Choosing and Installing Microbiological Safety Cabinets

Similar documents
Safety Services. Introduction

Biological Safety Cabinet Guidelines

The primary purpose of laboratory fume hoods is to keep toxic or irritating vapors out of the general laboratory working area.

Toolkit for safe Use of Microbiological Safety Cabinets(MSC s)

Use of Biosafety II cabinets

Kansas State University Fume Hood Operation

Vertebrate Animal Biosafety Level 1 Criteria

The routine maintenance and inspection of local exhaust ventilation (LEV)

LABORATORY SAFETY SERIES: Laboratory Hoods

"LABORATORY SAFETY SERIES"

LEV GUIDANCE FOR SAFE USAGE, TESTING AND MAINTENANCE OF LOCAL EXHAUST VENTILATION SYSTEMS WITHIN ANGLIA RUSKIN UNIVERSITY RISK MANAGEMENT

MANAGEMENT PROCEDURE FOR LABORATORY VENTILATION

Work Equipment: LOCAL EXHAUST VENTILATION

Safety Procedures on Vacating Premises

GSA POLICY ON LOCAL EXHAUST AND OTHER VENTILATION (FUME CUPBOARDS)

Selection, use and maintenance of Microbiological Safety Cabinets

Control of Allergies to Laboratory Animals

Laboratory Self Inspection Checklist LAB01

Contractor Control Procedures. Contractor Control Procedures. Working Together. November Borders College 24/11/2014.

TEMPLE UNIVERSITY ENVIRONMENTAL HEALTH AND RADIATION SAFETY

Use, storage and disposal of flammable liquids

ISO 7218 INTERNATIONAL STANDARD

1. The laboratory supervisor must enforce the institutional policies that control access to the laboratory.

Animal Biosafety Level 2

Faculty/School: Pharmacy Initial Issue Date: Oct 2016

TEMPLE UNIVERSITY ENVIRONMENTAL HEALTH AND RADIATION SAFETY

Laboratory Safety Training. Environmental Health and Safety

Biological materials manipulated in the laboratory: Bacteria Virus Protozoan

Safety Issues in Healthcare Programs / Healthcare Employment

BGC HOLDINGS LTD RESPIRATORY PROTECTIVE EQUIPMENT (RPE) POLICY

Vision Painting Inc Safety Management System

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

PERSONAL PROTECTIVE EQUIPMENT GUIDANCE

LABORATORY FUME HOOD SPECIFICATION AND MAINTENANCE PROGRAM

PI: Comments 1 12/18/14

Post MD in Residence Placement

ESTATES OFFICE OPERATIONS WORKS INSTRUCTIONS WI 6. Fume Cupboards, Ventilated Cabinets, Local Exhaust Ventilation

CTG Certification Protocol -- Version 3.0 SUMMARY

Biosafety Level 2 (BSL2) Laboratory Safety Inspection Checklist

THE UNIVERSITY OF WESTERN ONTARIO DIVISION OF HUMAN RESOURCES OCCUPATIONAL HEATH & SAFETY

BIOSAFETY SELF AUDIT PRINCIPAL INVESTIGATOR/PERMIT HOLDER: CONTAINMENT LEVEL: 1 2 (Shaded) RISK GROUP: 1 2 AUDIT TO BE COMPLETED BY (DATE):

STANDARD OPERATING PROCEDURES (SOP) FOR REPRODUCTIVE HAZARDS

TSS21 Sealed Thermostatic Steam Tracer Trap

THE UNIVERSITY OF WESTERN ONTARIO OCCUPATIONAL HEATH & SAFETY

Safety Tips for Using Germicidal Lamps

LABORATORY ANIMAL ALLERGEN PREVENTION PROGRAM

Exposure Control Plan for Drilling/Grinding Concrete

POLICY ON THE PROVISION & USE OF PERSONAL PROTECTIVE EQUIPMENT

CONTROL OF SUBSTANCES HAZARDOUS TO HEALTH PROCEDURE

Vertebrate Animal Biosafety Level Criteria for Vivarium Research Facilities

[Type here] MANAGEMENT OF X-RAY GENERATING EQUIPMENT

Laboratory Ventilation. Environmental, Health, and Safety

LEV Issues. Local Exhaust Ventilation. A Salesman Approaches! Why is LEV important? What is it supposed to do? What comprises an LEV system?

1.0 PURPOSE The purpose of this procedure is to describe the use of basic aseptic technique.

PV4 and PV6 Piston Valves

Title: Abrasive Blasting Effective Date: 11/17/2014 Control Number: THG_0034 Revision Number: 1 Date: 10/22/2015 Annual Review Completed: 5/13/2015

CHECKLIST FOR LABORATORY BASED INSPECTIONS

Health & Safety Policy HSP 08 Control of Substances Hazardous to Health (COSHH) Version Status Date Title of Reviewer Purpose/Outcome

Forced or Mechanical Ventilation - which uses mechanical supply and/or extraction to provide fresh air and is controllable.

Laboratory Health and Safety

3 Philosophy of use. Leaded Gloves. Leaded Apron. Respiratory Protection (RPE) Whole body protective suit

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

Product Description TUV PL-L

Section V Vertebrate Animal Biosafety Level Criteria for Vivarium Research Facilities

INFORMATION NOTE No 353: MICROBIOLOGICAL TESTING

Reviewed: DD Month Management of Closed Radioactive Sources

Proficiency Module Syllabus. P601 - Thorough Examination and Testing of Local Exhaust Ventilation Systems

5.0 Store. safely IN THIS SECTION: 5.1 Decanting or transferring

NUS Safety & Health Guidelines Procedure No: OSHE/SOP/GL/08

CCM Approval: IACUC Approval:

OFFICE OF STATE HUMAN RESOURCES

Department of Genetics

Tools to Enhance Laboratory Biosafety and Biosecurity Performing Risk Assessments

Laboratory and Satellite Rodent Housing

Dri-Line Mk3 Monnier Compressed Air Drain Trap

SAEMA Document No. SDN Original Issue Date: April 2017 Revision Reference: Revision Date: Not later than end of April 2019

DSEAR-Classification of Hazardous Areas (Zoning) and Selection of Equipment

Calibration Requirements for Direct Reading Confined Space Gas Detectors

Laboratory Personal Protective Equipment & Hazard Assessment Tool

PERFORM Operating Document

OCCUPATIONAL SAFETY AND ENVIRONMENTAL HEALTH GUIDELINE

Effective Date: 24-April-2017 Version: 6 Page: 1 of 8 TITLE: SAF-370, PERSONAL PROTECTIVE EQUIPMENT GUIDELINES. Table of Contents

Respiratory Protective Equipment

University of Dayton Respiratory Protection Program 29 CFR

UHSE. Bath University HR Department UHSE. Safe Use of Fume Cupboards. Document Information

Northern Kentucky University Issue Date: 11/02/2018 Revised Date: Title: PERSONAL PROTECTIVE EQUIPMENT PROCEDURE OBJECTIVE AND PURPOSE

A. Evaluation of the written program

Personal Protective Equipment

Aseptic processing. the starting material to the finished product, should be controlled by Validation Control of the aseptic process

Hazardous substance risk management

Instructions for Completing the UW-Madison Laboratory Chemical Hygiene Plan Template

Cabinet. 1.0 POLICY It is the policy of Calvin College to comply with the MIOSHA Respiratory Protection Standard Part 451.

POLICY ON THE PROVISION & USE OF PERSONAL PROTECTIVE EQUIPMENT

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

PSSI 36 General Confined Spaces, Tunnels, Culverts and Similar Spaces

Hazardous substances compliance tools

Approved Installation Method (AIM)

MIT Analytical X-Ray Safety Policies and Procedures

Installation of Ballast Water Management Systems

Transcription:

Choosing and Installing Microbiological Safety Cabinets Guidance for University Departments and Functions First Edition December 2006 Safety Services Office Issued with the approval of the Biological and Chemical Hazards Sub-Committee

Choosing and installing Microbiological Safety Cabinets The microbiological safety cabinet (MSC) is a basic tool in the laboratory for those who work with biological agents. These include: pathogenic micro-organisms (including genetically modified micro-organisms) cell cultures human and animal tissues and fluids. A microbiological safety cabinet is defined in the European Standard on Microbiological Safety Cabinets as a: "Ventilated enclosure intended to offer protection to the user and the environment from the aerosols arising from the handling of potentially hazardous and hazardous microorganisms, with air discharged to the atmosphere being filtered". There are four major components that contribute to ensuring safe working with MSCs: the design, construction and function of the cabinet itself good laboratory design (specifically with respect to cabinet location and room ventilation) safe systems of work that incorporate good operational technique regular appropriate testing and maintenance. The three basic types of cabinet are: Class I An open fronted cabinet designed to protect the operator by continuously drawing air into the front of the cabinet. This is the traditional cabinet of microbiology and clinical diagnostic laboratories. Its construction is simpler than the other types and is therefore cheaper to produce and buy. It is the cabinet of choice when the key requirement is the protection of the worker. Class II An open fronted cabinet designed to protect the operator from exposure and the work from external contamination. Inward air is directed downwards into a plenum below the work surface and is filtered before being redirected into the work area as a laminar down flow of clean air. The balance of this laminar down flow with the incoming air provides an air curtain at the open front which provides the operator protection. The split between exhausted and recycled air on each cycle is normally in the range 20/80 to 30/70. These cabinets are designed so that the work area is kept clean by a down-flow of HEPAfiltered air across the work. With good working technique it is possible to achieve a high degree of product protection whilst at the same time achieving a degree of operator protection of the same order as that achieved by Class I cabinets. They are typically used for cell and tissue culture applications and for other work where product protection from contamination is important. 1

Cabinets that meet the performance requirements of the British Standard should be able to afford the worker a degree of protection equivalent to that from a Class I cabinet. Their performance is however more affected by other factors, such as operator movement and air movements outside the cabinet. Class III A totally enclosed cabinet in which operations are conducted through gloves attached to glove ports. Air enters the cabinet through a HEPA filter at the side or rear of the cabinet and is exhausted in a similar way to a class I cabinet. Class III cabinets are used mainly for work with hazard group 4 organisms, or work with hazard group 3 organisms deemed to be high risk, for example where highly concentrated samples are being handled. They offer the greatest protection to the worker and work, but movements are more restricted and this may affect dexterity. Note - Laminar flow hoods MSCs should not be confused with laminar flow hoods (LAFs). These hoods provide a filtered air-flow which is intended for PRODUCT PROTECTION ONLY. The air can be directed either vertically or horizontally toward the operator. Neither type offers any operator protection. Typical uses for a LAF would be sterile ampoule filling and pouring of agar plates. They must never be used with any biological material of human origin. Other animal-derived material or tissue may only be used after a full risk assessment that: (a) confirms the total non-pathogenic and non-allergenic status of the material (b) provides a reason why a microbiological safety cabinets cannot be used. Conditions of purchase Users should always consult their Departmental Services Manager, Chief Technician or other appropriate local manager before selecting safety cabinets. The cabinet manufacturer or supplier must be able to provide a test certificate demonstrating type compliance with BS EN 12469:2000. Poorly sited cabinets can be adversely affected by disruptive airflows from obstacles, passing traffic or excessive airflows from poorly located room ventilation ducts. As a condition of purchase, the supplier should inspect the proposed location for the cabinet and confirm that it is an appropriate site (see the recommendations for siting and installation in part 4 of the BS 5276). The purchase contract should include a clause requiring in situ tests to confirm the performance after installation. These tests should include demonstration of meeting the Standard requirements for airflow and operator protection and the demonstration of filter integrity, both of the filter itself and of the filter housing. 2

Although the performance of Class II cabinets can be as good as Class I cabinets with respect to operator protection, they are more susceptible to the effects of air movements outside the cabinet. The use of a Class II cabinet, rather than a Class I or III, at containment level 3 must therefore always be justified. For Class II cabinets used for work with biological agents, additional appropriate 'in use' tests which reflect normal operating procedures in the laboratory may be required where work is proposed with hazard group 2 agents and must be done if the cabinet is to be used with hazard group 3 agents. Two examples of additional 'in use' tests are: the four-headed test as specified in the British Standard (but without the artificial arm) with an operator in position with both hands and lower arms within the cabinet throughout the test. The operator should perform repetitive and continuous procedures (e.g., pipetting to and from a multi-well plate and a bottle with a suitable automatic pipette) the same test but with a second person wearing a properly fastened laboratory coat or gown walking backwards and forwards behind the operator at approximately 100 paces per minute at the rate of 3 to 5 passes per minute. It should be a condition of your purchase contract that satisfactory performance in the post installation tests is demonstrated before any payment is made. Choosing the right configuration and location Arrangements for exhaust air The preferred option for venting safety cabinets is to duct the exhaust air to the exterior of the building. This option confers some significant safety advantages: the safety cabinet exhaust can provide a cheap and simple method of keeping a containment laboratory under negative pressure the discharge of fumigant gas after decontamination of the room or the cabinet is made significantly easier there may be occasions when a worker needs to treat cultures with small amounts of volatile toxic chemicals, in which circumstances discharging the exhaust air back into the laboratory would not be acceptable. Where this is not possible, and it is clear that the only risk in the work is microbiological, it can be acceptable at containment level 2 for cabinets to discharge the exhaust air back into the work room via a double HEPA filter. It should not be permitted at containment level 3. For cabinets with integral fans the exhaust ductwork should be kept below 2 metres in length and be air tight. Where the duct run has to be longer, the exhaust fan should be located as near the discharge end of the duct as is possible. 3

In summary, cabinets should where possible be exhaust type and hard ducted. Where this is not possible, the cabinet configuration should be discussed with the manufacturer or supplier, and the risk assessment for the proposed work should be fully considered. Recirculating cabinets It is recognised that recirculating cabinets are sometimes preferred for operational reasons, especially in buildings where access to suitable exhaust ductwork is a problem, or when the location of the cabinet is not considered permanent. In these situations, there is no reason not to install recirculating cabinets as long as the risk assessment of the proposed work has been considered. If a recirculating cabinet is to be purchased, procedures for fumigation should be considered before purchasing the unit. A fumigation unit incorporating a formaldehyde scavenger will be needed if formaldehyde is to be used as fumigant. If hydrogen peroxide is to be used for fumigation, the supplier of the fumigation equipment or service will need to be contacted in advance of purchase, to ensure that the cabinet to be purchased can be fumigated by this method without difficulties. Siting of cabinets Note from BS5726: 5.4 The siting of safety cabinets in laboratories should be considered at the initial stages of the planning of a new building or before modification of an existing building. Cabinets should be sited so as to minimise disturbance of the airflow at the front of the cabinet. BS 5726 gives recommendations on siting. Particular care must be taken in locating recirculating cabinets where the exhausted air may cause air disturbance at the front of the cabinet, adversely affecting containment performance. The key issues are: that the cabinet is located with sufficient clearance from walls, corners and doorways that no obstacles are placed where they may interfere with the airflow and that sufficient room is provided for the operator to avoid interference with other workers. Once the key requirements are met, the location is fixed and the cabinet passes the in situ tests, the position of the cabinet must not be changed unless full repeat tests are carried out. Examples of siting in different circumstances, and recommended distances, are given in the BS. The provision of gas and ultra-violet (UV) lighting Gas 4

Bunsen burners or other naked flames should not be used in microbiological safety cabinets for the following reasons: Disturbance of air-flow (hence loss of containment and operator protection) Fire risk Potential damage to the filters. With open-fronted cabinets the use of Bunsen burners may reduce the operator protection by disturbing the air-flows. They should never be used in Class II cabinets. Exceptionally they may be provided for Class I cabinets, but if so, they should be low profile microburners equipped with a lever control to give full flame only as required, in order to minimise disturbance. To minimise the risk of fire and heat damage, gas provision must be controlled via a solenoid valve, interlocked positively with the operation of the cabinet fan(s). UV light UV light is generally ineffective for the disinfection of safety cabinets: Radiation is directional and therefore for it to have any effect, the cabinet must be totally empty. The light has low penetration power and will not be effective on any part of a surface that is not properly clean. The microbicidal action of a UV lamp is relatively short - a fraction of the lamp s total lifetime as a source of visible (blue) light. Hence users may believe that a lamp has germicidal output because it still emits light, when in fact it no longer emits useful levels of UV. The use of UV introduces an additional hazard. Skin burns have been suffered by users who have been accidentally exposed. The lamp can only be safely left on when the lab is not in use (usually overnight.) Cabinets with UV lights should therefore not be purchased UNLESS use of UV light is an integral part of the experimental work planned. Where UV lights are already in place in existing cabinets, it is recommended that they are removed by the user department after discussion with the users involved. If they must be retained, or UV is needed in a new cabinet because of the nature of the experimental work, the following conditions must be met: UV lighting must be installed in a manner that cannot affect the performance or durability of the cabinet. Thus only materials that are unaffected by UV rays should be used for the construction and coating of the cabinet Electrical interlocking must be fitted and operational to prevent direct operator exposure to UV light 5

The efficacy of the microbicidal activity of the light must be monitored regularly The lamp must be changed whenever its efficacy is reduced (or regularly at a predetermined frequency that ensures the light is still effective). The proper use of safety cabinets All departments who purchase safety cabinets must have in place at least a Code of Practice, and preferably a set of local rules for use of the cabinets. All users of safety cabinets must be given training as required by BS5726. No person should be allowed to work at a microbiological safety cabinet unless proper training has been given and the person is competent to do the work. User training should include: a) classification of cabinets; b) appropriate and inappropriate use of cabinets; c) mode of operation and function of all controls and indicators; d) limitations of performance; e) how to work at cabinets safely; f) how to decontaminate cabinets after use; g) principles of airflow and operator protection tests. A GOOD CABINET CAN NEVER BE A SUBSTITUTE FOR GOOD PRACTICE OR GOOD MICROBIOLOGICAL TECHNIQUE. 6

Maintenance and testing All microbiological safety cabinets must be regularly serviced and tested to ensure their continued safe performance and to satisfy legislative requirements. The recommended maintenance and testing programme is subject to local circumstances but should normally be regarded as a minimum. In exceptional circumstances however, in low-risk areas an annual frequency for all operations may be acceptable but is subject to regular risk assessment review. The expected frequency for maintenance and testing is set out below: Operation Air-flows (contractor) (user) Filter integrity Mechanical and electrical function Mechanical integrity (including visible ductwork) Operator protection Frequency 6-monthly Monthly 6-monthly 6-monthly Annual Level 2 annual Level 3 6-monthly References British Standard BS 5726:2005 Microbiological safety cabinets. Information to be supplied by the purchaser to the vendor and to the installer, and siting and use of cabinets. Recommendations and guidance. Supersedes BS 5726-2:1992 and BS 5726-4:1992. British Standard BS EN 12469:2000 Biotechnology. Performance criteria for microbiological safety cabinets. Replaces Part 1 and 3 of BS 5726:1992. Acknowledgement This guidance is based on material from the MRC, whose permission to use it is gratefully acknowledged. 7