COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

Similar documents
COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

S Surge Arresters

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

2000 lb manual winch

Installation and Operation

VERTICAL SURFBOARD CARRIER READ ME! IMPORTANT WARNING!

S Loadbreak Apparatus Connectors WARNING: WARNING:

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

GRAVITY BIKE RACK ASSEMBLY & OPERATING INSTRUCTIONS

Norrsken Family Booklet

deluxe toilet safety support

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

This document to be used with Hurley traditional Davits

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

Effective May 2017 Supersedes August 2005 (S )

ATD /8 x 50 Retractable Air Hose Reel Owner s Manual

Inspection Recommendations

WALL-MOUNT GARDEN HOSE REEL OWNER S MANUAL

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

Triple Tine Mechanical Grapple

3M Liqui-Cel EXF-14x28 and 14x40 Series Membrane Contactor

STYLE 3414/3416 & 3421/3423 Apollo Monitor with Foldaway Legs OPERATING & MAINTENANCE INSTRUCTIONS

UE- 90- X X X X X X O P E R AT I N G M A N UA L 0 TO 90 HYDRAULIC UPENDER

COMPACT METAL bender 99826

OWNERS MANUAL. Model Shown with optional Primary Mooring Cleats. Portable Mooring System SAFETY OPERATION MAINTENANCE PARTS

Instruction manual. Type Vector manual group-operated switch. Answers for infrastructure and cities.

C - SERIES. Height Adjustable Portable Goal Supports. Installation & Owner s Instructions C1000 C2000. Made in the USA

Type Vector manual group-operated switch instruction manual. Installation operation maintenance E50001-F710-A420-X-4A00. Answers for energy.

Backboard and Rim Owners Manual

OPERATOR S MANUAL Expand-it Brushcutter Attachment UT15702A

Accu-Tab Systems 1000 Series by Axiall Corporation

foldable/adjustable sawhorse

Owner s Manual & Safety Instructions

MODEL SWH10 1,000 LB CAPACITY SWIVEL HOIST

OPERATOR'S MANUAL GRASS CATCHER GC-4D

Accu-Tab Systems 2000 P Series by Axiall Corporation

Sub-Base Assembly For Type-ML 32 & VR-1 Step Voltage Regulator Single-Phase Liquid-Filled Part # GEK 35171

Sunset Swings By Health in Motion, LLC

VOLLEYBALL SPIKE TRAINER. Assembly Instructions. Owner s Manual. Model # VST-400. Club Volleyball Gear

60 farm jack. Distributed exclusively by Harbor Freight Tools Mission Oaks Blvd., Camarillo, CA 93011

VOLLEYBALL SPIKE TRAINER. Assembly Instructions. Owner s Manual. Model # VST-100. Club Volleyball Gear WARNING

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

USER MANUAL. DM65 Manual Flush/Tilt Combo Mount

BS Series Basket Strainer

OPERATOR'S MANUAL. MODEL GC-F4 Fabric Grass Catcher P/N 9055 GRASS CATCHER GC-F4. PART Rev.2 SC301G

Compact Triple Cabinet Outlet Station Model B Installation and Operating Instructions

Mini Pod Press. #78H-M2 Mini Pod Press Manual-R1

Retractable Hose Reel with 3/8" x 50' PVC Hose

VOLLEYBALL SPIKE TRAINER. Assembly Instructions. Owner s Manual. Model # VST-300. Club Volleyball Gear. For fixed-height Basketball Hoop Systems

Portable Massage Table User Manual

Reliance Industries, LLC Operating instructions for the / Bolt-on D-Ring Anchorage. Model # 3071

Cocoa Patio Pond with Lit Spillway

INSTALLATION INSTRUCTIONS

RADROVER REAR RACK INSTALLATION MANUAL

SASK-A-POLE OWNERS AND USERS MANUAL

FLANGED TWO-PIECE BALL VALVES

Side-of-Pole Mount for 1 Module (SPM1) For Module Types A & B

User Instructions 1789 Parapet Wall Anchor

Caliber Sled Wheels Assembly Instructions for PN and 13579

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions

Pressure Dump Valve Service Kit for Series 2300 Units

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

3M Liqui-Cel EXF-10x28 Series Membrane Contactor with ANSI or JIS Connections with Integrated End Caps

FLANGED TWO-PIECE BALL VALVES

OPERATOR S MANUAL. Fabric Grass Catcher PART NO PRINTED 1/2011 PRINTED IN USA

INSTALLATION COMMISSIONING, OPERATION & MAINTENANCE MANUAL

Transcription:

Switches MN008005EN Effective April 2016 Supersedes S328-120-1 June 2013 D-73P3 bypass switches installation instructions COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii D-73P3 BYPASS SWITCHES INSTALLATION INSTRUCTIONS MN008005EN April 2016

Contents SAFETY INFORMATION Safety information...iv PRODUCT INFORMATION Introduction...1 Acceptance and initial inspection...1 Handling and storage...1 Standards...1 INSTALLATION PROCEDURE Switch configurations...1 Mounting the switch...2 Cross-arm mount...2 Pole mounting...2 Terminal connections...2 OPERATION....3 MAINTENANCE...3 D-73P3 BYPASS SWITCHES INSTALLATION INSTRUCTIONS MN008005EN April 2016 iii

! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 iv D-73P3 BYPASS SWITCHES INSTALLATION INSTRUCTIONS MN008005EN April 2016

Product information Introduction Eaton's Cooper Power series D-73P3 bypass switch is a single-phase 3-pull, 3-blade hookstick-operated switch. It is used for manually disconnecting a recloser or regulator without disturbing normal electrical service. The D-73P3 switch does not have current making or breaking capability without use of portable loadbreak tools. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user's purpose, please contact your Eaton representative. Installation procedure The switch must be properly selected for each installation with consideration to continuous current, BIL, and rated voltage. Switch configurations D-73P3 style bypass switches are available for both right (standard) and left bypass opening configuration. Left opening configuration is indicated by a L catalog number listed on nameplate. When opening switch with standard right configuration, the bypass blades opens to the right of the operator when standing in front of the switch. A left opening by-pass opens to the left. Operation procedures do not change based on right or left opening of the bypass blade. Acceptance and initial inspection Each switch is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the switch and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. Handling and storage Be careful during handling and storage of the switch to minimize the possibility of damage. If the switch is to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001 Certified Quality Management System D-73P3 BYPASS SWITCHES INSTALLATION INSTRUCTIONS MN008005EN April 2016 1

Mounting the switch 1. Eaton s D-73P3 line of bypass switches come equipped with blade stop pin to provide 90 blade opening stop. If 90 blade stop is not required, remove retaining clip from one side of pin closest to hinge contact, and slide stop pin out of blade assembly. 2. Optional 150 latch (option A) available to provide positive blade stop at 150 opening. To utilize 150 latch, ensure stop pin is positioned to alternate pin hole located closest to latch side contact. Cross-arm mount: The standard D-73P3 back strap is 15 galvanized steel with two 1/2-13 thread x 8 L carriage bolts each with nut, flat and lock washer. Adjust the bolt heads in the switch base slots as needed to closely fit the cross arms. Tighten mounting hardware to about 12-15 ft-lbs. Figure 1. Optional 150D positive latch. 3. D-73P3 bypass switch is made for mounting to either a single or double cross arm in an inverted or vertical position, as well as using optional pole mounting bracket (option M or X) to secure directly to pole with equipment positioned beneath. When mounting using back strap, position the switch on the cross arms using the supplied standard back strap and bolt assembly. Secure back strap to switch with cross arm between base using the supplied carriage bolts, lock washers, flat washers and nuts. Figure 2. Standard backstrap mount for cross-arm installation Pole mounting Optional pole mounting bracket provides a steel bracket for wood pole mounting. ½ galvanized hardware including bolts, flat-washer, lock-washer and nuts are supplied to attach the switch to bracket. The user supplies the hardware for mounting bracket to pole. Figure 3. Optional pole mounting bracket, available in standard (19.5 ) and extended length (25.5 ) Terminal connectors Before installing desired connectors on terminal pads. Consider using wire brush on terminal pads and electrical conductors and using oxidation inhibitor before inserting conductor into connector. Tighten connector hardware to about 12-15 ft-lbs. 2 D-73P3 BYPASS SWITCHES INSTALLATION INSTRUCTIONS MN008005EN April 2016

Operation In normal operation, the bypass blade is open and the two disconnect blades are closed (Figure 4), allowing the equipement to be in the circuit. When isolation of regulator or recloser is required, close the by-pass blade to provide a parallel current path. Open the disconnect blades to isolate the recloser/regulator from the circuit. To open the disconnect blades, position yourself with stable footing below switch, place the hookstick in pull ring on blade and pull down toward the hinge end of switch at a 45 angle. Once disconnect blade is open, complete blade travel to its stop position. To close the D-73P3 switch, place the hookstick in the pull ring on the blade and rotate the blade to an intermediate position. Look away from switch. Quickly and firmly drive the switch blade to the closed position. To open the D-73P3 by-pass switch, place the hookstick in the pull ring on the blade. Look away from switch. Quickly and firmly pull down towards the hinge end of the switch at a 45 angle. Once the switch blade is open complete the blade travel to its stop position. Carefully remove hookstick from the pull ring. All Eaton's D-73P3 switches include loadbreak hooks as standard offering to be used with loadbreak tool. To open the switch under load, use only an approved loadbreak tool or device designed for use with switches. Follow the instructions provided with such tools. Maintenance The D-73P3 bypass switch should require little maintenance. Following a program of periodic inspection and maintenance will prolong the life of the D-73P3 switch. 1. Operate the switch periodically to clean contact surfaces and to free moving parts 2. Check for burned or pitted contacts and replace if necessary 3. Inspect all blade spacers for looseness and if loose, tighten for even pressure across contacts. 4. Inspect mounting hardware and tighten as needed (12-15 ft-lbs.) Normal Position Bypass Position Figure 4. D-73P3 3-pull regulator/recloser bypass switch. D-73P3 BYPASS SWITCHES INSTALLATION INSTRUCTIONS MN008005EN April 2016 3

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN008005EN Rev 00 Supersedes S328101 Rev 0 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.