MAINTENANCE & ASSEMBLY INSTRUCTIONS FUSIBLE LINK. Inline Thermal Check Valve

Similar documents
INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Model Sanitary Vent SECTION I

INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Model Gauge Hatch SECTION I SECTION II

INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Model Pressure Vacuum Thief Hatch & Combo. Gauge Hatch SECTION I

Model Secure-Gard Pilot Operated Vent Valve SECTION II. Remove all packing material inside and outside of the valve prior to installation.

Model 3400 IOM Pressure Relief Vent SECTION I I SERIES DESIGN AND FUNCTION INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Model 3600 IOM Vacuum Relief Vent Side-Mounted Connection SECTION I I SERIES DESIGN AND FUNCTION

Model Vacu-Gard Blanketing Valve SECTION I I. DESCRIPTION AND SCOPE SECTION II II. PRIOR TO INSTALLATION SECTION III III.

Model 3100 IOM Pressure / Vacuum Relief Vent SECTION I I SERIES DESIGN AND FUNCTION INSTALLATION, OPERATION AND MAINTENANCE MANUAL

MODEL 345 PRESSURE REDUCING REGULATOR SECTION I I. DESCRIPTION AND SCOPE SECTION II II. INSTALLATION CAUTION CAUTION CAUTION IOM

INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM) MODEL B2 BACK PRESSURE REGULATOR. SECTION l

MODEL P5 PISTON SENSING SINGLE STAGE PRESSURE REDUCING REGULATOR SECTION I

MODEL C-CS CLEAN STEAM

Model TB 3-16 TECHNICAL BULLETIN. Secure-Gard Pilot Operated Vent Valve (POVV) BENEFITS TYPICAL APPLICATIONS FEATURES

Model 5200 Pilot Operated Pressure / Vacuum Relief Vent w/ Pipeaway Connection

MODEL SAP ULTRA HIGH PURITY, PRESSURE LOADED PRESSURE REDUCING REGULATOR SECTION I I. DESCRIPTION AND SCOPE II. REFERENCES SECTION II SECTION III

Model 5400 Pilot Operated Pressure Relief Vent

Pressure Regulators. Operating Instructions. Instrumentation

INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM) MODEL BQ BACK PRESSURE / RELIEF REG U LA TOR SECTION I

Model 5100 Pilot Operated Pressure / Vacuum Relief Vent End-of-line

MODELS CA-1 AND CA-2

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

Temperature Controllers

MODEL 1465 PRESSURE REDUCING REGU LA TOR SECTION I

INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM) MODEL 31-B. Back Pressure Relief Service Regulator SECTION I

PRESSURE RE DUC ING REGULATOR

64 Series Pressure Reducing Regulators

623 Series Dome Load Regulators

Float Operated Level Controllers

Operation Manual. Diaphragm Sensed Gas Pressure Regulators

Types 749B and R130 Changeover Manifolds

1805 Series Relief Valves

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

Operation Manual Piston Sensed Gas Pressure Regulators

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

MODELS D and DL PRESSURE REDUCING REGULATORS

MODELS 8311HP AND 8311LP

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

Pilot HON 625. Entwurf. Product information. serving the gas industry worldwide

1805 Series Relief Valves

Model 3100 TECHNICAL BULLETIN TB Pressure / Vacuum Vent End-of-Line

Types S100K and S102K Pressure Regulators

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

PRESSURE REDUCING REG U LA TORS

Tri-Safem Model I1 Regulator. INSTRUCTIONS and PARTS

PRO-50 Instrument Supply Regulator

MODELS 8310HP DIFFERENTIAL

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

MEGR-1912 Instruction Manual

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

Filling valves AL, ALM Series Automatic filling units ALOMDIW, ALOMDNW Series

MODEL DA0. DIRECT-ACTING, PRESSURE LOADED PRESSURE REDUCING REGULATOR for STEAM APPLICATIONS SECTION I

WW-730. Pressure Sustaining/Relief Control Valve

INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM) MODEL HP-1+6+S HIGH PRESSURE DIFFERENTIAL REDUCING REG U LA TOR SECTION I SECTION II

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

Type 0404 / /2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

453 Series Steam Heated Vaporizing Regulator

61 Series Pilots for Pilot-Operated Pressure Reducing Regulators

Installation, Operation, and Maintenance Manual

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

SINGLE STAGE ULTRA-HIGH PRESSURE REDUCING REGULATOR INSTALLATION AND OPERATION INSTRUCTIONS. Certified ISO 9001

MEGR-1627 Instruction Manual

Model Application TECHNICAL BULLETIN TB Vacu-Gard Tank Blanketing Valve 1 & 2 (DN25 & DN50) FEATURES

Operating Manual. R280 Pressure regulator made of brass. 1. Intended Use

Gas Pressure Regulator HON 300

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

Mooney * Noise Controller Installation, Operation, and Maintenance Manual

HIGH PRESSURE REGULATOR PACKAGES

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

GAS SUPPLY APPLICATION GUIDE

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

RESIDENTIAL REGULATORS

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

INSTRUCTIONS FOR MODEL SSC LOW DELIVERY PRESSURE GAS REGULATORS

TECHNICAL DATA. than the water inlet pressure to the concentrate

INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM) MODEL 31-N. Pressure Reducing Service Regulator SECTION I

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

R122H, R222, R232A, and R232E Series Instruction Manual

High Pressure Inlet Kits for CONCOA BlendMites and BlendMasters

ANDERSON GREENWOOD SERIES 9000 POSRV INSTALLATION AND MAINTENANCE INSTRUCTIONS

INSTRUCTIONS FOR FM4460N SERIES HIGH PRESSURE, METAL TUBE FLOWMETERS

1200B2 Series Service Regulators. Instruction Manual

Safety Relief Valve HON 832

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

Yoke Block Instruction Manual

Protocol Switchover Station

R600 and HSRL Series Instruction Manual

Installation and commissioning instructions 255 series and 256 series

Model Application TB TECHNICAL BULLETIN. Vacu-Gard Tank Blanketing Valve 1/2 (DN15) FEATURES

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

Yoke Block Instruction Manual

INSTRUCTIONS FOR SINGLE STAGE LECTURE BOTTLE REGULATORS

GM-7000 Series CE Approved Gas Control Valve

Transcription:

MAINTENANCE & ASSEMBLY INSTRUCTIONS IOM-FL 12-16 ISO Registered Company FUSIBLE LINK Inline Thermal Check Valve MODEL FL-200 REFERENCE DATA: FL-200 Series Assembly Drawing No. A88-60200-00. INSTALLATION: 1. Clean the piping of all foreign material including chips, welding scale, oil, grease and dirt before installing the thermal trip valve. 2. In placing thread sealant on pipe ends prior to engagement, ensure that excess material is removed and not allowed to enter the thermal trip valve upon startup. 3. Flow Direction: Install so the flow direction matches the flow arrow on the body of the thermal trip valve. PRINCIPLE OF OPERATION: 1. When the valve is installed it is open. 2. This valve will stay open until it is actuated by the fusible link. 3. This will cause the valve to close. MAINTENANCE: 1. All valves are leak tested at the factory at 200 PSIG and should be externally leak tight after installation. If after pro longed ser vice the valve should leak externally, it is recommended that the valve be replaced or sent to the factory for rebuilding.

THERMAL CHECK VALVE FL-200 SERIES Fusible Link NOTES: 1. Maximum pressure rating 130 psig (896 kpa) WOG. 2. No changes shall be made to parts, material or manufacturing process without prior ap prov al by Factory Mutual Research Corporation. 3. All valves to be assembled, inspected and test ed in strict accordance with Cashco Standard S-1549. 4. Link shown 17 out of position. 2 IOM-FL

FUSIBLE LINK Barstock Thermal Shutoff Valves MODEL FL-800 S and V REFERENCE DATA: FL-800 Series Assembly Drawing No. A66-60800-00, A66-60800-01, A66-60800-02 & A66-60800-03. INSTALLATION: 1. Clean the piping of all foreign material including chips, welding scale, oil, grease and dirt before installing the thermal trip valve. 2. In placing thread sealant on pipe ends prior to engagement, ensure that excess material is removed and not allowed to enter the thermal trip valve upon startup. 3. Flow Direction: Install so the flow direction matches the flow arrow on the body of the thermal trip valve. PRINCIPLE OF OPERATION: 1. When the valve is installed it is open. 2. This valve will stay open until it is actuated by the fusible link. 3. This will cause the valve to close. MAINTENANCE: 1. All valves are leak tested at the factory at 450 psig and should be externally leak tight after installation. If after prolonged ser vice the valve should leak externally, it is recommended the valve be replaced or sent to the factory for rebuilding. IOM-FL 3

BARSTOCK THERMAL SHUT-OFF VALVES FL-800 SERIES Fusible Link Type S (Standard) View 2 View 1 Fusible Link Type V (Vented) View 3 NOTES: 1. Maximum pressure rating 300 psig (2069 kpa) WOG. 2. Type S (Standard) Shut-off valve will not allow venting of downstream line after valve has ac tu at ed. 3. Type V (Vent) Shut-off valve will allow venting of downstream line. 4. No changes shall be made to parts, materials or manufacturing process without prior approval by Factory Mutual Research Corporation. 5. All valves to be assembled, inspected and test ed in strict accordance with Cashco standard S-1668. 4 IOM-FL

ATEX 94/9/EC: Explosive Atmospheres and Cashco Inc. Regulators NOTICE Only for Product Codes wherein hazard category ATEX has been selected. These valves satisfy the safety conditions according to EN 13463-1 and EN 13463-5 for equipment group IIG 2 c. Caution: Because the actual maximum temperature depends not on the equipment itself, but upon the fluid temperature, a single temperature class or temperature cannot be marked by the manufacturer. Specific Precaution to Installer: Electrical grounding of valve must occur to minimize risk of effective electrical discharges. Specific Precaution to Installer: Atmosphere vent holes should be plugged to further minimize the risk of explosion. Specific Precaution to Maintenance: The Valve Body/ Housing must be regularly cleaned to prevent buildup of dust deposits. Specific Precaution to Maintenance: Conduct periodic Continuity Check between Valve Body/ Housing and Tank to minimize risk of electrical discharges. Attention: When repairing or altering explosion-protected equipment, national regulations must be adhered to. For maintenance and repairs involving parts, use only manufacturer's original parts. ATEX requires that all components and equipment be evaluated. Cashco pressure regulators are considered components. Based on the ATEX Directive, Cashco considers the location where the pressure regulators are installed to be classified Equipment-group II, Category 3 because flammable gases would only be present for a short period of time in the event of a leak. It is possible that the location could be classified Equipment-group II, Category 2 if a leak is likely to occur. Please note that the system owner, not Cashco, is responsible for determining the classification of a particular installation. Product Assessment Cashco performed a conformity assessment and risk analysis of its pressure regulator and control valve models and their common options, with respect to the Essential Health and Safety Requirements in Annex II of the ATEX directive. The details of the assessment in terms of the individual Essential Health and Safety Requirements, are listed in Table 1. Table 2 lists all of the models and options that were evaluated and along with their evaluation. Models and options not listed in Table 2 should be assumed to not have been evaluated and therefore should not be selected for use in a potentially explosive environment until they have been evaluated. Standard default options for each listed model were evaluated even if they were not explicitly listed as a separate option in the table. Not all options listed in the tables are available to all models listed in the tables. Individual TB s must be referenced for actual options. When specifying a regulator that is to be used in a potentially explosive environment one must review the evaluations in Table 1 and 2 for the specific model and each and every option that is being specified, in order to determine the complete assessment for the unit. A summary of the models and options found to have an impact on ATEX assessment due to potential ignition sources or other concerns from the ATEX Essential Health and Safety Requirements, are listed below. 1. The plastic knob used as standard on some models, (P1, P2, P3, P4, P5, P7, 3381, 4381, 1171, and 2171) is a potential ignition source due to static electricity. To demonstrate otherwise, the knob must be tested to determine if a transferred charge is below the acceptable values in IEC 60079-0 Section 26.14 (See items 25, 27, and 28 in Appendix A). Until the plastic knob has been shown to be acceptable, then either the metal knob option, or a preset outlet pressure option is required to eliminate this ignition source (See items 45 and 64 in Tables). 2. The pressure gauges offered as options on a few of the regulator models (DA s, P1-7, D, 764, 521), use a plastic polycarbonate window that is a potential ignition source due to static electricity. To demonstrate that the gauges are not a potential source of ignition, the gauges would need to be tested to determine if a transferred charge is below

indicating the gauge is compliant with the ATEX Directive (See items 26, 27, and 28 in Appendix A). Until compliance is determined, regulators should not be ordered with pressure gauges for use in potentially explosive environments. 3. Tied diaphragm regulators with outlet ranges greater than 100 psig should be preset to minimize the risk that improper operation might lead to an outboard leak and a potentially explosive atmosphere (See item 6 in Table 1). 4. Regulators must be ordered with the non-relieving option (instead of the self-relieving option) if the process gas they are to be used with is hazardous (flammable, toxic, etc.). The self-relieving option vents process gas through the regulator cap directly into the atmosphere while the non-relieving option does not. Using regulator with the self- relieving option in a flammable gas system could create an explosive atmosphere in the vicinity of the regulator. 5. Regulators with customer supplied parts are to be assumed to not have been evaluated with regard to ATEX and thus are not to be used in a potentially explosive environment unless a documented evaluation for the specific customer supplied parts in question has been made. Refer to Table 1 for all models and options that have been evaluated. Product Usage A summary of ATEX related usage issues that were found in the assessment are listed below. 1. Pressure regulators and control valves must be grounded (earthed) to prevent static charge build-up due to the flowing media. The regulator can be grounded through any mounting holes on the body with metal to metal contact or the system piping can be grounded and electrical continuity verified through the body metal seal connections. Grounding of the regulator should follow the same requirements for the piping system. Also see item 30 in Table 1. 2. The system designer and users must take precautions to prevent rapid system pressurization which may raise surface temperatures of system components and tubing due to adiabatic compression of the system gas. 3. Heating systems installed by the user could possibly increase the surface temperature and must be evaluated by the user for compliance with the ATEX Directive. User installation of heating systems applied to the regulator body or system piping that affects the surface temperature of the pressure regulator is outside the scope of this declaration and is the responsibility of the user. 4. The Joule-Thomson effect may cause process gases to rise in temperature as they expand going through a regulator. This could raise the external surface temperature of the regulator body and downstream piping creating a potential source of ignition. Whether the Joule-Thomson effect leads to heating or cooling of the process gas depends on the process gas and the inlet and outlet pressures. The system designer is responsible for determining whether the process gas temperature may rise under any operating conditions. If a process gas temperature rise is possible under operating conditions, then the system designer must investigate whether the regulator body and downstream piping may increase in temperature enough to create a potential source of ignition. The process gas expansion is typically modeled as a constant enthalpy throttling process for determining the temperature change. A Mollier diagram (Pressure Enthalpy diagram with constant temperature, density, & entropy contours) or a Temperature Entropy diagram with constant enthalpy lines, for the process gas, can be used to determine the temperature change. Helium and hydrogen are two gases that typically increase in temperature when expanding across a regulator. Other gases may increase in temperature at sufficiently high pressures. Product Declaration If the above issues are addressed by selecting options that do not have potential sources of ignition, avoiding options that have not been assessed, and by taking the proper usage issue precautions, then Cashco regulators can be considered to be a mechanical device that does not have its own source of ignition and thus falls outside the scope of the ATEX directive. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifi cations of such product at any time without notice. Cashco, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Cashco, Inc. product remains solely with the purchaser. Cashco, Inc. P.O. Box 6 Ellsworth, KS 67439-0006 PH (785) 472-4461 Fax. # (785) 472-3539 www.cashco.com email: sales@cashco.com Printed in U.S.A. FL-IOM Cashco GmbH Handwerkerstrasse 15 15366 Hoppegarten, Germany PH +49 3342 30968 0 Fax. No. +49 3342 30968 29 www.cashco.com email: germany@cashco.com Cashco do Brasil, Ltda. Al.Venus, 340 Indaiatuba - Sao Paulo, Brazil PH +55 11 99677 7177 Fax. No. www.cashco.com email: brazil@cashco.com