WARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY

Similar documents
Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only

Your safety and the safety of others are very important.

installation instructions

Installation Instructions

ACCESSORY KIT INSTALLATION MANUAL

Natural Gas to L.P. Gas Conversion Kit

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Natural Gas to L.P. Gas Conversion Kit

Installation Instructions

ACCESSORY KIT INSTALLATION INSTRUCTIONS

/2004 US/CA

INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F29, F30, F31, F32 & F33

INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F13, RXGY-F27 AND RXGY-F28

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*

Installation Instructions For Natural Gas Conversion

INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F23, F24, F25, F26, F38, F39, F40 & F41

INSTALLATION INSTRUCTIONS

Propane Conversion Kit Instruction

USER S INFORMATION MANUAL

ACCESSORY KIT INSTALLATION INSTRUCTIONS

DANGER WARNING IMPORTANT

GAS VALVE RETROFIT KIT Pull Through Tube Heater Models

WARNING: AVERTISSEMENT. LP & HIGH ALTITUDE LP CONVERSION KIT FOR INSTALLATIONS IN the United STATES (0-10,000 Ft)

ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0347

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Natural Gas Conversion Kit

SL G3. Warning

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction

Operator: Save these instructions for future use!

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

Gas Conversion Kits CERAMIC HEATER SERIES (1, 2, 3, 4 Burner Units)

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0347

Installation Instructions For Propane Gas Conversion (Kit Part No ) This kit is designed for conversion to Propane Gas

GAS KITS & ACCESSORIES 504,986M 11/2004 HIGH ALTITUDE KIT

Operator: Save these instructions for future use!

Propane Conversion Kit Instructions

INSTALLATION INSTRUCTIONS

36H SERIES Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Gas Conversion Kits Push Through (Positive Pressure) Tube Heater Models

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

VR8205S,T Direct Ignition Combination Gas Controls

G96 Series BASOTROL Dual Operator Valve

SL G3 - Fuel Conversion to Natural Gas (LP to NG) P-Kit 301

Instructions for High Altitude Conversion

GM Series Dual-Block Multi-Function Gas Control Valves

GAS CONVERSION KIT Installation Instructions Range/Rangetop

WARNING: FOR OUTDOOR USE ONLY

Installation Instructions

V8200A,C,H,M and VR8200A,C,H,M Continuous Pilot Combination Gas Controls

VR8200A Continuous Pilot Combination Gas Controls

Operator: Save these instructions for future use!

VS8420 Millivolt Gas Valve

Gas Fired Residential Heating Boilers

Conversion instructions from natural gas to propane

INSTALLATION & OPERATION MANUAL FOR Stockpot Range

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

INSTALLATION, OPERATION, SERVICE & PARTS MANUAL FOR STOCK POT RANGE MODELS VSP100, VSP200 & VSP300

Natural Gas Conversion Kit

Gas Countertop Griddle

INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles

VR8305 Direct Ignition Combination Gas Control

Operator: Save these instructions for future use!

For *G7 / *GC2 & GUH* / GDD* Series Furnaces & Appliances Using Honeywell Gas Valves

BGA158 Series CE Approved Class A Shutoff Gas Valve

Installation Instructions

SPECIFICATIONS ATTENTION

BGA158 Series CE Approved Class B Shutoff Gas Valve

Operator: Save these instructions for future use!

Dual Solenoid Gas Valve Installation

INSTALLATION INSTRUCTIONS

For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum WARNING: FOR OUTDOOR USE ONLY

Parts List. Qty. Qty.

Installation Instructions

Operator: Save these instructions for future use!

VR8105, VR8205, and VR8305 Direct Ignition Combination Gas Controls

INSTRUCTION MANUAL. Gas Salamander

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

GM-7000 Series CE Approved Gas Control Valve

Gas Conversion Kit Pilot Ignition Heaters

INSTALLATION GUIDE Gas Rangetops

Installation Instructions

Operator: Save these instructions for future use!

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

INSTALLATION AND OPERATING INSTRUCTIONS BIG TEX VENTED GAS LOGS

Operator Manual Gas Griddle / Cheesemelter

Installation Instructions

LNVx Gas Conversion Kit Instructions

Transcription:

Form CP-UD-GC Obsoletes I-UD-GC (Version E) Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters General and Warnings All gas conversion must be done by a qualified service person in accordance with these instructions and in compliance with all codes and requirements. In Canada, gas conversion shall be carried out in accordance with the requirements of the Provincial Authorities having jurisdiction and in accordance with the requirements of the CAN/CGA-B49. and.2 installation code. WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. Read the installation, operation and maintenance instructions thoroughly before installing or servicing this equipment. FOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Leave the building immediately. Immediately call your gas supplier from a phone remote from the building. Follow the gas supplier s instructions. If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency, or the gas supplier. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. DANGER: The conversion kit is to be selected and installed by a qualified service person in accordance with these instructions and in compliance with all codes and requirements of authorities having jurisdiction. Failure to follow instructions could result in death, serious injury and/or property damage. The qualified agency performing this work assumes responsibility for this conversion. Form CP-UD-GC, P/N 97209R8, page

General and Warnings (cont d) DANGER: The gas burner in this gas-fired equipment is designed to provide safe complete combustion. However, if the installation does not permit the burner to receive the proper supply of combustion air, complete combustion may not occur. The result is incomplete combustion which produces carbon monoxide, a poisonous gas that can cause death. Safe operation of indirect-fired gas burning equipment requires a properly operating vent system which vents all flue products to the outside atmosphere. FAILURE TO PROVIDE PROPER VENTING WILL RESULT IN A HEALTH HAZARD WHICH COULD CAUSE SERIOUS PERSONAL INJURY OR DEATH. On separated combustion Model UDAS and UDBS heaters, install either the horizontal or vertical combustion air/vent system illustrated in the heater venting manual, using the concentric adapter supplied. For all heater installations, always comply with the combustion air requirements in the installation codes and instructions. Model UDAP and UDBP units installed in a confined space must be supplied with air for combustion as required by Code and in the heater installation manual. Combustion air at the burner should be regulated only by manufacturerprovided equipment. NEVER RESTRICT OR OTHERWISE ALTER THE SUPPLY OF COMBUS- TION AIR TO ANY HEATER. MAINTAIN THE VENT OR VENT/COMBUSTION AIR SYSTEM IN STRUCTURALLY SOUND AND PROPER OPERATING CONDITION. Hazard Intensity of Warnings in this Manual Application and Kit Selection HAZARD INTENSITY LEVELS. DANGER: Failure to comply will result in severe personal injury or death and/or property damage. 2. WARNING: Failure to comply could result in severe personal injury or death and/or property damage. 3. CAUTION: Failure to comply could result in minor personal injury and/or property damage. The gas conversion kits in these instructions are for Model UDAP, UDAS, UDBP, and UDBS heaters equipped with either a single-stage or two-stage valve. Conversion kits for Sizes 60-400 include two spring kits, one for a single-stage valve and one for a two-stage valve, and all conversion kits include burner orifices for multiple sizes. See pages 8 through 0 for a list of conversion kit components. Kit P/N s, Application, and Components Natural TO Propane Kits..pages 8-9 Propane TO Natural Kits..page 0 Gas Conversion Instructions Form CP-UD-GC, P/N 97209R8, page 2. Check kit contents for agreement with the parts list and the size of heater being serviced. (See the parts lists and application for each kit on pages 8-0.) Conversion of a unit using these kits will not alter the input rate. Refer to the rating plate on the heater for input rate and other appropriate information. (NOTE: If adjusted for high altitude operation, input rate will be affected; for high altitude input ratings and capacities refer to TABLE 3A on page for UDAS and UDAP or TABLE 3B on page 2 for Models UDBP and UDBS.) 2. Turn off the gas supply at a shutoff valve outside of the heater and turn off the electrical supply. Open the control access panel. 3. Select and Install the Regulator Spring Kit (valve conversion kit) Kits for Sizes 30 and 45 include a regulator spring kit for a single-stage valve. All kits for Sizes 60 though 400 include two regulator spring kits -- one for a single-stage valve and one for a two-stage valve. Check the package

FIGURE - Gas Valve and Burner Orifice (Fan model is illustrated; gas valve and orifice locations are the same on blower models.) carefully and choose the regulator spring kit that corresponds with the valve on the heater. NOTE: The other regulator spring kit will not be used. To install the spring regulator conversion kit, follow the valve manufacturer s installation instructions that are included with the spring conversion kit. After a new regulator spring kit is installed, it is necessary to adjust the spring for the correct manifold pressure. This adjustment can only be made after the heater is in operation; instructions are included in Step No. 7. WARNING: Regulator spring kits are not interchangeable. Each spring kit must be used only in the model and type of valve for which the kit is designated. Verify compatibility before installing the regulator spring kit. 4. Select and Install Burner Orifice - Applies to Models UDAP/UDAS/ UDBP/UDBS - All Sizes Remove or Install Air Restrictor Plate - Applies only to Models UDAP/ UDAS/UDBP/UDBS - Sizes 30, 45, 60, 75, 00, and 50 AND Models UDBP/UDBS Size 25 Form CP-UD-GC, P/N 97209R8, page 3

Gas Conversion Instructions (cont d) TABLE - Burner Orifice P/N s and Markings WARNING: Do not attempt to drill orifice. Use factory-supplied orifice only. 4A. Select orifice. Because each kit is designed to convert more than one size of heater, there are two or three burner orifices per kit. From TABLE below, find the marking that appears on the orifice for the heater being converted. Select the orifice from the kit that has the marking required for the size of heater. The other orifice(s) will not be used in this conversion. Burner Orifice - Models UDAP, UDAS, UDBP, and UDBS Natural Gas Size 30 45 60 75 00 25 P/N 96853 96838 96839 96855 2058 96840 Marking #37 #30 3.7MM #9 #0 #4 Propane P/N 96844 96845 96846 96852 96854 96847 Marking.6MM #48 2.3MM #39 3.0MM 3.2MM Size 50 75 200 225 250 300 350 400 Natural Gas P/N 358 9689 96892 222 208255 2222 2223 96897 Marking 5.9MM E 6.8MM 6.95MM L 8.0MM 8.7MM 9.6MM FIGURE 2 - ) Location of the Burner Orifice on all Models and Sizes 2) Location of the Air Restrictor Plate on UDAP, UDAS, UDBP, and UDBS 30, 45, 60, 75, 00, and 50 and UDBP and UDBS 25 when used with Propane only Air restrictor plate must be added when converting models and sizes listed to propane Air restrictor plate must be removed when converting to natural gas. Propane Venturi Tube P/N 96898 96899 96900 9690 96902 96903 96904 96905 Marking 9/64" #24 4.MM /64" #4 #8 #3 5.8MM Tabs are not bent; bend tabs to hold restrictor in place. Burner Orifice (NOTE: Before installing the new orifice, verify the marking with the size listed in TABLE above.) Gas Flow from Gas Valve Air Restrictor Plate FOR PROPANE ONLY - Applies to UDAP, UDAS, UDBP, and UDBS 30, 45, 60, 75, 00, 50 and UDBP and UDBS 25 DANGER: Failure to install or remove air restrictor plate according to directions could cause property damage, personal injury, and/or death. FIGURE 3 - Location of Holding Tabs on the Air Restrictor Plate used on UDAP, UDAS, UDBP, and UDBS 30, 45, 60, 75, 00, and 50 and UDBP and UDBS 25. Restrictor plate is used with Propane only To install, bend tabs (2 on each side) to hold in place. To remove, carefully unbend tabs. Form CP-UD-GC, P/N 97209R8, page 4

Instructions for Changing the Pressure Switch. In the control compartment, locate the pressure switch. 2. Mark and disconnect the two wires attached to the pressure switch. 3. Disconnect the sensing tube(s) from the pressure switch. 4. Locate the two screws holding the switch mounting bracket. Remove the screws (save screws) and the pressure switch. 5. Using the same screws, install the correct pressure switch. Attach the sensing tube(s) and wires. 4B. Select and follow instructions for type of conversion and size of heater. Natural Gas TO Propane - Applies to Models UDAP/UDAS/UDBP/ UDBS 30, 45, 60, 75, 00, 50 and UDBP/UDBS 25. ) Refer to FIGURES and 2 and locate the gas orifice. Carefully remove the natural gas orifice supplied with the furnace. 2) Slide the air restrictor plate over the venturi opening, positioning as illustrated in FIGURE 2. (NOTE: Verify diameter of opening with component list on pages 8-0.) 3) Refer to FIGURE 3. Holding the air restrictor plate in position, use a pair of pliers to bend the tabs to lock the air restrictor plate to the venturi tube. Be sure air restrictor is aligned and secure. 4) Install the propane orifice selected for the heater in Step 4A, page 4. Propane TO Natural Gas - Applies to Models UDAP/UDAS/UDBP/ UDBS 30, 45, 60, 75, 00, and 50 and UDBP/UDBS 25. ) Refer to FIGURES and 2 and locate the gas orifice. Carefully remove the propane orifice supplied with the furnace. 2) Refer to FIGURES 2 and 3 and locate the air restrictor plate on the venturi tube. Using a pair of pliers, very carefully unbend the tabs and remove the air restrictor plate. 3) Install the natural gas orifice selected for the heater in Step 4A, page 4. Natural Gas to Propane OR Propane to Natural Gas - Applies to Models UDAP/UDAS/UDBP/UDBS Sizes 75, 200, 225, 300, 350, 400 ) Refer to FIGURE and locate the gas orifice. Carefully remove the gas orifice supplied with the furnace. 2) Install the orifice selected for the heater in Step 4A, page 4. NOTE: Natural gas to propane kit for Size 75 includes a primary air restrictor that will not be used. WARNING: If the heater will be operated above 6000 ft (830M), a high altitude pressure switch must be used. 5. Check for high altitude. If the installation location is above 6000 ft (830M), verify that the altitude on the rating plate or high altitude label is above 6000 ft (830M). If the rating plate or label does not indicate an altitude above 6000 ft (830M), order and install the appropriate high pressure switch kit. Or, if the heater is equipped for above 6000 ft (830M) elevation and is being installed at a lower elevation, order the appropriate switch and install it (see instructions on the left). Contact your distributor to select the factory-authorized replacement part. 6. Turn on the electric and the gas. Relight, following the instructions on the heater. Check for gas leaks using a commercial leak detecting fluid or a rich soap and water solution. Leaks are indicated by the presence of bubbles. Check all connections. If a leak cannot be stopped by tightening, replace the part. 7. Adjust the manifold pressure. Follow requirements and instructions in ) through 7) below to adjust manifold gas pressure. ) The correct pressure adjustment depends on the area of the country in terms of elevation. If you don t know the elevation, check with your local gas company. Form CP-UD-GC, P/N 97209R8, page 5

Gas Conversion Instructions (cont d) 7. Adjust the manifold pressure. (cont d) TABLE 2 - Manifold Pressures by Altitude WARNING: Manifold gas pressure must never exceed 3.5 w.c. for natural gas or 0 w.c. for propane. 2) See TABLE 2 and determine the required manifold pressure. Feet Manifold Pressure Settings by Altitude for the UNITED STATES Altitude Natural Gas (inches w.c.) Propane (inches w.c.) Meters Single Stage and Two Stage High Fire Two Stage Low Fire Single Stage and Two Stage High Fire Two Stage Low Fire 0-2000 0-60 3.5.8 0.0 5.0 200-3000 6-95 3..6 8.8 4.4 300-4000 96-220 3.0.5 8.5 4.2 400-5000 22-525 2.8.5 8. 4. 500-6000 526-830 2.7.4 7.7 3.9 600-7000 83-235 2.6.3 7.4 3.7 700-8000 236-2440 2.5.3 7. 3.5 800-9000 244-2745 2.4.2 6.7 3.4 900-0000 2746-3045 2.3.2 6.7 3.4 Feet Manifold Pressure Settings by Altitude for CANADA Altitude Natural Gas (inches w.c.) Propane Gas (inches w.c.) Meters Single Stage and Two Stage High Fire Two Stage Low Fire Single Stage and Two Stage High Fire Two Stage Low Fire 0-2000 0-60 3.5.8 0.0 5.0 200-4500 6-373 2.8.5 8. 4. 3) See FIGURE 4 and locate the /8 outlet pressure tap on the valve. Turn the knob on the top of the valve to OFF. Connect a manometer to the /8 pipe outlet pressure tap in the valve. Use a water column manometer that is readable to the nearest tenth of an inch. (NOTE: A manometer (fluid-filled gauge) is recommended rather than a spring type gauge due to the difficulty of maintaining calibration of a spring type gauge.) 4) Single Stage and Two Stage High Fire - Turn the knob on the top of the valve to ON. Remove the cap from the pressure adjusting screw and adjust the manifold pressure to the pressure selected from TABLE 2. Adjust pressure by turning the regulator screw IN (clockwise) to increase pressure or OUT (counterclockwise) to decrease pressure. Two Stage Low Fire - Disconnect the wire from the HI terminal on the gas valve and check the low fire pressure. Turn the regulator screw to adjust the low fire outlet pressure to the Low Fire pressure selected from TABLE 2. Re-connect the wire to the gas valve. CAUTION: DO NOT bottom out the gas valve regulator adjusting screw. This can result in unregulated manifold pressure causing excess overfire and heat exchanger failure. 5) Turn up the thermostat. On Models UDAS and UDBS, depress and hold the safety door switch. Cycle the burner once or twice to properly seat the adjustment spring in the valve. Re-check the pressure(s). When the outlet pressure is right for the installation, remove the manometer and replace the cap. Check for leakage at the pressure tap fitting. Form CP-UD-GC, P/N 97209R8, page 6

FIGURE 4 - Top View of Valves identifying Pressure Taps and Adjustment Screws Single-Stage Valve Inlet Pressure Tap Two-Stage Valve /8 Outlet Pressure Tap Inlet Pressure Tap /8 Outlet Pressure Tap Outlet Pressure Adjustment Screw Adjust Low Fire Outlet Pressure Adjust High Fire Outlet Pressure 6) With the heater operating, determine that the inlet pressure to the heater is between 5 and 3.5 inches w.c. for natural gas or between 0 and 3.5 inches w.c. for propane gas. Take this reading as close as possible to the heater. (The gas valves have an inlet pressure tap; see FIGURE 4.) If the inlet pressure is not within the specified range, the inlet pressure must be corrected and the manifold (outlet) pressure re-checked. 7) If the gas valve has been adjusted for operation above 2000 ft, find the High Altitude Adjustment label in the kit. Using a permanent marker, fill-in the appropriate information from TABLE 3A, page, for UDAP or UDAS or TABLE 3B, page 2, for UDBP or UDBS. Select a location for the label on the outside of the heater access panel so that it will be conspicuous to anyone operating or servicing the unit. Be sure the surface is clean and dry and adhere the label. (NOTE: At altitudes from 0-2000ft/0-60M, this label is not used.) 8. Check for safe and proper operation of the heater by observing operation for at least one complete cycle. (NOTE: Models UDAS and UDBS, depress and hold the safety door switch.) 9. Fill in the information required on the gas conversion tape. Select a location near the rating plate. Be sure the surface is clean and dry and affix the tape to the heater. Close the access door. Form CP-UD-GC, P/N 97209R8, page 7

Application and Components P/N 20727 Applies to: Models UDAP, UDAS Sizes 30 and 45 98720 Regulator Spring Conversion Kit for a SINGLE STAGE Valve, Honeywell #39369 96844 SIZE 30, Burner Orifice,.6mm 96845 SIZE 45, Burner Orifice, #48 96687 Primary Air Restrictor, -3/8 (35mm) diameter opening 6439 Conversion Tape 37752 Propane Disk 97062 2000ft/60M only) P/N 202936 Applies to: Models UDBP, UDBS Sizes 30 and 45 98720 Regulator Spring Conversion Kit for a SINGLE STAGE Valve, Honeywell #39369 96844 SIZE 30, Burner Orifice,.6mm 96845 SIZE 45, Burner Orifice, #48 203078 Primary Air Restrictor, -3/6 (30mm) diameter opening 6439 Conversion Tape 37752 Propane Gas Disk 97062 2000ft/60M only) P/N 20728 Applies to: Models UDAP, UDAS Sizes 60 and 75 98720 Regulator Spring Conversion Kit for a SINGLE STAGE Valve, Honeywell #39369 97207 STAGE Valve, Honeywell #39602 96846 SIZE 60, Burner Orifice, 2.3mm 96852 SIZE 75, Burner Orifice, #39 96688 Primary Air Restrictor, -3/4 (44mm) diameter opening 6439 Conversion Tape 37752 Propane Disk 97062 2000ft/60M only) Form CP-UD-GC, P/N 97209R8, page 8 Natural TO Propane Kits for Models UDAP UDAS, UDBP, and UDBS P/N 202937 Applies to: Models UDBP, UDBS Sizes 60 and 75 98720 STAGE Valve, Honeywell #39369 97207 STAGE Valve, Honeywell #39602 96846 SIZE 60, Burner Orifice, 2.3mm 96852 SIZE 75, Burner Orifice, #39 20205 Primary Air Restrictor, -9/6 (40mm) diameter opening 6439 Conversion Tape 37752 Propane Disk 97062 2000ft/60M only) P/N 202938 Applies to: Models UDAP, UDAS, UDBP, UDBS Sizes 00 and 25 98720 STAGE Valve, Honeywell #39369 97207 STAGE Valve, Honeywell #39602 96854 SIZE 00, Burner Orifice, 3.0mm 96847 SIZE 25, Burner Orifice, 3.2mm 96688 Primary Air Restrictor, -3/4 (44mm) diameter opening (Do not use restrictor on UDAP and UDAS 25.) 6439 Conversion Tape 37752 Propane Disk 97062 2000ft/60M only)

Application and Components (cont d) Natural TO Propane Kits for Models UDAP UDAS, UDBP, and UDBS (cont d) P/N 20730 Applies to: Models UDAP, UDAS, UDBP, UDBS Sizes 50 and 75 98720 STAGE Valve, Honeywell #39369 97207 STAGE Valve, Honeywell #39602 96898 SIZE 50, Burner Orifice, 9/64 96899 SIZE 75, Burner Orifice, #24 96688 Primary Air Restrictor, -3/4 (44mm) diameter opening (Use restrictor on Size 50 only.) 6439 Conversion Tape 37752 Propane Disk 97062 2000ft/60M only) P/N 20732 Applies to: Models UDAP, UDAS, UDBP, UDBS Sizes 300, 350, and 400 98720 STAGE Valve, Honeywell #39369 97207 STAGE Valve, Honeywell #39602 96903 SIZE 300, Burner Orifice, #8 96904 SIZE 350, Burner Orifice, #3 96905 SIZE 400, Burner Orifice, 5.8MM 6439 Conversion Tape 37752 Propane Disk 97062 2000ft/60M only) P/N 2073 Applies to: Models UDAP, UDAS, UDBP, UDBS Sizes 200, 225, and 250 98720 STAGE Valve, Honeywell #39369 97207 STAGE Valve, Honeywell #39602 96900 SIZE 200, Burner Orifice, 4.mm 9690 SIZE 225, Burner Orifice, /64 96902 SIZE 250, Burner Orifice, #4 6439 Conversion Tape 37752 Propane Disk 97062 2000ft/60M only) Form CP-UD-GC, P/N 97209R8, page 9

Application and Components (cont d) Propane TO Natural Conversion Kit P/N 20733 Applies to: Models UDAP, UDAS, UDBP, UDBS Sizes 30 and 45 9872 STAGE Valve, Honeywell #394588 96853 SIZE 30, Burner Orifice, #37 96838 SIZE 45, Burner Orifice, #30 6439 Conversion Tape 40 Natural Gas Disk 97062 2000ft/60M only) Propane TO Natural Conversion Kit P/N 20734 Applies to: Models UDAP, UDAS, UDBP, UDBS Sizes 60 and 75 9872 STAGE Valve, Honeywell #394588 97208 Form CP-UD-GC, P/N 97209R8, page 0 Propane TO Natural Kits for Models UDAP, UDAS, UDBP, and UDBS STAGE Valve, Honeywell #396205 96839 SIZE 60, Burner Orifice, 3.7mm 96855 SIZE 75, Burner Orifice, #9 6439 Conversion Tape 40 Natural Gas Disk 97062 2000ft/60M only) Propane TO Natural Conversion Kit P/N 20735 Applies to: Models UDAP, UDAS, UDBP, UDBS Sizes 00 and 25 9872 STAGE Valve, Honeywell #394588 97208 STAGE Valve, Honeywell #396205 2058 SIZE 00, Burner Orifice, #0 96840 SIZE 25, Burner Orifice, #4 6439 Conversion Tape 40 Natural Gas Disk 97062 2000ft/60M only) Propane TO Natural Conversion Kit P/N 20736 Applies to: Models UDAP, UDAS, UDBP, UDBS Sizes 50 and 75 9872 STAGE Valve, Honeywell #394588 97208 STAGE Valve, Honeywell #396205 358 SIZE 50, Burner Orifice, 5.9mm 9689 SIZE 75, Burner Orifice, E 6439 Conversion Tape 40 Natural Gas Disk 97062 2000ft/60M only) Propane TO Natural Conversion Kit P/N 20737 Applies to: Models UDAP, UDAS, UDBP, UDBS Sizes 200, 225, and 250 9872 STAGE Valve, Honeywell #394588 97208 STAGE Valve, Honeywell #396205 96892 SIZE 200, Burner Orifice, 6.8mm 222 SIZE 225, Burner Orifice, 6.95mm 208255 SIZE 250, Burner Orifice, L 6439 Conversion Tape 40 Natural Gas Disk 97062 2000ft/60M only) Propane TO Natural Conversion Kit P/N 20738 Applies to: Models UDAP, UDAS, UDBP, UDBS Sizes 300, 350, and 400 9872 STAGE Valve, Honeywell #394588 97208 STAGE Valve, Honeywell #396205 2222 SIZE 300, Burner Orifice, 8.0mm 2223 SIZE 350, Burner Orifice, 8.7mm 96897 SIZE 400, Burner Orifice, 9.6mm 6439 Conversion Tape 40 Natural Gas Disk 97062 2000ft/60M only)

TABLE 3A - s and Capacities by Altitude for Models UDAP and UDAS BTUH s and Capacities by Altitude in the UNITED STATES for Model UDAP and Model UDAS ALTITUDE Feet Meters Size 30 Size 45 Size 60 Size 75 0-2000 0-60 30000 24600 30000 45000 37350 45000 60000 49800 42000 75000 62250 52500 200-3000 6-95 28200 2324 28200 42300 3509 42300 56400 4682 39480 70500 5855 49350 300-4000 96-220 27600 22632 27600 4400 34362 4400 55200 4586 38640 69000 57270 48300 400-5000 22-525 27000 2240 27000 40500 3365 40500 54000 44820 37800 67500 56025 47250 500-6000 526-830 26400 2648 26400 39600 32868 39600 52800 43824 36960 66000 54780 46200 600-7000 83-235 25800 256 25800 38700 322 38700 5600 42828 3620 64500 53535 4550 700-8000 236-2440 25200 20664 25200 37800 3374 37800 50400 4832 35280 63000 52290 4400 800-9000 244-2745 24600 2072 24600 36900 30627 36900 49200 40836 34440 6500 5045 43050 900-0000 2746-3045 24000 9680 24000 36000 29880 36000 48000 39840 33600 60000 49800 42000 Feet Meters Size 00 Size 25 Size 50 Size 75 0-2000 0-60 05000 88200 73500 20000 00800 84000 50000 24500 05000 75000 45250 22500 200-3000 6-95 98700 82908 69090 2800 94752 78960 4000 7030 98700 64500 36535 550 300-4000 96-220 96600 844 67620 0400 92736 77280 38000 4540 96600 6000 33630 2700 400-5000 22-525 94500 79380 6650 08000 90720 75600 35000 2050 94500 57500 30725 0250 500-6000 526-830 92400 7766 64680 05600 88704 73920 32000 09560 92400 54000 27820 07800 600-7000 83-235 90300 75852 6320 03200 86688 72240 29000 07070 90300 50500 2495 05350 700-8000 236-2440 88200 74088 6740 00800 84672 70560 26000 04580 88200 47000 2200 02900 800-9000 244-2745 8600 72324 60270 98400 82656 68880 23000 02090 8600 43500 905 00450 900-0000 2746-3045 84000 70560 58800 96000 80640 67200 20000 99600 84000 40000 6200 98000 Feet Meters Size 200 Size 225 Size 250 Size 300 0-2000 0-60 200000 66000 40000 225000 86750 57500 250000 207500 75000 300000 249000 20000 200-3000 6-95 88000 56040 3600 2500 75545 48050 235000 95050 64500 282000 234060 97400 300-4000 96-220 84000 52720 28800 207000 780 44900 230000 90900 6000 276000 229080 93200 400-5000 22-525 80000 49400 26000 202500 68075 4750 225000 86750 57500 270000 22400 89000 500-6000 526-830 76000 46080 23200 98000 64340 38600 220000 82600 54000 264000 2920 84800 600-7000 83-235 72000 42760 20400 93500 60605 35450 25000 78450 50500 258000 2440 80600 700-8000 236-2440 68000 39440 7600 89000 56870 32300 20000 74300 47000 252000 20960 76400 800-9000 244-2745 64000 3620 4800 84500 5335 2950 205000 7050 43500 246000 20480 72200 900-0000 2746-3045 60000 32800 2000 80000 49400 26000 200000 66000 40000 240000 99200 68000 Feet Meters Size 350 Size 400 0-2000 0-60 350000 290500 245000 400000 332000 280000 200-3000 6-95 329000 273070 230300 376000 32080 263200 300-4000 96-220 322000 267260 225400 368000 305440 257600 400-5000 22-525 35000 26450 220500 360000 298800 252000 500-6000 526-830 308000 255640 25600 352000 29260 246400 600-7000 83-235 30000 249830 20700 344000 285520 240800 700-8000 236-2440 294000 244020 205800 336000 278880 235200 800-9000 244-2745 287000 23820 200900 328000 272240 229600 900-0000 2746-3045 280000 232400 96000 320000 265600 224000 ALTITUDE BTUH s and Capacities by Altitude in CANADA for Models UDAP and UDAS Feet Meters Size 30 Size 45 Size 60 Size 75 0-2000 0-60 30000 24600 30000 45000 37350 45000 60000 49800 42000 75000 62250 52500 200-4500 6-373 27000 2240 27000 40500 3365 40500 54000 44820 37800 67500 56025 47250 Feet Meters Size 00 Size 25 Size 50 Size 75 0-2000 0-60 05000 88200 73500 20000 00800 84000 50000 24500 05000 75000 45250 22500 200-4500 6-373 94500 79380 6650 08000 90720 75600 35000 3400 94500 57500 32300 0250 Feet Meters Size 200 Size 225 Size 250 Size 300 0-2000 0-60 200000 66000 40000 225000 86750 57500 250000 207500 75000 300000 249000 20000 200-4500 6-373 80000 5200 26000 202500 7000 4750 225000 89000 57500 270000 226800 89000 Feet Meters Size 350 Size 400 0-2000 0-60 350000 290500 245000 400000 332000 280000 200-4500 6-373 35000 264600 220500 360000 302400 252000 Form CP-UD-GC, P/N 97209R8, page

TABLE 3B - s and Capacities by Altitude for Models UDBP and UDBS ALTITUDE BTUH s and Capacities by Altitude in the UNITED STATES for Models UDBP and UDBS Feet Meters Size 30 Size 45 Size 60 Size 75 0-2000 0-60 30000 24600 30000 45000 36900 45000 60000 49200 42000 75000 6500 52500 200-3000 6-95 28200 2324 28200 42300 34686 42300 56400 46248 39480 70500 5780 49350 300-4000 96-220 27600 22632 27600 4400 33948 4400 55200 45264 38640 69000 56580 48300 400-5000 22-525 27000 2240 27000 40500 3320 40500 54000 44280 37800 67500 55350 47250 500-6000 526-830 26400 2648 26400 39600 32472 39600 52800 43296 36960 66000 5420 46200 600-7000 83-235 25800 256 25800 38700 3734 38700 5600 4232 3620 64500 52890 4550 700-8000 236-2440 25200 20664 25200 37800 30996 37800 50400 4328 35280 63000 5660 4400 800-9000 244-2745 24600 2072 24600 36900 30258 36900 49200 40344 34440 6500 50430 43050 900-0000 2746-3045 24000 9680 24000 39600 32472 39600 48000 39360 33600 60000 49200 42000 Feet Meters Size 00 Size 25 Size 50 Size 75 0-2000 0-60 05000 8750 73500 20000 99600 84000 50000 24500 05000 75000 45250 22500 200-3000 6-95 98700 892 69090 2800 93624 78960 4000 7030 98700 64500 36535 550 300-4000 96-220 96600 8078 67620 0400 9632 77280 38000 4540 96600 6000 33630 2700 400-5000 22-525 94500 78435 6650 08000 89640 75600 35000 2050 94500 57500 30725 0250 500-6000 526-830 92400 76692 64680 05600 87648 73920 32000 09560 92400 54000 27820 07800 600-7000 83-235 90300 74949 6320 03200 85656 72240 29000 07070 90300 50500 2495 05350 700-8000 236-2440 88200 73206 6740 00800 83664 70560 26000 04580 88200 47000 2200 02900 800-9000 244-2745 8600 7463 60270 98400 8672 68880 23000 02090 8600 43500 905 00450 900-0000 2746-3045 84000 69720 58800 96000 79680 67200 20000 99600 84000 40000 6200 98000 Feet Meters Size 200 Size 225 Size 250 Size 300 0-2000 0-60 200000 66000 40000 225000 86750 57500 250000 207500 75000 300000 249000 20000 200-3000 6-95 88000 56040 3600 2500 75545 48050 235000 95050 64500 282000 234060 97400 300-4000 96-220 84000 52720 28800 207000 780 44900 230000 90900 6000 276000 229080 93200 400-5000 22-525 80000 49400 26000 202500 68075 4750 225000 86750 57500 270000 22400 89000 500-6000 526-830 76000 46080 23200 98000 64340 38600 220000 82600 54000 264000 2920 84800 600-7000 83-235 72000 42760 20400 93500 60605 35450 25000 78450 50500 258000 2440 80600 700-8000 236-2440 68000 39440 7600 89000 56870 32300 20000 74300 47000 252000 20960 76400 800-9000 244-2745 64000 3620 4800 84500 5335 2950 205000 7050 43500 246000 20480 72200 900-0000 2746-3045 60000 32800 2000 80000 49400 26000 200000 66000 40000 240000 99200 68000 Feet Meters Size 350 Size 400 0-2000 0-60 350000 290500 245000 400000 328000 280000 200-3000 6-95 329000 273070 230300 376000 308320 263200 300-4000 96-220 322000 267260 225400 368000 30760 257600 400-5000 22-525 35000 26450 220500 360000 295200 252000 500-6000 526-830 308000 255640 25600 352000 288640 246400 600-7000 83-235 30000 249830 20700 344000 282080 240800 700-8000 236-2440 294000 244020 205800 336000 275520 235200 800-9000 244-2745 287000 23820 200900 328000 268960 229600 900-0000 2746-3045 280000 232400 96000 320000 262400 224000 ALTITUDE BTUH s and Capacities by Altitude in CANADA for Models UDBP and UDBS Feet Meters Size 30 Size 45 Size 60 Size 75 0-2000 0-60 30000 24600 30000 45000 36900 45000 60000 49200 42000 75000 6500 52500 200-4500 6-373 27000 2240 27000 40500 3320 40500 54000 44280 37800 67500 55350 47250 Feet Meters Size 00 Size 25 Size 50 Size 75 0-2000 0-60 05000 8750 73500 20000 99600 84000 50000 24500 05000 75000 45250 22500 200-4500 6-373 0500 8750.8 7350 08000 89640 75600 35000 3400 94500 57500 32300 0250 Feet Meters Size 200 Size 225 Size 250 Size 300 0-2000 0-60 200000 66000 40000 225000 86750 57500 250000 207500 75000 300000 249000 20000 200-4500 6-373 80000 5200 26000 202500 7000 4750 225000 89000 57500 270000 226800 89000 Feet Meters Size 350 Size 400 0-2000 0-60 350000 290500 245000 400000 328000 280000 200-4500 6-373 35000 264600 220500 360000 295200 252000 Form CP-UD-GC, P/N 97209R8, page 2 www.rezspec.com; (800) 695-90 200 Thomas & Betts, All rights reserved. Trademark Notes: Reznor is a trademark of Thomas & Betts. All other trademarks are the property of their respective owners. 9/0 Form CP-UD-GC (Version.)