" 0.087 0.678 0.087 CR 49 ARG95 0.022(#2) / 0.148(#4) CL P1-S N U-Factor 0.24 SHGC (N) 0.19 VT (N) 0.44 26 NO FOAM: CS28/AIR/CS73 (DS/DS) 7/8" 0.125 0.639 0.123 CR 49 AIR 0.021(#2) / 0.148(#4) CL P1-S N U-Factor 0.27 SHGC (N) 0.20 VT (N) 0.41 27 NO FOAM: CS28/ARG90/CS73 (SS/SS) 7/8" 0.087 0.678 0.087 CR 47 ARG90 0.023(#2) / 0.148(#4) CL P1-S N U-Factor 0.24 SHGC (N) 0.19 VT (N) 0.43 28 FOAM: CS28/ARG95/CS73 (DS/DS) 7/8" 0.125 0.639 0.123 CR 49 ARG95 0.021(#2) / 0.148(#4) CL P1-S N U-Factor 0.22 SHGC (N) 0.19 VT (N) 0.41 CR 40

F4008.01-116-45 Page 7 of 8 Revised Report Date: 06/22/16 The Condensation Resistance results obtained from this procedure are for controlled laboratory conditions and do not include the effects of air movement through the specimen, solar radiation, and the thermal bridging that may occur due to the specific design and construction of the fenestration system opening. Ratings values included in this report are for submittals to an NFRC-licensed IA and are not meant to be used directly for labeling purposes. Only those values identified on a valid Certification Authorization Report (CAR) by an NFRC accredited Inspection Agency (IA) are to be used for labeling purposes. The ratings values were rounded in accordance to NFRC 601, NFRC Unit and Measurement Policy. Intertek-ATI is an NFRC accredited simulation laboratory and all simulations were conducted in full compliance with NFRC approved procedures and specifications. The values included in this report are not considered in compliance with ANSI/NFRC 100, ANSI/NFRC 200, and/or NFRC 500 unless the associated validation test requirements have been satisfied, as applicable. Intertek-ATI will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Intertek-ATI for the entire test record retention period. The test record retention end date for this report is February 1, 2020. Results obtained are simulated values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the product simulated. This report may not be reproduced, except in full, without the written approval of Intertek-ATI For INTERTEK-ATI: SIMULATED BY: REVIEWED BY: Megan M. Yingst Simulation Technician Kristen L. Louder Senior Simulation Technician Simulator-In-Responsible-Charge MMY:mmy F4008.01-116-45 Attachments (pages): This report is complete only when all attachments listed are included. Appendix A: Drawings and Bills of Material (16)

F4008.01-116-45 Page 8 of 8 Revised Report Date: 06/22/16 Revision Log Rev. # Date Page(s) Revision(s).01R0 02/01/16 All Original report issued to North East Windows USA, Inc..01R1 06/22/16 All Revised models (part 3012) to match part drawings; updated results. This report produced from controlled document template ATI 00037, Revised 10/2/2012.

All drawings and Bills of Material used to simulate this product are enclosed in this Appendix Appendix A F4008.01-116-45