TECHNICAL BULLETIN PINPOINT CONDUIT COUPLING AND SPLICING RECOMMENDATIONS

Similar documents
MV-105 MEDIUM VOLTAGE CABLE. 5kV, 8kV, 15kV, 25kV & 35kV

Work Standard CABLE PULLING OPERATIONS

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

Baseline Two-Wire Technology

Recommendations for Marking Power Facilities

Electrical Tapes Selection Guide. 3Innovation

AMTEC SUPPORT GRIPS STANDARD, HEAVY DUTY & CONDUIT GRIPS

INSTALLATION INFORMATION

EASIDEW TRANSMITTER with Current Source Output

TDUX Inflatable Duct Sealing System 1.0 General Product Information

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

Recommendations for Marking Communication Facilities

VERSION 1.2 R-TRACK USER GUIDE. ZiPPERTUBiNG CO. THE. (480)

ESA Elbow Sealing Adapter Kit

CABLE PULLING GUIDELINES

RTD Temperature sensor TH11

Block & Tackle. Block & Tackle. Klein s line of block and tackle is engineered for high-strength requirements.

Gel Drop Seal for FOSC 450 Fiber Optic Splice Enclosure Installation Instructions

Installation Guideline for Placing Fiber Optic Cable into an Underground Duct

Typical Strength of Glued Connection. Typical Strength of Screwed Connection

PURA. Pure Gas Dewpoint Transmitter. Users Guide

Recommendations for Marking Gas Facilities Using 3M EMS Electronic Markers

The Outer Seal is highly abrasion resistant and provides mechanical stiffness to the splice in order to better match the cable stiffness.

Fiber Optic Lighted Bubbler Spillway Pot (DLP-45) Installation Manual

Teledyne Oil & Gas North Williamson Blvd. Daytona Beach, FL USA (phone) (fax)

STATIONARY TRUCK INTERNAL HALYARD V-CLEAT FLAGPOLES FOR QUICK AND PROFESSIONAL INSTALLATION READ ALL INSTRUCTIONS BEFORE PROCEEDING

tubepress press procedure

OPERATING and MAINTENANCE INSTRUCTIONS MAXIS Grips

Primary Terminals & Connectors

NEXT GENERATION FLEX FENCE

Amphenol. PowerLink Solar Cables. Amphenol 97 Series Connectors are UL recognized and CSA recognized.

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

Installation and Operating Instructions for Automotive Winch Synthetic Rope

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

will not support combustion

Introduction GUIDELINES FOR INSTALLATION PREINSULATED TUBE UNITHERM... Principal of Operation

City of Crystal Lake Community Development Department

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

Type 715P/717P, Orange Drop, High Voltage, Polypropylene Film/Foil

Intro: by firechim on October 3, 2013

Figure 1: Hydrostatic Pressure Forces Are Perpendicular to the Surface

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

Protected Microducts, Overview and Current Trends

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Instruction Manual. PE-25/32/37 Tapping Machines. POLYTAPP Valves

LUDLUM MODEL 239-1F FLOOR MONITOR. Revised December 2010

S Loadbreak Apparatus Connectors WARNING: WARNING:

I. Purpose... 1 II. Introduction... 2 III. General and Safety Precautions... 2 IV. Reference Documents... 3 V. Installation Overview...

CY LSOH Screened Halogen Free Control Cables with improved fire performance

PERMANENT POOLS. Location

Instruction Manual. PE Pipe Squeeze-off Tool Model TR650

C-Line Electrical Connectors

Installation Operation Maintenance

pvc well casing & drop pipe

Nottingham Township 909 Sugar Run Road Eighty Four PA (724) Fax (724)

STRAIGHT CONNECTOR 5 80 N N N N N N N. Copyright 2016 by K-net All Rights Reserved

XIAMETER RSN-0997 Resin

FOSC-400B4-MC-X06-X-NV

Underground Cable Installation Practices

FEATURES: DESCRIPTION MIN. TENSILE STRENGTH APPROX. WIDTH WP12 1,250 lbs/568 kgs 1/2 (13mm)

SUMITOMO RECOMMENDED PROCEDURE SRP SP-F f Slotted Core Ribbon Cable Preparation (FRP)

WARNING! DO NOT THROW AWAY THESE INSTRUCTIONS! READ AND UNDERSTAND BEFORE USING EQUIPMENT!

Made in the USA. For Fall Protection Only. SafeLok Part Description

1074 Kenran Industrial Dr. St. Louis, MO Phone: Taylortec WV-9A Work Vest

3M Electrial Markets Division EMS. Electronic Marker System

LED 14W POLO BULKHEAD WITH MICROWAVE SENSOR

MULETAPE, ROPE, GRIPS, AND LINES

Vented VW Settlement Cell

SPOOLER INSTRUCTIONS. STEP 12 If you are going to paint your posts, that should be done at this time.

Fall Protection Checklist. Guardrail System

FOR MORE INFORMATION CONTACT OUR NEAREST BRANCH OFFICE

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

Type MMV Medium Power Cable

User Instruction Manual For Davit Rescue System

Installation and Operation Instruction Manual

Comtran Cable. Commercial Premise & Specialty Datacom Products. Cat 5e - Cat 6A. LSZH & Industrial Ethernet. Indoor/Outdoor & Outside Plant

Socket P2RF-05-S P2RF-08-S Clip & Release Lever Nameplate R99-11

8. Fall Protection Procedures WAC

Bore-Gard Installation - 1,000 ft. Perry, Oklahoma

Page 1 of 1 04/19/13 SBR

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

City of DuBois PERMIT APPLICATION P. O. Box 408, 16 West Scribner Ave - DuBois, PA Phone: Fax:

Installation, Operation & Maintenance Manual

3 Scotch-Weld Polyurethane Reactive Adhesive Applicator Replacement Part Installation Guide

GAS DISTRIBUTION PRODUCTS TRANSITION FITTINGS

Cat Fence Installation Instructions for Regular and Snow Protection Kits with Extra Posts. List of items shown

Bulletin Swimming pool, hot tub and spa installations Rules , , , , , and

Utility Anchor System

Proper Operation of Heath Consultants Incorporated Plunger Bar

Airwalker. Installation and Safety Information. Stretch Products for Dance, Therapy, Education, and Fitness

Lectric Cycles Mid-Drive Electric Motor Installation

PART I. GENERAL REQUIREMENTS FOR PERMANENTLY INSTALLED POOLS, STORABLE POOLS, OUTDOOR SPAS, OUTDOOR HOT TUBS, OR FOUNTAINS

APPLICATIONS ROV & AUV SEISMIC PRODUCTION SYSTEMS DOWNHOLE JUMPER & CABLE SYSTEMS DRILLING CONTROL

installation best practices pocket guide

eabf Fiber Optic Cable and MicroDuct Installation Manual AFLglobal.com or (800) Duraline.com or (800)

INSTRUCTIONS FOR USE

A hose layline contains important information for specifying the replacement assembly: manufacturer, hose trade name, working pressure and hose ID.

Splicing Instructions. Standard Double Braid Eye Splice Type 1 Double Braid Ropes

Transcription:

TECHNICAL BULLETIN PINPOINT CONDUIT COUPLING AND SPLICING RECOMMENDATIONS CONTENTS: 1.0 General Information 2.0 Preparation and Splicing of PinPoint Wire 3.0 PinPoint Direct Bury Splice Kit Specifications 4.0 Contact Information While this information is presented in good faith and believed to be accurate, A-D Technologies does not, however, guarantee satisfactory results from reliance on such information due to the many variables attendant with every situation. Persons or parties utilizing this publication are solely responsible for the proper selection, installation, operation, maintenance and utilization of all products. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding the performance, merchantability, fitness, or any other matter with respect to the products, nor as a recommendation to use any product in conflict with the intellectual property rights of any third party. A-D Technologies reserves the right, without notice, to alter or improve the design or specifications of the products described herein. [All sales are pursuant to A-D Technologies terms and conditions of sale] Reproduction of this document, in part or in whole, is permitted solely for the purpose of distribution to other persons within your organization or contractors doing work for your company. All other distribution will require written consent from A-D Technologies. Page 1 of 10

1.0 GENERAL INFORMATION 1.1 PinPoint conduit is an ideal product for direct bury, Horizontal Directional Drilling (HDD), and plow applications where there is a need to have the ability to locate either a duct or a cable by electronic means. Utility protection is important to every provider due to the high cost of service outages, restoral, and customer inconvenience. PinPoint conduit provides a permanent, economical way to supply locate capabilities for buried facilities when placed into duct. This includes the use of dielectric fiber optic cable, which does not have any metal in the construction. A metallic conductor is necessary to provide a path for the electronic signal to pass. It is easy to locate PinPoint duct. A signal is applied to one end of the locate wire with a transmitter, and a portable receiver picks up the signal to help identify the route of the PinPoint. Note that soil conditions, depth of cover, and equipment type may affect the accuracy of the locate procedure. Typical transmitter and receiver combinations are shown (Figure 1). These include but are not limited to 3M, Metrotech, and Radio Detection. Figure 1 1.2 The PinPoint wire is applied to the outside of the conduit during the manufacturing process. Narrow webbing connects the wire to the duct for ease of access for splicing. Placing the wire on the outside does not compromise the wall thickness or strength of the duct. PinPoint duct is available in 0.50 through 2- inch diameters. The copper clad wire is embedded in a layer of HDPE for corrosion and electrical protection. Specifications for PinPoint conduit are shown (Table A). Page 2 of 10

CU- Clad Wire Size AWG Min. Inside Diameter Normal Duct Size 0.50" SDR- 11 18 0.644" 1" SDR-11 18 1.042" 1.25" SDR- 11 18 1.313" 1.50" SDR- 11 18 1.506" 2" SDR-11 18 1.885" Avg. Outside Diameter 0.840 + Minimum Wall Table A Maximum Wall Bend Radius Safe Working Pull Strength Avg. Weight Lbs./ft. 0.004 0.076" 0.096" 9" 497 lbs. 0.077 1.315 + 1,220 0.005 0.114" 0.134" 14" lbs. 0.189 1.660 + 1,962 0.006 0.151" 0.171" 17" lbs. 0.312 1.900 + 2,569 0.006 0.173" 0.194" 19" lbs. 0.407 2.375 + 0.006 0.216" 0.242" 24" 4,008 lbs. 0.635 The PinPoint wire may acquire induced foreign voltage during certain field conditions. Adjacent or parallel power lines may cause a voltage level that can be hazardous. Always test for foreign power prior to stripping or working with the PinPoint wire, using acceptable test equipment. 1.3 A cross-section of PinPoint duct is shown (Figure 2). Figure 2 No special tools are required for installing PinPoint conduit. PinPoint duct is available with an optional Silicore super-slick permanent lining to reduce friction and maximize cable installation distances (Figure 3). Page 3 of 10

Figure 3 1.4 To install PinPoint conduit, employ standard HDPE duct installation procedures. When it is necessary to splice the PinPoint wire to maintain electrical continuity, it is recommended to use a utility knife with a hook blade to separate the wire from the duct. A general-purpose wire stripper is sufficient for removing the PinPoint wire jacket for splicing. The wire is spliced using the PinPoint Direct Bury Splice Kit; A-D Technologies part number 1-907132. The kit contains two gel filled water resistant splice closures and two twist-on wire connectors (Figure 4). Figure 4 Page 4 of 10

The PinPoint wire splice connector has the following capacities (Table B). 2-5 #16 Solid or Stranded Wires 2-6 #18 Solid or Stranded Wires 3 each #12 Solid or Stranded Wires 4 each #14 Solid or Stranded Wires 2 ea. #14 and 1ea. #12 Solid or Stranded Wires 2 ea. #16 and 2 ea. #14 Solid or Stranded Wires Table B 2.0 PREPARATION AND SPLICING OF PINPOINT WIRE 2.1 In order to splice the PinPoint locate wire, begin by cutting the duct perpendicular with duct cutters, so there is a clean face for coupling the duct. The ends of each duct should overlap slightly to allow coupling of the ducts. Measure and mark the ducts to be coupled at 10 and 17 inches from the end (Figure 4). Separate the PinPoint wire from the duct using a utility knife with a hook blade, or other approved knife. Cut through the web to the 17-inch mark. Make the cut as close to the duct wall as possible, to not leave a ridge on the duct when coupling the duct. 2.2 Cut each duct again at the 10-inch mark, and join the ducts with an approved coupler according to the manufacturer s directions (Figures 5-7). Figure 5 Figure 6 Figure 7 Page 5 of 10

If a ridge remains after separating the PinPoint wire from the duct, shave any remaining HDPE with the knife until smooth. Shave the duct for a length of 10 inches, which should be enough for the coupler length requirements. Should the coupler be longer than this, continue shaving the ridge until it matches half the length of the coupler. 2.3 Strip back 5/8 of the HDPE jacket from around the PinPoint wire (Figures 7-8). Using the wire splice connector from the kit, place the connector fully onto both wire ends, and twist (clockwise) until it becomes tight (Figures 10-11). Pull each wire separately to ensure the connector threads have captured the wire. Figure 8 Figure 9 Figure 10 Figure 11 2.4 Insert the PinPoint wires with the connector into the gel-filled closure. Push the connector fully to the bottom of the closure so that it is surrounded by the silicone sealant (Figures 12-13). Place the PinPoint wires into the grooves at the entrance of the splice, fold and lock the cap into place (Figures 14-15). Page 6 of 10

Figure 12 Figure 13 Figure 14 Figure 15 2.5 Fold the Excess slack of the PinPoint wire back onto the duct, and tape or tie wrap to the duct (Figures 16-17). Figure 16 Page 7 of 10

Figure 17 3.0 PINPOINT DIRECT BURY SPLICE KIT SPECIFICATIONS 3.1 Application The PinPoint direct bury splice kit includes two electrical spring connectors to connect two or three pre-stripped copper clad steel wire ends, with two silicon sealed snap closures for water resistance. 3.2 Regulatory Agencies UL Listed as a Wire Connector System for use with Underground Conductors. Tested per UL Standard 486D for use in damp or wet conditions. Not to be used in continuous submersion applications. 3.3 Engineering Specification The direct bury splice kit effectively seals out moisture when using two or more conductors. The electrical connector shall be a equipped with a steel spring shell, covered with a PVC insulator. The sealant tube is made of polypropylene and filled with silicone electrical insulating gel. Installation of the kit according to recommendations will help ensure a water-resistant connection for use in locating the PinPoint conduit. Page 8 of 10

3.4 Construction Connector: Steel spring shell, flame retardant PVC insulator Tube: Sunlight and Impact Resistant Blended Polypropylene Gel: Silicone electrical insulating gel 3.5 The PinPoint splice connector specifications are shown (Figure 9 and Table B). Figure 9 APPLICATION TEMPERATURE 32 0 F 120 0 F (0 0 C 49 0 C) OPERATING TEMPERATURE -29 0 F 250 0 F (-34 0 C 121 0 C) VOLTAGE RATING 600 V DO NOT STORE OVER 120 0 F (49 0 C) NOT FOR USE IN DIRECT ULTRAVIOLET (SUNLIGHT) EXPOSURE TABLE B 4.0 CONTACT INFORMATION 4.1 Customer Service 1-800-847-7661 or 1-865-218-3460 Fax 1-865-218-3461 3.6 Web: www.adtechnologies.com 3.7 Email: moreinfo@adtechnologies.com 3.8 For further information on this product, contact Customer Service who can arrange for a Field Support Engineer to contact you directly. Page 9 of 10

3.9 A-D Technologies has a library of Technical Bulletins that are for use by our customers and their placing crews. Page 10 of 10