MEMORANDUM. NFPA Technical Committee on Lightning Protection Systems. NFPA 780 Supplement ROC TC FINAL Ballot Results (F2012Cycle)

Similar documents
An Update on IEC TC 81 (Lightning Protection)

VISUAL AIDS FOR DENOTING OBSTACLES

M E M O R A N D U M. NFPA Technical Committee on Fire Tests. NFPA 252 First Draft TC FINAL Ballot Results (F2016)

VISUAL AIDS FOR DENOTING OBSTACLES

IBC: 404.1, 404.9, , , , , , TABLE

Driveway Design Criteria

Part B: Airport Configurations

DISTRIBUTION: Electronic Recipients List TRANSMITTAL LETTER NO. (13-01) MINNESOTA DEPARTMENT OF TRANSPORTATION. MANUAL: Road Design English Manual

Amendment: To Return a portion of a Report in the form of an Identifiable Part of Proposal and related Comment 130-1

DETECTABLE WARNING SURFACES SHALL BE PROVIDED AT THE FOLLOWING LOCATIONS ON PEDESTRIAN ACCESS ROUTES:

Revisions to Larimer County Urban Area Street Standards (2016 Update)

dpd Seattle Permits Tip Getting a Grip on Handrails PURPOSE OF HANDRAILS

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

ADA Operations Contact Info

3-13 UFC - GENERAL PROVISIONS AND GEOMETRIC DESIGN FOR ROADS, STREETS, WALKS, AND OPEN

Field Design, Construction and inspection of ADA compliant Curb ramps. Mike Anderson City of Lee s Summit Construction Manager (816)

ADA Training Standard Plans

Field guide for Accessible Public Rights-of-Way Edition

TESTING APPLICATION STANDARD (TAS)

Developed by: The American Traffic Safety Services Association (ATSSA) 15 Riverside Parkway, Suite 100 Fredericksburg, VA

Revisions to the Regulations for Agility Trials

Chapter Twenty-eight SIGHT DISTANCE BUREAU OF LOCAL ROADS AND STREETS MANUAL

Designing Pedestrian Facilities for Accessibility. Module 3 Curb Ramps & Blended Transitions

October 2004 REVISIONS (2) SUPERELEVATION DEVELOPMENT 11.3(2)

Revision 7/2/02 MEASURING WRAVMA DRAWING DESIGNS WITH SCORING TEMPLATES

Figure 1: Graphical definitions of superelevation in terms for a two lane roadway.

Committee on NFPA 85

FIELD EVENTS DIAGRAMS

M E M O R A N D U M. Technical Committee on Respiratory Protection Equipment. NFPA 1989 First Draft Technical Committee FINAL Ballot Results (A2018)

September 2008 REVISIONS (1) SYMMETRICAL VERTICAL CURVE EQUATIONS 12.5(12) VERTICAL CURVE COMPUTATIONS 12.5(14) TURNING LANE LENGTHS 15.

TRAFFIC CONTROL DEVICES

Domed Ceilings and Barrel Vaults

GENERAL HEALTH AND SAFETY REQUIREMENTS

WFDF Official Rules of Flying Disc Sports Article III - Guts

The field of play must be rectangular and marked with lines. These lines belong to the areas of which they are boundaries.

Annex. Annex Annexe 10 XXXXXXXXXXXXXXX XXXXXXXX XXXXXXXXXXXXXXX. Aerodrome XXXXXXXX. XXXX Edition, 20XX. XXXX Edition, 20XX.

Trigonometry Problems

Check with local zoning official for property line distance requirements.

UPDATE ARLINGTON COUNTY. Bicycle Parking Standards

CHAPTER 16 PEDESTRIAN FACILITIES DESIGN AND TECHNICAL CRITERIA TABLE OF CONTENTS

ADA Design Overview. Section 2. ADA Design Overview. Pedestrian Access Routes. Pedestrian Access Routes. Overview

Sorcerer and Warlock

OPENINGS AND REINFORCEMENTS 26

Implementing Provisions for Art. 411 of the ICR Ski Jumping

DESIGN CRITERIA DIVISION 4900 TRAFFIC SIGNALS

Geometric Design Tables

ADA Training Accessible Pedestrian Signal (APS) 2018 MnDOT

SECTION 1A NEW JERSEY TURNPIKE GEOMETRIC DESIGN

MEASURING INSTRUCTIONS Step-by-Step. Lazy-L Pools. Step #1: Measure the Width (A) and the Length (B)

IECEx Certificate of Conformity Annexe

M E M O R A N D U M. Technical Committee on Special Operations Protective Clothing and Equipment

UNIVERSITY OF HONG KONG LIBRARY. Hong Kong Collection

UIAA Standard (UIAA = Union Internationale des Associations d Alpinisme) January Mountaineering and Climbing Equipment. Connectors.

City of Roseville Section 13 Design Standards. _Bikeways January 2016 SECTION 13 BIKEWAYS

RESIDENTIAL BUILDING PLAN REVIEW CHECKLIST

Learning Objectives Source/Example Questions

American Railway Engineering and Maintenance of Way Association Letter Ballot. Draft

The Agility Association of Canada

CHAPTER 2G. PREFERENTIAL AND MANAGED LANE SIGNS

PLACEMENT OF SIGNS RECOMMENDED PRACTICES SUB-SECTION

This Chapter sets forth the minimum design, technical criteria and specifications to be used in the preparation of all roadway plans.

NEEC National Electrical Engineering Consultancy

CHAPTER 6H. TYPICAL APPLICATIONS

ORDINANCE NO AN ORDINANCE OF THE CITY OF FOLSOM AMENDING CHAPTER OF THE FOLSOM MUNICIPAL CODE CONCERNING SWIMMING POOLS, SPAS AND HOT TUBS

6.7 Aircraft Protection

EQ: GPE.7 How do I find the perimeter and area of polygons?

Chapter 5. General Site and Building Elements

Installation Instructions Topo Ceiling System

Field guide for Accessible Public Rights-of-Way Edition

ORNAMENTAL CANTILEVER GATE INSTRUCTIONS

Alberta Infrastructure HIGHWAY GEOMETRIC DESIGN GUIDE AUGUST 1999

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

MSC Guidelines for Independent Fuel Tanks

Homework 2 Bathymetric Charts [based on the Chauffe & Jefferies (2007)]

ADA Technical Frequently Asked Questions

Finding the Area of a Major League Baseball Field

REFINE DEVELOP INTRODUCE

FIRE & LIFE SAFETY STANDARD

CTC Area of study Climbable Guards 2007/2008 Code Changes SECTION GUARDS

Committee on NFPA 85

SWIMMING POOL, SPA, & HOT TUB GUIDELINES

SECTION 3 STREET DESIGN

2018 Annual Inspection Report

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Finding the Area of a Major League Baseball Field

PHASE 1 WIND STUDIES REPORT

Including Revision 1 dated May 2012 and Revision 2 dated May 2012

Three Springs Design Guidelines Fencing and Wall Standards

To position power poles a safe distance from the road to minimise the likelihood of being accidentally hit by vehicles.

SWIMMING POOL & SPA DOCUMENT SUBMITTAL LIST

(12) Patent Application Publication (10) Pub. No.: US 2015/ A1

Math 20-3 Admission Exam Study Guide Notes about the admission exam:

Ground Fault Circuit Interrupter(GFCI) Policy

CROSS COURSE INSTRUCTION DOCUMENT

Key Comparison of Safety Requirements in Europe, North America and Australia for Electronic Products

FINAL EXPRESS TERMS FOR PROPOSED BUILDING STANDARDS OF THE CALIFORNIA DEPARTMENT OF PUBLIC HELATH

ATTACHMENT NO. 18 GMI-C. National Committee on Uniform Traffic Control Devices GMI SIGNS TECHNICAL COMMITTEE RECOMMENDATION

I am transmitting to you herewith the following decision of the Standards Council.

ADA on Construction. Guidance for Section C Plan Preparers

Aluminum Sheeting Guide (ASG)

Transcription:

National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Lightning Protection Systems Kimberly Shea Date: April 19, 2012 Subject: NFPA 780 Supplement ROC TC FINAL Ballot Results (F2012Cycle) According to the final ballot results, the revised committee action on Proposal 780-23 received the necessary affirmative votes to pass ballot. 28 Members Eligible to Vote 0 Not Returned 27 Affirmative on All (w/comment R. Rapp) 1 Negative (W. Heary) 0 Abstentions The attached report includes one affirmative comment and one explanation of negative vote. There are two criteria necessary for each proposal to pass ballot: (1) simple majority and (2) affirmative 2 / 3 vote. The mock examples below show how the calculations are determined. (1) Example for Simple Majority: Assuming there are 20 vote eligible committee members, 11 affirmative votes are required to pass ballot. (Sample calculation: 20 members eligible to vote 2 = 10 + 1 = 11) (2) Example for Affirmative 2 / 3 : Assuming there are 20 vote eligible committee members and 1 member did not return their ballot and 2 members abstained, the number of affirmative votes required would be 12. (Sample calculation: 20 members eligble to vote 1 not returned 2 abstentions = 17 x 0.66 = 11.22 = 12 ) As always please feel free to contact me if you have any questions.

780-23 Log #70 Thomas R. Harger, Harger Lightning Protection Inc. Move requirements in section 4.8 Strike Termination Devices on Roofs to before section 4.7 Zones of Protection and renumber sections accordingly. This will result in section 4.7 Strike Termination Devices on Roofs followed by section 4.8 Zones of Protection Relocation of these sections will place requirements for locating strike termination devices immediately following requirements for strike terminations. Zone of Protection requirements then follow. The intent is to clarify requirements and application of the standard. Requirements of where strike terminals are required are followed by requirements that allow for omissions of devices. Currently these requirements are intermingled causing confusion and misapplication of the standard. Change A.4.7.3.4 to A.4.8.3.4. Change A.4.7.4.1 to A.4.8.4.1. Change A.4.7.4.2 to A.4.8.4.2. Change A.4.8.1 to A.4.7.1. Change A.4.8.4 to A.4.7.4. Change A.4.8.9.3 to A.4.7.9.3. Change Figure 4.7.3.3(a) to 4.8.3.3(a). Change Figure 4.7.3.3(b) to 4.8.3.3(b). Change Figure 4.7.3.4(a) to 4.8.3.4(a). Change Figure 4.7.3.4(b) to 4.8.3.4(b). Change Figure 4.7.4.1 to 4.8.4.1. Change Figure 4.8.1 to 4.7.1. Change Figure 4.8.2 to 4.7.2. Change Figure 4.8.3(a) to 4.7.3(a). Change Figure 4.8.3(b) to 4.7.3(b). Change Figure 4.8.6.2 to 4.7.6.2. Change Figure 4.8.6.5 to 4.7.6.5. Change Figure 4.8.9.3 to 4.7.9.3. Change Figure A.4.7.3.4 to A.4.8.3.4. Change Figure A.4.7.4.1 to A.4.8.4.1. Change Figure A.4.8.4 to A.4.7.4 Revise 4.7 to read as follows: 4.8 Zones of Protection. The geometry of the structure shall determine the zone of protection. Revise 4.7.1 to read as follows: 4.8.1 One or more of the methods described in 4.8.2 through 4.8.4 and Section 4.7 shall be used to determine the overall zone of protection. Revise 4.7.2 to read as follows: 4.8.2 Roof Types. The zone of protection for the following roof types shall include the roof and appurtenances where protected in accordance with Section 4.7: (1) Pitched roofs (2) Flat or gently sloping roofs (3) Dormers (4) Domed roofs (5) Roofs with ridges, wells, chimneys, or vents Revise 4.7.3 to read as follows: 4.8.3 Multiple-Level Roofs. Revise 4.7.3.1 to read as follows: 4.8.3.1 For structures with multiple-level roofs no more than 15 m (50 ft) in height, the zone of protection shall include areas as identified in 4.8.3.3 and 4.8.3.4. Revise 4.7.3.2 to read as follows: 4.8.3.2 The zone of protection shall be permitted to be delineated by a cone with the apex located at the highest point 1

of the strike termination device, with its surface formed by a 45-degree or 63-degree angle from the vertical, based on the height of the strike termination device above the ground as defined in 4.8.3.3 and 4.8.3.4. Revise 4.7.3.3 to read as follows: 4.8.3.3 Structures that do not exceed 7.6 m (25 ft) above earth shall be considered to protect lower portions of a structure located within a one-to-two zone of protection as shown in Figure 4.8.3.3(a) and Figure 4.8.3.3(b). Revise 4.7.3.4 to read as follows: 4.8.3.4* Structures that do not exceed 15 m (50 ft) above earth shall be considered to protect lower portions of a structure located within a one-to-one zone of protection as shown in Figure 4.8.3.4(a) and Figure 4.8.3.4(b). Revise 4.7.4 to read as follows: 4.8.4 Rolling Sphere Method. Revise 4.7.4.1 to read as follows: 4.8.4.1* The zone of protection shall include the space not intruded by a rolling sphere having a radius of the striking distance determined for the type of structure being protected, as shown in Figure 4.8.4.1. Revise 4.7.4.1.1 to read as follows: 4.8.4.1.1 Where the sphere is tangent to earth and resting against a strike termination device, all space in the vertical plane between the two points of contact and under the sphere shall be considered to be in the zone of protection. Revise 4.7.4.1.2 to read as follows: 4.8.4.1.2 A zone of protection shall also be formed where such a sphere is resting on two or more strike termination devices and shall include the space in the vertical plane under the sphere and between those devices, as shown in Figure 4.8.4.1. Revise 4.7.4.1.3 to read as follows: 4.8.4.1.3 All possible placements of the sphere shall be considered when determining the overall zone of protection using the rolling sphere method. Revise 4.7.4.1.4 to read as follows: 4.8.4.1.4 The striking distance of an ordinary structure shall not exceed 46 m (150 ft). Revise 4.7.4.2 to read as follows: 4.8.4.2 For structure heights exceeding the striking distance above earth or above a lower strike termination device, the zone of protection shall be the space in the vertical plane between the points of contact, and also under the sphere where the sphere is resting against a vertical surface of the structure and the lower strike termination device(s) or earth. Revise 4.7.4.3 to read as follows: 4.8.4.3 Under the rolling sphere method, the horizontal protected distance found geometrically by Figure A.4.8.4.1 also shall be permitted to be calculated using the following formula (units shall be consistent, m or ft): Add formula here. Revise 4.7.4.3.1 to read as follows: 4.8.4.3.1 For the formula to be valid, the sphere shall be either tangent to the lower roof or in contact with the earth, and in contact with the vertical side of the higher portion of the structure. Revise 4.7.4.3.2 to read as follows: 4.8.4.3.2 In addition, the difference in heights between the upper and lower roofs or earth shall be the striking distance or less. Revise 4.8 to read as follows: 4.7 Strike Termination Devices on Roofs. Revise 4.8.1 to read as follows: 4.7.1* Location of Devices. As shown in Figure 4.7.1, the distance between strike termination devices and ridge ends on pitched roofs, or edges and outside corners of flat or gently sloping roofs, shall not exceed 0.6 m (2 ft). Revise 4.8.1.1 to read as follows: 4.7.1.1 Strike termination devices shall be placed on ridges of pitched roofs, and around the perimeter of flat or gently sloping roofs, at intervals not exceeding 6 m (20 ft). Revise 4.8.1.2 to read as follows: 4.7.1.2 Strike termination devices 0.6 m (2 ft) or more above the object or area to be protected shall be permitted to be placed at intervals not exceeding 7.6 m (25 ft). Revise 4.8.2 to read as follows: 4.7.2 Pitched Roof Area. For a pitched roof with eave heights over 15 m (50 ft) but less than 46 m (150 ft) above grade, it shall be permitted to omit strike termination devices at the eaves if the slope of that roof is equal to or steeper than the tangent of the arc at the eave elevation of a rolling sphere having a 46 m (150 ft) radius. (See Figure 4.7.2.) Revise 4.8.2.1 to read as follows: 4.7.2.1 Except for the gutter, any portion of the building that extends beyond that tangent shall be protected. Revise 4.8.2.2 to read as follows: 2

4.7.2.2 Eaves over 46 m (150 ft) above grade shall be protected in accordance with 4.7.1. Revise 4.8.2.3 to read as follows: 4.7.2.3 The tangent of the rolling sphere arc shall be considered a vertical line over 46 m (150 ft) above grade, except as permitted by 4.8.3.4. Revise 4.8.3 to read as follows: 4.7.3 Flat or Gently Sloping Roof Area. Flat or gently sloping roofs that exceed 15 m (50 ft) in width or length shall have additional strike termination devices located at intervals not to exceed 15 m (50 ft) on the flat or gently sloping areas, as shown in Figure 4.7.3(a) and Figure 4.7.3(b), or such area can also be protected using taller strike termination devices that create zones of protection using the rolling sphere method so the sphere does not contact the flat or gently sloping roof area. Revise 4.8.4 to read as follows: 4.7.4* Dormers. Revise 4.8.4.1 to read as follows: 4.7.4.1 Dormers as high as or higher than the main roof ridge shall be protected with strike termination devices, conductors, and grounds. Revise 4.8.4.2 to read as follows: 4.7.4.2 Dormers and projections below the main ridge shall require protection only on those areas extending outside a zone of protection. Revise 4.8.5 to read as follows: 4.7.5 Roofs with Intermediate Ridges. Strike termination devices shall be located along the outermost ridges of buildings that have a series of intermediate ridges at the same intervals as required by 4.7.1. Revise 4.8.5.1 to read as follows: 4.7.5.1 Strike termination devices shall be located on the intermediate ridges in accordance with the requirements for the spacing of strike termination devices on flat or gently sloping roofs. Revise 4.8.5.2 to read as follows: 4.7.5.2 If any intermediate ridge is higher than the outermost ridges, it shall be treated as a main ridge and protected according to 4.7.1. Revise 4.8.6 to read as follows: 4.7.6 Flat or Gently Sloping Roofs with Irregular Perimeters. Structures that have exterior wall designs that result in irregular roof perimeters shall be treated on an individual basis. Revise 4.8.6.1 to read as follows: 4.7.6.1 The imaginary roof edge formed by the outermost projections shall be used to locate the strike termination devices in accordance with 4.7.1. Revise 4.8.6.2 to read as follows: 4.7.6.2 In all cases, however, strike termination devices shall be located in accordance with Section 4.8, as shown in Figure 4.7.6.2. Revise 4.8.6.3 to read as follows: 4.7.6.3 Strike termination devices installed on vertical roof members shall be permitted to use a single main-size cable to connect to a main roof conductor. Revise 4.8.6.4 to read as follows: 4.7.6.4 The main roof conductor shall be run adjacent to the vertical roof members so that the single cable from the strike termination device is as short as possible and in no case longer than 4.9 m (16 ft). Revise 4.8.6.5 to read as follows: 4.7.6.5 The connection of the single cable to the down conductor shall be made with a tee splice or other fitting listed for the purpose, as shown in Figure 4.7.6.5. Revise 4.8.7 to read as follows: 4.7.7 Open Areas in Flat Roofs. The perimeter of open areas, such as light or mechanical wells, shall be protected if the open area perimeter exceeds 92 m (300 ft), provided both rectangular dimensions exceed 15 m (50 ft). Revise 4.8.8 to read as follows: 4.7.8 Domed or Rounded Roofs. Strike termination devices shall be located so that no portion of the structure is located outside a zone of protection, as set forth in Section 4.8. Revise 4.8.9 to read as follows: 4.7.9 Chimneys and Vents. Strike termination devices shall be required on all chimneys and vents that are not located within a zone of protection, including metal chimneys having a metal thickness of less than 4.8 mm (3/16 in.). Revise 4.8.9.1 to read as follows: 4.7.9.1 Chimneys or vents with a metal thickness of 4.8 mm (3/16 in.) or more shall require only a connection to the lightning protection system. 3

Revise 4.8.9.2 to read as follows: 4.7.9.2 The connection for 4.7.9.1 shall be made using a mainsize lightning conductor and a connector that has a surface contact area of not less than 1940mm2 (3 in.2) and shall provide two or more paths to ground, as is required for strike termination devices. Revise 4.8.9.3 to read as follows: 4.7.9.3* Required strike termination devices shall be installed on chimneys and vents, as shown in Figure 4.7.9.3, so that the distance from a strike termination device to an outside corner or the distance perpendicular to an outside edge is not greater than 0.6 m (2 ft). Revise 4.8.9.4 to read as follows: 4.7.9.4 Where only one strike termination device is required on a chimney or vent, at least one main-size conductor shall connect the strike termination device to a main conductor at the location where the chimney or vent meets the roof surface and provides two or more paths to ground from that location in accordance with Section 4.9 and 4.9.2. Revise 4.8.10 to read as follows: 4.7.10 Metal Roof Top Units. Strike termination devices shall be required in accordance with 4.7.10.1 through 4.7.10.3.2 on all roof top mechanical units with continuous metal housings less than 4.8 mm (3/16 in.) thick such as air-conditioning/heating units, metal air intake/exhaust housings, and cooling towers, that are not located in a zone of protection. Revise 4.8.10.1 to read as follows: 4.7.10.1 Air terminals shall be installed in accordance with 4.7.1 through 4.7.3. Revise 4.8.10.2 to read as follows: 4.7.10.2 The air terminals shall be mounted on bases having a minimum contact area of 1940mm2 (3 in.2), each secured to bare metal of the housing or mounted by drilling and tapping to the unit s frame in accordance with 4.16.3.2 and 4.16.3.3. Revise 4.8.10.3 to read as follows: 4.7.10.3 At least two main-size conductors shall be installed to connect the unit to the lightning protection system. Revise 4.8.10.3.1 to read as follows: 4.7.10.3.1 The connection shall be made to bare metal at the base or lower edges of the unit using main-size lightning conductors and bonding devices that have a surface contact area of not less than 1940 mm2 (3 in.2) and shall provide two or more paths to ground, as is required for strike termination devices. Revise 4.8.10.3.2 to read as follows: 4.7.10.3.2 The two main bonding plates shall be located a far apart as practicable at the base or lower edges of the unit s electrically continuous metal housing and connected to the lightning protection system. Revise A.4.7.3.4 to read as follows: A.4.8.3.4 Research indicates that the probability of low-amplitude strikes to the vertical side of a structure of less than 60 m (200 ft) in height are low enough that they need not be considered (see IEC 62305-3, Protection Against Lightning, Section 5.2.3.1). It is suggested that a wall or surface with a slope characterized by an angle from vertical of no more than 15 degrees be considered essentially vertical as it relates to the electric field gradient that could result in the generation of streamers. See Figure A.4.8.3.4. IEC 62305-3, Protection Against Lightning, Section 5.2.3.2 acknowledges that the rules for the placement of strike termination devices can be relaxed to the equivalent of IEC Lightning Protection Class IV for upper parts of tall structures where protection is provided on the top of the structure. Figure A.4.8.3.4 identifies the maximum values of protection angle versus class of lightning protection system based on IEC 62305-3. The 15- degree angle from vertical falls well within the limits specified for a Class IV lightning protection system at a height of 60m(200 ft). Revise A.4.7.4.1 to read as follows: A.4.8.4.1 Figure A.4.8.4.1 depicts the 46 m (150 ft) rolling sphere method for structures of selected heights up to 46 m (150 ft). Based on the height of the strike termination device for a protected structure being 7.6 m (25 ft), 15 m (50 ft), 23 m (75 ft), 30m(100 ft), or 46m(150 ft) above ground, reference to the appropriate curve shows the anticipated zone of protection for objects and roofs at lower elevations. Revise A.4.8.4 to read as follows: A.4.7.4 Figure A.4.7.4 illustrates dormer protection. The Technical Committee accepted the submitter's text with revisions to appropriately retain the annex material and figures/tables. Affirmative: 27 Negative: 1 4

HEARY, W: I do not believe surge protection belongs in this document. RAPP, R: 4.8 Zones of Protection. The geometry of the structure shall determine the zone of protection. Should be "shall determine the "zones" of protection, there are more than one from any structure. Revise 4.7.4.1.1 to read as follows: 4.8.4.1.1 Where the sphere is tangent to earth and resting against a strike termination device, all space in the verticalplane between the two points of contact and under the sphere shall be considered to be in the zone of protection. "resting against", means it could be resting on the side of the strike termination device, I believe it should read, "resting on the tip of". Revise 4.7.4.1.2 to read as follows: 4.8.4.1.2 A zone of protection shall also be formed where such a sphere is resting on two or more strike termination devices and shall include the space(shall include the space not intruded) in the vertical plane under the sphere and between those devices, as shown in Figure 4.8.4.1. Revise 4.8.2 to read as follows: 4.7.2 Pitched Roof Area. For a pitched roof with eave heights over 15 m (50 ft) but less than 46 m (150 ft) above grade, it shall be permitted to omit strike termination devices at the eaves if the slope of that roof is equal to or steeper than the tangent of the arc at the eave elevation of a rolling sphere having a 46 m (150 ft) radius. (See Figure 4.7.2.) I have never agreed with this unsubstantiated method of protection that does not meet the rest of the standard's requirements but has been included in the standard to ease the installers potential problems with the installation. Delete it. Revise 4.8.6.1 to read as follows: 4.7.6.1 The imaginary roof edge formed by the outermost projections shall be used to locate the strike termination devices in accordance with 4.7.1. "imaginary roof edge" - vague and unenforceable language - Revise 4.8.6.5 to read as follows: 4.7.6.5 The connection of the single cable to the down conductor shall be made with a tee splice or other fitting listed for the purpose, as shown in Figure 4.7.6.5. Remove "tee splice or other" Revise A.4.7.3.4 to read as follows: A.4.8.3.4 Research indicates...what research? It needs to be included with date and titles, etc... Revise A.4.7.3.4 to read as follows: A.4.8.3.4 Research indicates that the probability of low-amplitude strikes to the vertical side of a structure of less than 60 m (200 ft) in height are low enough that they need not be considered (see IEC 62305-3, Protection Against Lightning, Section 5.2.3.1). It is suggested that a wall or surface with a slope characterized by an angle from vertical of no more than 15 degrees be considered essentially vertical as it relates to the electric field gradient that could result in the generation of streamers. See Figure A.4.8.3.4. IEC 62305-3, Protection Against Lightning, Section 5.2.3.2 acknowledges that the rules for the placement of strike termination devices can be relaxed to the equivalent of IEC Lightning Protection Class IV for upper parts of tall structures where protection is provided on the top of the structure. Figure A.4.8.3.4 identifies the maximum values of protection angle versus class of lightning protection system based on IEC 62305-3. The 15- degree angle from vertical falls well within the limits specified for a Class IV lightning protection system at a height of 60m(200 ft). The references to IEC Standards, indicates in my opinion, a weakness of the NFPA 780 document to not doing it's own research and documentation and coming to its own conclusions. 5