C645A-E Pressure Switches

Similar documents
C437D,E,F,G,H,J,K and C637B Gas Pressure Switches

DS06D,G Dial Set Pressure Regulating Valve

D05T Compact Design Pressure Regulating Valves

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

36H SERIES Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

GM Series Dual-Block Multi-Function Gas Control Valves

SPECIFICATIONS ATTENTION

P7911C PressureTrol Controller

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

G96 Series BASOTROL Dual Operator Valve

P7810C PressureTrol Controller

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

V8200A,C,H,M and VR8200A,C,H,M Continuous Pilot Combination Gas Controls

P7810A-D Pressuretrol Controller

VR8305 Direct Ignition Dual Automatic Valve Combination Gas Controls

VR8205S,T Direct Ignition Combination Gas Controls

VR8305 Direct Ignition Combination Gas Control

D05 Pressure Regulating Valves

G92 Series BASOTROL Automatic Pilot Gas Valve

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

GM-7000 Series CE Approved Gas Control Valve

VR8200A Continuous Pilot Combination Gas Controls

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

DS05C,D,G Dial Set Pressure Regulating Valves

VR8105, VR8205, and VR8305 Direct Ignition Combination Gas Controls

Dual Solenoid Gas Valve Installation

V5097A-E Industrial Gas Valves

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

North American Pressure Switches

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

SPECIFICATIONS CAPACITY

O.K. Safety first CDN USA. Table of Contents. Approvals. Attention IFGC CSA UL ANSI NFPA

BGA158 Series CE Approved Class B Shutoff Gas Valve

Propane Conversion Kit Instruction

Installation Instructions

BGA158 Series CE Approved Class A Shutoff Gas Valve

V5197A. Firing Rate Gas Valve APPLICATION FEATURES PRODUCT HANDBOOK

installation instructions

ACCESSORY KIT INSTALLATION MANUAL

OC Panel High Limit Aquastat Kit, Manual Reset p/n

Installation Instructions

Gas Pressure Switch for DMV safety shutoff valves

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

Propane Conversion Kit Instruction

WARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY

Gas Pressure Switch for DMV safety shutoff valves

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Propane Conversion Kit Instruction

PRESSURE SWITCHES Bulletin 8757

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*

Model 130M Pneumatic Controller

VR8104, VR8204, and VR8304 Intermittent Pilot Combination Gas Controls

Operator: Save these instructions for future use!

BGC258 Series BASOTROL Gas Valve

Valve Proving System VDK 200 A S06*

V5097A-E Industrial Gas Valves

Propane Conversion Kit Instructions

Operator: Save these instructions for future use!

/2004 US/CA

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

VS8420 Millivolt Gas Valve

Gas Pressure Switch for DMV safety shutoff valves

ACCESSORY KIT INSTALLATION INSTRUCTIONS

SL G3. Warning

USER S INFORMATION MANUAL

VRB00 Series CLASS B SERVO REGULATED COMBINATION VALVES

Valve Proving System VDK 200 A S02

Your safety and the safety of others are very important.

Gas Fired Residential Heating Boilers

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

MULTIFUNCTIONAL CONTROL FOR GAS BURNING APPLIANCE

Automatic Valve Proving Control

SPECIFICATIONS. Normally closed automatic shutoff valve with proof of closure. Fast opening, fast closing. ATTENTION

Dual Modular Safety Shutoff Valves with Two-stage operation and Proof of Closure. DMV-ZRD/612 Series DMV-ZRDLE/612 Series

Introduction. Description. Series P48 Pressure Controls for Steam, Air or (hot) Water. Feature and Benefits

VR8345M Universal Electronic Ignition Gas Control

VR46.5V(A)/VR86.5V(A) SERIES

Pressure switch for gas and air

Dual Modular Safety Shutoff Valves with Two-stage operation and Proof of Closure DMV-ZRD/612 Series DMV-ZRDLE/612 Series

VR400/VR800 SERIES. Honeywell CLASS A SERVO REGULATED COMBINATION VALVES APPLICATION DESCRIPTION INSTRUCTION SHEET

Pressure Switch for gas and air

Instructions for High Altitude Conversion

Pressure Switch for gas and air GGAO-A4

Pressure Switch for gas and air

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

SL G3 - Fuel Conversion to Natural Gas (LP to NG) P-Kit 301

INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

LGB Series 1 & 2 Section And Base Assembly

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

SV - Safety Shutoff Valve with Proof of Closure 1/2" NPT - 2" NPT. SV/614 Series SV-DLE/614 Series

VK41../VK81.. GAS CONTROLS FOR COMBINED VALVE AND IGNITION SYSTEM SPECIFICATIONS APPLICATION DESCRIPTION INSTRUCTION SHEET

Transcription:

C645A-E Switches FEATURES PRODUCT DATA C645A,B,D,E GENERAL C645A,B with Window C645C The C645 pressure switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes. C645A,B models are for use on natural gas, LP gas, or air. C645B047 includes a scaleplate stop to meet American Gas Association (AGA) requirements for gas-fired boilers with inputs over 2-/2 million Btuh. C645C,D models are for use on air only. C645E for use with distillate fuel oil. Spring-loaded diaphragm actuates snap-acting Micro Switch. Switch can be wired to turn on alarm. C645A,C and D models break control circuit on pressure fall. C645B models break control circuit on pressure rise. Lockout and manual reset optional in A and C models. Removable, zinc-plated cover protects scaleplate and adjusting screw. Lockout models have external manual reset lever. Pipe tappings allow selection of positive pressure, differential-pressure, or venting connections. Optional switch position indicator available. Models of C645A,B available with cover window for setpoint visibility. Buna-N fiber-reinforced material for increased control diaphragm strength. Two seal-off diaphragms for added reliability. Contents General... Features... Specifications... 2 Ordering Information... 2 Installation... 4 Settings and Adjustments... 6 Operation and Checkout... 7 Copyright 995 Honeywell Inc. All Rights Reserved 60-259-8

SPECIFICATIONS Models: C645A,C,D Switches break a circuit when pressure falls to scale setting minus the differential. Refer to Table. C645B Switches break a circuit when pressure rises to scale setting. Refer to Table. C645E breaks circuit when pressure falls to scale setting minus the differential. Refer to Table. Table. switch model selection. Differential Differential Maximum Maximum Scale Scale Natural Switch Range Range Surge Surge Range Range or LP Switching Position (in. wc) (kpa) Cover Models (in. wc) (kpa) Gas Air Action Indicator Nom. Max. Nom. Max. (psi) (kpa) Window C645A 3 to 2 0.7 to 5.2 5 to 35.2 to 8.7 C645B 3 to 2 0.7 to 5.2 C645C 5 to 35.2 to 8.7 0.6 to 5.3 0. to.3 Yes Yes Auto Recycle or Lockout a Optional 3 0.2 0.7 5 34.5 Optional Yes Yes c 4 0.2.0 5 34.5 Yes Yes Yes Lockout b Yes 3 0.2 0.7 5 34.5 Optional Yes Yes Yes 4 0.2.0 5 34.5 Yes No Yes Auto Recycle or Lockout a Optional 0.2 0.8 0.05 0.02.5 0.3 No 2 to 20 d 0.5 to 5 No Yes Auto Recycle No 3 0.2 0.7 5 34.5 No C645D 3 to 2 0.7 to No Yes Auto Recycle No 3 0.2 0.7 5 34.5 No 5.2 C645E 3 to 2 0.7 to No Yes Auto Recycle No 3 0.2 0.7 5 34.5 No 5.2 a Locks out when pressure falls to setpoint minus differential; can be reset manually after pressure rises to setpoint. Locks out when pressure rises to setpoint; can be manually reset after pressure falls to setpoint minus differential. Without indicator on Auto Recycle; with indicator on Lockout model. With surge orifice. Switch Ratings (Amperes): Model 20 Vac 240 Vac C645A Full Load 7.4 3.7 C645B Locked Rotor 44.4 22.2 C645D C645C Full Load 8.0 5. Locked Rotor 48.0 30.6 C645E Full Load 7.4 3.7 Locked Rotor 44.4 22.2 All models also rated 2A at 30 Vac. Alternate Electrical Ratings when used with Honeywell Flame Safeguard Programmers (all C645 models): Ignition Transformer Pilot Valve 50 Main Valve 540 VA 250 VA with 0 times inrush. 400 VA with 2-/2 times inrush. ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE wholesaler or your distributor, refer to the TRADELINE catalog or price sheets for complete ordering number, or specify. Order number. 3. Optional specifications. 2. Air or gas control on C645A,B models. 4. Accessories, if desired. If you have additional questions, need further information, or would like to comment on our products or services please write or phone:. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory). 2. Honeywell Home and Building Control Customer Relations Honeywell, 885 Douglas Drive North Minneapolis, Minnesota 55422-4386 In Canada Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario MV 4Z9. International sales and service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A. 60-259 8 2

Switching: Spdt Micro Switch snap-acting switch (Fig. 3). Minimum Ambient Temperature: -20 F (- 29 C). Maximum Ambient Temperature: 25 F (52 C). Connections: /4-8 NPT female tapping for main or high pressure connection. /8-27 NPT female tapping for venting or low-pressure connection. Approvals: Underwriters Laboratories Inc. listed: C645AE File no. MP268, Guide no. MFHX; for use in ambient temperatures normally prevailing in occupiable spaces, which usually are not higher than 77 F (25 C) but can occasionally be as high as 04 F (40 C) for brief periods. Canadian Standards Association listed: C645A-E, File no. LR620-369, Guide no. 40-A-2; for use subject to same ambient temperature restrictions as Underwriters Laboratories Inc. Factory Mutual Approved. Industrial Risk Insurers: C645A-D models with window in cover approvable for applications on burners over 5 million Btuh (5 thousand cfh) input. Optional Specifications:. C645A with position indicator and manual reset. 2. C645A operation to.5 in. WC with position indicator and manual reset. 3. C645B with position indicator and manual reset. 4. C645C with position indicator and manual reset. 5. C645D with 2 in. (50.8 mm) differential. Accessories:. C645A,B,D: Mounting Bracket: part no. 5865AC. 2. C645C: Mounting Bracket: part no. 2657A. 3. C645A: Cover with Window: part no. 37637B. 4. C645B: Cover with Window: part no. 37637C. 2-7/8 (73) 3-/2 (88.9) MOUNTING BRACKET (OPTIONAL) 3-/2 (88.9) 4 (0.6) 4-3/4 (20.6) 3/6 (2) (4.8) /4-8 NPT /8-27 NPT 3/8 (9.5) 5/8 (5.9) 3/8 (9.5) -/8 (28.6) IMPORTANT: FOR MODELS WITH LOCKOUT, DO NOT OBSTRUCT MANUAL RESET LEVER. 2-/2 (63.5) -5/6 (33.3) M7564 Fig.. Dimensions of C645A,B,D, and E in in. (mm). 3 60-259 8

MOUNTING BRACKET (OPTIONAL) 5/6 (7.9) -/8 (29) MANUAL RESET LEVER 3-7/8 (98.4) 3-5/8 (92) 3/6 (4.8) DIA. /4-8 INCH NPT 3/4 (9) 5 (27) -3/6 (46) 3 (76.2) 2-5/8 (66.7) 9/32 (7.) DIA. (2) (25.4) -/4 (3.7) 2-/4 (57.) 3/4 (9) 2-3/4 (69.8) IMPORTANT: FOR MODELS WITH LOCKOUT, DO NOT OBSTRUCT MANUAL RESET LEVER. 7-7/8 DIA. (200) /8-27 INCH NPT M7563 Fig. 2. Dimensions of C645C in in. (mm). INSTALLATION When Installing this Product... Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. Installer must be a trained, experienced service technician. After installation is complete, check out product operation as provided in these instructions. CAUTION Disconnect power supply before beginning installation to prevent electrical shock or equipment damage. Mounting The C645 has a hexagonal fitting with a /4 in. NPT tapping, which is the high pressure connection in differential applications. The bleed fitting is /8 in. NPT female tapped. In differential pressure control applications using air, connect the lower pressure to the bleed fitting (Fig. 3 and 4). In applications using combustible gases, vent the bleed tapping according to applicable standard code or jurisdictional authority. The C645A,B,D can be mounted in any position but are more accurate when mounted horizontally. The C645C is mounted with the diaphragm vertical and the bleed fitting at the bottom. 60-259 8 4

The C645E002 Distillate Fuel Oil Switch is the same as the C645A006 Gas Switch except that it does not have a 0.05 in. (0.38 mm) diameter (nominal) orifice in its /4 in. NPT main (high pressure) connection. (This orifice is required in a C645A Gas Switch to restrict gas leakage, but it is too small for oil applications.) The C645E002 has a 0.25 in. (3.8 mm) diameter (nominal) opening in its /4 in. NPT main connection into its pressure chamber. CAUTION Vent the bleed tapping back to the oil supply tank not to the combustion chamber. MANUAL RESET LEVER ON LOCKOUT MODELS ONLY OPENING FOR /2 INCH CONDUIT Wiring Disconnect power supply before connecting wiring to prevent electrical shock and equipment damage. All wiring must agree with applicable codes, ordinances, and regulations. An opening is provided to accommodate rigid conduit or armored cable for line voltage operation (Fig. 3 and 4). Do not overload the switch contacts (see Switch Ratings in Specifications section). The switching schematic is shown in Fig. 5. COVER SCALE PLATE BLEED FITTING Fig. 4. C645C with cover removed. SET POINT ADJUSTMENT M756 SET POINT ADJUSTMENT SCALE PLATE BLEED FITTING OPENING FOR /2 INCH CONDUIT COVER W B 2 MICRO SWITCH R C645A,C,D BREAKS R-W, MAKE R-B ON PRESSURE FALL. MANUAL RESET MODELS LOCK OUT. MANUAL RESET LEVER ON LOCKOUT MODELS ONLY M7560 2 C645B BREAKS R-B, MAKES R-W ON PRESSURE RISE AND LOCKS OUT. M7565 Fig. 3. C645A,B,D with cover removed. Fig. 5. Schematic showing switch in zero pressure condition. 5 60-259 8

SETTINGS AND ADJUSTMENTS Setpoint Adjustment Tables 2 through 4 give the pressure and switching for each setpoint. To adjust the pressure setting, turn the setpoint adjustment screw (Fig. 3 and 4) clockwise to increase the pressure setting and counterclockwise to decrease the pressure setting. Table 2. C645A,D,E control points. Setpoint Switching in. of Water kpa 3 a R-W makes 3 0.8 R-B makes 2 0.5 9 b R-W makes 9 2.2 5 b R-W makes 5 3.7 2 c R-W makes 2 5.2 R-B makes 8 4.5 35 d R-W makes 35 8.7 R-B makes 3 7.7 a Nominal differential in. of water (0.2 kpa). Differential between and 3 in. of water (0.2 and 0.7 kpa). Maximum differential 3 in. of water (0.7 kpa). Maximum differential 4 in. of water (.0 kpa). Table 3. C645B control points. Setpoint Switching in. of Water kpa 3 a R-W makes 3 0.8 R-B makes 2 0.5 9 b R-W makes 9 2.2 5 b R-W makes 5 3.7 2 c R-W makes 2 5.2 R-B makes 8 4.5 35 d R-W makes 35 8.7 R-B makes 3 7.7 45 e R-W makes 45.2 R-B makes 39 9.8 a Nominal differential in. of water (0.2 kpa). Differential between and 3 in. of water (0.2 and 0.7 kpa). Maximum differential 3 in. of water (0.7 kpa). Maximum differential 4 in. of water (.0 kpa). Maximum differential 5.7 in of water (.4 kpa). Table 4. C645C Control Points. Setpoint Switching in. of Water kpa a R-W makes 0.25 R-B makes 0.8 0.2 3 b R-W makes 3 0.75 R-B makes 2.6 0.64 5 b R-W makes 5.24 R-B makes 4.3.2 Top Scale c R-W makes 6.50 R-B makes 5.2.3 a Nominal differential 0.2 in. of water (0.05 kpa). b Differential between 0.2 and 0.8 in. of water (0.05 and.2 kpa). c Maximum differential 0.8 in. of water (0.2 kpa). C645B047 Scaleplate Stop Adjustment The C645B047 is the same as the C645B03 except for a scaleplate stop. Specifications Scaleplate Stop: Limits maximum setting, factory-set at 5-/4 in. of water (.3 kpa). Scale Range: 3 to 2 in. of water (0.75 to 5.23 kpa). Adjusting Wrench: Part no. 23466 included with the C645B047. To Adjust Scaleplate Stop Remove cover. Loosen scaleplate stop locking screw about /2 turn counterclockwise with the 23466 Adjusting Wrench. Move scaleplate stop until bottom edge is aligned with desired maximum setting. Tighten scaleplate stop locking screw clockwise. Replace cover. 60-259 8 6

LOCKING SET POINT INDICATOR 23466 ADJUSTING WRENCH SCALEPLATE STOP Fig. 6. Adjusting C645B047 scaleplate stop. M7562 Manual Resetting The C645A,C manual reset models lock out at scale setting minus the differential and require manual resetting after the pressure rises to scale setting to resume normal operation. The C645B locks out at scale setting and requires manual resetting after the pressure falls to scale setting minus the differential to resume normal operation. To reset, push the reset button as far as it will go; then release. IMPORTANT Lockout models cannot be made to recycle automatically by permanently holding in the reset lever. OPERATION AND CHECKOUT Operation The C645A,C,D,E spring-loaded diaphragm actuates the Micro Switch snap-acting switch to break a control circuit when pressure falls to scale setting minus differential. The switch can be wired to turn on an alarm at the same time. When the pressure rises to the scale setting, the control circuit requires manual resetting to reset and turn off alarm. Optional C645A model will recycle automatically when the control circuit returns to scale setting. The C645B spring-loaded diaphragm actuates the Micro Switch snap-acting switch which breaks a control circuit, locks out, and turns on an alarm (if so wired) when the pressure rises to the scale setting. When pressure falls to the scale setting minus the differential, the switch lockout can be manually reset, turning off the alarm Checkout C645A,B Gas or Air Switch Set cutoff pressure. Open main supply line. Depress reset lever on lockout models until switch makes R-W. Set controller and limit switch to call for heat. For C645A close main shutoff valve. Valve should close when pressure reaches cutoff point. For C645B wait a few minutes for the pressure to rise; then lower the scale setting until the switch makes R-W and locks out. NOTE: To more accurately check C645A, use slow bleedoff. For C645B, jumper other limit and let pressure rise to cutoff setting. For C645A reconnect the control valve, open the shutoff valve, press the reset lever (if necessary), and return the pressure switch to its original setting. For C645B raise setting to normal. Depress reset lever. Allow system to operate through at least one complete cycle to make certain all components are functioning properly. C645C,D Air Switch Only Set cutoff pressure. Turn on fan. If using a manual rest C645, depress and hold lever until switch makes R-W. Block fan inlet or filter area. Switch should break R-W, make R-B when pressure drops to cutoff point. Manual reset models lock out. Remove obstruction. Depress reset lever and allow system to operate through at least one complete cycle to make certain all components are functioning properly. C645E002 Distillate Fuel Oil Switch The C645E002 is the same as the C645A006 Gas Switch except the C645E002 has a 0.25 in. NPT main connection in its pressure chamber. See Checkout for C645A. 7 60-259 8

Home and Building Control Honeywell Inc. 985 Douglas Drive North Golden Valley, Minnesota 55422 Home and Building Control Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario MV 4Z9 60-259 8 F.P. Rev. 5-95 8 www.honeywell.com/bbc