A Numerical Study of the Performance of a Heat Exchanger for a Miniature Joule-Thomson Refrigerator

Similar documents
Influence of Ambient Temperature on Performance of a Joule-Thomson Refrigerator

Micro Channel Recuperator for a Reverse Brayton Cycle Cryocooler

Cooling Characteristics of GM-type Pulse Tube Refrigerator with Neon as Working Gas

Vibration-Free Joule-Thomson Cryocoolers for Distributed Microcooling

Earlier Lecture. In the earlier lecture, we have seen Kapitza & Heylandt systems which are the modifications of the Claude System.

Modeling and Optimization of a Mixed-Gas Joule-Thomson Cryoprobe System

Mid InfraRed Instrument (MIRI) Cooler Cold Head Assembly Acceptance Testing and Characterization

CFD Flow Analysis of a Refrigerant inside Adiabatic Capillary Tube

Effect of Coiled Capillary Tube Pitch on Vapour Compression Refrigeration System Performance

CFD Simulation and Experimental Validation of a Diaphragm Pressure Wave Generator

Single Phase Pressure Drop and Flow Distribution in Brazed Plate Heat Exchangers

Helium-Liquefaction by Cryocooler for High-Field Magnet Cooling

AN EXPERIMENTAL INVESTIGATION ON HELIUM LIQUEFACTION USING TWO-STAGE GIFFORD McMAHON CRYOCOOLER

Figure 1 Schematic of opposing air bearing concept

Supercritical CO2 Power Cycles: Design Considerations for Concentrating Solar Power

Predicting the Suction Gas Superheating in Reciprocating Compressors

An Experimental Performance Study of Vortex Tube Refrigeration System

CYCLE ANALYSIS OF LINEAR COMPRESSORS USING THREE- DIMENSIONAL CFD

Effect of Hot End Obstruction and Nozzle on the Performance of Vortex Tube

A. M. Dalavi, Mahesh Jadhav, Yasin Shaikh, Avinash Patil (Department of Mechanical Engineering, Symbiosis Institute of Technology, India)

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

Development of High Efficiency 4K Two-Stage Pulse Tube Cryocooler

University of Cincinnati

OPTIMIZATION OF RECUPERATER FIN GEOMETRY FOR MICRO GAS TURBINE

Open Cycle Joule-Thomson Cryocooling by Mixed Coolant

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

Experimental Investigation on Stirling type Thermally Coupled Three Stage Pulse tube Cryocoolers with U type Configuration

An Investigative and Synoptic Review on Helium Liquefaction Using a Commercial 4 K Gifford- McMahon Cryocooler

Recuperative Cooling Capability of Miniature Thermoacoustic Expanders (MTAEs) around 77 K

ASSIGNMENT 2 CHE 3473

FABRICATION AND OPTIMIZATION OF PERFORMANCE OF VORTEX TUBE PARAMETERS

ASSIGNMENT 2 CHE 3473

Performance Testing of a High Capacity Compressor for a 20K 20W Cryocooler

An Investigation of Liquid Injection in Refrigeration Screw Compressors

Improvement of the Volumetric and Isentropic Efficiency Due to Modifications of the Suction Chamber

TESTING AND ANALYZING ON P-V DIAGRAM OF CO 2 ROLLING PISTON EXPANDER

University of Cincinnati

ANALYSIS OF HEAT TRANSFER THROUGH EXTERNAL FINS USING CFD TOOL

Study on the Influencing Factors of Gas Mixing Length in Nitrogen Displacement of Gas Pipeline Kun Huang 1,a Yan Xian 2,b Kunrong Shen 3,c

CFD Simulation of the Flow Through Reciprocating Compressor Self-Acting Valves

Investigation to Improve Efficiency of Transcritical R744 Two-Stage Vapor Compression Systems

Development of a Passive Helium Heat Switch for Fast Cool Down by Two-Stage Cryocooler

Comparative Analysis of Two Types of Positive Displacement Compressors for Air Conditioning Applications

Experimental Analysis and CFD Simulation of Pressure Drop of Carbon Dioxide in Horizontal Micro Tube Heat Exchangers

Two-stage pulse tube refrigerator with step displacer as phase shifter

Influencing Factors Study of the Variable Speed Scroll Compressor with EVI Technology

A Numerical Simulation of Fluid-Structure Interaction for Refrigerator Compressors Suction and Exhaust System Performance Analysis

COMPUTATIONAL FLUID DYNAMICS ANALYSIS OF HELICAL NOZZLES EFFECTS ON THE ENERGY SEPARATION IN A VORTEX TUBE

Thomas Jefferson National Accelerator Facility Newport News, Virginia, 23606, USA

Simulator For Performance Prediction Of Reciprocating Compressor Considering Various Losses

Numerical Simulation for the Internal Flow Analysis of the Linear Compressor with Improved Muffler

AIR EJECTOR WITH A DIFFUSER THAT INCLUDES BOUNDARY LAYER SUCTION

JT Micro Compressor Test Results

EXPERIMENTAL PERFORMANCE ANALYSIS OF VORTEX TUBE FOR VARIOUS PARAMETERS

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events

Modeling and Testing of an Automobile AC Scroll Compressor, Part II: Model Validation

Optimization of rotor profiles for energy efficiency by using chamber-based screw model

A NEW PROCESS FOR IMPROVED LIQUEFACTION EFFICIENCY

Continuously Variable Inertance Tubes for Pulse Tube Refrigerators

Thermal Testing of an EM Two-Stage Coaxial Pulse Tube Cold Finger for Earth Observation Missions

Basics of Low-temperature Refrigeration

Bradley Moore 1 University of Wisconsin - Madison

Investigation of Suction Process of Scroll Compressors

Visual Observation of Nucleate Boiling and Sliding Phenomena of Boiling Bubbles on a Horizontal Tube Heater

Cryogenic Engineering Prof. M. D. Atrey Department of Mechanical Engineering Indian Institute of Technology, Bombay

Development of Two Opposing Nozzle Vortex Tube Using Air as Working Fluid

Transient Analyses In Relief Systems

First Experimental Data of the Cryogenic Safety Test Facility PICARD

Heat Transfer Research on a Special Cryogenic Heat Exchanger-a Neutron Moderator Cell (NMC)

ALICE SPD cooling system

Supercritical CO 2 Power Cycles: Design Considerations for Concentrating Solar Power

Proceedings of the ASME th Biennial Conference on Engineering Systems Design and Analysis ESDA2014 June 25-27, 2014, Copenhagen, Denmark

A Twin Screw Combined Compressor And Expander For CO2 Refrigeration Systems

MATHEMATICAL MODELING OF PERFORMANCE OF A LIQUD PISTON COMPRESSOR

Oil-Lubricated Compressors for Regenerative Cryocoolers Using an Elastic Membrane

Hermetic Compressor With Improved Motor Cooling

The Estimation Of Compressor Performance Using A Theoretical Analysis Of The Gas Flow Through the Muffler Combined With Valve Motion

Fundamentals of Turboexpanders Basic Theory and Design

Dynamic Operation of a 4 K Pulse Tube Cryocooler with Inverter Compressors

STUDY OF CRYOGENIC SYSTEMS WITH ASPEN - HYSYS ANALYSYS

Two-way Fluid Structure Interaction (FSI) Analysis on the Suction Valve Dynamics of a Hermetic Reciprocating Compressor

Enter your parameter set number (1-27)

EXPERIMENTAL STUDY ON THE DISCHARGE CHARACTERISTICS OF SLUICE FOR TIDAL POWER PLANT

Thermodynamic Modeling and Mechanical Design of a Liquid Nitrogen Vaporization and Pressure Building Device

Axial and Radial Force Control for CO2 Scroll Expander

Seminar 65 Compression Challenges for Low GWP Refrigerants

Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance

Design of a Partial Admission Impulse Turbine for an Automotive ORC-Application. Harald S. Kunte, Joerg R. Seume

HYDROGEN FAST FILLING TO A TYPE IV TANK DEVELOPED FOR MOTORCYCLES

Part 6: Critical flow orifices

1 SE/P-02. Experimental and Analytical Studies on Thermal-Hydraulic Performance of a Vacuum Vessel Pressure Suppression System in ITER

SIMULATION OF AIR LIQUEFACTION USING ASPEN PLUS

CFD analysis & Experimental Investigation of Shell & Tube Type Heat Exchanger with modified Slotted Baffles

Purdue e-pubs. Purdue University. Stephan Lehr Technische Universitaet Dresden. Follow this and additional works at:

Investigation of failure in performance of linear compressor & its rectifications

EXAM # 2. First Name Last Name CIRCLE YOUR LECTURE BELOW: INSTRUCTIONS

EXPERIMENTAL ANALYSIS OF FIN TUBE AND BARE TUBE TYPE TUBE-IN-TUBE HEAT EXCHANGER

SIMULATION OF ENVIRONMENTAL FLIGHT CONDITIONS

HTR Systems and Components

Transcription:

A Numerical Study of the Performance of a Heat Exchanger for a Miniature Joule-Thomson Refrigerator Yong-Ju Hong 1, Seong-Je Park 1, and Young-Don Choi 2 1 Korea Institute of Machinery & Materials, Daejeon, Korea 2 Department of Mechanical Engineering, Korea University, Seoul, Korea ABSTRACT Miniature Joule-Thomson refrigerators have been widely used for rapid cooling of infrared detectors, cryosurgery probes, thermal cameras, and missile guidance homing systems, due to their special features of simple configuration, compact structure and rapid cooldown characteristics. The thermodynamic performance of the J-T refrigerator depends upon the hydraulic and heat transfer characteristics of the recuperative heat exchanger. The typical recuperative heat exchanger of the J-T refrigerator has the double helical tube and fin configuration. In this study, an effectiveness-ntu approach is adopted to predict the thermodynamic behaviors of the heat exchanger for the Joule-Thomson refrigerator. The thermodynamic properties from the NIST REFPROP 1 database is used to account for the real gas effects. The results show the effect of the operating conditions on the performance of the heat exchanger and refrigerator for the given heat exchanger. The influences of mass flow rate and the supply pressure on the effectiveness of heat exchanger and the ideal cooling capacity are discussed in details. INTRODUCTION Miniature Joule-Thomson (J-T) refrigerators have been widely used for rapid cooling of infrared detectors, cryosurgery probes, thermal cameras, and missile guidance homing systems, due to their special features of simple configuration, compact structure and rapid cooldown characteristics. Nitrogen (NBP 77.35 K) and argon gas (NBP 87.3 K) are typically used as the cryogen due to their availability, low cost and relatively low cryogenic temperature. The cooldown time, the cold end temperature, the running time and the gas consumption are the important indicators of the Joule-Thomson refrigerator performance. The cooling power of the J-T refrigerator is generated by the isenthalpic expansion of the high pressure gas through the throttling process. The J-T effect could be amplified by using an expanded gas to cool incoming gas within a recuperative heat exchanger. The thermodynamic performance of J-T refrigerator is highly dependent upon the hydraulic and heat transfer characteristics of the recuperative heat exchanger. The typical recuperative heat exchanger of the J-T refrigerator has the double helical tube and fin configuration to increase heat transfer area as shown in Figure 1. Limited experimental and theoretical studies on the performance of the refrigerator were performed due to the complexity of the geometry of the recuperative heat exchanger of the 379

380 recuperator modeling and performance investigations Helical Tube Fin Figure 1. The typical recuperative heat exchanger of J-T refrigerator. Joule-Thomson refrigerator. Ng et al. 2 and Xue et al. 3 reported the experimental and numerical study of the J-T refrigerator for steady-state characteristics with the argon gas. Numerical studies of J-T refrigerator with the nitrogen gas for transient characteristics with one dimensional transient model were reported by Chien et al. 4, Chou et al. 5, and Chua et al. 6 developed the geometry model of the Hampson-type cryocooler with argon gas as a cryogen. The steady state governing equations were solved numerically. In this study, an effectiveness-ntu approach is adopted to predict the thermodynamic behaviors of the heat exchanger for the J-T refrigerator with nitrogen and argon gas. RECUPERATIVE HEAT EXCHANGER A schematic diagram of a J-T cooling cycle is found in Figure 2. It consists of a counter flow heat exchanger with helical fins, a pressure vessel, an evaporator (expansion space) and a J-T valve. From point 1 to point 2, the high pressure gas is cooled in the counter flow heat exchanger by the low pressure returning gas after J-T expansion (from point 2 to point 3). An energy balance of the J-T valve requires that the specific enthalpy at the valve outlet must equal the specific enthalpy at the valve inlet. The ideal cooling capacity at the evaporator is given by where ṁ is the mass flow rate. (1) (2) Figure 2. The schematic diagram of a J-T cooling cycle.

Heat exchanger for a miniature J-t refrigerator 381 The enthalpy of high pressure gas leaving each element and the enthalpy of low pressure gas entering each element could be calculated according to where Q i is the recuperative heat transfer of each element. The heat transfer between the fluids is related to the temperature difference according to: (5) where ε is the effectiveness of each element and C min is smaller capacity rate between two recuperating stream. The effectiveness-ntu relationship associated with a counter-flow heat exchanger is follows. 7 (3) (4) (7) where Cr is capacity ratio of two streams and UA is the conductance of the each element. UA is related to the convective heat transfer characteristics of two stream and conduction through the wall of the tube according to (6) (8) where A high is the inner surface of the finned tube, A low is the outer surface of the finned tube, η is the efficiency of the fin and η f is the adiabatic fin efficiency. The heat transfer characteristics of the heat exchanger is highly dependent on the local distribution of the pressure and temperature. Heat transfer coefficients of each element for high pressure gas and low pressure gas could be expressed as 7 (9) (10) where D H is the diameter of the helix and D low is the hydraulic diameter of the passage of the low pressure returning gas as shown in Figure 3. (11) Figure 3. Cross-sectional view of a recuperative heat exchanger.

382 recuperator modeling and performance investigations The pressure drop of the each element along the longitudinal direction could be calculated according to (12) where U is the gas velocity of each element and x is the longitudinal direction of the heat exchanger. The friction factors of each element for high pressure gas and low pressure gas could be calculated according to 8 (13) (14) (15) where X T is the non-dimensional transverse pitch and X L is the longitudinal pitch of the finned tube. Thermodynamic properties of the gas are varied along the high pressure and low pressure passages. In the analysis, the thermodynamic properties from the REFPROP 1 were used to account the J-T cooling effects of the gas. The geometric dimensions of the recuperative heat exchanger are listed in Table 1. The analysis was carried out for the nitrogen and argon gas with inlet pressures of 10, 20, 30, 40, 50 MPa and at 300 K. RESULTS AND DISCUSSION The heat exchanger effectiveness has significant effects on the liquefied yield fraction of the cryogen and the cooling capacity of the J-T refrigerator. Figure 4 shows the variation of the effectiveness of the heat exchanger with different mass flow rates for nitrogen gas. The effectiveness decreases as the mass flow rate increases. The decrease in the effectiveness comes from the decrease of the heat exchanger NTU. The effectiveness at 10 MPa is significantly lower than the effectiveness when the pressure is above 20 MPa. The effectiveness is almost the same when the inlet pressure is above 30 MPa. The ideal cooling capacity of the J-T refrigerator is shown in Figure 5 as a function of the mass flow rate for nitrogen gas. The ideal cooling capacity increases as the mass flow rate through the (16) Table 1. Dimensions of a recuperative heat exchanger

Heat exchanger for a miniature J-t refrigerator 383 Figure 4. Variation of the effectiveness with different mass flow rates of the nitrogen gas. heat exchanger increases. At the higher inlet pressure, the ideal cooling capacity is more linearly proportional to the mass flow rate. There exists an optimal mass flow rate for the maximum of the ideal cooling capacity wirh the inlet pressure of 10 Mpa and 20 MPa. At the pressure of 20 MPa, the maximum of ideal cooling capacity occurs when the mass flow rate is about 3 times larger than that of the pressure of 10 MPa. At the pressure of 10 MPa and above mass flow rate of 0.2 g/s, the J-T refrigerator does not have the cooling capacity due to the small effectiveness of the heat exchanger. The ideal cooling capacity is higher for higher pressure up to 40 MPa. The results show that the ideal cooling capacity of 50 MPa is below the 40 MPa. The thermodynamic characteristics (enthalpy) of the nitrogen gas results in the decrease of the cooling capacity. Figure 6 shows the variation of the effectiveness of the heat exchanger with different mass flow rates of the argon gas. It is clear that the heat exchanger with the argon gas has the high effectiveness. Figure 7 shows the variation of the ideal cooling capacity of the heat exchanger with different mass flow rates of the argon gas. There exists an optimal mass flow rate for the maximum of ideal cooling capacity at the inlet pressure of 10 MPa. At 10 MPa, the refrigerator with the argon gas has the wide operating range of the mass flow rate up to 0.43 g/s. The refrigerator with argon gas as a cryogen has a higher ideal cooling capacity than one with nitrogen gas as a cryogen. At the higher inlet pressure, the ideal cooling capacity is more linearly proportional to the mass flow rate than that of the nitrogen. Figure 5. Variation of the ideal cooling capacity with different mass flow rates of the nitrogen gas.

384 recuperator modeling and performance investigations Figure 6. Variation of the effectiveness with different mass flow rates of the argon gas. Figure 7. Variation of the ideal cooling capacity with different mass flow rates of the argon gas Figure 8 shows the temperature and pressure profile along the longitudinal direction of the heat exchanger with the nitrogen (for the mass flow rate 0.0198 g/s (1slpm) and 0.1975 g/s (10 slpm)) at the inlet pressure of 40 MPa. At the mass flow rate of 1 slpm, the pressure drop of the heat exchanger is negligibly small, and the temperature differences between the high pressure and low pressure gas are small due to the high effectiveness of the heat exchanger. The increases of the mass flow rate results in the increases of the pressure drop of and the relaxation of the temperature gradient. The temperature and pressure profile of the heat exchanger with the argon (for the mass flow rate 0.0282 g/s (1slpm) and 0.2818 g/s (10 slpm)) are shown in Figure 9. Comparison of the temperature profiles of the nitrogen and argon leads one to conclude that the argon develops a more nonlinear temperature profile along the heat exchanger than the nitrogen. It is obvious that the small pressure drop of the low pressure gas occur along the heat exchanger for the nitrogen and argon gas.

Heat exchanger for a miniature J-t refrigerator 385 Figure 8. The temperature and pressure profile with the nitrogen at the pressure of 40 MPa. Figure 9. The temperature and pressure profile with the argon at the pressure of 40 MPa SUMMARY In the present study, effectiveness-ntu approach was adopted to predict the thermodynamic behaviors of the heat exchanger for the J-T refrigerator with the nitrogen and argon gas. The results show that the effectiveness of the heat exchanger decreases as the mass flow rate increases, but the ideal cooling capacity at high pressure do not decrease. At low pressure, the refrigerator has the limited operating range in the mass flow rate. The argon develops a more nonlinear temperature profile along the heat exchanger than nitrogen, and the small pressure drop of the low pressure gas occur along the heat exchanger for the nitrogen and argon gas. ACKNOWLEDGMENT This work was supported by the Program for the leading technology in specialized research field from Korea Institute of Machinery & Materials. REFERENCES 1. Lemmon, E. W., McLinden, M. O., Huber, M. L., NIST Reference Fluid Thermodynamic and Transport Properties-REFPROP, NIST, Boulder (2002).

386 recuperator modeling and performance investigations 2. Ng, K. C., Xue, H., Wang, J. B., Experimental and numerical study on a miniature Joule-Thomson cooler for steady-state characteristics, Int. J. of Heat and Mass Transfer, Vol. 45 (2002), pp. 609 618. 3. Xue, H., Ng, K.C., Wang, J.B., Performance evaluation of the recuperative heat exchanger in a miniature Joule-Thomson cooler, Applied Thermal Engineering, Vol. 21 (2001), pp.1829-1844. 4. Chien, S. B., Chen, L. T., Chou, F. C., A study on the transient characteristics of a self-regulating Joule-Thomson cryocooler, Cryogenics, Vol. 36, Issue: 12, December 1996, pp. 979-984. 5. Chou, F. C., Pai, C. F., Chien, S. B., Chen, J. S., Preliminary experimental and numerical study of transient characteristics for a Joule-Thomson cryocooler, Cryogenics, Vol. 35, Issue: 5, May 1995, pp. 311-316. 6. Chua, H. T., Wang, X., Teo, H. Y., A Numerical study of the Hampson-type miniature Joule-Thomson cryocooler, Int. J. of Heat and Mass Transfer, vol. 49 (2006), pp. 582-593. 7. Mills, A.F., Heat and Mass Transfer, Richard D. Irwin, Inc.,Chicago (1995) 8. Timmerhaus, K. D., Flynn, T. M., Cryogenic Process Engineering, Plenum Press, New York (1989).