Instructions for SILEX 1C Mixed bed cartridge filter

Similar documents
ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

Prestige Water Equipment Ltd.

Installation and commissioning instructions 255 series and 256 series

WARNING! Equipment for treatment of water intended for human consumption (Directive 98/83 CE).

Manual Actuated Boiler Blowdown Valves

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

Nitrogen Tyre Inflator Owner s Manual

NORMAL OPERATING DISPLAYS GENERAL OPERATION

The ultimate in water softening

CARTRIDGE FILTERS TECHNICAL MANUAL MT 080. Installation, commissioning and maintenance instructions. 08/02 Edition

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Easy Nest Kits. Installation Suggestions

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

GENO -Flushing Compressor Product Data Sheet F 02

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

O&M Receiving and Inspection. Storage of Water Treatment Media

RARS5000 AIR BODY SAW OWNER S OPERATING MANUAL

Installation, Operation and Maintenance Instructions for Pacific PA Non-Storage Heat Exchanger

BS Series Basket Strainer

AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS

FILTER REGULATORS MODEL NO: CAT155 & CAT156 FITTING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Installation and Instructions 2. Product Features 3-6. Key Pad Functions 7. Distributor Information Programming Guide 8. Master Programming Guide 9-14

INSTRUCTION MANUAL Pressure Relief Device LPT

OPERATING MANUAL. Contents. Bottom outlet ball valve Type ecoline

Pure Water Power Purification System 4-Stage RODI Operations Manual

AIR HAMMERS MODEL NO: CAT138/CAT139 OPERATING & MAINTENANCE INSTRUCTIONS PART NO: / GC064

CARTRIDGE FILTERS. Models: CF50, CF75, CF100, CF150,

WW-720. Pressure Reducing Control Valve

Operation Manual. Carbon Filtration Industrial Drive, Orlinda, TN fax

WW-720. Pressure Reducing Control Valve

Flamco Flamco-Fill STA Flamco-Fill STM

Budget Range Operators Handbook

PRESSURISED PAINT CONTAINER

CAPITAL CONTROLS SERIES NXT3000

Installation guide Scale Control. Before installing read this guide first

Prestige Water Equipment Ltd.

Flowmeter. Original operating manual DFM

Summary of the MRA LPG Codes of Practice

VERTICAL AIR COMPRESSORS

Instruction Manual. LKHSP Self-Priming Centrifugal Pump (Appendix) ESE02222-EN

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

Series SFD. Clean Air Filter. Variations. Made to Order. Type. Cartridge (replaceable element) Disposable (non-replaceable element) Up to 100

14. Exploded View. Page 68

SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL

Operating Instructions

BOSS PULISCI PROVA IMPIANTI MEDIA

OPERATION MANUAL RTI RHS650 RTI TECHNOLOGIES, INC East Market Street York, PA Manual P/N

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

INSTALLATION INSTRUCTIONS

Dri-Line Mk3 Monnier Compressed Air Drain Trap

Installation, Operation and Maintenance Instructions Buffer Vessel OM006

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

Operating and maintenance manual Filter and reducing station Series / 1.0

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

1200B2 Series Service Regulators. Instruction Manual

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Eaton Filtration, LLC

D05 Pressure Regulating Valves

5 Gallon Pressure Pot with HVLP Spray Gun and Hose

553 Series.

MODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL

BCV31 DN40 - Blowdown Control Valve

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS

Reverse Osmosis System Installation Guide and Operation Manual.

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Product Sheet Spraymist Unit

CAST IRON SAFETY VALVE TYPE 6301

Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability.

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Instruction Manual. Alfa Laval SB Pressure Exhaust Valve ESE02965-EN Original manual

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

Owners Manual Models: 075-AQF-CX. Aquatrol Backwashing Catalytic Carbon Filter. Visit us online at.

Eaton Filtration, LLC

CRP Ltd INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SYRINGE SAMPLING SYSTEMS

OFFICINE OROBICHE S.p.A. 1/9

1800C and 1800C-HC Series Service Regulators

Latvin Luxury Shower Panel. Telephone Product Specification. ~ Minimum Working Pressure 1.0 bar ~ Maximum Working Pressure 3.

Installation guide Scale Control. Before installing read this guide first

CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES

Installation Instructions and User Guide 15mm & 22mm Thermostatic Mixing Valve

GREIG FILTERS, INC. OPERATION MANUAL

Bermad Pressure Reducing. Model: 42T

11. Spare Parts. applications since applications since

Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0

INSTRUCTION MANUAL & PARTS

Jacuzzi. J-CQ420 Cartridge Filter Installation and Operating Instructions

OPERATION & MAINTENANCE INSTRUCTIONS

Horizontal Bladder Tanks

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

VERTICAL AIR COMPRESSORS

SV60 Safety valves. for use with steam, gas and liquids

SRV66 Sanitary Pressure Reducing Valve

Transcription:

D01B-30A-UK1 January 2017 Instructions for SILEX 1C Mixed bed cartridge filter With conductivity sensor Gravity flow or pressure installation SILHORKO-EUROWATER A/S Phone +45 86 57 12 22 DK-8660 Skanderborg info@eurowater.com Denmark www.eurowater.com

Call-out service Service agreements Consumables Modernizations International after sales service EUROWATER has an international sales and service organization with an experienced staff of engineers and specially trained service technicians. Our service is fully documented, characterized by a short reaction time and it is our goal to be easy to work with in all situations. We offer customized service agreements, high quality consumables and modernizations. In order to keep your critical systems running EUROWATER offer call-out service for urgent needs, individual service agreement on preventive maintenance, access to high-quality spare parts and consumables as well as modernizations in all shapes and sizes. Spare parts and consumables We offer a wide range of spare parts, service kits, and consumables. Our service cars are equipped with a broad range of spare parts, mainly of our own make. We continuously supply spare parts for more than 25-year-old plants. Read more about spare parts and consumables in the last chapter. Rental plants for temporary needs In case of temporary needs, such as emergency or planned maintenance, EUROWATER offers a wide range of mobile rental plants, ready for use upon delivery. Training The more you know about your water treatment plant, the better equipped you are to deal with the routine operations of the plant, thereby minimizing down time. As part of our commitments to provide a first class service, we offer specialized operator training for your staff. Contact EUROWATER is an international group with subsidiaries in 14 countries servicing our customers through 23 local offices. Moreover, the company is represented in most of the other European countries through independent distributors who are all water treatment specialists. Find your local sales and service office on our international website: www.eurowater.com Page 2 9

Contents 1. Introduction... 4 1.1. List of figures... 4 2. General information... 4 2.1. Plant description... 4 2.2. Quality requirements of the untreated water... 4 2.3. The contents of dissolved salts in the water - conductivity... 4 2.4. Storage of a SILEX cartridge... 4 2.5. Life... 4 3. Installation instructions... 5 3.1. Gravity flow installation... 5 3.2. Pressure installation... 6 4. Conductivity meter... 7 4.1. Secon V3-10... 7 5. Operating instruction... 8 5.1. Replacing the SILEX cartridge... 8 5.2. Handling the exhausted cartridge... 8 6. Disposing of plant... 8 7. Consumables and selected spare parts... 9 7.1. Cartridges and regeneration... 9 7.2. Spare parts... 9 Page 3 9

1. Introduction The instructions are made so that they can be followed section by section. It is recommended to follow the instructions carefully since any service calls due to faulty installation, plant start, operation or insufficient maintenance are not covered by our guarantee. 1.1. List of figures Figure 1 - Gravity flow installation... 5 Figure 2 - Pressure installation... 6 Figure 3 - Conductivity meter Secon V3-10... 7 2. General information 2.1. Plant description A complete SILEX plant comprises a tank, a cartridge, and a conductivity meter that continuously indicates the conductivity of the demineralized water. The SILEX cartridge contains cation and anion exchange resins with a certain demineralization capacity. At exhausted capacity the used cartridge is exchanged for a regenerated cartridge. The used cartridge is returned in the original packing to the address of the regeneration centre: Here the cartridge will be regenerated and then returned, ready for use. 2.2. Quality requirements of the untreated water The temperature of the water to be demineralized must not exceed 35 C and must not contain iron, manganese, oil, or large quantities of organic matter. Common tap water will normally meet these requirements. 2.3. Dissolved salts in the water - conductivity The electronic conductivity meter continuously indicates the conductivity of the demineralized water in µs/cm. The conductivity is a measure of dissolved solids in the water. Lower conductivity means fewer dissolved solids. Water type Distilled water Demineralized SILEX water Conductivity 7-10 µs/cm < 0.1 µs/cm 2.4. Storage of a SILEX cartridge On account of the ion exchange resins the SILEX cartridge must be stored in a frost-free room. Unused cartridges must be stored as cool as possible preferably at refrigerator temperature i.e. 4-8 C. Storage at higher temperatures adds to the risk of growth of micro-organisms just like the cartridge's ability to produce water of low conductivity is reduced. 2.5. Life Cartridges that are stored at refrigerator temperature should be used within six months from the delivery date. When stored at room temperature the cartridges should be used within three months. It is of greatest importance for the life of the cartridges that they are stored and exchanged under as sterile conditions as possible, so that the risk of contamination from the surroundings and the operator is minimized. Page 4 9

3. Installation instructions 3.1. Gravity flow installation 1. Use the angle fittings supplied to mount the SILEX plant on the wall close to a stop valve. The water feed to the plant is regulated with the stop valve (pos. 1) 2. The maximum flow must not exceed 2 l per minute. If the flow can increase above this load, install a valve on the inlet set to a maximum flow of 2 l/min. at maximum mains pressure and lock the valve in this position (pos. 3). 3. The water is fed through the hose coupling (½") on the right side of the plant. The demineralized water exits through a hose connected to the coupling on the left side of the plant. This hose must not be fitted with any closing device and must be of synthetic or other corrosion-resistant material. 4. N.B.: A small and limited discharge of tiny particles (< 0.5 mm diameter) of ion exchange media cannot be excluded. If such a discharge can harm the subsequent installation in any way, please install a suitable mechanical filter after the outlet of the SILEX plant (pos. 13). 5. Provide an adjustable non-return valve between the mains piping and the SILEX installation. Check and follow local regulations. Figure 1 - Gravity flow installation 1. Stop valve 7. Transformer 12. Angle fittings 3. Regulating valve 8. Conductivity meter 13. Filter 6. Air vent 9. SILEX unit According to EN 61010-1 item 1.4 the plant is installed under installation category II. The transformer shall comply with EN 60742. Page 5 9

3.2. Pressure installation 1. Mount the SILEX plant on the wall with the fittings supplied. 2. The plant is designed for a maximum pressure of 6 bar. Exceeding the maximum operating pressure of the plant can cause reflux in the installation or temperature increase in the liquid during a standstill. In that case, please install a pressure reducing valve (pos. 4), a diaphragm pressure extension tank (pos. 10), or a relief valve on the plant inlet (pos. 11). 3. Provide a stop valve (6 bar) on the plant inlet and outlet in order to shut off the water supply for replacement of the cartridge. 4. The maximum plant flow is 2 l/minute. If the flow can exceed that, fit a valve on the plant inlet and set it at a maximum flow of 2 l/minute at maximum mains pressure. Lock the valve in this position. 5. The water is fed through the hose coupling (½") on the right side of the plant and the coupling on the left side carries demineralized water. The outlet line, including valves and fittings, must be of corrosion-resistant material. 6. N.B.: A small and limited discharge of tiny particles (< 0.5 mm diameter) of ion exchange media cannot be excluded. If such a discharge can harm the subsequent installation in any way, please install a suitable filter after the outlet of the SILEX plant (pos. 13). 7. Install a non-return valve (pos. 2) between the mains piping and the SILEX installation. Check and follow local regulations. Figure 2 - Pressure installation 1. Stop valve 6. Air vent 11. Relief valve, if any 2. Non-return valve 7. Transformer 12. Angle fittings 3. Regulating valve 8. Conductivity meter 13. Filter 4. Pressure reducing valve, if any 9. SILEX unit 5. Pressure gauge 10. Diaphragm pressure extension According to EN 61010-1 item 1.4 the plant is installed under installation category II. Transformer shall comply with EN 60742 Page 6 9

4. Conductivity meter The electronic conductivity meter continuously measures and displays the quality of the demineralized water. 4.1. Secon V3-10 The water quality is expressed as the water's capability of conducting an electric current and the conductivity is measured in µs/cm. A high conductivity means plenty of mineral salts in the water and thus a poor water quality. Conversely, a low conductivity means few mineral salts and a good water quality. 1. Connect the supplied wall plug transformer 100-240VAC / 9-24VDC to the conductivity meter. Plug the transformer into a 240 V wall socket and switch it on. 2. The meter is now in operation and the water conductivity is displayed by 5 LED lights with the following scale. Figure 3 - Conductivity meter Secon V3-10 3 LED green < 0,1 μs/cm 2 LED green < 0,5 μs/cm 1 LED green < 1,0 μs/cm 1 LED yellow < 5,0 μs/cm 1 LED red < 10 μs/cm 1 LED red flashing ( ) > 10 μs/cm Page 7 9

5. Operating instructions During normal operation, the SILEX runs by itself. There are no manual or automatic controls. The only requirement is for the operator to monitor the conductivity sensor regularly to ensure it does not exceed the specified value for the intended application. When the conductivity is too high for the application, or the ion exchangers are exhausted, the cartridge must be replaced with a regenerated one. 5.1. Replacing the SILEX cartridge 1. Close the stop valve at the inlet. 2. Close the stop valve at the outlet. 3. Release the internal pressure by loosening the air vent. 4. Disconnect the inlet and outlet hoses. 5. Remove the top flange by unscrewing the four bolts. 6. Remove the exhausted cartridge. Hang it to drip-dry only! Drying it completely destroys the resins! 7. Unmount the SILEX unit, place it on the floor by a drain, and tip it to drain the remaining water completely. 8. Open the plastic bag with the new cartridge, and use the bag itself as a funnel to slowly lower the cartridge into the vessel. 9. Remove the plastic bag and carefully tug the clamp on the cartridge to avoid creases on the sides. 10. Vibrate the vessel by tapping it, so the cartridge settles completely. It is very important that the cartridge fits tightly inside the unit. 11. Mount the top flange and tighten the hand screws until the top flange and vessel are flush. Make sure gasket, o-ring and bearing surfaces are completely clean before tightening. 12. Open the air vent. 13. Open the inlet stop valve and then close the air vent when water flows from it. 14. Open the outlet stop valve. The SILEX is now in operation again. 5.2. Handling the exhausted cartridge 1. Place the exhausted, but still moist, cartridge in the plastic bag. Seal it and place it in original packaging. 2. Dispatch the cartridge to the regeneration center. IF THE ION EXCHANGERS DRY OUT THEY STOP WORKING AND CANNOT BE RETURNED FOR REGENERATION CENTER. 6. Disposing of plant When the system or parts thereof are no longer in use, they must be disposed of through approved public or private systems, in accordance with environmental regulations. When in doubt, please contact your local EUROWATER office or distributor. Page 8 9

7. Consumables and selected spare parts EUROWATER plants last for many years, but consumables, such as filter media, salt for regeneration, ion exchange resin and filters, have a certain capacity or lifespan and must be replaced at certain intervals. EUROWATER carries all consumables and spare parts necessary to keep your water treatment plant running for years, even decades. Here are some common consumables, spare parts and upgrades you can order now. > You can also contact EUROWATER and learn about your options. 7.1. Cartridges and regeneration SILEX cartridges have a limited capacity and must be replaced when exhausted. EUROWATER has a wellestablished cartridge return system that ensures almost no down-time for the plant. 7.2. Spare parts A regenerated cartridge with a mix of anion and cation ion exchangers, ready to be loaded into the SILEX plant. A list of common spare parts can be supplied on request. Spare parts list with detailed 3D drawings. Page 9 9