" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd>

Similar documents
You Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services

Sharing practice: OEM prescribed maintenance. Peter Kohler / Andy Webb

Failure Contributors of MV Electrical Equipment and Condition Assessment Program Development

Low Voltage Electricity System Safety Rules & Associated Safety Guidance

Testing Distribution Switchgear for Partial Discharge

Advanced Test Equipment Rentals ATEC (2832) OMS 600

EDUCATION DEPARTMENT ACCU-TEST

Development of a Plant Health Index for Eskom Distribution Substations

MISSOURI UNIVERSITY OF SCIENCE & TECHNOLOGY Procedure: 3.6

2017 NWHA TECHNICAL SEMINAR. Arc Flash Hazard Awareness MIKE BRENDLE LLC

Infrared Thermography Inspection Guidelines. Date Issued:

Neil Kane Managing Director EMT UK

Innovative Techniques for Mitigating Arc Flash Exposure

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO

Categorizing Faults via DGA. GE Grid Solutions M&D

EFFECTIVE CONDITION ASSESSMENT OF MV SWITCHGEAR

Online DGA-monitoring of power transformers

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures

SECTION 51 NFPA 70E POLICY. Health & Safety Policy and Procedures Manual

Arc Flash. Safety 21

Power Unit 075. Maintain Substation Circuit Breakers

SUBSTATION EXPLOSION BARRY GASS HIGH VOLTAGE TRAINING. Barry Gass Training Manager High Voltage Training South Africa

It is essential that the maintenance staff is qualified for electrical works and follows safety procedures.

Electrical Safety. Hazard Awareness

SF 6 Product Guide. Gas Analysis Instruments and Accessories

Original Date of Issue: 04/09

Field Instruction. The purpose of this instruction is to inform all Horizon Power workers of the safety requirements when working from a EWP.

sdfghjklzxcvbnmqwertyuiopasdfghjklzxcvbnmqw ertyuiopasdfghjklzxcvbnmqwertyuiopasdfghjklzx

EVT * -Pro Electronic Valve Tester

Reliability of Safety-Critical Systems Chapter 4. Testing and Maintenance

These Electricity Safety Rules and associated National Safety Instructions are written to safeguard personnel working for or on behalf of National

Electrical Safety. Introduction

Why do I need to do an Arc-Flash Analysis?

ON-LINE MONITORING OF REGULATOR TRANSFORMER AT THE MARGEM DIREITA SS IN ITAIPU. M. E. G. ALVES* Treetech Sistemas Digitais Ltda.

Optimized Maintenance Planning for Transmission Power Systems.

Advanced Pump Control for Irrigation Applications

CON ACT. Parts and Service News For the Power Transformer and

Isolation of power supplies

Monitoring transformers with infrared cameras

Power Supply Facilities Failure (Units 3-4 Temporary M/C (A), etc.) March 22, 2013 Tokyo Electric Power Company

TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing

SAFE-WORK PRACTICES Working On Or Near Energized Electrical Equipment CAT A-1 SOP #4

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers

Risk Assessment Procedure

Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace

Preparer: Owner: Approver: EHS Team Member TES Manager Site Manager

Nordel GRID DISTURBANCE AND FAULT STATISTICS

PURE H2O FORUM. Safeguarding Operations Personnel Understanding Arc Flash & Developing an Electrical Safety Program

MIL-STD-883G METHOD

FINAL FACILITY STUDY. KV1C Transformer Addition at Badwater Substation 2009-T1. November 17, 2009

GAS PIPELINE SAFETY GUIDE.

STCP 01-1 Issue 005 Operational Switching

COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE

Recent Advances in Transmission Insulators Prof.B. Subba Reddy Department of Electrical Engineering Indian Institute of Science Bangalore

Aquavar SOLO 2 Frequently Asked Questions

MARKET OUTLOOK. Power Chemicals Petroleum Water/Wastewater Oil & Gas Pulp & Paper and more

Acoustic Pulse Reflectometry Brings an End to Tube Inspection Sampling By Dr. Noam Amir, Chief Technology Officer, AcousticEye

POWER PLANT RELAY REPLACEMENT DELIVERABLE ARC FLASH

Electrical Safety in the Food Industry

Periodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels

ESSENTIAL FUNCTIONS ANALYSIS of Decontamination/Radwaste Technician

CTRL UL101 MORE THAN JUST A LEAK DETECTOR

About ABB Micafil Facts

Advances in Low Voltage Motor Control Center (MCC) Technology Help Reduce Arc-Flash Hazards and Minimize Risks

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

23.1 Functions, Basic Configuration, and Interfaces

Power System Safety Rules. Revision

Electrical Safety For Managers Updated For E. ElectricalTrainingPro.com

Improve Reliability of Turbomachinery Lubrication and Sealing Systems

This presentation provides an overview of modern methods for minimizing the arc-flash hazard.

LECTURE 3 MAINTENANCE DECISION MAKING STRATEGIES (RELIABILITY CENTERED MAINTENANCE)

Identification and Screening of Scenarios for LOPA. Ken First Dow Chemical Company Midland, MI

Hazardous Energy Control (Lockout-Tagout)

Standard. Extra High Voltage (EHV) Indoor Gas Insulated Switchgear Standard R Version 1.0, June 2018

Every things under control High-Integrity Pressure Protection System (HIPPS)

SEMEM3-78 Testing and calibrating instrumentation and control equipment and circuits

Analysis of Pressure Rise During Internal Arc Faults in Switchgear

Arc Flash 101. presented by Arc Flash Blaster LLC

TECHNICAL DIAGNOSTICS FOR POWER APPARATUS. H. Sander, J. Schwab, M. Muhr

C I R E D 18 th International Conference on Electricity Distribution Turin, 6 th to 9 th June 2005

The Best Use of Lockout/Tagout and Control Reliable Circuits

MECHANICAL EQUIPMENTS: COMPRESSORS, PUMPS, SEALS, SPEED DRIVES, CONTROL VALVES & ACTUATORS & SAFETY RELIEF VALVES

Schedule of Quantity and Rate for Annual Maintenance Rate Contract for Electrical Jobs for the year (Section-F) Cleaning Jobs.

Electrical Safety in Hospitals

CASE STUDY. Compressed Air Control System. Industry. Application. Background. Challenge. Results. Automotive Assembly

List all key terms and acronyms used in the procedure, and their definitions.

70e Training - Electrical Safety in the Workplace

Rigel 601 CHECKBOX. Instruction Manual. 348A551 Issue 2.0. April Seaward Electronic Ltd. Issue 2.0

Distribution Transformer Instruction Manual

ICM Project Underground Infrastructure and Cable

Axpo Power Ltd. 2) GE Grid Solutions

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

This Procedure details the procedures to be followed in order to achieve Safety from the System when:

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

Keeping your critical equipment up and running. What the LifeSense system can do for you. LifeSense technology: monitors in real time

Why do I need dual channel safety? Pete Archer - Product Specialist June 2018

Appendix A: Energized Work Permit

MANAGING ARC FLASH: A Risk Management Approach. Steve Williams Engineers Australia - Electrical College 14 June 2017, Brisbane

Electrical & Arc Flash Safety Program 2007

Electrical. OSHA Office of Training and Education 1

Transcription:

" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd> High Voltage Forum Brisbane 2013

Duty of Care As part of an asset owner Duty of care to their workers & contractors Asset owners and or operations groups are required to ensure the place of work is safe. Instrument transformers & current transformers are critical components of the substations and are used to measure voltage and current for metering / indication & protection. As these assets age, the risk of failure increases lightening prone areas often weaken the internal insulation, external contamination (ozone, water) are the main factors causing degradation on the surface of this equipment. Partial discharge can develop either internally or superficially. Inservice / on line testing is used to detect partial discharge on line before they reach critical levels without taking the equipment out of service or manipulating its operating conditions.

When an unplanned outage occurs, production stops, and in most cases, will cause waste and damage to occur within the plant. By using On-Line Partial Discharge (PD) Testing it is possible to have a Real Time report on the condition of circuit breaker porcelain bushings while plant is still running and in service, with no production outages required. This is ideal for the any 24/7 operation such as mining, refineries and export operations / hydro electric power stations etc.

Failure 1 33kV Current Transformer Failure

The weakest links in a switchyard installation can often be Circuit breakers / voltage transformers / current transformers and surge arrestors in older pre 1970 switchyards. The failure mechanism in most cases is the ingress of moisture and free water contaminating the oil surrounding the paper taped stress control bushing

Failure 2 132kV CB Failure

132kV CB Failure

Extremely dangerous and potentially fatal The bushing will initially produce PD and as this level increases over time will develop into an internal arc. This is accompanied by a rapid rise in pressure followed by a burn through period, as indicated in the image above.

Pressure release mechanism In the absence of a suitable pressure release mechanism, arcing faults are extremely dangerous and potentially fatal as temperatures can reach 6000 C. The high arc temperature causes a rapid rise in pressure within the bushing causing the bushing to rupture. The diagram below shows a typical example of the release of arc flash energy where inadequate pressure release mechanisms are in place.

Internal Pressure Rise

Burn Through

Failure 3 132kV Voltage Transformer Failure

Failure 4 11kV Synchronising breaker Failure

Failure 5

Being recorded in real time Identifying the location of suspect bushings does require extensive experience to know where to place the various numbers of sensors, (it is not possible to use one sensor) and to analyse this data from the various sensors as it is being recorded in real time.

In Service Testing With the aid of the latest technology, it is now possible to detect potential failures in CB Bushings in-service / on-line, thereby preventing catastrophic arcing failure of the bushings. Apart from the unplanned loss of supply and fire caused when a failure occurs, it has the potential to inflict serious harm to site personnel if they are in the vicinity of a porcelain bushing explosion.

Unlike conventional PD monitors The HVS equipment acquires and stores the actual pulse shape of each signal measured. This enables both frequency and time-domain analysis. The data acquired allows for identification of internal discharges, surface discharges and corona discharges. The bushings per circuit breaker (Load side of CB and Line side of CB) were ranked into three risk different categories: Low / Medium / High. Specific recommendations and order of priority were then given to the client to enable correct order of replacement parts to minimize risk within the switchyard and for possible replacement programs that fitted into production shutdowns.

In-Service Detecting 132kV Voltage Transformer

Case study: Work performed An on-line PD survey of the client s 1970 switchyard was carried out by High Voltage Solution (HVS) using inhouse developed sensors, coupled with an instrument having three input channels that allow for sequential acquisition of PD signals.

Using RFI Equipment

Being able to record and analyse Finding sources of PD early reduces repair costs and helps keep HV apparatus operating efficiently and maximize unit lifespan. Being able to record and analyse the PD signals and make decisions for further actions is a big plus.

summary of test results From the on-line PD tests HVS was able to measure PD in progress on selected CB bushings. This gave the asset owner the luxury of having a controlled shutdown which controlled the risk to both personnel & adjacent assets within the switchyard.

Instrument's used to detect potential failures Acoustic detector Infra-red camera Corona Camera RFI Freq

Questions