Back to Basics: Pumping Systems RM ASHRAE TECH CONFERENCE

Similar documents
Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

Hydronic Systems Balance

Expansion Tank Design (Chilled Water)

FACHGESPRÄCH 3 NPSH NPSH3. Let us call it: CAVITATION A LOOK UNDER THE HOOD

TUTORIAL. NPSHA for those who hate that stuffy word. by Jacques Chaurette p. eng. copyright 2006

Centrifugal Pump Intro

The Advancement of Pressure Independent Technology

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

Figure 4 Figure 5 Figure 6

ELECTRONIC VALVE SIZING AND SELECTION

PROCESS ROTATING EQUIPMENT (CENTRIFUGAL PUMPS )

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

SAMSON SOLUTIONS Energy and Power (Critical Applications)

Fundamentals of Hydronic Design. Fundamentals of Hydronic Design. Fundamentals of Hydronic Design. Fundamentals of Hydronic Design

The Hoffman Specialty Series 2000 consists of main

Joint Expo 2012 February 7-8, 2012 BASIC HYDRAULICS

SELECTION & APPLICATION

Pump Selection and Sizing (ENGINEERING DESIGN GUIDELINE)

HVAC Hydronic Pumps: B&G Triple Duty Valve for Proportional Balance

PUMP CONSULTING & TRAINING LLC Joseph R. Askew 1811 Stonecrest Ct. Lakeland, Fl

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes.

Application Worksheet

BACK PRESSURE / SUSTAINING

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

Geothermal Alliance of Illinois Non-Pressurized Flow Centers

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

BACK PRESSURE / SUSTAINING

TECHNICAL DATA. Q = C v P S

SINGLE VALVE WITH LOW-FLOW BYPASS

TECHNICAL INSTRUCTIONS Iron Body Series 597 SI

Quiz #1 Thermodynamics Spring, 2018 Closed Book, Open Appendices, Closed Notes, CLOSED CALCULATORS

PREVIEW COPY. Table of Contents. Basic Pumping Concepts...3. Maintaining Packing and Seals Lesson Three Maintaining Centrifugal Pumps...

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller.

SUBMERSIBLE PUMP HEAD CALCULATION

Pump ED 101. Intro to Centrifugal Pumps. Joe Evans, Ph.D. Script for Power Point Presentation. Part 1 Elementary Mechanics & Hydraulics

TECHNICAL DATA. Q = C v P S

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps

TECHNICAL DATA. Q = C v P S

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

Process Dynamics, Operations, and Control Lecture Notes - 20

TECHNICAL DATA. Q = C v P S

SIZING THE EXTROL DIAPHRAGM-TYPE HYDRO-PNEUMATIC TANK

SINGER MODEL 106/206-RPS-L&H

IRC 2011 All Rights Reserved

TECHNICAL DATA. Q = C v P S

UNUSUAL ASPECTS OF PUMP SYSTEMS. Jacques Chaurette p. eng. ww.lightmypump.com July 2003

Applied Fluid Mechanics

VAREC 180 SERIES PRESSURE REGULATORS

THE INNER WORKINGS OF A SIPHON Jacques Chaurette p. eng. January 2003

Some system examples

Pumping Systems for Landscaping Pumps, Controls and Accessories. Mark Snyder, PE

TECHNICAL DATA. Q = C v P S

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

Valve Sizing Considerations. Steven Hocurscak Metso Automation

TECHNICAL DATA. Q= Cv S

SECTION TESTING ADJUSTING AND BALANCING FOR HVAC

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

ASHRAE made significant changes in 2001 to the calculations. Fundamentals of Safety Relief Systems

Reliability: Piping Distribution & Storage Matter. Instructor: Kurt Thielemann Principal

SIZING THE WELL-X-TROL

Dean Pump Self-Priming Chemical Process Pumps

Bulletin TCR-104 & 109 Filling and adding to the Glycol pressure system

SG TF. Q = 963 Cv (P1 - P2)(P1 + P2) TECHNICAL INFORMATION. Flow Q (GPM)

Anti-Cavitation Trim. Eliminates cavitation damage Reduces noise Preserves valve and surrounding pipe systems. singervalve.com

FLUID DYNAMICS Ch.E-204 Umair Aslam Lecturer Department of Chemical Engineering

SyncroFlo Municipal University and Hydraulic Institute, Pump Systems Optimization

Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide

S-CO 2 Brayton Recompression Loop Design and Control

Digester Processes. 1. Raw Sludge Pumping System

my SYSTEM A guide to common applications in water distribution systems

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

TESTING OF BELIMO PRESSURE INDEPENDENT CHARACTERIZED CONTROL VALVES

TECHNICAL DATA OBSOLETE

CASH VALVE TYPE KP BACK PRESSURE VALVES

Engineering Letter. Pump Protection

TECHNICAL DATA. Page 1 of 12

VB-7212 Series. Application. Features. Applicable Literature. 5/8" O.D., 45 SAE Flared Stem Up Open, Two-Way Valves General Instructions

Contents. Catalog HY /US Load and Motor Control Valves SERIES CAVITY DESCRIPTION FLOW PRESSURE PAGE NO. LPM/GPM BAR/PSI

Simple Set. Pressure Independent Control Valves 2 Way 1/2-2

VBS-9263 Series. Application. Features. Applicable Literature

Accessories. Valves. Adjustable Pressure Relief Valves

TECHNICAL DATA Q= C. Table 1 - Specifications

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out

ATL R/V Atlantis AUXILIARY PLANT OPERATION APPENDIX OPERATING PROCEDURES

Consider the design of a central chilled water cooling system for a clubhouse and

Bermad Pressure Reducing. Model: 42T

Pump-Fan-Compressor Sizing

TECHNICAL DATA. Table 1 - Specifications

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

بسم هللا الرحمن الرحيم. University of Khartoum Faculty of Engineering Mechanical Engineering Department

LP Separator Level Control by Variable Speed and Multi Stage Brine Reinjection Pumps at Kawerau and Nga Awa Purua Geothermal Projects, New Zealand

Copyright, 2005 GPM Hydraulic Consulting, Inc.

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

PEERLESS PUMP COMPANY SYSTEM ANALYSIS FOR PUMPING EQUIPMENT SELECTION

INTEROFFICE MEMORANDUM MODIFICATIONS TO DEW POINT CONTROL PROCESS

PRESSURE DROP CHARTS

Transcription:

Back to Basics: Pumping Systems RM ASHRAE TECH CONFERENCE 4/29/2016 1

AGENDA Closed loop heating and cooling piping systems Expansion Tanks Pumps 2

BASIC PUMPING LOOP Nice and simple too simple? Constant energy draw of pump? Compatibility of source and load flow and temperatures Too low/high boiler/chiller return temp Too high radiant floor temp Too low chilled beam temp Too little chiller/boiler flow 3

DIRECT RETURN Simple, minimal pipe Extreme head differences will create balancing and control difficulties 4

REVERSE RETURN Eliminates extreme head differences Extra pipe loop layouts are less extra than linear 5

REVERSE RETURN Loop Layout 6

DIRECT/REVERSE RETURN This shows multiple riser low rise. For single riser layouts, each floor can be RR with DR risers Can combine RR and DR for multiple loops/wings. Minimizes pipe, maintains balance advantages 7

OPTIONS TO REVERSE RETURN BRANCH DP CONTROLLERS AUTO FLOW VALVES PRESSURE INDEPENDENT CONTROL VALVES 8

VARIABLE PRIMARY Variable flow through chiller/boiler to a minimum. Bypass or 3- way valves to maintain min flow. Manifold the pumps to disassociate pump flow from chiller/boiler staging and provide easy redundancy Select chillers to allow both higher AND lower than normal flows 9

PRIMARY SECONDARY - SYSTEM SOURCE LOAD Independent loops, not affected by each other Integrates different source and load needs Based on minimal pressure drop at decoupler 10

PRIMARY SECONDARY - SYSTEM Design load Lots of pumps redundancy adds even more 11

PRIMARY SECONDARY - SYSTEM Part load - stage chillers and pumps to keep source flow greater than load flow Low DT syndrome forces multiple chillers to run even at plant load less than 1 chiller s capacity. Pump energy 12

PRIMARY SECONDARY @ LOAD LOAD SOURCE Energy must balance Can set up for variable or constant source flow/dt Can set up for variable or constant load flow/dt High source DT, low load DT Different load supply temp than source supply temp 13

PRIMARY SECONDARY @ LOAD Constant flow to load Load capacity changed via supply water temp Excellent for AHU preheat, 100% OA, or DOAS coil Avoids oversizing Helps destratification Freeze protection 14

DISTRIBUTED PRIMARY SECONDARY Total pump HP is less than a single source pump Very small systems cycle/modulate zone pumps Very large systems Each zone is a building 15

DISTRIBUTED PRIMARY SECONDARY Total pump HP is less than a single source pump Very small systems cycle/modulate zone pumps Very large systems Each zone is a building 16

Miscellaneous Pipe Layouts Single pipe loops Old school baseboard Water source heat pumps Process cooling Two pipe changeover Either heat or cool through same piping, and usually same coils as well. Changeover decision Source equipment changeover Three pipe systems Literally old school (was common in unit ventilator systems in schools). Also high rise terminal systems. Huge energy waste just to save a pipe. 17

Expansion Tanks To limit the maximum pressure at weakest system component Maintain a minimum pressure to eliminate cavitation and boiling Provide a reference pressure (analogous to an electrical ground) 18

Expansion Tanks Point of no pressure change Reference pressure for automatic fill Isolates pump head from sensitive components 19

Expansion Tanks 20

Expansion Tanks Usually at suction of pump, downstream of generating equipment Only one tank per system Primary secondary Campus Additions 21

Expansion Tank Sizing Information needed: Vs=Volume of system dl=density of fluid at lower temperature dh=density of fluid at higher temperature α=expansion coefficient of pipe ΔT=expected fluid temp range Pa=Atmospheric pressure PL=Minimum allowable pressure at tank = fill pressure PH=Maximum allowable pressure at tank Link to form 22

Expansion Tank Sizing Closed (plain steel) tank: Vt=Vs[(dL/dH-1)-3αΔT] / [(Pa/PL)-(Pa/PH)] Diaphragm/Bladder Tank: Vt=Vs [(dl/dh-1)-3αδt] / [1-(PL/PH)] Precharge pressure equals PL Total expanded volume (upper term) must not exceed acceptance volume All pressures are absolute (atm + gauge) MUST SPECIFY FILL/PRECHARGE (PL) 23

Expansion Tank Sizing 24

Expansion Tank Sizing Effect of Glycol: Expansion of plain water, 40 o -180 o dl/dh-1 62.42/60.57 1 =.0305 Expansion of 30% Prop. Glycol, 40 o -180 o dl/dh-1 64.47/61.92 1 =.0401 Glycol expands 1.35 times as much as water 25

Diaphragm Type Tank Bladder Type Tank 26

Diaphragm Type Tank 27

Bladder Type Tank 28

Expansion Tank Sizing Effect of location in building Mechanical room at bottom of building. 29

Expansion Tank Sizing Mechanical room on top 30

ENERGY ASPECTS OF PUMPS Always a parasitic loss in HVAC Not doing the heat transfer, just getting it there. Better than air Water has a much higher energy density BHP = (GPM*Ft. Head)/(3960*Pump Efficiency) BTU/H =(GPM*500*DT) Glycol affects the 500 GPM FACTOR 30% 40% 50% 40 DEG 484 469 444 180 DEG 446 434 423 31

Pump/Pipe Sizing Corrections - Glycol 32

Pump Selection System curve Best efficiency point Max impeller size Non-overloading VFD, constant, or ride the curve Future operation NPSH 33

PUMP SELECTION TRIMMING IMPELLER CAUSES RECIRCULATION WITHIN THE VOLUTE, REDUCING EFFICIENCY. OPERATING TO THE RIGHT SIDE OF CURVE CAUSES HYDRODYNAMIC STALL UNPREDICTABLE LOW NPSH CAUSES LOCALIZED PRESSURE BELOW VAPOR PRESSURE OF FLUID IMPELLER VOLUTE ARRANGMENT 34

Pump Selection Usually only an issue with hot/open systems or suction lift. All pressures absolute (ATM + gauge) Vapor pressure 90 o -.7 psi 180 o 7.5 psi 200 o 11.5 psi 35

Pump Selection NPSHA Examples Condensate Return ( 200 o atmospheric tank) h p = 12 psia = 27.7ft h z = 4 ft h vpa = 11.5 psia = 26.5 ft h f = 2 ft 27.7 + 4-26.5-2 = 3.2 ft 36

Pump Selection NPSHA Examples Cooling Tower h p = 12 psia = 27.7ft h vpa =.7 psia = 1.6 ft 27.7 + 4-1.6-5 = 25.1 ft h z = 4 ft h f = 5 ft 37

Cavitation Example 38

Cavitation Example Wort Cavitation 39

Pump Selection Flat Riding the curve variable volume Steep VFD variable volume and constant volume 40

Pump Selection Flattens curve (start with steep curve pumps) Provides 70% - 80% back-up. Check single pump operation for overloading and right end of curve operation Use two similar pumps 41

Pump Selection 42

STUFF Open systems Static head Remote sump cooling tower NPSH Don t pump air For cooling towers, pumping gravel sound is probably air, not cavitation. 43

STUFF Variable Speed Pumping in Constant Volume or Pressure applications Use of VSP as throttling valve or control valve Pressure is maintained by impeller speed, so if pressure at pump needs to stay constant regardless of flow, may not be much advantage to VSP. Steep vs flat curves Domestic Water Booster If dominated by friction rather than lift, VFD is appropriate. Steam Boiler Feed Meet pressure relief setting per code at max speed, operate at lower speed to meet operating pressure. Remote sump cooling tower 44

VFD WITH CONSTANT HEAD 45

FURTHER INFORMATION Manufacturer info (particularly high efficiency equipment) ASHRAE PDS GOOGLE 46