36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

Similar documents
Operator: Save these instructions for future use!

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

36H SERIES Combination Gas Valve

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

Dual Solenoid Gas Valve Installation

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

GM-7000 Series CE Approved Gas Control Valve

G96 Series BASOTROL Dual Operator Valve

VR8205S,T Direct Ignition Combination Gas Controls

G92 Series BASOTROL Automatic Pilot Gas Valve

BGC258 Series BASOTROL Gas Valve

GAS VALVE RETROFIT KIT Pull Through Tube Heater Models

VR8305 Direct Ignition Combination Gas Control

Installation Instructions

VR8105, VR8205, and VR8305 Direct Ignition Combination Gas Controls

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

GM Series Dual-Block Multi-Function Gas Control Valves

Natural Gas to L.P. Gas Conversion Kit

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Gas Conversion Kits CERAMIC HEATER SERIES (1, 2, 3, 4 Burner Units)

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

BGA158 Series CE Approved Class B Shutoff Gas Valve

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

BGA158 Series CE Approved Class A Shutoff Gas Valve

INSTALLATION GUIDE Gas Rangetops

Installation Instructions

Natural Gas to L.P. Gas Conversion Kit

ACCESSORY KIT INSTALLATION INSTRUCTIONS

installation instructions

Gas Conversion Kits Push Through (Positive Pressure) Tube Heater Models

Installation Instructions For Natural Gas Conversion

Your safety and the safety of others are very important.

V8200A,C,H,M and VR8200A,C,H,M Continuous Pilot Combination Gas Controls

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

ACCESSORY KIT INSTALLATION MANUAL

VS8420 Millivolt Gas Valve

VR8200A Continuous Pilot Combination Gas Controls

VR8305 Direct Ignition Dual Automatic Valve Combination Gas Controls

VR46.5V(A)/VR86.5V(A) SERIES

VR8104, VR8204, and VR8304 Intermittent Pilot Combination Gas Controls

SPECIFICATIONS ATTENTION

Propane Conversion Kit Instructions

INSTALLATION INSTRUCTIONS

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*

ACCESSORY KIT INSTALLATION INSTRUCTIONS

H15 Series BASO 100% Shutoff, Automatic Pilot Valve

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only

Instructions for High Altitude Conversion

Model PSI Compressor with 3-Gallon Air Tank 12VDC

SPECIFICATIONS CAPACITY

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

Gas Conversion Kit Pilot Ignition Heaters

/2004 US/CA

SL G3. Warning

ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0347

WARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY

Types 749B and R130 Changeover Manifolds

Installation Instructions For Propane Gas Conversion (Kit Part No ) This kit is designed for conversion to Propane Gas

C645A-E Pressure Switches

WARNING: FOR OUTDOOR USE ONLY

! WARNING. Model PFC-1-G (direct acting) PFC-1-GR (reverse acting) Modulating Pneumatic Liquid Level Controls INSTRUCTION MANUAL MM-110B

GEN-1e CO2 Generator OVERVIEW INSTALLATION PROPANE GENERATORS ONLY NATURAL GAS GENERATORS ONLY

WARNING: AVERTISSEMENT. LP & HIGH ALTITUDE LP CONVERSION KIT FOR INSTALLATIONS IN the United STATES (0-10,000 Ft)

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

Natural Gas Conversion Kit

Pressure Differential Automatic Manifold For LPG. PDH1000 Series. LPG Installation & Operations Instructions

VR8345M Universal Electronic Ignition Gas Control

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Installation Instructions

Valve Proving System VDK 200 A S06*

Valve Proving System VDK 200 A S02

Crest Heating Boilers FBN(L) Series &

SPECIFICATIONS. Normally closed automatic shutoff valve with proof of closure. Fast opening, fast closing. ATTENTION

VK41../VK81.. GAS CONTROLS FOR COMBINED VALVE AND IGNITION SYSTEM SPECIFICATIONS APPLICATION DESCRIPTION INSTRUCTION SHEET

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

INSTALLATION AND OPERATION INSTRUCTIONS

VRB00 Series CLASS B SERVO REGULATED COMBINATION VALVES

VK8515M(R) MODULATING GAS CONTROL APPLICATION DESCRIPTION SPECIFICATIONS INSTRUCTION SHEET. Electrical data

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

V5197A. Firing Rate Gas Valve APPLICATION FEATURES PRODUCT HANDBOOK

INSTALLATION INSTRUCTIONS

SL G3 - Fuel Conversion to Natural Gas (LP to NG) P-Kit 301

Conversion instructions from natural gas to propane

ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0347

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

200 PSI COMPRESSORS - MODEL NUMBERS

Operation Manual. Diaphragm Sensed Gas Pressure Regulators

Installation Instructions

Transcription:

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The 36C/36D series HSI, DSI proven pilot gas valves are for use on Spark or Hot Surface Ignition systems and replaces many O.E.M. gas valves. These valves may be mounted in any position except upside down. Inlet screen and pilot gas filter provide maximum protection against chips and dirt. ON/OFF switch and regulator adjustment (on some models) are on top of valve for quick setup. Large, easy-grip pipe boss speeds installation. UNIVERSAL ELECTRONIC IGNITION GAS VALVES One Model Fits Most Applications LP Internal Regulator Conversion Reducer Inlet Wiring Model Coil Gas Pipe Opening Regulator Adjustment Convertible Kit Line Flow Bushing Pressure Side See Number Voltage Type Size Characteristic Setting Range Nat./LP Included Interrupter Direction Kit Tap Taps Figure ➀ 36C68-923 24 VAC Natural 3 /4 x 3 /4 Fast Open 3.5 2.5 5.0 Yes Yes No Str. Thru Yes No No 3 LP Internal Regulator Conversion Reducer Inlet Wiring Model Coil Gas Pipe Opening Regulator Adjustment Convertible Kit Line Flow Bushing Pressure Side See Number Voltage Type Size Characteristic Setting Range Nat./LP Included Interrupter Direction Kit Tap Taps Figure ➀ 36C74-913 24 VAC Natural 3 /4 x 3 /4 Step 0.9 /3.5 2.5 5.0 No No No Str. Thru Yes Yes No 3 36C76-906 24 VAC Natural 3 /4 x 3 /4 2 Stage 1.0 /3.5 2.5 5.0 No No No Str. Thru No Yes No 5 Bimetal, 36C76-920 24 VAC Natural 3 /4 x 3 /4 2 Stage 1.3 /3.5 2.5 5.0 No No No Str. Thru No Yes No 5 Bimetal, 36C76-962 24 VAC LP 3 /4 x 3 /4 2 Stage 5.0 /11.0 9.0 12.0 No No No Str. Thru No No No 5 Bimetal, 36C76-963 24 VAC Natural 3 /4 x 3 /4 2 Stage 2.0 /3.5 2.5 5.0 No No No Str. Thru Yes Yes No 5 Bimetal, 36D13-508 24 VAC Natural 1 /2 x 1 /2 2 Stage 1.1 /3.5 Non- No No No Str. Thru No No No 6 Relay, Adjustable Lo 1.1/Hi 3.5 36D13-905 24 VAC Natural 3 /4 x 3 /4 2 Stage 1.1 /3.5 2.5 5.0 No No No Str. Thru No No No 6 Relay, Lo 1.1/Hi 3.5 36D13-914 24 VAC LP 3 /4 x 3 /4 2 Stage 2.5 /11.0 Non- No No No Str. Thru No No No 6 Relay, Adjustable Lo 2.5/Hi 11.0 Indicates Canadian Model Number ➀ Wiring diagrams see pages 4 & 5 White-Rodgers is a division of Emerson Electric Co. www.white-rodgers.com PART NO. 37-6516A 0646

PRECAUTIONS DO NOT BEGIN INSTALLATION UNTIL YOU READ THE FOLLOWING PRECAUTIONS.! WARNING If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. 1. Failure to turn off electric or main gas supply to heating system could cause personal injury and/or property damage by shock, gas suffocation, fire, and/or explosion. 2. Do not use this control on circuits exceeding specified voltage. Higher voltage will damage the control and may cause shock or fire hazard. 3. NEVER USE FLAME OR ANY KIND OF SPARK TO CHECK FOR GAS LEAKS COULD CAUSE FIRE AND/OR EXPLOSION. 4. Do not use a control set for natural gas with LP gas, or a control set for LP gas with natural gas. Personal injury and/or property damage, gas suffocation, fire, and/or explosion may result.! CAUTION 1. Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring can cause equipment damage, property damage and/or personal injury. 2. This control is not intended for use in locations where it may come in direct contact with water. Suitable protection must be provided to shield the control from exposure to water (dripping, spraying, rain, etc.). SPECIFICATIONS Electrical Rating: 0.6 amps End to End Dimensions: 3 15 /16 Ambient Operating Range: 40 to +175 F ( 40 to 79 C) Maximum Pressure Rating: 1 /2 PSI (14.0 W.C.) Agency: A.G.A. and C.G.A. design certified 1" Pressure Drop Capacity Rated Range of Regulation BTU/HR BTU/HR AGA STD. NAT GAS LP GAS AGA STD. NAT GAS LP GAS Pipe Size 1000 BTU/CU. FT. 2500 BTU/CU. FT. 1000 BTU/CU. FT. 2500 BTU/CU. FT. 1/2 X 3/8 100,000 162,000 15,000-100,000 15,000-162,000 1/2 X 1/2 230,000 372,600 30,000-290,000 30,000-469,000 1/2 X 3/4 230,000 372,600 30,000-290,000 30,000-469,000 3/4 X 3/4 280,000 453,600 50,000-400,000 50,000-648,000 2

MAIN PIPING CONNECTIONS NOTE All piping must comply with local codes, ordinances, and/or national fuel gas codes. 1. Turn off electrical power to the system at the fuse box or circuit breaker. Also turn off the main gas supply. 2. If replacing an existing valve, disconnect all plumbing and electrical connections from the old control. 3. The valve may be installed in any position except upside down. The arrow on the bottom plate indicates the direction of gas flow through the valve. See page 3. 4. You should use new pipe that is properly chamfered, reamed, and free of burrs and chips. If you are using old pipe, be sure it is clean and free of rust, scale, burrs, chips, and old pipe joint compound. 5. Apply pipe joint compound (pipe dope) or teflon tape that is approved for all gases, only to the male threads of the pipe joints. DO NOT apply compound or teflon tape to the first two threads. 6. If you are using a vise or open-end wrench to hold the valve while installing piping, do not tighten excessively, as this may damage the valve. 7. See wiring pages 4 and 5 when making electrical connections. After all gas and electrical connections are completed, turn gas on and check for gas leaks with leak detection solution or soap suds. Bubbles forming indicate a leak. SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY. Upright, 90 from upright or vertical UPRIGHT LEFT OR RIGHT INLET BOSS UP OR DOWN NOTE: Always Include A Drip Leg In Piping Horizontal 3 in. minimum Drop Gas Valve Piped Gas Supply Horizontal Riser 3 in. minimum Drop Tubing Gas Supply INSTALLATION Piped Gas Supply Gas Valve Figure 1. Typical gas valve piping Gas Valve Riser 3 in. minimum PILOT GAS CONNECTION The valve is shipped with the pilot outlet plugged. For installations requiring pilot gas, remove the plug and use the fitting packed separately with the control. Install fitting into pilot gas outlet turning until finger-tight. Insert clean, deburred tubing all the way through the fitting. While holding the tubing securely, slowly tighten fitting until you feel a slight "give". Tighten the fitting an additional 1½ turns. Pilot gas outlet PILOT PRESS TAP NOTE: Control shown may not be identical to replacement control. Figure 2. Mounting positions Gas outlet Gas valve side view 3

WIRING DIAGRAMS SYSTEM WIRING REFER TO AND FOLLOW THE APPLIANCE MANUFACT- URER'S WIRING DIAGRAM. USE THE TABLE ON PAGE 1 TO IDENTIFY THE PROPER TERMINAL IDENTIFICATION FIGURE FOR THE GAS VALVE. NOTE All wiring should be installed in accordance with local and national electrical codes and ordinances. Always check that the electrical power supply used agrees with the voltage and frequency shown on the gas control. Wiring for 36C68-923 & 36C74-913 Gas Valves MAIN VALVE RELAY Figure 3 4 terminal panel PILOT ADJ. REDUNDANT PILOT/VALVE Main Valve Redundant Valve Coil (Pilot Valve) Redundant Solenoid External Leads Main Valve Relay 4-TERMINAL PANEL (DSI/HSI) WITH 1 /4 DUAL MALE TERMINALS Wiring for 36C76-920 & 36C76-962, -963 Gas Valves D-1 REDUNDANT/ PILOT VALVE D-2 W-1 D-1 D-2 C-1 Figure 4 Bi-metal two stage W-1 C-1 MAIN VALVE W-2 C-2 PILOT ADJ. W-2 C-2 HI-LO OPERATOR 4

Wiring for 36C76-906 Gas Valve WIRING DIAGRAMS D-1 REDUNDANT/ PILOT VALVE W-1 D-1 C-1 Figure 5 Bi-metal two stage W-1 C-1 MAIN VALVE W-2 C-2 C-2 HI-LO OPERATOR PILOT ADJ. W-2 Wiring for 36D13-508, -905, & -914 Gas Valves Figure 6 Relay two stage 3 REDUNDANT VALVE 2ND STAGE RELAY 36D13 PILOT ADJ. 2 2 MAIN VALVE 1 4 INSTALLATION (cont'd) Outlet Pressure Adjustments These controls are shipped from the factory with the regulator set to the outlet pressure shown in the table on page 1. Consult the appliance rating plate and set the outlet pressure to match the appliance manufacturers specifications. Conversion from Natural Gas to L.P. 1. Remove regulator cover screw. 2. Turn regulator adjustment screw counterclockwise and remove from valve. 3. Remove regulator spring from valve. 4. Insert proper spring Nat./L.P. into the valve. 5. Replace the regulator adjustment screw and adjust to appliance manufacturers specifications. 6. Replace regulator cover screw. Conversion Outlet Pressure from Pilot Gas Regulator Model Natural/LP Adjustment Adjustment 36C68-923 See Conversion See Fig. 7 See Fig. 7 from Natural Gas to L.P. 36C74-913 Not Convertable See Fig. 7 See Fig. 8 36C76-906 Not Convertable See Fig. 7 See Fig. 7 36C76-920 Not Convertable See Fig. 7 See Fig. 7 36C76-962 Not Convertable See Fig. 7 See Fig. 7 36C76-963 Not Convertable See Fig. 7 See Fig. 7 36D13-508 Not Convertable See Fig. 7 See Fig. 7 36D13-905 Not Convertable See Fig. 7 See Fig. 7 36D13-914 Not Convertable See Fig. 7 Non-Adjustable 5

INSTALLATION (cont'd) OUTLET PRESSURE REGULATOR ADJUSTABLE REGULATION RANGE ADJUSTMENT FOR VALVES WITH AN FOR 36C74-913 ADJUSTABLE REGULATION RANGE The pressure regulator has been factory adjusted for 3.5" The pressure regulator has been factory adjusted (see control for specific setting). Although additional adjustments will not normally be necessary, you may adjust the regulator. Do not force the adjusting screw beyond the limits that it can easily be adjusted. 1. Energize system to ignite main burner. 2. Remove "Reg. Adj." cover screw. 3. To DECREASE outlet pressure, turn the adjusting screw (beneath the cover screw) counterclockwise. To INCREASE outlet pressure, turn the adjusting screw clockwise. 4. Replace the cover screw. Cycle the valve two or three times to verify regulator setting. PILOT GAS ADJUSTMENT This control was factory preset and will not normally require additional adjustment of pilot flame. If the pilot flame is low and does not engulf the bulb of the sensor, the system will not energize the main valve. If pilot gas pressure is too high, gas will sputter past the ignition electrode, and may not ignite. High pilot gas pressure may also cause the flame to lift off the burner, causing the flame sensor bulb to sense "low" heat. To adjust the pilot flame, remove the cover screw and gasket (see fig. 7). To REDUCE pilot flame, turn the pilot adjust screw (beneath the cover screw) clockwise. To INCREASE pilot flame, turn the pilot adjust screw counterclockwise. Replace gasket and tighten cover screw. REGULATOR COVER SCREW W.C. (Natural Gas, full flow) or 11.0 W.C. (LP Gas, full flow). Although additional adjustments will not normally be necessary, the regulator may be adjusted if required. Do not force the adjusting screw beyond the limits that it can easily be adjusted. 1. Attach a manometer to the outlet pressure tap of the valve. 2. Energize valve to ignite main burner. 3. Remove "Reg. Adj." cover screw. 4. To DECREASE outlet pressure, turn the adjusting screw (beneath the cover screw) counterclockwise. To INCREASE outlet pressure, turn the adjusting screw clockwise. 5. Replace the cover screw. Cycle the valve two or three times to verify regulator setting. REGULATOR COVER SCREW Figure 8. Gas valve top NATURAL LP GAS SELECTOR PILOT ADJUST COVER SCREW PILOT ADJUST COVER SCREW Figure 7. Adjustable regulator range 6

PARTS & ACCESSORIES Item Model Number Number Description F92-0656 L.P. to natural gas conversion kit for 36C, 36D, 36E and 36F gas valves with regulation range of 2.5 to 5 W.C. Item Model Number Number Description F6-1794 Bracket for Bryant pilots when retrofitting with Cycle-Pilot. F92-0659 Natural to regulated L.P. gas conversion kit for 36C, 36D, 36E and 36F gas valves with regulation range of 7.5 to 12.0 W.C. F92-0737 Natural to unregulated L.P. gas conversion kit for 36C gas valves. F69-0727 1 /4 brass compression fitting for pilot line connections. F69-1988 Brass compression fitting adapter for 1 /8 pilot line connections. 7 /16-24 thread. F92-0514 Reducer bushings for 36C and 36E gas valves. Contains one 3 /4 x 1 /2 N.P.T. and one 3 /8 x 1 /2 N.P.T. F92-0866 Conversion kit for 36C gas valves with regulation range of 4.2 to 11.0 W.C. F92-0773 Adapter bracket for remote rod adjustment of A-cock on older 36C type gas valves. Not for new style knob pictured in this catalog. F115-0059 36 replacement harness assembly for connection of 50A22-201 to 36C84-426 in the 21D18-5 Cycle- Pilot retrofit kit or to 36C84-436 in the 21D18-15. F115-0064 36 replacement harness assembly for connection of 5059-23 to 36C84-426 in the 21D18-3 Cycle- Pilot retrofit kit. F115-0087 36 replacement harness assembly for connection of 5059-23 to 36E86-302 in the 21D18-14 Cycle- Pilot retrofit kit. F115-0100 Harness assembly for HSI systems with 36E gas valves; connects the 767A ignitor with the 50E47 or the 50F47 ignition module. 7