Control Valve Sizing. Sizing & Selection 3 P 1. P 2 (Outlet Pressure) P V P VC. CONTENTS Introduction Nomenclature Calculating C v

Similar documents
Application Worksheet

REFERENCE GUIDE. Rev. 0 15/09/2016

Appendix A Frequently Asked Questions

The Discussion of this exercise covers the following points:

Engineering Information. Flow Data. Flow Data. Importance of Valve Sizing. Estimating Cv or Orifice Size:

Sizing Pressure Regulators & Control Valves

SG TF. Q = 963 Cv (P1 - P2)(P1 + P2) TECHNICAL INFORMATION. Flow Q (GPM)

Modeling a Pressure Safety Valve

How to use the PBM Flow Calculator Spreadsheet (V2.04)

OVERVIEW. Flow Coefficient C v. Operating Conditions. Specific Gravity

INTRODUCTION TO REGULATOR AND RELIEF VALVE SIZING. Introduction

MASS FLOW SYSTEMS MASS FLOW MEASURING, CONTROLLING AND BLENDING SYSTEMS

VBS-9263 Series. Application. Features. Applicable Literature

IRC 2011 All Rights Reserved

VB-7212 Series. Application. Features. Applicable Literature. 5/8" O.D., 45 SAE Flared Stem Up Open, Two-Way Valves General Instructions

Applied Fluid Mechanics

VB-7213 Series. Application. Features. Applicable Literature. 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions

VB-7263 Series. Application. Features. Applicable Literature

Methods of Rating Flow

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes.

Cavitation in Valves

The Hoffman Specialty Series 2000 consists of main

Figure Vapor-liquid equilibrium for a binary mixture. The dashed lines show the equilibrium compositions.

MODELING AND SIMULATION OF VALVE COEFFICIENTS AND CAVITATION CHARACTERISTICS IN A BALL VALVE

VB-7273 Series. Application. Features. Applicable Literature

Multiple Tube - Teflon PTFE-Glass Flowmeters

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

****** * EX * ****** DWN W.W.POWELL CALCULATION OF FLOW LOSSES IN INLET CHK D.PAPA AND DISCHARGE HEADERS ASSOCIATED WITH

VB-7211 Series. Application. Features. Applicable Literature. 1/2" to 1-1/4" Union End NPT Stem Up Open, Two-Way Valves General Instructions

Single Tube Flowmeters

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438

Aspects of Flow Control in Metering Henry Gomes SGS Kuwait WLL

Gerald D. Anderson. Education Technical Specialist

Multiple Tube Flowmeters

Valve Sizing Considerations. Steven Hocurscak Metso Automation

Process Dynamics, Operations, and Control Lecture Notes - 20

Case 12 Multistage Centrifugal Refrigeration System Halocarbon Refrigerant

Distributed By: M&M Control Service, Inc INFORMATION Page # Globe and Ball Valves I-2

The Shand & Jurs Model Vapor Guard Tank Blanketing Valve

1 PIPESYS Application

Engineering. Table of Contents. Engineering G-1. INFORMATION PAGE # Control Valves Selection and Sizing

VALVE SIZING & SELECTION TECHNICAL REFERENCE

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

J. David Hailey Ph.D. Vice President, Business Development COSA Xentaur 7125 North Loop East Houston, TX 77028

International Journal of Technical Research and Applications e-issn: , Volume 4, Issue 3 (May-June, 2016), PP.

Gas Proportioners - Back Pressure Compensated

NORDCALC Introduction... 2 Registration... 2 Flow Calculations tab Torque Calculation & Actuator Mounting Data tab... 21

Name Chemistry Pre-AP

Air Eliminators and Combination Air Eliminators Strainers

Pressure and Temperature Controls

BACK PRESSURE / SUSTAINING

Tutorial. BOSfluids. Relief valve

Protective Atmospheres, Measurement Technologies and Troubleshooting Tools

Technical Committee on LP-Gas at Utility Gas Plants

CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER

COMPAFLOW. Compressed Air. Volumetric flow. Gas. Mass flow. Steam. Net volumetric flow. Liquid

BACK PRESSURE / SUSTAINING

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

fserve. Experience In Motion

The capacity of the cargo tank venting system (46 CFR );

1. A pure substance has a specific volume of 0.08 L/mol at a pressure of 3 atm and 298 K. The substance is most likely:

TECHNICAL INSTRUCTIONS Iron Body Series 597 SI

44 (0) E:

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

Device Description. Operating Information. CP Q (eq. 1) GT. Technical Bulletin TB-0607-CFP Hawkeye Industries Critical Flow Prover

EDUCTOR. principle of operation

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Operational Settings:

SIZING AND CAPACITIES OF GAS PIPING

CONTROL VALVE WHAT YOU NEED TO LEARN?

SFC. SKYLINE FLOW CONTROLS INC. The Leader of Accurate and Reliable Flow Measurement DESCRIPTION & APPLICATIONS: ADVANTAGES:

SIZING AND CAPACITIES OF GAS PIPING

INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR NPTEL ONLINE CERTIFICATION COURSE. On Industrial Automation and Control

LOW PRESSURE EFFUSION OF GASES adapted by Luke Hanley and Mike Trenary

SIZING AND CAPACITIES OF GAS PIPING Reserved

DFT Valves. Selecting Control Valves

Gas viscosity ( ) Carr-Kobayashi-Burrows Correlation Method Lee-Gonzalez-Eakin Method. Carr-Kobayashi-Burrows Correlation Method

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES

UNIT 10 - GASES. Notes & Worksheets - Honors

The water supply for a hydroelectric plant is a reservoir with a large surface area. An outlet pipe takes the water to a turbine.

Restriction Orifice. Single or Multi Stage Orifice to. Reduce Pressure or. Limit the Flow Rate

Design Review Agenda

Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance

BASICS OF RELIEF VALVES

Chapter 13 Temperature, Kinetic Theory, and the Gas Laws 497

Sizing Pulsation Dampeners Is Critical to Effectiveness

SB AXIAL FLOW VALVES

STANDARD FOR CONTROL VALVE SEAT LEAKAGE

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

The Application of Temperature and/or Pressure Correction Factors in Gas Measurement

PURE SUBSTANCE. Nitrogen and gaseous air are pure substances.

4.) There are no forces of attraction or repulsion between gas particles. This means that

OIL AND GAS INDUSTRY

Becker* Products Below Ground Ball Valve Regulators

To convert to millimeters of mercury, we derive a unit factor related to the equivalent relationship 29.9 in. Hg = 760 mm Hg.

Single & Headered Relief Vent Piping Analysis

Seated valve for steam (PN 25)

SIZING OF WATER PIPING SYSTEM

3-way control valves VK 3

Transcription:

Sizing & Selection 3 Control Valve Sizing CONTENTS Introduction 3-1 Nomenclature 3-1 Calculating for Liquids 3-3 Liquid Sizing Examples 3-7 Calculating for Gases 3-10 Gas Sizing Examples 3-13 Calculating for Two Phase Flow 3-15 Vapor Pressure Charts 3A-1 Steam Tables 3A-7 Fluid Property Correlation Constants 3A-21 Pipe Data 3A-29 INTRODUCTION Valtek uses a systematic method for selecting body types, sizes, materials, pressure ratings and trim sizes based on flow characteristics Valtek control valve flow capacity ( ) is based upon the industry standard, ANSI/ISA S7501 This standard and the corresponding measuring standards contain Equations used to predict the flow of compressible and incompressible fluids in control valves Slightly different forms of the basic Equation are used for liquids and gases Basic steps for sizing and selecting the correct valve include calculating the required Equations for calculating for both gases and liquids are found in this section Valtek has programmed the ANSI/ISA sizing Equations and procedures, making computer-aided sizing available on IBM-PC or compatible computers These programs permit rapid control valve flow capacity calculations and valve selection with minimal effort The programs also include exit velocity, noise prediction and actuator sizing calculations See Section 22 for more details on computer-aided valve selection These instructions are designed to expose the user to the different aspects of valve sizing The step-by-step method outlined in this section is the most common method of sizing NOMENCLATURE Flow Capacity The valve sizing coefficient most commonly used as a measure of the capacity of the body and trim of a control valve is One is defined as one US gallon per minute of 60 degree Fahrenheit water that flows through a valve with a one psi pressure drop The general Equation for is as follows: flow specific gravity at flowing temperature pressure drop When selecting a control valve for an application, the calculated is used to determine the valve size and the trim size that will allow the valve to pass the desired flow rate and provide stable control of the process fluid Pressure Profile Fluid flowing through a control valve obeys the basic laws of conservation of mass and energy, and the continuity Equation The control valve acts as a restriction in the flow stream As the fluid stream approaches this restriction, its velocity increases in order for the full flow to pass through the restriction Energy for this increase in velocity comes from a corresponding decrease in pressure Maximum velocity and minimum pressure occur immediately downstream from the throttling point at the narrowest constriction of the fluid stream, known as the vena contracta Downstream from the vena contracta, the fluid slows and part of the energy (in the form of velocity) is converted back to pressure A simplified profile of the fluid pressure is shown in Figure 3-1 The slight pressure losses in the inlet and outlet passages are due to frictional effects The major excursions of pressure are due to the velocity changes in the region of the vena contracta P VC P 2 (Outlet Pressure) P (Valve Pressure Drop) P V (Vapor Pressure) (Pressure at Vena Contracta) Figure 3-1: Pressure Profile of Fluid Passing Through a Valve Rev 6/94 3-1

Volumetric Flow Rate C V q / ΔP/G f F L q max ΔP ch ΔP/G f Figure 3 2: Choked Pressure Drop Liquid Pressure Recovery Factor, F L The liquid pressure recovery factor, F L, predicts the amount of pressure recovery that will occur between the vena contracta and the valve outlet F L is an experimentally determined coefficient that accounts for the influence of the valve s internal geometry on the maximum capacity of the valve It is determined from capacity test data like that shown in Figure 3-2 F L also varies according to the valve type High recovery valves such as butterfly and ball valves have significantly lower pressures at the vena contracta and hence recover much farther for the same pressure drop than a globe valve Thus they tend to choke (or cavitate) at smaller pressure drops than globe valves Allowable Pressure Drop The capacity curve shown in Figure 3-2 shows that, with constant upstream pressure, flow rate, q, is related to the square root of pressure drop through the proportionality constant The curve departs from a linear relationship at the onset of "choking" described using the F i factor The flow rate reaches a maximum, q max, at the fully choked condition due to effects of cavitation for liquids or sonic velocity for compressible fluids The transition to choked flow may be gradual or abrupt, depending on valve design ANSI/ISA liquid sizing Equations use a pressure recovery factor, F L, to calculate the ΔP ch at which choked flow is assumed for sizing purposes For compressible fluids, a terminal pressure drop ratio,, similarly describes the choked pressure drop for a specific valve When sizing a control valve, the smaller of the actual pressure drop or the choked pressure drop is always used to determine the correct This pressure drop is known as the allowable pressure drop, ΔP a Cavitation In liquids, when the pressure anywhere in the liquid drops below the vapor pressure of the fluid, vapor bubbles begin to form in the fluid stream As the fluid decelerates there is a resultant increase in pressure If this pressure is higher than the vapor pressure, the bubbles collapse (or implode) as the vapor returns to the liquid phase This two-step mechanism called cavitation produces noise, vibration, and causes erosion damage to the valve and downstream piping The onset of cavitation known as incipient cavitation is the point when the bubbles first begin to form and collapse Advanced cavitation can affect capacity and valve performance, which begins at a ΔP determined from the factor, F i The point at which full or choked cavitation occurs (severe damage, vibration, and noise) can be determined from Equation 33 Under choked conditions, allowable pressure drop, is the choked pressure drop Liquid Critical Pressure Ratio Factor, F F The liquid critical pressure ratio factor, F F, multiplied by the vapor pressure, predicts the theoretical vena contracta pressure at the maximum effective (choked) pressure drop across the valve Flashing If the downstream pressure is equal to or less than the vapor pressure, the vapor bubbles created at the vena contracta do not collapse, resulting in a liquid-gas mixture downstream of the valve This is commonly called flashing When flashing of a liquid occurs, the inlet fluid is 100 percent liquid which experiences pressures in and downstream of the control valve which are at or below vapor pressure The result is a two phase mixture (vapor and liquid) at the valve outlet and in the downstream piping Velocity of this two phase flow is usually very high and results in the possibility for erosion of the valve and piping components Choked Flow Choked flow occurs in gases and vapors when the fluid velocity reaches sonic values at any point in the valve body, trim, or pipe As the pressure in the valve or pipe is lowered, the specific volume increases to the point where sonic velocity is reached In liquids, vapor formed as the result of cavitation or flashing increases the specific volume of the fluid at a faster rate than the increase in flow due to pressure differential Lowering the downstream pressure beyond this point in either case will not increase the flow rate for a constant upstream pressure The velocity at any point in the valve or downstream piping is limited to sonic (Mach 1) As a result, the flow rate will be limited to an amount which yields a sonic velocity in the valve trim or the pipe under the specified pressure conditions 3-2

Reynolds Number Factor, F R The Reynolds Number Factor, F R, is used to correct the calculated for non-turbulent flow conditions due to high viscosity fluids, very low velocities, or very small valve Piping Geometry Factor, Valve sizing coefficients are determined from tests run with the valve mounted in a straight run of pipe which is the same diameter as the valve body If the process piping configurations are different from the standard test manifold, the apparent valve capacity is changed The effect of reducers and increasers can be approximated by the use of the piping geometry factor, Velocity As a general rule, valve outlet velocities should be limited to the following maximum values: Liquids 50 feet per second Gases Approaching Mach 10 Mixed Gases 500 feet per second and Liquids The above figures are guidelines for typical applications In general, smaller sized valves handle slightly higher velocities and large valves handle lower velocities Special applications have particular velocity requirements; a few of which are provided below Liquid applications where the fluid temperature is close to the saturation point should be limited to 30 feet per second to avoid reducing the fluid pressure below the vapor pressure This is also an appropriate limit for applications designed to pass the full flow rate with a minimum pressure drop across the valve Valves in cavitating service should also be limited to 30 feet per second to minimize damage to the downstream piping This will also localize the pressure recovery which causes cavitation immediately downstream from the vena contracta In flashing services, velocities become much higher due to the increase in volume resulting from vapor formation For most applications, it is important to keep velocities below 500 feet per second Expanded outlet style valves such as the Mark One-X help to control outlet velocities on such applications Erosion damage can be limited by using chrome-moly body material and hardened trim On smaller valve applications which remain closed for most of the time such as heater drain valves higher velocities of 800 to 1500 feet per second may be acceptable with appropriate materials Gas applications where special noise attenuation trim are used should be limited to approximately 033 Mach In addition, pipe velocities downstream from the valve are critical to the overall noise level Experimentation has shown that velocities around 05 Mach can create substantial noise even in a straight pipe The addition of a control valve to the line will increase the turbulence downstream, resulting in even higher noise levels Expansion Factor, Y The expansion factor, Y, accounts for the variation of specific weight as the gas passes from the valve inlet to the vena contracta It also accounts for the change in cross-sectional area of the vena contracta as the pressure drop is varied Ratio of Specific Heats Factor, F k The ratio of specific heats factor, F k, adjusts the Equation to account for different behavior of gases other than air Terminal Pressure Drop Ratio, The terminal pressure drop ratio for gases,, is used to predict the choking point where additional pressure drop (by lowering the downstream pressure) will not produce additional flow due to the sonic velocity limitation across the vena contracta This factor is a function of the valve geometry and varies similarly to F L, depending on the valve type Compressibility Factor, Z The compressibility factor, Z, is a function of the temperature and the pressure of a gas It is used to determine the density of a gas in relationship to its actual temperature and pressure conditions CALCULATING C V FOR LIQUIDS Introduction The Equation for the flow coefficient ( ) in non-laminar liquid flow is: q G f ΔP a (31) Valve sizing coefficient Piping geometry factor q Flow rate, gpm ΔP a Allowable pressure drop across the valve for sizing, psi G f Specific gravity at flowing temperature 3-3

Table 3-I: Typical Valve Recovery Coefficient and Incipient Cavitation Factors NOTE: Values are given for full-open valves See charts below for part-stroke values Valve Type Flow Direction Trim Size F L F i F d Globe Over Seat Full Area 085 075 70 10 Over Seat Reduced Area 080 072 70 10 Under Seat Full Area 090 081 75 10 Under Seat Reduced Area 090 081 75 10 Valdisk 60 o Open Full 076 065 36 71 Rotary Disc 90 o Open Full 056 049 26 71 ShearStream 60 o Open Full 078 065 51 10 Rotary Ball 90 o Open Full 066 044 30 10 CavControl Over Seat All 092 090 N/A 2/ d MegaStream Under Seat All ~10 N/A ~10 (n s /25d) 2/3** ChannelStream Over Seat All ~10 087 to 0999 N/A 040* Tiger-Tooth Under Seat All ~10 084 to 0999 ~10 035* * Typical ** n s number of stages The following steps should be used to compute the correct, body size and trim number: Step 1: Calculate Actual Pressure Drop The allowable pressure drop, ΔP a, across the valve for calculating, is the smaller of the actual ΔP from Equation 32 and choked ΔP ch from Equation 33 ΔP - P 2 (32) Step 2: Check for Choked Flow, Cavitation and Flashing Use Equation 33 to check for choked flow: ΔP ch F L 2 ( - F F P V ) (33) F L Liquid pressure recovery factor F F Liquid critical pressure ratio factor P V Vapor pressure of the liquid at inlet temperature, psia Upstream pressure, psia See Table 3-I for F L factors for both full-open and partstroke values F F can be estimated by the following relationship: P V F F 096-028 (34) P C F F Liquid critical pressure ratio P V Vapor pressure of the liquid, psia P C Critical pressure of the liquid, psia (see Table 3-II) 3-4

If ΔP ch (Equation 33) is less than the actual ΔP (Equation 32), use ΔP ch for ΔP a in Equation 31 Liquid critical pressure ratio, F F 10 09 08 07 06 05 0 10 20 30 40 50 60 70 80 90 100 P v Vapor Pressure P c Critical Pressure Figure 3-3: Liquid Critical Pressure Ratio Factor Curve Table 3-II: Critical Pressures Critical Critical Liquid Press Liquid Press (psia) (psia) Ammonia 16361 Hydrogen Chloride 12054 Argon 7070 Isobutane 5292 Benzene 7100 Isobutylene 5292 Butane 5512 Kerosene 3500 Carbon Dioxide 10702 Methane 6673 Carbon Nitrogen 4924 Monoxide 5071 Nitrous Oxide 10511 Chlorine 11172 Oxygen 7320 Dowtherm A 5470 Phosgene 8232 Ethane 7085 Propane 6159 Ethylene 7305 Propylene 6703 Fuel Oil 3300 Refrigerant 11 6394 Fluorine 7570 Refrigerant 12 5982 Gasoline 4100 Refrigerant 22 7497 Helium 329 Sea Water 32000 Hydrogen 1881 Water 32082 It may also be useful to determine the point at which substantial cavitation begins The following Equation defines the pressure drop at which substantial cavitation begins: 2 ΔP (cavitation) F i ( - P V ) (35) In high pressure applications, alternate analysis may be required; verify analysis with factory if ΔP > ΔP (cavitation) > 300 psi (globe valves) or 100 psi (rotary valves) F i P V Liquid cavitation factor (Typical values for F i are given in Table 3-I) Upstream pressure, psia Vapor pressure of the liquid, psia The required for flashing applications is determined by using the appropriate ΔP allowable [ΔP ch calculated from Equation 33] Step 3: Determine Specific Gravity Specific gravity is generally available for the flowing fluid at the operating temperature The appendix provides fluid property data for 268 chemical compounds, from which the specific gravity, G f can be calculated Step 4: Calculate Approximate Generally the effects of nonturbulent flow can be ignored, provided the valve is not operating in a laminar or transitional flow region due to high viscosity, very low velocity, or small In the event there is some question, calculate the, from Equation 31, assuming 1,and then proceed to steps 5-7 If the Reynolds number calculated in Equation 36a is greater than 40,000, F R can be ignored (proceed to step 8 after step 5) Step 5: Select Approximate Body Size Based on From the tables in section 4, select the smallest body size that will handle the calculated Step 6: Calculate Valve Reynolds Number Re v and Reynolds Number Factor F R Use Equation 36a to calculate valve Reynolds Number Factor: N 4 F d q F L2 2 1/4 Re v +1 (36a) ν F L N 2 d 4 Use Equation 36b to calculate valve Reynolds Number Factor F R if Re v < 40,000, otherwise F R 10: s 0655 F R 1044-358 (36b) t s Laminar flow 1 q μ 2/3 s (36c) F s N s ΔP t Turbulent flow (Equation 31) F s streamline flow factor 3-5

Table 3-III: Piping Geometry Factors for Valves with Reducer and Increaser, F p versus /d 2 / d 2 d / D 050 060 070 080 090 4 099 099 100 100 100 6 098 099 099 100 100 8 097 098 099 099 100 10 096 097 098 099 100 12 094 095 097 098 100 14 092 094 096 098 099 16 090 092 095 097 099 18 087 090 094 097 099 20 085 089 092 096 099 25 079 084 089 094 098 30 073 079 085 091 097 35 068 074 081 089 096 40 063 069 077 086 095 NOTE: The maximum effective pressure drop (ΔP choked) may be affected by the use of reducers and increasers This is especially true of Valdisk valves Contact factory for critical applications Table 3-IV: Piping Geometry Factors for Increaser Only on Valve Outlet, F p versus / d 2 / d 2 d / D 050 060 070 080 090 4 100 100 100 100 100 6 101 101 101 101 101 8 101 102 102 102 101 10 102 103 103 103 102 12 103 104 104 104 103 14 104 105 106 105 104 16 106 107 108 107 105 18 108 110 111 110 106 20 110 112 112 112 108 25 117 122 124 122 113 30 127 137 142 137 120 35 144 165 179 165 132 40 175 241 314 241 150 d Valve port inside diameter in inches D Internal diameter of the piping in inches (See Tables 3-VII and 3-VIII) F d 2/3 F L 2 2 1/6 F s +1 (36d) F L 1/3 N 2 d 4 q G f F R - P 2 (36e) d Valve inlet diameter, inches F d Valve style modifier (Table 3-1) F s Laminar, or streamline, flow factor q Flow rate, gpm N 2 890 when d is in inches N 4 17,300, when q is in gpm and d in inches N s 47 when q is in gpm and ΔP in psi μ absolute Viscosity, centipoise ν kinematic viscosity, centistokes μ/g f For laminar and transitional flow, note the ΔP is always taken as - P 2 Step 8: Calculate Piping Geometry Factor If the pipe size is not given, use the approximate body size (from step 5) to choose the corresponding pipe size The pipe diameter is used to calculate the piping geometry factor,, which can be determined by Tables 3-III and 3-IV If the pipe diameter is the same as the valve size, is 1 and does not affect Step 7: Recalculate Using Reynolds Number Factor If the calculated value of F R is less than 048, the flow is considered laminar; and the is equal to s calculated from Equation 36c If F R is greater than 098, turbulent flow can be assumed (F R 10); and is calculated from Equation 31 Do not use the piping geometry factor F p if F R is less than 098 For values of F R between 048 and 098, the flow is considered transitional; and the is calculated from Equation 36e: Step 9: Calculate the Final Using the value of, calculate the required from Equation 31 Step 10: Calculate Valve Exit Velocity The following Equation is used to calculate entrance or exit velocities for liquids: 0321 q V (37) 3-6

V Velocity, ft/sec q Liquid flow rate, gpm Applicable flow area, in 2 of body port (Table 3-VIII) After calculating the exit velocity, compare that number to the acceptable velocity for that application It may be necessary to go to a larger valve size Step 11: Recalculate If Body Size Changed Recalculate if the has been changed due to selection of a larger body size Step 12: Select Trim Number First identify if the valve will be used for on/off or throttling service Using the tables in Section 4, select the appropriate trim number for the calculated and body size selected The trim number and flow characteristic (Section 9) may be affected by how the valve will be throttled When cavitaiton is indicated, refer to Section 14 to evaluate special trims for cavitation protection LIQUID SIZING EXAMPLES Example One Given: Liquid Water Critical Pressure (P C ) 32062 psia Temperature 250 F Upstream Pressure ( ) 3147 psia Downstream Pressure (P 2 )1047 psia Specific Gravity 094 Valve Action Flow-to-open Line Size 4-inch (Class600) Flow Rate 500 gpm Vapor Pressure (P V ) 30 psia Kinematic Viscosity (ν) 0014 centistokes Flow Characteristic Equal Percentage Step 1: Calculate actual pressure drop using Equation (32) ΔP 3147 psia - 1047 psia 210 psi Step 2: Check for choked flow Find F L using Table 3- I Looking under globe, flow-under, find F L as 090 Next, estimate F F using Equation 34: F F 096-028 30 093 32062 Insert F L and F F into Equation 33: ΔP ch (090) 2 [3147 - (093)(30)] 2323 psi Since the actual ΔP is less than ΔP ch, the flow is not choked; therefore, use the smaller (or actual ΔP ) to size the valve At this point, also check for incipient cavitation using Equation 35 and Table 3-I: ΔP (cavitation) (081) 2 (3147-30) 187 psi Since ΔP (actual) exceeds ΔP (cavitation), substantial cavitation is occurring, but flow is not choked Special attention should be paid to material and trim selection Step 3: The specific gravity for water is given as 094 Step 4: Calculate the approximate using Equation 31 and assuming is 10: 094 500 334 210 Step 5: From the tables (Mark One, flow-under, equal percentage, Class 600) select the smallest body size for a of 334, which is a 2-inch body Step 6: Calculate the Reynolds Number Factor, F R, using Equations 36a and 36e as required (17,300) (1) (500) (090) 2 (334) 2 Re v +1 114 x 10 6 (0014) (090)(334) (890)(2) 4 Step 7: Since R ev > 40,000, F R 10 and the recalculated remains as 334 Step 8: Using the 2-inch body from step 5, determine the using Table 3-III, where: d/d 2/4 05 and /d 2 334/2 2 835 Therefore according to Table 3-III, the is 097 Step 9: Recalculate the final : 500 094 345 097 210 Step 10: Using Equation 37, the velocity for a 2-inch body is found to be nearly 51 ft/sec Since this application is cavitating, damage may result in a 2-inch valve A 3-inch body reduces velocity to about 23 ft/sec which 1/4 3-7

is a more acceptable value However, special trim may be required to eliminate cavitation damage NOTE: In this example, a 2 x 4-inch Mark One -X might also be chosen It is less costly than a 3-inch valve and the larger outlets will lower the velocities It will also be less costly to install in a 4-inch line Step 11: Since the body size has changed, recalculate the by following steps 8 and 9 The for a 3-inch body is nearly 10, and the final is 334 Step 12: Referring to the tables, a 33, 3-inch valve would require at least a trim number of 125 Trim number 20 may also suffice and have no reduced trim price adder Refer to Section 14 on special trims for cavitation protection Example Two Given: Liquid Ammonia Critical Pressure (P C ) 16382 psia Temperature 20 F Upstream Pressure ( ) 1497 psia Downstream Pressure (P 2 ) 647 psia Specific Gravity 065 Valve Action Flow-to-close Line Size 3-inch (Class 600) Flow Rate 850 gpm Vapor Pressure (P V ) 456 psia Kinematic Viscosity (v) 002 centistokes Flow Characteristic Linear Step 1: Calculate actual pressure drop using Equation 32 ΔP 1497 psia - 647 psia 85 psid Step 2: Check for choked flow Find F L using Table 3-I Looking under globe, flow-over, find F L as 085 Next, estimate F F using Equation 34: 456 F F 096-028 091 16382 Insert F L and F F into Equation 33: ΔP ch (choked) (085) 2 [1497 - (091)(456)] 782 ps Since the actual ΔP is more than ΔP ch, the flow is choked and cavitating; therefore, use the ΔP ch for ΔP a to size the valve Since the service is cavitating, special attention should be made to material and trim selection CavControl or ChannelStream should be considered Step 3: The specific gravity for ammonia is given as 065 Step 4: Calculate the approximate using Equation 31: 065 850 775 782 Step 5: From the tables (Mark One, flow-over, linear, Class 600) select the smallest body size for a of 775, which is a 3-inch body Steps 6 and 7: Turbulent flow is assumed, so Reynolds Number Factor is ignored, F R 10 Step 8: With the 3-inch body and 3-inch line, 1 Step 9: Since 1, the final remains as 775 Step 10: Using Equation 37, the velocity for a 3-inch body is found to be over 38 ft/sec Since this application is cavitating, this velocity may damage a 3-inch valve However, since the size is restricted to a 3-inch line, a larger valve size cannot be chosen to lower the velocity Damage problems may result from such a system A cavitation control style trim should be suggested; see Section 14 Step 11: If cavitation control trim is not selected, recalculation is not necessary since the body size or trim style did not change Step 12: Referring to the tables, a 775, 3-inch valve would use a trim number of 200 or the full size trim number 262 Use of this trim, however, could result in cavitation damage to body and trim; see Section 14 Flashing Liquids Velocity Calculations When the valve outlet pressure is lower than or equal to the saturation pressure for the fluid temperature, part of the fluid flashes into vapor When flashing exists, the following calculations must be used to determine velocity Flashing requires special trim designs and/or hardened materials Flashing velocity greater than 500 ft/sec requires special body designs If flow rate is in lb/ hr: V 0040 w x v x 1- f2 + v g2 (38) 100% 100% 3-8

if the flow rate is given in gpm, the following Equation can be used: V 20 q 1- x v 100% f2 + x v 100% g2 (39) V Velocity, ft/sec w Liquid flow rate, lb/hr q Liquid flow rate, gpm Valve outlet flow area, in 2, see Table 3-VIII v f2 Saturated liquid specific volume (ft 3 /lb at outlet pressure) v g2 Saturated vapor specific volume (ft 3 /lb at outlet pressure) x % of liquid mass flashed to vapor Calculating Percentage Flash The % flash (x) can be calculated as follows: Flashing Liquid Example Assume the same conditions exist as in Example One, except that the temperature is 350 F rather than 250 F By referring to the saturated steam temperature tables, you find that the saturation pressure of water at 350 F is 1345 psia, which is greater than the outlet pressure of 105 psia (90 psia) Therefore, the fluid is flashing Since a portion of the liquid is flashing, Equations 39 and 310 must be used x (% flashed) can be determined by using Equation 310: h f1 h f2 h fg2 3218 Btu/lb at 350 F (from saturation temperature tables) 3023 Btu/lb at 105 psia (from saturation pressure tables) 8864 Btu/lb at 105 psia (from saturation pressure tables) 3218-3023 x x 100% 22% 8864 h f1 - h f2 x x 100% (310) h fg2 Therefore, the velocity in a 3-inch valve can be determined by using Equation 39: x % of liquid mass flashed to vapor h f1 Enthalpy of saturated liquid at inlet temperature h f2 Enthalpy of saturated liquid at outlet pressure h fg2 Enthalpy of evaporation at outlet pressure v f2 v g2 00178 ft 3 /lb at 105 psia (from saturation pressure tables) 4234 ft 3 /lb at 105 psia (from saturation pressure tables) (20)(500) 22% 22% V 1-00178 + 4234 707 100% 100% For water, the enthalpies (h f1, h f2 and h fg2 ) and specific volumes (v f2 and v g2 ) can be found in the saturation temperature and pressure tables of any set of steam tables V 156 ft/sec Flashing velocity is less than 500 ft/sec, which is acceptable for Mark One bodies Hardened trim and CavControl should also be considered 3-9

CALCULATING FOR GASES Introduction Because of compressibility, gases and vapors expand as the pressure drops at the vena contracta, decreasing their specific weight To account for the change in specific weight, an expansion factor, Y, is introduced into the valve sizing formula The form of the Equation used is one of the following, depending on the process variables available: w 633 Y x γ 1 (311) x (312) G g Z xm w (313) Z x (314) M w Z w Gas flow rate, lb/hr Piping geometry factor Valve sizing coefficient Y Expansion factor x Pressure drop ratio γ 1 Specific weight at inlet conditions, lb/ft 3 Q Gas flow in standard ft 3 /hr (SCFH) G g Specific gravity of gas relative to air at standard conditions Absolute upstream temperature o R ( o F + 460 o ) Z Compressibility factor M w Molecular weight Upstream absolute pressure, psia Q 1360 Y w 193 Y Q 7320 Y NOTE: The numerical constants in Equations 311 314 are unit conversion factors The following steps should be used to compute the correct, body size and trim number: Step 1: Select the Appropriate Equation Based on the information available, select one of the four Equations: 311, 312, 313 or 314 Step 2: Check for Choked Flow Determine the terminal pressure drop ratio,, for that particular valve by referring to Table 3-V Next, determine the ratio of specific heats factor, F k, by using the Equation below: k F k 140 F k Ratio of specific heats factor k Ratio of specific heats (taken from Table 3-VI) (315) Calculate the ratio of actual pressure drop to absolute inlet pressure, x, by using Equation 316: ΔP x (316) x Ratio of pressure drop to absolute inlet pressure ΔP Pressure drop ( - P 2 ) Inlet pressure, psia Outlet pressure, psia P 2 Choked flow occurs when x reaches the value of F k Therefore, if x is less than F k, the flow is not choked If x is greater, the flow is choked If flow is choked, then F k should be used in place of x (whenever it applies) in the gas sizing Equations Table 3-V: Pressure Drop Ratios, Valve Type Flow Direction Trim Size Globe Flow-to-close Full Area 070 Flow-to-close Reduced Area 070 Flow-to-open Full Area 075 Flow-to-open Reduced Area 075 High Performance 60 o Open Full 036 Butterfly 90 o Open Full 026 Multi-stage Under Seat All ~100 Ball 90 o Open Full 030 3-10

Figure 3-4: Compressibility Factors for Gases with Reduced Pressures from 0 to 40 (Reproduced from charts of LC Nelson and EF Obert, Northwestern Technological Institute) Compressibility Factor, Z 40 30 20 10 Tr500 Tr100 105 110 115 120 130 140 150 160 180 200 250 300 350 400 500 600 800 1000 1500 Tr120 Tr100 Step 3: Calculate the Expansion Factor The expansion factor, Y, may be expressed as: Y 1 - x 3F k NOTE: If the flow is choked, use F k for x 0 0 5 10 15 20 25 30 35 40 Step 4: Determine the Compressibility Factor (317) To obtain the compressibility factor, Z, first calculate the reduced pressure, P r, and the reduced temperature, T r : P r (318) P C P r Reduced pressure Upstream pressure, psia P C Critical Pressure, psia (from Table 3-VI) T r (319) T C T r Reduced temperature Absolute upstream temperature T C Critical absolute temperature (from Table VI) Using the factors P r and T r, find Z in Figures 3-4 or 3-5 Reduced Pressure, Pr Compressibility Factor, 2 102 100 098 096 094 092 090 088 086 084 082 080 Tr250 E0174 Tr200 Tr180 Tr160 Tr150 078 076 Tr140 074 072 070 Tr130 068 066 Tr120 Tr120 064 0 1 2 3 4 5 6 Reduced Pressure, Pr E0175 Figure 3-5: Compressibility Factors for Gases with Reduced Pressures from 0 to 6 (Reproduced from charts of LC Nelson and EF Obert, Northwestern Technological Institute) 3-11

Table 3-VI: Gas Physical Data Critical Critical Ratio of Pressure Temperature Molecular Specific Gas (psia) ( o R) Weight (M w ) Heats (k) Air 4924 2271 2897 140 Ammonia 16361 7298 170 131 Argon 7070 2711 399 167 Carbon Dioxide 10702 5472 440 129 Carbon Monoxide 5071 2389 280 140 Ethane 7085 5494 301 119 Ethylene 7306 5080 281 124 Helium 329 901 400 166 Hydrogen 1882 594 202 140 Methane 6674 3428 1604 131 Natural Gas 6674 3428 1604 131 Nitrogen 4924 2268 280 140 Oxygen 7320 2780 320 140 Propane 6159 6653 441 113 Steam 32082 11651 1802 133 Step 5: Calculate Using the above calculations, use one of the four gas sizing Equations to determine (assuming is 1) Step 6: Select Approximate Body Size Based on From the tables in the appendix, select the smallest body size that will handle the calculated Q a M (gas) (320) 5574 kt Q a M w M (gas) (321) 1036 kt G g Step 7:Calculate Piping Geometry Factor If the pipe size is not given, use the approximate body size (from step 6) to choose the corresponding pipe size The pipe size is used to calculate the piping geometry factor,, which can be determined by Tables 3-III or 3-IV If the pipe diameter is the same as the valve size, is 1 and is not a factor Step 8: Calculate the Final With the calculation of the, figure the final Step 9: Calculate Valve Exit Mach Number Equations 320, 321, 322 or 323 are used to calculate entrance or exit velocities (in terms of the approximate Mach number) Use Equations 320 or 321 for gases, Equation 322 for air and Equation 323 for steam Use downstream temperature if it is known, otherwise use upstream temperature as an approximation Q a M (air) (322) 1225 T w v M (steam) (323) 1514 T M Mach number Q a Actual flow rate, ft 3 /hr (CFH, not SCFH; see page 3-13) Applicable flow area, in 2, of body port (Table 3-VIII) Absolute temperature o R, ( o F + 460 o ) w Mass flow rate, lb/hr v Specific volume at flow conditions, ft 3 /lb G g Specific gravity at standard conditions relative to air M w Molecular weight k Ratio of specific heats 3-12

NOTE: To convert SCFH to CFH use the Equation: (P a )(Q a ) (P S )(Q) (324) T a P a Actual operating pressure Q a Actual volume flow rate, CFH T a Actual temperature, R ( F + 460 ) P S Standard pressure (147 psi) Q Standard volume flow rate, SCFH Standard temperature (520 Rankine) T S T S After calculating the exit velocity, compare that number to the acceptable velocity for that application Select a larger size valve if necessary Refer to section 13 to predict noise level Caution: Noise levels in excess of 110 dba may cause vibration in valves/piping resulting in equipment damage Step 10: Recalculate if Body Size Changed Recalculate if has changed due to the selection of a larger body size Step 11: Select Trim Number Identify if the valve is for on/off or throttling service Using the tables in Section 4, select the appropriate trim number for the calculated and body size selected The trim number and flow characteristic (Section 9) may be affected by how the valve is throttled GAS SIZING EXAMPLES Example One Given: Gas Steam Temperature450 F Upstream Pressure ( ) 140 psia Downstream Pressure (P 2 ) 50 psia Flow Rate 10,000 lb/hr Valve Action Flow-to-open Critical Pressure (P C ) 32062 psia Critical Temperature (T C ) 7055 F Molecular Weight (M w ) 18026 Ratio of Specific Heats (k) 133 Flow Characteristic Equal percentage Line Size 2-inch (Class 600) Specific Volume 1041 Step 1: Given the above information, Equation 313 can be used to solve for Step 2: Referring to Table 3-V, the pressure drop ratio,, is 075 Calculate F k using Equation 315 and x using Equation 316: 133 F k 095 140 140-50 x 064 140 Therefore, F k is (095)(075) or 071 Since x is less than F k, flow is not choked Use x in all Equations Step 3: Determine Y using Equation 317: Y 1-064 070 3 (071) Step 4: Determine Z by calculating P r and T r using Equations 318 and 319: 140 P r 004 32082 450 + 460 T r 078 7055 + 460 Using Figure 3-4, Z is found to be 10 Step 5: Determine using Equation 313 and assuming is 1: 10,000 (910) (10) 470 (193) (140) (070) (064) (1802) Step 6: From the tables (Mark One, flow-under, equal percentage, Class 600), select the smallest body size for a of 47, which is a 2-inch body Steps 7 and 8: Since the pipe size is the same as the body, is 1 and is not a factor Therefore, the is 47 Step 9: The gas is steam, calculate the Mach number using Equation 323 Assume a constant enthalpy process to find specific volume at downstream conditions; from steam tables, v 1041 ft 3 /lb at T 2 414 o F : (10,000) (1041) M 074 1515 (314) 414 + 460 This is greater than Mach 05 and should be reviewed for excessive noise and use of noise reducing trim 3-13

Step 10: If body size does not change, there is no impact on calculation Step 11: Referring to the tables, a 47, 2-inch Mark One would use a trim number of 162 If noise is a consideration, see Sections 13 and 14 Example Two Given: Gas Natural Gas Temperature 65 F Upstream Pressure ( ) 13147 psia Downstream Pressure (P 2 ) 997 psia Flow Rate 2,000,000 SCFH Valve Action Flow-to-open Critical Pressure (P C ) 67292 psia Critical Temperature (T C ) 3428 R Molecular Weight (M w ) 16042 Ratio of Specific Heats (k) 131 Flow Characteristic Linear Line Size Unknown (Class 600) Step 1: Given the above information, Equation 314 can be used to solve for C V Step 2: Referring to Table 3-V, the pressure drop ratio,, is 075 by assuming a Mark One flow-under Calculate F k using Equation 315 and x using Equation 316: 131 F k 0936 140 13147-997 x 092 13147 Therefore, F k is (094)(075) or 070 Since x is greater than F k, flow is choked Use F k in place of x in all Equations Step 3: Determine Y using Equation 317: Y 1-070 0667 3 (070) Step 4: Determine Z by calculating P r and T r using Equations 318 and 319: 13147 P r 197 6674 T r 65 + 460 153 3428 Using Figure 3-5, Z is found to be about 086 Step 5: Determine C V using Equation 314 and assuming is 1: (2,000,00) (1604)(525)(086) C V 317 (7320)(13147)(667) 070 Step 6: From the tables (Mark One, flow-under, linear, Class 600), select the smallest body size for a of 317, which is a 1 1/2-inch body Steps 7 and 8: Since the pipe size is unknown, use 1 as the factor Therefore, the C V is 317 Step 9: Since the gas is natural gas, calculate the Mach number using Equation 320: (297,720*) M 661 5574 (177) (131)(65 + 460) 1604 *NOTE: To convert SCFH to CFH, use Equation 324 Step 10: Mach numbers in excess of sonic velocity at the outlet of the valve are not possible A larger valve size should be selected to bring the velocity below the sonic level To properly size the valve, select a size to reduce the velocity to less than 10 Mach Step 11: Using Equation 320, solve for the recommended valve area required for 05 Mach velocity: 297,720 CFH 05 M 163 in 2 5574 A 131 (65 + 460) 1604 Solve for the valve diameter from the area by: 4 4 (163) πd 2 or d 46 in π π Thus a 6-inch valve is required Step 12: Referring to the C V tables, a C V of 317, 6-inch Mark One would use a trim number of 162 Since the flow is choked, noise should be calculated from Section 13, and special trim may be selected from Section 14 3-14

CALCULATING FOR TWO PHASE FLOW Introduction The method of calculation for two phase flow assumes that the gas and liquid pass through the valve orifice at the same velocity The required is determined by using an equivalent density for the liquid gas mixture This method is intended for use with mixtures of a liquid and a non-condensable gas To size valves with liquids and their own vapor at the valve inlet will require good engineering judgement Nomenclature: flow area of body port (Table 3-VIII) ΔP a allowable pressure drop q f volumetric flow rate of liquid, ft 3 /hr q g volumetric flow rate of gas, ft 3 /hr w f liquid flow rate, lb/hr w g gas flow rate, lb/hr G f liquid specific gravity at upstream conditions G g gas specific gravity at upstream conditions upstream temperature ( o R) Step 1: Calculate the Limiting Pressure Drop First it must be determined whether liquid or gas is the continuous phase at the vena contracta This is done by comparing the volumetric flow rate of the liquid and gas Whichever is greater will be the limiting factor: If q f > q g, then ΔP a ΔP a for liquid If q g > q f, then ΔP a ΔP a for gas The ΔP a for liquid or gas is either - P 2 or the choked pressure drop of the dominating phase if the valve is choked (See the gas and liquid choked pressure Equations) Step 2: Calculate the Equivalent Specific Volume of the Liquid-gas Mixture (f g v g ) v e + f f v f f g f f v g Y 2 w g (w g + w f ) w f (w g + w f ) (27 G g ) v f 1 (624 G f ) Y gas expansion factor (Equation 317) Step 3: Calculate the Required of the Valve w g + w f F p 633 ΔP a Use the smaller of - P 2 and ΔP ch for P a Step 4: Select Body Size Based on From the tables in the appendix, select the smallest body size that will handle the calculated Step 5: Calculate Piping Geometry Factor If the pipe size is not given, use the approximate body size (from step 6) to choose the corresponding pipe size The pipe size is used to calculate the piping geometry factor,, which can be determined by Tables 3-III or 3-IV If the pipe diameter is the same as the valve size, is 1 Step 6: Calculate Final With the calculation of the, figure the final Step 7: Calculate the Valve Exit Velocity (q f + q g ) Velocity w f q f 624 G f w g q g 27 G g P 2 Area applicable flow area After calculating the exit velocity, compare that number to the acceptable velocity for that application Select a larger valve size if necessary Recommended two phase flow velocity limits are similar to those for flashing when the gaseous phase is dominant If liquid is the dominant phase, velocity of the mixture should be less than 50 ft/sec in the body Step 8: Recalculate if Body Size Changed Recalculate if has been changed due to the selection of a larger body size Step 9: Select Trim Number Identify if the valve will be used for on/off or throttling service Using the tables in Section 4, select the appropriate trim number for the calculated and body size selected The trim number and flow characteristic (Section 9) may be affected by how the valve is throttled Special trim and materials may be required if high noise levels or cavitation are indicated v e 3-15

Table 3-VII: Pipe Flow Areas, A p (Square Inches) Nominal Schedule Pipe Diameter 10 20 30 40 60 80 100 120 140 160 STD XS XXS 1 /2 030 023 017 030 023 005 3 /4 053 043 030 053 043 015 1 086 072 052 086 072 028 1 1 /2 204 177 141 204 177 095 2 336 295 224 336 295 177 3 739 661 541 739 661 416 4 1273 1150 1032 928 1273 1150 780 6 2889 2607 2377 2115 2889 2607 1883 8 518 512 500 479 457 435 406 385 365 500 457 371 10 825 807 789 747 718 681 645 601 567 789 747 12 1179 1148 1119 1062 1016 961 908 866 805 1131 1084 14 1431 1405 1379 1353 1290 1227 1155 1096 1039 983 1379 1327 16 1887 1857 1826 1767 1694 1609 1526 1445 1353 1290 1826 1767 18 2405 2371 2304 2237 2138 2042 1933 1827 1738 1637 2337 2270 20 2986 2910 2835 2780 2652 2527 2388 2270 2138 2027 2980 2835 24 434 425 411 402 382 365 344 326 310 293 425 415 30 678 661 649 663 602 574 542 513 36 975 956 938 914 870 830 782 42 1328 1302 1282 1255 1187 1132 1064 Table 3-VIII: Valve Outlet Areas Valve Valve Outlet Area, Size (Square Inches) (inches) Class Class Class Class Class Class Class 150 300 600 900 1500 2500 4500 1 /2 020 020 020 020 020 015 011 3 /4 044 044 044 037 037 025 020 1 079 079 079 061 061 044 037 1 1 /2 177 177 177 150 150 099 079 2 314 314 314 278 278 177 123 3 707 707 707 651 594 398 278 4 1257 1257 1257 1182 1029 651 398 6 2827 2827 2827 2597 2273 1507 1029 8 5027 5027 4877 4418 3848 2597 1963 10 7854 7854 7466 6910 6013 4128 2827 12 11310 11310 10843 9712 8462 5836 4128 14 13789 13789 13029 11786 10171 7088 5027 16 18265 18265 17087 15394 13273 9280 6362 18 23370 22698 21382 19483 16787 11786 8446 20 29104 28353 26159 24053 21073 14314 10153 24 42456 41548 38013 34636 30233 20739 14314 30 67196 66052 58835 54119 47606 32589 36 96211 90792 85530 42 132025 119459 NOTE: To find approximate fluid velocity in the pipe, use the Equation V P V v / A P where: V P Velocity in pipe Valve Outlet area from Table 3-VIIl V v Velocity in valve outlet A P Pipe area from Table 3-VII To find equivalent diameters of the valve or pipe inside diameter use: d 4 /π, D 4A p /π 3-16