MSC Guidelines for Independent Fuel Tanks

Similar documents
MSC Guidelines for Vents, Fills and Sounds

MSC Guidelines for Pressure Vessels

MSC Guidelines for Engine Cooling Systems

MSC Guidelines for Compressed Air Systems

MSC Guidelines for Sanitary & Sewage Systems

MSC Guidelines for Refrigeration Machinery

MSC Guidelines for Review of Inland Tank Barge Stability Procedure Number: C1-13 Revision Date: May 13, 2016

MSC Guidelines Potable Water Systems

T. O. PHILLIPS, CDR, Tank Vessel and Offshore Division

MSC Guidelines for Gas Carrier Barge Cargo Authority Procedure Number: C1-41 Revision Date: January 27, 2012

MSC Guidelines for Review of Vapor Control Systems Procedure Number: C1-46 Revision Date: 01/08/2018

MSC Guidelines for the Review of Vapor Control Systems Procedure Number: C1-46 Revision Date: March 30, 2012

MSC Guidelines for Tank Barge General Arrangements Procedure Number: C1-16 Revision Date: June 1, 2017

MSC Guidelines for Review of Stability for Sailing Catamaran Small Passenger Vessels (T)

MSC Guidelines for Review of General Arrangement Plans for Small Passenger Vessels (T)

MSC Guidelines for Review of Cargo and Miscellaneous Vessel Stability (Subchapter I)

MSC Guidelines for Review of Passenger Vessel Stability (Subchapters K & H)

MSC Guidelines for Review of Gas Carrier/Barge Structures

MSC Guidelines for Review of Emergency Evacuation Plans (NVIC 8-93)

MSC Guidelines for Carbon Dioxide Fire Suppression Systems

MSC Guidelines for Review of Gas Carrier Stability (Intact, Damaged, Lightship, and Special Loading Authorization)

MSC Guidelines for Review of Emergency Evacuation Plans (Subchapter K)

MSC Guidelines for the Review of Mobile Offshore Drilling Unit (MODU) General Arrangement Plans Procedure Number: C2-36 Revision Date: 10/18/2016

Guidelines for Clean Agent Fire Suppression Systems

MSC Guidelines for Review of General Arrangements (Subchapters H, I, K, R, & U)

Rules for the Installation, Inspection and Testing of Air Reservoirs (Other than on Locomotives)

MSC Guidelines for Bilge and Ballast Systems

MSC Guidelines for Review of Stability for Towing Vessels (M)

MSC Guidelines for Liquefied Gas Barge General Arrangements

MSC Guidelines for the Submission of Stability Test (Deadweight Survey or Inclining Experiment) Results

Horizontal Bladder Tanks

Vertical Bladder Tanks

MSC Guidelines for the Review of OSV Stability

ASME Boiler & Pressure Vessel Code Analysis of the 1497 MHz High-Current Cryomodule Helium Vessel

Liquefied gas cargo tanks and process pressure vessels

Model MTB-ASME Vertical Bladder Tanks

Model MTB-ASME Horizontal Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

Regulations Respecting Compressed Gas Pressure Vessels

Vertical and Horizontal Bladder Tanks

Use equation for the cylindrical section and equation or for the ends.

PIP PNE00012 Piping Examination and Leak Test Guide

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

MSC Guidelines for Review of Rigging Systems for Sailing Vessels

MSC Guidelines for Fire Main Systems Procedure Number: E1-09 Revision Date: 04/16/2018

HOT OILING OPERATIONS ALL HSE PRC 172. Approved By: Manager, HSE Performance Assurance. Table of Contents

TP1 and TP2 Temporary Cone Shaped Strainers

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124

Limited quantities of compressed gases.

WELCOME to CAUx Local India 2018

U.S. COAST GUARD MARINE SAFETY CENTER PLAN REVIEW GUIDELINE

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

High-Pressure Boiler Inspection Procedures: A Complete Checklist

VERTICAL BLADDER TANK

General Inspection Guidance for Waste Management Units Requiring Air Emission Controls Under RCRA Air Standard Subpart CC

HORIZONTAL BLADDER TANK

OPENINGS AND REINFORCEMENTS 26

Marine Safety Center Technical Note

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS

Design of Pressure vessel for the Hydrocarbon release from the Vent Header Lines

CERTIFICATION OF COMPLIANCE OF THE USER S DESIGN SPECIFICATION

PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys

A Rationale for Pressure Relief Device(s) Qualification Requirements (LH2)

TECHNICAL DATA OBSOLETE

The capacity of the cargo tank venting system (46 CFR );

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

MSC Guidelines for Commercial Fishing Vessel Stability Procedure Number: H2-20 Revision Date: 06/17/2013

Flange Bolt Torquing. for Resistoflex Plastic-Lined Piping Products. Torquing. Retorquing. Hydrotesting. Annual retorquing

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

THE PROCESS OF JOINT INTEGRITY

INJECTION ODORIZING SYSTEMS : DOSAODOR TYPE

Other Si min/max. Cr min/max. 0.4/ / / / Bal.

RULES OF TENNESSEE WILDLIFE RESOURCES AGENCY BOATING AND LAW ENFORCEMENT

Cast iron swing check valve. BS EN 12334:2001 PN16

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT. Number: 2015 IFC Effective Date: February 1, 2017 Page 1 of 5

Section 20 TABLE OF CONTENTS Pressurized Equipment and Systems. 20.A General B Compressed Air and Gas Systems

CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems.

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

INTERLOCKED METAL HOSE

PRESSURE RETEST. 49 CFR, (g) Co#: Vin#: DOT Spec: MAWP:

Health and Safety at Work (Hazardous Substances Reduced Secondary Containment for Certain Above Ground Stationary Tanks) Safe Work Instrument 2017

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT

CURI Pierside Stainless Diesel Tank

Check with local zoning official for property line distance requirements.

Pipe Thread Connection 1/2 inch NPT. Friction Loss Refer to Figure 3

East Building, PHH-30 U.S. Department New Jersey Avenue S.E. of Transportation Washington, D.C DOT-SP (ELEVENTH REVISION)

STANDARD SPECIFICATION FOR SPLIT TEES (HOT TAP MATERIAL)

Installation of Ballast Water Management Systems

KC Series Gas Components and Supply Design Guide

STORAGE OF COMPRESSED GAS CYLINDERS (SAF-SPI-15)

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

SECTION BUTTERFLY VALVES

RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF MOBILE OFFSHORE DRILLING UNITS TITLE MOBILE OFFSHORE DRILLING UNITS SECTION 6 PIPING CHAPTERS SCOPE

Model C Pipe Line Strainer 6, 8 & 10 Inch (DN150, DN200 & DN250) 250 psi (17,2) General Description. Technical Data. Page of 6 MAY, 2006 TFP1644

MSC Guidelines for the Review of Oil Spill Response Vessels (OSRV), Lightship and Stability

GUIDELINES. Systems. Pressure. Guidelines Acceptance of equipment, establishment of safe operating limits and fitness for service

[Reserved] Packagings ICC 3 1 3AA 3AL 3AX 3A480X 3AAX

Transcription:

References: Contact Information a. 46 CFR 58.50 (Independent Fuel Tanks) b. 46 CFR 119.440 (Independent Fuel Tanks) c. 46 CFR 182.440 (Independent Fuel Tanks) C. J. Robuck, LCDR, Chief, Engineering Division d. CG-5213 Policy Letter 9260 dated January 12, 2011, Notice Regarding Flanged Cleanouts for Independent Fuel Tanks Located on Weather Decks of Unmanned Barges If you have any questions or comments concerning this document, please contact the Marine Safety Center by e-mail or phone, referring to Procedure Number: E1-16. E-mail: MSC@uscg.mil Phone: 202-795-6729 Website: www.dco.uscg.mil/msc Responsibilities: Using applicable portions of references (a) through (d), the submitter shall provide sufficient documentation and plans to indicate compliance with the applicable requirements. Design calculations are required for tanks larger than 400 gallons. To facilitate plan review and project management, all plans and information specified in these guidelines should be submitted as one complete package through a single point of contact for the project. General Guidance: Independent tanks are freestanding; that is, the tank boundaries are not common to the ship s structure. Independent tanks are permanently affixed to the vessel and are not intended for removal from the vessel. Independent tanks intended for storage of combustible or flammable products or hazardous NLS must be designed in accordance with 46 CFR 58.50 or an industry standard which provides a level of safety equivalent to that required by 46 CFR 58.50. General design criteria for rectangular tanks having capacity < 400 gallons (Subchapter F) Materials and plate thickness shall not be less than those listed in Table 58.50-10(a).

Vertical baffle plates shall be provided at intervals not to exceed 30 inches in any horizontal dimension. The plates shall be of the same material and not less than the minimum required plate thickness. (46 CFR 58.50-10(a)(7)) Where baffle plates are provided at less than 30 inch intervals, baffles plates are omitted completely or the design is not in accordance with 58.50, the following design criteria are acceptable: a) ABS Deep Tank rules; the design head shall be based on a height not less than four feet above the tank top. Use ABS Steel Vessels on Rivers & Intracoastal Waterways, Steel Vessels < 295 Feet, or Steel Vessel rules, as appropriate, to verify the design. b) Other acceptable industry design standards may be utilized. The design head shall be equal to hydrostatic load at 4 feet above the tank top PLUS dynamic load estimated by the following: Dynamic load = K(L h )/(B + 1), where: K = 0 for rivers routes 1 for lakes bays and sound routes 2 for oceans routes L h = Hydrostatic Load B = Number of baffles General design criteria for rectangular tanks having capacity > 400 gallons (Subchapter F) Plate thickness and structures must be determined by calculations; however, materials and plate thickness shall not be less than those listed in Table 58.50-10(a). The design shall provide a safety factor of 4 based on the ultimate strength of the plating materials. The design head (load) shall be based on a height of not less than 4 feet above the tank top. Vertical baffle plates shall be provided at intervals not to exceed 30 inches in any horizontal dimension. The plates shall be of the same material and not less than the minimum required plate thickness. Where baffle plates are provided at less than 30 inch intervals, baffles plates are completely omitted or the design is not in accordance with 58.50, the following design criteria are acceptable: 2

a) ABS deep tank rules; the design head shall not be less than four feet above the tank top. Use ABS Steel Vessels on Rivers & Intracoastal Waterways, Steel Vessels < 295 Feet, or Steel Vessel rules, as appropriate. b) Other acceptable industry design standards may be utilized. The design head shall be equal to hydrostatic load at 4 feet above the tank top PLUS dynamic load as noted for tanks < 400 gallons. General design criteria for cylindrical tanks (Subchapter F) Tank design may be in accordance with ASME Boiler and Pressure Vessel Code (BPVC), Section V111, Division 1. Materials and plate thickness shall not be less than those listed in Table 58.50-10(a). a) The design shall provide a safety factor of 4 based on the ultimate strength of the plating materials. The design head (load) shall be based on a height of not less than 4 feet above the tank top. b) Part UG of BPVC shall be used for head and shell design and Part UW for weld details. A joint efficiency (E) of 1 is acceptable. Radiography is not required. c) Flat heads must be designed to have the appropriate stiffeners and support. Use of ABS deep tank rules or ASME Pressure vessel code is acceptable for the flat head design. Vertical baffle plates shall be provided at intervals not to exceed 30 inches in any horizontal dimension. The plates shall be of the same material and not less than the minimum required plate thickness. Where baffle plates are provided at less than 30 inch intervals, baffles plates are completely omitted or the design is not in accordance with 58.50, the design head shall be equal to hydrostatic load at 4 feet above the tank top PLUS dynamic load as noted for tanks < 400 gallons. Requirements for all tanks (subchapter F) Fill, return, and vent openings shall be located on the tank top. Openings in the bottom or sides of the tank are limited to supply piping, a threaded plug or cap for cleaning purposes and level gauges. Location of machinery fuel supply piping penetrations is unrestricted. Use of manholes located on the tank sides or bottom is prohibited. (Title 46 CFR 58.50-10(a)(4)) 3

a) Independent tanks located on unmanned barge weather decks may be provided with a nozzle and blank flange assembly for cleanout purposes subject to the following: (reference (d)) i. Location on the tank is unrestricted ii. Nozzle must be welded to the tank iii. Flange must be at least ASME B16.5, Class 150 iv. Gasket must be appropriate for the fluid in the tank v. Flange shield is required on the flange IAW ASTM F1138. Liquid level gauge connections shall be located at more than two inches from the bottom of the tank. The gauges shall be constructed of heat resistant materials, be adequately protected from damage and be fitted with self-closing valves located at the tank connection. (46 CFR 58.50-10(a)(4) & (6)) Positive shut-off valves, located at the tank, are required in piping subject to head pressure from the fuel in the tanks. The valve shall be operable from outside the space in which the tank is located. (46 CFR 56.50-60(d)) Fuel oil tank vents shall extend above the weather deck at a location not less than three feet from any opening into any living quarters. (46 CFR 56.50-85(a)(4)) Small tanks may have a vent not more than 25% greater in cross sectional area than the fill line; otherwise the tank vent size shall not be less than 2.5 inches. (46 CFR 56.50-85(a)(10)) Fuel tank vents shall be fitted with a single flame screen of 30 by 30 mesh or two screens of at least 20 by 20 mesh. (46 CFR 56.50-85(a)(8)) Tanks shall be electrically bonded to the common ground. (46 CFR 58.50-10(b)(5)) Installation of portable fuel tanks is not permitted. (46 CFR 58.50-10(b)(4)) The interior of tanks shall not be galvanized. The exterior of the tanks shall be protected from corrosion. (46 CFR 58.50-10(a)(9)) Fuel tanks shall be located as near as possible to the space being served. Tanks used for emergency lighting systems shall be located on an open deck 4

or in an adequately ventilated metal compartment. Maximum compartment temperature for all tanks is 150 F. (46 CFR 58.50-10(b)(1)) Longitudinal seams on cylindrical tanks shall be located at the top of the tank. (46 CFR 58.50-10(b)(2)) Tanks with flanged up edges which may trap moisture are prohibited. (46 CFR 58.50(a)(3)) Nozzle, flange and pipe connections shall be brazed or welded to the tank. (46 CFR 58.50-10(a)(5)) Baffle plates shall be connected to the walls by welding or brazing. Limber holes shall be provided at the bottom and top of the baffle plates. (46 CFR 58.50-10(a)(7)) The location of tanks shall be such to allow for examinations, testing and cleaning. (46 CFR 58.50-10(b)(3)) Tanks on small passenger vessels (subchapters T and K) Tank material and thickness must be as indicated in Table 182.440(a)(1) or 119.440(a)(1), as appropriate. Tanks having a capacity over 570 liters (150 gallons) must be designed to withstand maximum head that they may be subject to, but in no case can thickness be less than specified in the appropriate table. (46 CFR 182.440(a)(1), 46 CFR 119.440(a)(1)) Other materials that provide an equivalent level of safety can be approved by the Commandant. (46 CFR 182.440(a)(3), 46 CFR 119.440(a)(3)) FRP tanks may be used for diesel fuel tanks provided: a) The material is fire retardant (flammability determined by ASTM D 635 and ASTM D 2863). Average extent of burning must be less than 10mm (0.394in), the average burn time is less than 50 seconds, and the limiting oxygen index is greater than 21. (46 CFR 182.440(a)(2)(i), 46 CFR 182.440(a)(2)(i)) b) The tanks meet UL 1102. (46 CFR 182.440(a)(2)(ii), 46 CFR 119.440(a)(2)(ii)) c) Baffle plates, if installed, must be the same material and not less than the minimum thickness of the tank walls. Limber holes at the bottom and air 5

holes at the top must be provided. (46 CFR 182.440(a)(2)(v), 46 CFR 119.440(a)(2)(v)) Openings for fill, vent, and fuel supply pipes must be on the topmost surfaces of the tank except for threaded plugs or caps for tank cleaning or openings for supply piping or tubular gauge glasses in diesel fuel tanks. (46 CFR 182.440(a)(5), 46 CFR 119.440(a)(5)) All tank joints, nozzles, flanges, or other pipe connection fittings to a metal tank must be welded or brazed. (46 CFR 182.440(a)(6-7), 46 CFR 119.440(a)(6-7)) Vertical baffle plates must be fitted for metal tanks that exceed 760mm (30in) in any horizontal direction. (46 CFR 182.440(a)(8), 46 CFR 119.440(a)(8)) Baffles must be the same material and not less than the minimum thickness required in the tank walls. They must be connected by welding or brazing. (46 CFR 182.440(a)(9), 46 CFR 119.440(a)(9)) There must be a means of accurately determining the amount of fuel in each tank. (46 CFR 182.445(b), 46 CFR 119.445(b)) Gasoline fill pipes and sounding pipes must extend to within one-half of their diameter from the bottom of the tank on vessels certificated under subchapter T. The use of gasoline in independent fuel tanks on vessels certificated under subchapter K is only acceptable on a case-by-case basis, as determined by the Commandant. (46 CFR 182.445(e), 46 CFR 119.405) Each unpressurized fuel tank must be fitted with a vent pipe connected to the highest point of the tank, and that vent pipe must be protected by a flame screen or flame arrestor. (46 CFR 182.450, 46 CFR 119.450) Disclaimer: This guidance is not a substitute for applicable legal requirements, nor is it itself a rule. It is not intended to nor does it impose legally-binding requirements on any party. It represents the Coast Guard s current thinking on this topic and may assist industry, mariners, the general public, and the Coast Guard, as well as other federal and state regulators, in applying statutory and regulatory requirements. You can use an alternative approach for complying with these requirements if the approach satisfies the requirements of the applicable statutes and regulations. If you want to discuss an alternative, you may contact the Marine Safety Center (MSC), the unit responsible for implementing this guidance. 6