PROCEDURE FOR INITIAL AND PERIODIC INSPECTION POTENTIALLY EXPLOSIVE ATMOSPHERES (HAZARDOUS AREA) ORIGINAL EDITION

Similar documents
MIE TALK May INTRODUCTION. South African Flameproof Association Page 1 of 19

Operating Instructions

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations.

Operating Instructions

Further technical information is available on

CABLE ENTRIES IN HAZARDOUS AREAS CORRECT SELECTION, INSTALLATION AND MAINTENANCE

Operating Instructions

Ground Fault Circuit Interrupter(GFCI) Policy

Arran LED Floodlight Luminaire

Pioneers. Ex-ENGINEERING. Quality

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS

The definition of a competent person given in the Electricity at Work Regulations 1989 (EWR) is as follows:

Health & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures

ENGINEERING STANDARD FOR HAZARDOUS AREA SECOND EDITION JANUARY 2016

Inspection of in-service Explosion Protected Equipment - Unsafe Conditions and Cures. Johannes Auret, Explolabs and CERTEX SAFA SYMPOSIUM 2011 CTICC

Electrical Safety Work Practices

Manual Actuated Boiler Blowdown Valves

Original Date of Issue: 04/09

Low Voltage Electricity System Safety Rules & Associated Safety Guidance

2. The purpose of this program is to achieve the following objectives:

PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS

IECEx Certificate of Conformity Annexe

Inspection Recommendations

Magnetic level switch type MR783 Instruction Manual

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

Operating Instructions for Intrinsically Safe Pressure Transmitters Series DMG/******** for Hazardous Application in Coal Mining Industry

ES18 Security Theory/Regulations Answer Schedule

Intrinsic safety 101 hazardous locations

Norrsken Family Booklet

PV4 and PV6 Piston Valves

INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC) SCHEME FOR CERTIFICATION TO STANDARDS RELATING TO EQUIPMENT FOR EXPLOSIVE ATMOSPHERES (IECEx SCHEME)

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

Lockout / Tagout Safety Program

NZQA registered unit standard version 3 Page 1 of 7. Plan electrical installations for explosive atmospheres

IEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031)

Status Date Prepared Reviewed Endorsed Approved

MODELS (2 foot Version) (4 foot Version)

Portable Appliance Testing

Contractors' Code of Safe Practice

CERTIFICATION IMPACT ANALYSIS: IEC 60065, SEVENTH EDITION vs. GB Audio, video and similar electronic apparatus Safety requirements

To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TABLE OF CONTENT

Status Date Prepared Reviewed Endorsed Approved

Project: Consultant : MEP Contractor: PREPARED BY: DORMAN SMITH SWITCHGEAR - DUBAI REVIEWED BY CONSULTANT : Page 1 of 15

Status Date Prepared Reviewed Endorsed Approved

INSTALLATION GUIDE Gas Rangetops

LTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.

11/2/2017. Course Objectives. Overview

PLANT/EQUIPMENT/ASSET HAZARD REPORT

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING

Welding With Arc Welding Equipment

Pressure Switches Application Guideline

QPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems

The evolution of the Ex-proof flame path

IECEx Certificate of Conformity

VS18/26 with PROFINET and EtherNet/IP Interface. ATEX Installation Instructions

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

Portable Electric Tools

Bulletin Swimming pool, hot tub and spa installations Rules , , , , , and

General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association

IECEx OPERATIONAL DOCUMENT

NZQA registered unit standard version 3 Page 1 of 6

Overview. SEMEMI211 SQA Unit Code HF4E 04 Carrying out modifications or rewiring electrical circuits

Responsibilities: Effective Date: November Revision Date: May 1, VP, Facilities and Construction Management. Issuing Authority:

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

RTD Temperature sensor TH11

Confined Spaces. 1. Definition Permit/Non-Permit

Supplementary Operator s Manual 42/24-14 EN Rev. 3

Health & Safety: Electrical safety

INSTRUCTION MANUAL Pressure Relief Device LPT

DuPage County Environmental, Safety, Health & Property Loss Control Program Hazardous Energy Control (Lockout/Tagout)

SEMME2135 Assisting in modifying and adding electrical circuits in yachts and boats

TP1 and TP2 Temporary Cone Shaped Strainers

Rigel 601 CHECKBOX. Instruction Manual. 348A551 Issue 2.0. April Seaward Electronic Ltd. Issue 2.0

BUTTERFLY VALVES Series 800

WHEATLEY Series 500 Swing Check Valve

Electro-Pneumatic Converter YT-940 SERIES

: Electric Power Generation, Transmission, and Distribution. Region IV - OSHA

Lockout/Tagout Safety Policy

MAINTENANCE & ASSEMBLY INSTRUCTIONS FUSIBLE LINK. Inline Thermal Check Valve

Manual Power relay SR853

OSAT Series. Intrinsically Safe Infrared Temperature Sensor Operator's Guide

Sanitary RTD Temperature sensor TH17. Measuring System Sanitary RTD assembly with connection head TH17 for food and dairy applications.

USER MANUAL. JET TST and JET TST S.

Ventam 85 Installation & Commissioning Instructions

Pressure Measurement Single-range transmitters for general applications

CP10 Sensor Installation and Maintenance Instructions

C&G 2395 Exam Paper April Section A - All questions carry equal marks. Answer all three questions. Show all calculations.

CFSW. Hinges with built-in safety multiple switch

Safety Powder Spray Systems

Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace

Contractor handbook. Purpose

Florida Building Code 6 th Edition (2017) Residential. Broward County Edition Loose-leaf Supplement

Confined Space Policy

VG5 Supplementary instructions

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

The Proper Procedure

Transcription:

PROCEDURE FOR INITIL ND PERIODIC INSPECTION IN POTENTILLY EXPLOSIVE TMOSPHERES (HZRDOUS RE) ORIGINL EDITION DEC. 1997 This Standard is the property of Iranian Ministry of Petroleum. ll rights are reserved to the owner. Neither whole nor any part of this document may be disclosed to any third party, reproduced, stored in any retrieval system or transmitted in any form or by any means without the prior written consent of the Iranian Ministry of Petroleum.

CONTENTS : PGE No. 0. INTRODUCTION... 2 1. SCOPE... 3 2. REFERENCES...3 3. CHNGE IN RE CLSSIFICTION... 3 4. INITIL ND PERIODIC INSPECTION... 3 4.1 Isolation... 4 4.2 Insulation Testing in Hazardous reas... 4 4.3 Earth Continuity Testing... 4 4.4 lterations to pparatus Systems and Installations... 4 4.5 Electrical Protective Devices... 4 4.6 Flameproof Enclosures... 4 4.7 Portable and Transportable pparatus and Its Connections... 5 4.8 attery-operated Vehicles... 5 5. RECORDS KEEPING... 6 6. SCHEDULES FOR INSPECTIONS OF ELECTRICL PPRTUS WITH DIFFERENT TYPES OF PROTECTION... 6 7. REMRKS ON SPECIFIC ITEMS OF SCHEDULES... 9 1

0. INTRODUCTION With all the accuracy and precaution which may be exercised for preparation of hazardous area classification drawing, selection of electrical equipment and their installation in compliance with the internationally recognized standards, Codes and Recommendations etc. Safeguarding against explosion in Potentially explosive gas atmosphere can not be guaranteed unless the equipment and/or installations in condition to proper and safe operation are properly inspected, tested, maintained and repaired as required by trained and responsible personnel. It should be noted that correct functional operation does not itself necessarily indicate conformity with the recommendation for safe use of apparatus. It is a well planned, timely and organized periodic inspection, which reveals the defects or shortcoming that may otherwise lead to disasters and fatalities. To avoid such mishaps and failures, there is a need for periodic inspection and necessary spare and rectification of faults. This Procedure deals with the initial and periodic inspections of electrical apparatus in potentially explosive atmosphere. The inspection, maintenance, replacement and repair of apparatus, systems and installation shall be carried out only by personnel whose training include instruction on the general principles of area classification and on various methods of safeguarding. They should know the instructions of manufacturers and Certifying odies. Regularly retraining to be arranged for them to refresh their knowledge in hazardous atmospheres. 2

1. SCOPE This Standard covers the requirements for initial and periodic inspection of electrical apparatus installed in potentially explosive gas atmospheres. It describes in details the items to be inspected in equipment with type of protections: Ex "d", Ex "i", Ex "p", Ex "n", and Ex "e". The schedules of inspection shall be supplemented with any specific instruction, dictated by Certifying uthority in addition to those recommended in this Standard. 2. REFERENCES Throughout this Standard the following dated and undated standards/codes are referred to. These referenced documents shall, to the extent specified herein, form a part of this standard. For dated references, the edition cited applies. The applicability of changes in dated references that occur after the cited date shall be mutually agreed upon by the Company and the Vendor. For undated references, the latest edition of the referenced documents (including any supplements and amendments) applies. IEC (INTERNTIONL ELECTROTECHNICL COMMISSION) IEC 34.5 Part 5 IEC 79 Parts 0, 1, 2, 3, 5, 7, 10, 11, 13, 14, and 15 IEC 144 IEC 529 "Classification of Degree of Protection Provided by Enclosure" "Electrical pparatus for Explosive Gas tmosphere" "Degrees of Protection of Enclosure, for Low Voltage Switchgear and Control-Gear" "Degrees of Protection Provided by Enclosure (IP Code)" SI (RITISH STNDRDS INSTITUTION) S5345Parts1to9 "Code of Practice for Selection, Installation and Maintenance for Electrical pparatus for Use in Potentially Explosive tmosphere (Other than Mining pplications or Explosive Processing and Manufacture)" S 5501 Parts1to8 "Electrical pparatus for Potentially Explosive tmospheres" IPS (IRNIN PETROLEUM STNDRDS) IPS-E-EL-110 Part 1 "Electrical rea Classification" Part 2 "Safeguarding" 3. CHNGE IN RE CLSSIFICTION To keep hazardous area classification up-to-date, it is necessary to make changes on drawings as soon as it occurs and withdraw the old area classification drawings from users and take them out from service. 4. INITIL ND PERIODIC INSPECTION 3

ll apparatus, systems and installations shall be inspected on initial installation and after replacement in accordance with the "Initial" column of the inspection schedules. Following any repair, adjustment or modification those parts of the installation which have been disturbed shall be checked in accordance with the relevant items in the Initial column of the inspection schedule: If at any time there is a change in the area classification, or in the characteristics of the flammable material used in the area, a check shall be made to ensure that all apparatus have the correct group and temperature class and continue to comply with the revised area classification drawing. 4.1 Isolation Unless it is part of an intrinsically-safe circuit apparatus containing live parts and located in a hazardous area it must not be opened (except as noted below) without isolating all the incoming connections including the neutral conductor isolation in this context means the withdrawal of fuses and links or the locking-off of an isolator or switch. However, if the continuing absence of flammable atmosphere can be guaranteed by the authority responsible for that area, and a certificate issued to this effect, essential work necessitating the exposure of live parts may be carried out by an authorized employee. 4.2 Insulation Testing in Hazardous reas y obtaining "Hot Work Permit", measurement of insulation resistance is allowed. 4.3 Earth Continuity Testing It must be ensured that earthing is proper and earthing connections are clean and tight. 4.4 lterations to pparatus Systems and Installations No modification, addition or deletion shall be made to any certified or "approved" apparatus, system or installation without the permission writing of the certifying or approving authority (such permission shall be obtained through the Manufacturer of the apparatus) unless it can be verified that such change does not invalidate the certification or approval. No modification shall be made to the safety features of apparatus which relies on the techniques of segregation, pressurizing, or other methods of safeguarding without the permission of the engineer responsible. When apparatus in a hazardous area is permanently withdrawn from service the associated wiring shall be removed from the hazardous area or shall be correctly terminated in an enclosure appropriate to the area classification. Where apparatus in a hazardous area is temporarily removed form service the exposed conductors shall be correctly terminated as above, or adequately insulated, or solidly bonded together and earthed. The cable cores of intrinsicallysafe circuits shall be either insulated from each other or bonded together and insulated form earth. 4.5 Electrical Protective Devices During commissioning, and subsequently at intervals determined by the engineer responsible but not exceeding two years, all electrical protective devices shall be examined and, if considered necessary, tested to ensure that they operate at their minimum practicable setting. 4.6 Flameproof Enclosures When re-assembling flameproof enclosures all joints shall be thoroughly cleaned and lightly greased to prevent corrosion and to assist weatherproofing. lind bolt-holes should be kept reasonably clean of grease to avoid damage due to hydraulic lock. 4

Only non-metallic scrapers and non-corrosive cleaning fluids should be used to clean flanges. When inspecting apparatus with flameproof enclosure, care should be exercised to ensure that: a) The safe gap complies with the requirements of IEC Publications 79.1 and 79.1 or pertinent protection certificate. b) External solid obstacles which are not part of apparatus such as steel-work, walls, weather guards, mountingbrackets pipes or other electrical equipment approaching the flameproof apparatus have a minimum distance described below from the outer edges of the enclosure flange on opening: pparatus Group II propane 10 mm " " II ethylene 30 mm " " II C hydrogen 40 mm 4.7 Portable and Transportable pparatus and Its Connections The apparatus group and "T" class should be appropriate to all of the gases and vapors in which the apparatus may be used. Ordinary industrial portable or transportable apparatus should not be used in a hazardous area unless its use is undertaken under a controlled procedure and the specific location has been assessed to ensure that potentially flammable gas or vapor is absent during the period of use. Should plugs and sockets be in a hazardous area, they should be suitable for use in the particular zone of risk and should have mechanical and/or electrical interlocking to prevent danger during insertion or removal of the plug. In many cases the type of cable to be used will be stated on the apparatus certificate. In cases where this is not so, the cable should be suitable for rough usage and other adverse environmental conditions, e.g. elevated temperatures, presence of solvents. It should also be suitable for the circuit protective arrangement, e.g. where earth monitoring is used, the necessary number of conductors should be included. Where the apparatus needs to be earthed the cable may include an earthed flexible metallic screen in addition to the earth conductor. 4.8 attery-operated Vehicles The frequency of inspection and maintenance of battery operated vehicles which are specially designed for hazardous areas, assumes additional importance for mobile equipment which, from the arduous nature of the work it is called upon to perform, is subject to vibration road shock and minor accidental collisions. The frequency of inspection and maintenance shall be determined by the conditions of service but in any case a weekly examination of the battery and its housing shall be made to ensure that: a) There has been no spillage of electrolyte. b) The battery terminals are clean, dry, tight and protected (e.g. with petroleum jelly). c) The straps between battery cells are undamaged. d) The battery mountings and cover are secure. check shall also be made to ensure that no abnormal fractional rubbing of mechanical moving parts of the truck has developed. t less-frequent intervals all electrical apparatus on the vehicle shall be inspected to ensure that it has remained securely mounted and that it otherwise complies with the appropriate checks in the inspection schedules (see Clause 6). Particular attention shall be paid to interconnecting wiring and to the tightness of glands and terminations. Except for the purposes of charging (which shall be carried out only in a non-hazardous area) the battery cover shall be kept locked in position, and the charging plug(s) and socket(s) securely mated, at all times. 5

Fault-finding and rectification shall always be carried out in a non-hazardous area. 5. RECORDS KEEPING system shall be established to record: a) ll apparatus, systems and installations. b) The result of inspection and tests. c) The actions taken to correct defects found during inspection. 6. SCHEDULES FOR INSPECTIONS OF ELECTRICL PPRTUS WITH DIFFERENT TYPES OF PROTECTION 6.1 The inspection schedules referred to in Clause 4 follows. 6.2 Figure(s) in column of "Remarks" indicate the sub-clause number to which reference is made in Clause 7. Note: The above mentioned schedules are not only useful for hazardous areas but they can also be applied for initial and periodic inspection of electrical apparatus in safe areas. 6

INSPECTION SCHEDULES FOR ELECTRICL PPRTUS, RECOMMENDTION FOR DIFFERENT TYPES OF PROTECTIONS IN HZRDOUS EXPLOSIVE TMOSPHERE CHECK THT: pparatus is appropriate to classification. INSPECTION* CTEGORY Initial Periodic Ex "d" TYPE OF PROTECTION Ex Ex Ex "i" "p" "n" Ex "e" REMRKS SEE CLUSE 7 Surface temperature class is correct. Surface temperature is below ignition temperature. pparatus sub-group (if any) is correct. System group or class if (any) is correct. pparatus carries the correct circuit identification. 7.1 Obstructions referred to Clause 4.6 do not conflict with requirements. Enclosures, glasses and glass metal seals are satisfactory and undamaged Gaps are free from corrosion. Dimension of gaps are correct. There is no unauthorized modification. olts, glands and stoppers are complete and tight. There is no undue accumulation of dust or dirt. ll conduit runs and fittings are tight and free from corrosion. Enclosed break and hermetically sealed devices are undamaged. 7.2 Earthing is satisfactory, permanent, and not via plug and socket. Condition of enclosure gasket is satisfactory. Electrical connections are tight. Motors air gaps and other running clearances are satisfactory. Motors fan and coupling are not rubbing on cowls/guards. ll lamps fitted to intrinsically safe apparatus are of the type and rating specified in the certificate 7.4 7.3.* For implementation of Category, and Category see notes in Page 9. (to be continued) 7

(continued) CHECK THT: The intrinsically safe circuit is isolated from earth or earthed at one point only. INSPECTION* CTEGORY TYPE OF PROTECTION Initial Periodic Exd Exi Exp Exn Exe REMRKS SEE CLUSE 7 Earthing connections are permanent and not made via plug and socket. Cable screens are correctly earthed. Size, type and segregation of cables are satisfactory and there is no obvious damage. dequate segregation exists between terminals. Segregation is maintained on relays and similar devices having moving parts. 7.4 There is no obvious damage to apparatus. arrier units are of correct type installed in accordance with the certification requirements and are adequately earthed. Electrical connections are tight and electrical clearance and creepage distances are adequate. Rating of replaceable fuses complies with certification requirements. - Source of pressure is free from contamination. Pressure flow is correct. Pressure flow indicators, alarms and interlocks function are adequate. - Ducting, piping and enclosures are in good condition. Electrical protection of motors to be according to drawing. There shall be no noticeable damage to cables and glands. 7.4 Guards where used are present and correctly located. pparatus is adequately protected against corrosion, the weather vibration and other adverse factors. Ditto Notes: Category "" Inspection should be carried out in all cases and where periodic, they should be at intervals not exceeding two years. More frequent and more detail inspection will be necessary where there is corrosive or other adverse atmosphere, a high risk of mechanical damage or vibration or where there are onerous circumstances, the need for more frequent inspection may also be determined by operating experience. 8

Category "" The need for the method and the frequency of Category "" inspection is at the descretion of the Engineer responsible. It is not intended that periodic inspection should incur undue disturbance of apparatus unless considered necessary by the Engineer responsible. 7. REMRKS ON SPECIFIC ITEMS OF SCHEDULES 7.1 pparatus should be positively identified with its circuit to ensure that correct isolation can be carried out. 7.2 ccumulation of dust or dirt can interfere with heat dissipation and result in surface temperature higher than those permitted in the hazardous areas relevant to type of protection. 7.3 n initial inspection is necessary after relamping relevant to enclosure type of protection. 7.4 n increased frequency of inspection may be necessary. 9