Evaluating 2-1/2 Direct Fill Lines Colton, New York

Similar documents
Tanker Fill Tests. Evaluating Direct Fill Lines DeKalb County, Alabama. November 16, Tests DeKalb County, AL

Chapter 14 Water Shuttle Operations

PROPERTY INSURANCE ASSOCIATION OF LOUISIANA

Flow Material Length. Weight GPM LPM. Style 3095

PHILADELPHIA FIRE DEPARTMENT HIGH PRESSURE FIRE HYDRANT SYSTEM PFD TRAINING MANUAL SUPPLEMENT ENGINE PRACTICES SUPPLEMENT 101 PAGE 1

TurboDraft Fire Eductor

Developed by Engineer Ben Wynkoop, Lieutenant Randy Stuart, and Firefighter Alex Klinger September 2011

TurboDraft. Fire Eductor Operating Instructions.

Water Thiefs APPLIANCES APPLIANCES WATER THIEFS

AirCannonPlans.Com. High Powered Water Cannon

Apparatus Operator Refresher Training Program

Essentials of Fire Fighting

Replace Old Obsolete Systems!

Water Supply for Suburban and Rural Firefighting

Developed by Lt. Randy Stuart Eng. Ben Wynkoop, and FF. Alex Klinger in Sept 2011

then the work done is, if the force and the displacement are in opposite directions, then the work done is.

MANUAL FLOW CONTROL 2-1/2" - 18" QUICKSET FLOW CHART

SEMI FIXED/PORTABLE LINE PROPORTIONERS SLP NPR270

Atlantic County Tender Task Force B Bravo Division When Atlantic County Tender Task Force B is required the following procedure should be followed:

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

PRO SINK -R 1 and 2. Dilution system CONTENTS

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

INSTRUCTOR GUIDE REFERENCES: PUMPING APPARATUS DRIVER/OPERATOR HANDBOOK, FIRST EDITION, IFSTA

Des Plaines Fire Dept. Engineer Program

Cozumel Turbodraft. Operational Considerations

Portable Hydrostatic Pneumatic Test Pump. Procedure Manual

MUSTER Page 1

Storage Systems and Accessories

1 Exam Prep. Tabs and Highlights

Essentials of Fire Fighting 6 th Edition Firefighter I

Varying pump capacity affects the required hoseline diameter

VERTICAL BLADDER TANK

Installation Instructions for NP100 Series Nitrogen Control Panels

Upon completion of this unit of study, the student should be able to: 1. Identify the parts of a water distribution system.

The Evaluator shall ask the Apparatus Driver/Operator questions regarding the mechanical systems and size of the apparatus.

Pumping Systems for Landscaping Pumps, Controls and Accessories. Mark Snyder, PE

APPS-160 Gen 2 User Manual

Portable Hydrostatic Electric Test Pump. Procedure Manual. Dixon 800 High Street Chestertown, MD Fax: dixonvalve.

Briggs linear 4-wheel chassis irrigation booms. Models R50/2 R57/2 R60/2 R64/2 R76 lane spacing from 50 to 96 metres

2.5 & 5.0 GALLON PRESSURE TANKS

Blue Points 1 ¼ WELL POINT INSTALLATION INSTRUCTIONS

Odorization Program and Odorizer Updates Regulator Station Updates

MEDICAL EQUIPMENT CATALOG

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised

Liquid Level Controllers

A T JUNIPER (LIVERPOOL) Ltd. Juniper 2x25 Gallon Multi-Engine Compressor Washing Rig Part No. JMP/CFM56/D/4777/C400

ETL listed for installations within 5 ft. (1.5M) of outer edge of water

Vertical and Horizontal Bladder Tanks

KILGORE FIRE DEPARTMENT

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

ABRASIVE SYSTEM ABRASIVE REGULATOR II 800# BULK ABRASIVE DELIVERY POT Abrasive Regulator II and 800# Pot Manual

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2014 Edition)

PRODUCT INFORMATIONAL BULLETIN

Installation Manual. Model # SF-3W 9/16/03 REV 1. Arch Chemicals, Inc Lower River Road. P.O. Box 800 Charleston, TN PULSAR

SECRETARY OF THE AIR FORCE 17 APRIL 2000 LOADMASTER MAFFS CHECKLIST. Summary of Revisions: Redundant pages removed.

HORIZONTAL BLADDER TANK

FOAM TANK (1/2) DATA SHEET

III. Identify the initial installation requirements for standpipe systems

Rain Barrels. Did You Know?

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller.

Pumping Apparatus Driver/Operator Apparatus Testing. Chapter Test. Directions: Write the correct letter on the blank before each question.

Standard Operating and Maintenance Instructions for Pumping System Model PS-150

APPLICATION FOR A PERMIT TO CONSTRUCT OR ALTER A PUBLIC SWIMMING POOL, SPA POOL, WADING POOL OR FOUNTAIN

Models 106-RF / 206-RF Rate of Flow Control Valve

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C

Office Use Only Fee Paid

Apparatus Driver/Operator Evaluation Form Rosenbauer Tanker:

COPY OF STATE CHARTER & CONTRACT WITH CITY / COUNTY, INDICATING DISTRICT OF AUTHORITY, MUST ACCOMPANY THIS CERTIFICATE OF ELIGIBILITY

Irrigation System Winterization and Pressurization Procedures

Water Hammer In Irrigation Systems 1

Horizontal Bladder Tanks

Vertical Bladder Tanks

FIREFIGHTING EQUIPMENT

Instruction presentation Special valves

Family Swimming Pool Planning Guide

Operating Instructions Model and Hydrostatic Test Pump

All information correct as of 25 th September 2013 and subject to change without notice. 6 inch HURRICANE modular dredge equipment operations manual.

PARTS LIST FOR ELBOWS, COUPLERS,TUBING & HOSES

Variable Rate Manure Spreader: Technology to Validate a Nutrient Management Plan

Check & Demo Shielding Gas Waste. Index

GETZ EQUIPMENT INNOVATORS RECOVERY SYSTEM CLEAN AGENT FE-36 / HALOTRON 1 PART NO. 4G59751 OPERATIONS MANUAL

!!!! SERVICE MANUAL PRESSURE POT 2 GALLON. Service Manual: LT Washington St 931 Progress Ave., #7

The Glockemann Pump Site & Installation Guide

Chapter Overview. NFPA Standards NFPA 1001 Standard. Fire Fighter I

Putting it All Together: Making Sense of Drip Irrigation UC Master Gardener Conference August 24, 2017

Appendix K Appendix K

KJ4000 Operating Instructions & Parts Manual NSN

Cable Pressurization Buffering

POOL AND HOT TUB/SPA REGULATIONS A BUILDING PERMIT IS REQUIRED BEFORE THE INSTALLATION OF A POOL.

Please Contact Do It American for Pricing

ABRASIVE REGULATOR II

Air Eliminators and Combination Air Eliminators Strainers

OPERATING MANUAL LO-CROSS-FLOW CF M

ABRASIVE REGULATOR II

Installation Guide. buoy.ai

Optimizing Gas Supply for Industrial Lasers

Model MTB-ASME Vertical Bladder Tanks

HYDRANT/WATER POINT INSPECTION AND MAINTENANCE

DW Module 8: Distribution Answer Key

Model MTB-ASME Vertical Bladder Tanks

Transcription:

www.gotbigwater.com Tanker Fill Tests Evaluating 2-1/2 Direct Fill Lines Colton, New York August 24, 2008

Overview On August 23 rd and 24 th, 2008, the Colton (NY) Fire District hosted a Rural Water Supply Operations Seminar and Drill presented by GBW Associates, LLC. During the drill, it became obvious that all of the tankers were hampered in their fill times when using their 2-1/2- inch direct fill lines. After the water shuttle drill on second day of the seminar, several tankers were tested using various fill methods in an effort to show which methods worked best in terms of reducing fill times. The results of those tests are documented in this presentation.

The Tankers Colton Tanker 4 1978 Saulsbury tanker body/ 2003 International Chassis 1,800 gallon tank Hale 350 gpm PTO pump 10-inch square dump (with rear, side adaptor chute) One, 2-1/2-inch direct fill line w/quarter-turn ball valve.

The Tankers Colton Tanker 88 1978 Saulsbury tanker body/ 2003 International chassis 1,800 gallon tank Hale 350 gpm PTO pump 10-inch square dump (with rear, side adaptor chute) One, 2-1/2-inch direct fill line w/quarter-turn ball valve.

The Tankers Pierrepont Tanker 35 1989 Four Guys 1,800 gallon tank Hale 500 gpm pump 8-inch round dump w/cam lock flexible tube Two, 2-1/2-inch direct fill lines w/quarter-turn ball valves.

The Tankers Hopkinton Engine Tanker 44 1981 E-One 2,200 gallon tank Hale 1,500 gpm pump 5-inch round dump equipped with a Jet Dump No direct fill must be filled back through the dump or through the pump.

The Problem All four of the tankers had small, 2-1/2inch direct fill lines three of them had a 2-1/2-inch, ¼-turn ball valve as their control mechanism. The small, direct fill lines seemed to result in personnel wanting to connect 2-1/2-inch hose to the inlets. The use of 2-1/2-inch hose to fill the tankers resulted in very slow fill times when compared with how fast the tankers could dump.

2-1/2-inch Direct Fills Tanker 4 Tanker 88 When used with 2-1/2-inch hose, these direct fills severely hampered fill times during the drill. Tanker 35 Engine/Tanker 44

The Hypothesis Using 4-inch hose connected directly to a tanker s 2-1/2-inch direct fill inlet will improve the tanker s fill rate. Using an over-the-top fill pipe will improve a tanker s fill rate in comparison to using a 2-1/2-inch direct fill inlet.

The Test Set-up Colton FD s fire boat was used to pump the water needed for the tests. The boat was set-up to draft along the shore of the Raquette River and it pumped to a 4 x 2-1/2 x 2-1/2 gated wye, uphill through 300 ft of 4 LDH.

The Test Set-up The gated wye had a pressure gauge placed in-line between the wye and the 4-inch supply hose. The gauge was used to measure inlet pressure at the wye. A 100-ft length of 2-1/2- inch or 4-inch was then used to connect to the direct fill inlets on the tankers. In-line Gauge Water Flow

Establishing Constants In order to collect comparable data, a few constants had to be established. When pumping to the gated wye, the fireboat would always maintain a reading of 50 psi on the in-line gauge with water flowing. When connecting the 4-inch hose to the direct fills, a 4 x2-1/2 adaptor would always be used. The hose lines used for filling would always be 100-ft in length from the wye to the direct fill inlet. All tankers were completely empty before being filled.

Test Results: Tanker 4 Single, 2-1/2 fill hose connected to the 2-1/2 direct fill 6 minutes, 42 seconds 268 gpm Single, 4 fill hose connected to the 2-1/2 direct fill 2 minutes, 53 seconds 625 gpm A 133% improvement over a single, 2-1/2 hose!

Test Results: Tanker 4 w/fill Pipe Because Tanker 4 has a ladder rack over top of its hose bed, a decision was made to fashion a 4, overthe-top fill pipe that would allow a direct flow of water into the tank s fill tower. The fill pipe was made using Schedule 40 PVC pipe and it was outfitted with a 4 Storz swivel connection. The pipe was anchored to the ladder rack so that no one would have to hold the device during the fill process.

Test Results: Tanker 4 w/fill Pipe Single, 4 fill hose connected to the 4 over the top fill pipe 2 minutes, 15 seconds 800 gpm A 199% improvement over a single, 2-1/2 hose line!

Test Results: Tanker 88 Single, 2-1/2 fill hose connected to the 2-1/2 direct fill 5 minutes, 32 seconds 325 gpm Single, 4 fill hose connected to the 2-1/2 direct fill 3 minutes, 12 seconds 563 gpm A 73% improvement over a single, 2-1/2 hose!

Test Results: Tanker 88 w/fill Pipe The Colton FD had a homemade, over-the-top fill pipe that was designed to be hand-held. The device was made using 3- inch aluminum pipe and was outfitted with a 2-1/2 NST female swivel connection. The fill pipe would normally be supplied by a 2-1/2 supply hose and someone would hold the pipe in position on top of the tanker.

Test Results: Tanker 88 w/fill Pipe Single, 2-1/2 hose to the fill pipe 4 minutes, 13 seconds 427 gpm A 31% improvement over a single, 2-1/2 hose to the 2-1/2 direct fill inlet. A 24% reduction in flow compared to a single, 4 to the 2-1/2-inch direct fill inlet.

Test Results: Tanker 35 Single, 2-1/2 fill hose connected to the 2-1/2 direct fill 4 minutes, 56 seconds 365 gpm Single, 4 fill hose connected to the 2-1/2 direct fill 3 minutes, 30 seconds 514 gpm A 41% improvement over a single, 2-1/2 hose!

Test Results: Engine Tanker 44 Single, 2-1/2 fill hose connected to the 2-1/2 direct fill 4 minutes, 53 seconds 461 gpm Single, 4 fill hose connected to the 2-1/2 direct fill 3 minutes, 19 seconds 677 gpm A 47% improvement over a single, 2-1/2 hose!

Summary It was demonstrated with all four tankers that 4 hose is clearly a better choice to use for filling tankers when given the choice between using 2-1/2 or 4 hose. Even when the direct fill piping is 2-1/2, 4-inch hose is still a better choice. While it may appear that only a couple minutes where shaved off of each fill time, in a tanker shuttle operation, these shaved minutes mean more trips can be made thus more water hauled and thus a higher, total delivery rate.

Summary In terms of the over-the-top fill pipes, they both out performed the single, 2-1/2 hose connected to the 2-1/2 direct fill inlet. Something to consider if a retrofit of a direct inlet is not feasible. Again, the large conduit excelled. The 4- inch over-the-top fill pipe filled at an incredible 800 gpm. Quite an achievement for a homemade system.

This program was developed by GBW Associates, LLC 2008 No part may be used or copied without expressed written consent. For more information contact us at thebigcamel@gotbigwater.com