TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

Similar documents
DF1 and DF2 Diffusers

TSS21 Sealed Thermostatic Steam Tracer Trap

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

Dri-Line Mk3 Monnier Compressed Air Drain Trap

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

PV4 and PV6 Piston Valves

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

AVC32 Carbon Steel Air Vent for Steam Systems

TP1 and TP2 Temporary Cone Shaped Strainers

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

AVM7 Stainless Steel Thermostatic Air Vent

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

MF2M Monnier Miniature Compressed Air Filter

CVS10 Sanitary Check Valves

DCV6 Disc Check Valve

CP10 Sensor Installation and Maintenance Instructions

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

CA44, CA44S, CA46 and CA46S Air and Gas Traps

Airodyn, BRair and BRoil Compressed Air Drain Traps

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

ML3M Monnier Miniature Compressed Air Lubricator

FV Flash Vessel Installation and Maintenance Instructions

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

S and SF Inverted Bucket Steam Traps

APT14, APT14HC and APT14SHC Spares 2

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

TW Temperature Control Valve

Manual Actuated Boiler Blowdown Valves

BPT13 Balanced Pressure Thermostatic Steam Traps

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

CA10S, CA14 and CA14S Air and Gas Traps

BCV31 DN40 - Blowdown Control Valve

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

SRV66 Sanitary Pressure Reducing Valve

CS10-1 Stainless Steel Clean Steam Separator

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

Spirax Compact FREME Flash Recovery Energy Management Equipment

PC10HP Pipeline Connector (ASME 600)

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

Thermocirc Installation and Maintenance Instructions

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

MFP14-PPU (Vented) Automatic Packaged Pump Units

SRV2S Pressure Reducing Valve

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

BRV71 and BRV73 Pressure Reducing Valves

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

SCA Series Inverted Bucket Steam Traps

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

BCV31 DN20 - Blowdown Control Valve

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

BDV1 and BDV2 Blowdown / Depressurisation Valves

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

Vane Flow Switches Colima FLU Series

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

QuickHeat TM Packaged Heat Exchanger Solutions

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

M111 Spiraflo Transducer

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

BCVi43 Blowdown Control Valve

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

BDV60 Blowdown Vessel Installation and Maintenance Instructions

LP10-4 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance IM-P402-92

Colima TOR Magnetic Level Switches

BSA and BSAT Bellows Sealed Stop Valves Installation and Maintenance Instructions

595-K/L and 596-K/L Series Self Operated Valves Installation and Maintenance Instructions

Transcription:

3500032/2 IM-P350-02 CH Issue 2 TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Operation 6. Spare parts and maintenance IM-P350-02 Printed in the CH UK Issue 2 Copyright 20041

1. Safety information Safe operation of these products can only be guaranteed if they are properly installed, commissioned, used and maintained by qualified personnel (see Section 1.11) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. 1.1 Intended use Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended use/application. The products comply with the requirements of the European Pressure Equipment Directive 97/23/EC and fall within category 'SEP'. It should be noted that products within this category are required by the directive not to carry the mark. i) The products have been specifically designed for use on steam, water, compressed air and other non-hazardous fluids which are in Group 2 of the above mentioned Pressure Equipment Directive. The products use on other fluids may be possible but, if this is contemplated, Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered. ii) Check material suitability, pressure and temperature and their maximum and minimum values. If the maximum operating limits of the product are lower than those of the system in which it is being fitted, or if malfunction of the product could result in a dangerous overpressure or overtemperature occurrence, ensure a safety device is included in the system to prevent such over-limit situations. iii) Determine the correct installation situation and direction of fluid flow. iv) Spirax Sarco products are not intended to withstand external stresses that may be induced by any system to which they are fitted. It is the responsibility of the installer to consider these stresses and take adequate precautions to minimise them. v) Remove protection covers from all connections before installation. 1.2 Access Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting to work on the product. Arrange suitable lifting gear if required. 1.3 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. 1.4 Hazardous liquids or gases in the pipeline Consider what is in the pipeline or what may have been in the pipeline at some previous time. Consider: flammable materials, substances hazardous to health, extremes of temperature. 1.5 Hazardous environment around the product Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive noise, moving machinery. 1.6 The system Consider the effect on the complete system of the work proposed. Will any proposed action (e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel at risk? Dangers might include isolation of vents or protective devices or the rendering ineffective of controls or alarms. Ensure isolation valves are turned on and off in a gradual way to avoid system shocks. 2 IM-P350-02 CH Issue 2

1.7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that the system has depressurised even when the pressure gauge indicates zero. 1.8 Temperature Allow time for temperature to normalise after isolation to avoid danger of burns. 1.9 Tools and consumables Before starting work ensure that you have suitable tools and/or consumables available. Use only genuine Spirax Sarco replacement parts. 1.10 Protective clothing Consider whether you and/or others in the vicinity require any protective clothing to protect against the hazards of, for example, chemicals, high/low temperature, radiation, noise, falling objects, and dangers to eyes and face. 1.11 Permits to work All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to the Installation and Maintenance Instructions. Where a formal 'permit to work' system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibility is safety. Post 'warning notices' if necessary. 1.12 Handling Manual handling of large and/or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. 1.13 Residual hazards In normal use the external surface of the product may be very hot. If used at the maximum permitted operating conditions the surface temperature of some products may reach temperatures of 350 C. Many products are not self-draining. Take due care when dismantling or removing the product from an installation (refer to 'Maintenance instructions'). 1.14 Freezing Provision must be made to protect products which are not self-draining against frost damage in environments where they may be exposed to temperatures below freezing point. 1.15 Disposal Unless otherwise stated in the Installation and Maintenance Instructions, this product is recyclable and no ecological hazard is anticipated with its disposal providing due care is taken. 1.16 Returning products Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination residues or mechanical damage which may present a health, safety or environmental risk. This information must be provided in writing including Health and Safety data sheets relating to any substances identified as hazardous or potentially hazardous. IM-P350-02 CH Issue 2 3

2. General product information Description The TA10A and TA10P are stainless steel self-powered temperature control valves, which have been specifically designed for steam tracing applications, but can also be used for other applications such as tank heating. Available types: TA10A For air temperature sensing. TA10P Immersion/remote sensor for product sensing. Note: the TA10P is supplied with a 1 m capillary tube for remote sensing. Temperature ranges: Range 1 0 C to 50 C (TA10A and TA10P) Range 2 20 C to 70 C (TA10P only) Note: The maximum temperature overrun is 50 C Technical data Proportional band 15 C Note: The TA10 is calibrated so that it is fully closed at set point. Sizes and pipe connections ½" and ¾" screwed BSP (BS 21 parallel) or NPT. Pressure / temperature limits Body design conditions PN25 PMA Maximum allowable pressure 25 bar g TMA Maximum allowable temperature 200 C Minimum allowable temperature 0 C PMO Maximum operating pressure 14.6 bar g for saturated steam service TMO Maximum operating temperature 200 C Minimum operating temperature 0 C Note: For lower operating temperatures consult Spirax Sarco. DPMX Maximum differential pressure 10 bar g Designed for a maximum cold hydraulic test pressure of: 38 bar g 4 IM-P350-02 CH Issue 2

TA10P TA10A Fig. 1 IM-P350-02 CH Issue 2 5

3. Installation Note: Before actioning any installation observe the 'Safety information' in Section 1. Isolation valve Pressure gauge Strainer Steam supply TA10A TA10P Sensor Steam trap Steam trap Fig. 2 Typical application 3.1 Ensure all pipework is cleaned out before installing the valve. It is recommended that a strainer is fitted before the valve (see Figure 2). 3.2 Ensure the valve is fitted with the flow arrow pointing in the right direction. 3.3 The valve bonnet should always lie below the centre line of the valve body - preferably vertically downwards. 3.4 For the TA10P version only, the capillary tube must always be installed with a degree of 'slack' so as not to restrict the overrun movement of the actuator. The sensor should be strapped to the outside of the pipe or vessel being controlled (see Figure 3). Sensor (TA10P) Strapped to product line Fig. 3 Sensor strapped to product line 3.5 Apart from the remote sensing bulb, do not insulate any part of the valve body to control system. 6 IM-P350-02 CH Issue 2

4. Commissioning It is accepted that all normally established safety procedures will be adhered to when operating steam systems. 4.1 Open the steam supply to the TA10 valve. 4.2 Allow the valve body to warm up for a period of approximately 30 minutes with steam passing. 4.3 With reference to Figure 4, screw the adjustment head all the way on (clockwise) until it contacts the stop face on the bonnet. This is the lowest temperature of the adjustment range. Screw back from the stop, at the rate of 20 C for one complete revolution or 30 C for each hexagon 'flat', the amount required to achieve the desired set temperature. Finer adjustment may be required once the conditions have stabilised at the required temperature. Finally lock the adjustment with the grub screw. 4.4 As an alternative to the procedure in Section 4.3 (Note: a test point or pressure gauge will be required): Gradually unscrew the adjustment head until the valve just begins to open (check test point). This setting then relates to the prevailing ambient or product temperature. Knowing the prevailing temperature, the control can then be readjusted to the required set temperature at the same rate as 4.3 above. Finer adjustment may be required once the conditions have stabilised at the required temperature. Finally lock the adjustment with the grub screw. Valve body Grub screw Adjustment head Stop face on the bonnet Fig. 4 5. Operation Raising the temperature of the sensor will cause the control system to expand thereby applying a closing force to the valve seat. Should the temperature continue to rise above the set point, an inbuilt overrun device will provide substantial protection for the control system. Cooling the sensor will cause the control system to contract allowing the valve to open under the control of a return spring. Should a leak develop in the control system the same return spring will ensure the valve fails in the open position. IM-P350-02 CH Issue 2 7

6. Spare parts and maintenance Spare parts The spare parts available are shown in solid outline. Parts drawn in broken line are not supplied as spares. Available spares Internal assembly Control system (State type and range) A, B, C D How to order spares Always order spares by using the description given in the column headed 'Available spares' and state the size and type of control. Example: 1 - Internal assembly for a Spirax Sarco ½" TA10P steam tracing temperature control valve. TA10 TA10P C B D D Fig. 5 A Maintenance Note: Before actioning any maintenance programme observe the 'Safety information' in Section 1. How to fit - Isolate the control and remove the control system by withdrawal of the grub screw from the adjustment head, followed by unscrewing the adjustment head from the valve. - Unscrew the pilot seal assembly (item A) from the bonnet. Do not remove from the bonnet unless the ball and spring (items B and C) cannot easily be withdrawn. - Replace with new parts. Apply proprietary sealing compound sparingly to threaded parts, and reassemble. Tighten to torques shown in Table 1. - Screw on the adjustment head of the control system and follow the procedure in Section 4 for bringing the temperature control valve back into service. Table 1 Recommended tightening torques Assembly items Torque N m Bonnet/ body 190 ± 10 Bellows seal assembly/ bonnet 115 ± 5 8 IM-P350-02 CH Issue 2