SAFETY FEATURES OF PORTABLE CRYOGENIC LIQUID CONTAINERS FOR INDUSTRIAL AND MEDICAL GASES

Similar documents
USE OF RESIDUAL PRESSURE VALVES

REFERENCE GUIDE ON MEDICINAL GAS CYLINDER VALVES

GUIDELINES FOR HANDLING EXTERNALLY CONTAMINATED MEDICAL CYLINDERS IN A PANDEMIC SITUATION

SAFETY TRAINING LEAFLET 06 CARBON DIOXIDE

LABELLING OF MEDICAL GAS CONTAINERS

SAFETY PRINCIPLES FOR PRESSURE REGULATORS FOR MEDICAL OXYGEN CYLINDERS

CATALOGUE OF EIGA MEDICAL GASES PUBLICATIONS

PREVENTION OF EXCESSIVE PRESSURE DURING FILLING OF CRYOGENIC VESSELS

METHODS TO PREVENT THE PREMATURE ACTIVATION OF RELIEF DEVICES ON TRANSPORT TANKS

SAFETY TRAINING LEAFLET 02 BASIC RULES FOR SAFETY AND GOOD HOUSEKEEPING

BCGA GUIDANCE NOTE 17

MEDICAL GAS CYLINDERS COLOUR CODING TD 09/15/E

DESIGN CONSIDERATIONS TO MITIGATE THE POTENTIAL RISKS OF TOXICITY WHEN USING NON- METALLIC MATERIALS IN HIGH PRESSURE OXYGEN BREATHING GAS SYSTEMS

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar

SAFETY BULLETIN 01/05

CYLINDER VALVE GUIDELINES TD 12/15/E

A REFERENCE GUIDE FOR REQUALIFICATION OF GAS CYLINDERS

MANAGEMENT OF CHANGE AIGA 010/04. Asia Industrial Gases Association

PERMISSIBLE CHARGE/FILLING CONDITIONS FOR ACETYLENE CYLINDERS, BUNDLES, & BATTERY VEHICLES

USE OF NON-METALLIC MATERIALS IN HIGH PRESSURE OXYGEN BREATHING GAS APPLICATIONS

PURPOSE OF THE POLICY

HAZARDS ASSOCIATED WITH THE USE OF ACTIVATED CARBON CRYOGENIC GAS PURIFIERS

Instruction manual. for. high purity gas pigtails 200 bar / 300 bar

300 BAR HIGH STRENGTH SEAMLESS STEEL GAS CYLINDERS

for the of and the EM55-1

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

300 BAR HIGH STRENGTH SEAMLESS STEEL GAS CYLINDERS

DESCRIPTION OF THE PRESSURE TEST METHODS USED DURING CYLINDER MANUFACTURE

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124

PERIODIC INSPECTION OF STATIC CRYOGENIC VESSELS

Compressed Gases and Cryogens

300 BAR HIGH STRENGTH SEAMLESS STEEL GAS CYLINDERS

ISO INTERNATIONAL STANDARD. Gas cylinders Safe handling. Bouteilles à gaz Sécurité de manutention. Second edition

RECERTIFICATION GUIDELINES FOR HIGH PRESSURE CYLINDERS TD 30/18/E

CYLINDER RETEST STATIONS

Developing a Policy for Auto Transportation of Medical Oxygen in High Pressure Cylinders and Cryogenic Vessels

Decant Filling of Gas Cylinders

PSSI 36 General Confined Spaces, Tunnels, Culverts and Similar Spaces

BOC Healthcare training

Quebec Quebec Tel : Fax : MSDS: Methane, Oxygen in Nitrogen Mixture PRODUCT INFORMATION

Drum / cylinder handling

BOC Healthcare Training

PRESSURE REDUCING STATION INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

ISO INTERNATIONAL STANDARD. Gas cylinders Cylinder valves with integrated pressure regulators Specification and type testing

Working in Gas Hazard Areas

Before using or working with the Grab n Go Heliox system, please read and understand the usage and safety instructions provided in this booklet.

ISO INTERNATIONAL STANDARD. Flow-metering devices for connection to terminal units of medical gas pipeline systems

Liquid Gas Cylinder (LGC)

Alkylphosphines. Storage and Handling Recommendations

SAFETY POLICY AND PROCEDURE MANUAL All Euramax Subsidiaries. Number K-3.0 Welding Safety Procedures

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Compressed Gas Safety Standard

Oxygen Usage Best Practice Guide

Quebec Quebec Tel : Fax : MSDS: Hydrogen 25% in Nitrogen Mixture PRODUCT INFORMATION

ISO INTERNATIONAL STANDARD. Cryogenic vessels Pressure-relief accessories for cryogenic service Part 1: Reclosable pressure-relief valves

Transport of gas tanks for motor vehicles

Tri-Tech Medical Inc.

ISO INTERNATIONAL STANDARD. Transportable gas cylinders Inspection and maintenance of cylinder valves

Health & Safety Policy Arrangements Temporary Compressed Gas Installation (Inert and Oxidising Gas Only) (HSA 23)

DF1 and DF2 Diffusers

623 Series Dome Load Regulators

Pressure Regulators. Instructions for Use

Cal/OSHA T8 CCR 1536 Cal/OSHA T8 CCR 4799 Cal/OSHA T8 CCR 4845 Cal/OSHA T8 CCR 4848

ISO 9539 INTERNATIONAL STANDARD. Gas welding equipment Materials for equipment used in gas welding, cutting and allied processes

Health and Safety Guidance Note No 37

Compressed Gases Storage and Handling Safety Policy. Individual Unit Function: Safety Procedure No.: SOP-0103 Page: 1 of 6

ST/SG/AC.10/C.3/2016/8. Secretariat. United Nations. Transport of gas tanks for motor vehicles. Introduction

453 Series Steam Heated Vaporizing Regulator

Quebec Quebec Tel : Fax : MSDS: Argon Compressed PRODUCT INFORMATION

Savard Labor & Marine Staffing, Inc. Compressed Gas Safety Program Rev3/14

Quebec Quebec Tel : Fax : MSDS: Hydrogen Sulfide in Nitrogen Mixture PRODUCT INFORMATION

Tri-Safem Model I1 Regulator. INSTRUCTIONS and PARTS

Pressure Regulator. Instructions for Use

Compressed Gas Cylinders - Guideline

Quebec Quebec Tel : Fax : MSDS: Methane Compressed PRODUCT INFORMATION

INTERNATIONAL ISO STANDARD Anaesthetic machines for use with humans. Appareils d anesfhesie pour utilisation chez I homme

Seat Tightness of Pressure Relief Valves

SOUTH AFRICAN NATIONAL STANDARD

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

Pressure Regulators. Operating Instructions. Instrumentation

Compressed Gases Safety Program

ISO INTERNATIONAL STANDARD. Small craft Liquefied petroleum gas (LPG) systems

Type 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies

Summary of the MRA LPG Codes of Practice

Installation Instructions JATCO Environmental Protection Tank Model J-7000

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Technical Information

Glasgow City Council EDUCATION SERVICES. Technician Support Service

SEMS II: BSEE should focus on eliminating human error

BRITISH STANDARD BS 341-4: Transportable gas container valves. Part 4: Pressure relief devices ICS

Ontario ENGINEERING STANDARD SPECIFICATION 1.0 PURPOSE

INSTALLATION MANUAL Matheson Tri-Gas Cabinet Enclosures

IMPLEMENTATION OF EIGA CARBON DIOXIDE STANDARDS

TECHNICAL INFORMATION

PRESSURE SYSTEMS POLICY

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series

CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

GOOD MANUFACTURING PRACTICE GUIDE PART I FOR MEDICAL GASES

Jupiter Type 4 Tube Owner s Manual

USER MANUAL. 1. Principle of operation. 2. Delivery condition. SPRING-LOADED SAFETY VALVES zarmak. Edition: 07/2016 Date: V (ex.

AND OPERATION INSTRUCTIONS

Transcription:

SAFETY FEATURES OF PORTABLE CRYOGENIC LIQUID CONTAINERS FOR INDUSTRIAL AND MEDICAL GASES AIGA 016/04 Asia Industrial Gases Association 298 Tiong Bahru Road, #20-01 Central Plaza, Singapore 168730 Tel : +65 6276 0160 Fax : +65 6274 9379 Internet : http://www.asiaiga.org

SAFETY FEATURES OF PORTABLE CRYOGENIC LIQUID CONTAINERS FOR INDUSTRIAL AND MEDICAL GASES KEYWORDS CRYOGENIC LIQUID VESSEL STORAGE COUPLING MEDICAL CLEANING PIPING SYSTEM LABELLING SAFETY Disclaimer All publications of AIGA or bearing AIGA s name contain information, including Codes of Practice, safety procedures and other technical information that were obtained from sources believed by AIGA to be reliable and/ or based on technical information and experience currently available from members of AIGA and others at the date of the publication. As such, we do not make any representation or warranty nor accept any liability as to the accuracy, completeness or correctness of the information contained in these publications. While AIGA recommends that its members refer to or use its publications, such reference to or use thereof by its members or third parties is purely voluntary and not binding. AIGA or its members make no guarantee of the results and assume no liability or responsibility in connection with the reference to or use of information or suggestions contained in AIGA s publications. AIGA has no control whatsoever as regards, performance or non performance, misinterpretation, proper or improper use of any information or suggestions contained in AIGA s publications by any person or entity (including AIGA members) and AIGA expressly disclaims any liability in connection thereto. AIGA s publications are subject to periodic review and users are cautioned to obtain the latest edition. AIGA 2005 - AIGA grants permission to reproduce this publication provided the Association is acknowledged as the source ASIA INDUSTRIAL GASES ASSOCIATION 298 Tiong Bahru Road #20-01 Central Plaza Singapore 168730 Tel: +65 62760160 Fax: +65 62749379 Internet: http://www.asiaiga.org

Acknowledgement This document is adopted from the European Industrial Gases Association document IGC Doc 93/03 Safety Features of Portable Cryogenic Liquid Containers for Industrial and Medical Gases and acknowledgement and thanks are hereby given to EIGA for permission granted for the use of their document

Table of Contents 1 Introduction... 1 2 Scope... 1 3 Safety features... 1 3.1 External contamination... 1 3.2 Back Contamination from the Consumer s Process... 1 3.3 Pressure in Excess of Design Pressure... 1 3.4 Liquid and Gaseous Connections... 2 3.5 Modification to Liquid and Gas Outlet Connections... 2 3.6 Identification and Labelling... 2 3.7 Storage of gases... 2

1 Introduction A nursing home ordered four liquid cylinders with medical oxygen but received mistakenly one filled with industrial nitrogen together with three filled with medical oxygen. A maintenance employee at the nursing home was asked to connect a new oxygen vessel to the oxygen supply system. He selected the nitrogen vessel not observing the text of the label and tried to connect it to the oxygen supply system. He failed since the connectors were not compatible. He then removed a fitting from an empty oxygen liquid cylinder, installed it on the liquid nitrogen cylinder and then connected the nitrogen cylinder to the medical oxygen supply system. Four patients suffered asphyxiation and died as a result of breathing the nitrogen. The above accident and similar ones have initiated a revision of the EIGA Safety Info on Portable Liquid Cylinders issued in 1993. It is strongly recommended that each EIGA member company ensure that the appropriate customers receive this information and, if needed, further training in the handling of medical gases and associated equipment. Special attention should be paid to the fact that a contributing cause to several incidents has been the mix-up of medical and industrial gases at the delivery to the medical gas customer. 2 Scope The scope of this Safety Info is the external safety features of portable cryogenic containers within the range of above 0.5 bar(g) pressure and a net liquid capacity no greater than 1,000 litres, but excluding Home Care portable cryogenic containers. 3 Safety features 3.1 External contamination External contamination may occur while containers are in use, in storage or during transportation. Atmospheric pollutants and other contaminants such as oil, particulate matter, etc. can create potential hazards where oxidizing gases are involved especially liquid oxygen - and react with explosive violence. Therefore, it is recommended that such containers are thoroughly inspected before filling and that all control and safety devices are kept clean and free of any hydrocarbon substances. 3.2 Back Contamination from the Consumer s Process In order to protect against contamination it is essential that equipment is installed within the consumer s fixed supply system that will prevent such an occurrence for example by the installation of non-return valves. Such a device should be adequately sized and specified to accommodate the pressure range that the container, and/or the consumer s supply system, will operate within. 3.3 Pressure in Excess of Design Pressure Containers can be utilised within process systems where pressures in excess of the container s design parameters can occur. Examples are: compressed gas cylinders, pressure swing absorber systems and membrane systems. It is critical that adequate safeguards are incorporated within the design of any process system utilising gaseous product from the container. A relief device set at the design pressure of the cryogenic liquid container and capable of discharging the maximum flow achievable from the high pressure source, should be installed between the liquid container and the high pressure source. A pressure reducing valve should be installed between the high pressure source and the cryogenic liquid container that is capable of controlling a down stream pressure below the design pressure of the 1

cryogenic liquid container. 3.4 Liquid and Gaseous Connections Connections utilised for liquid cylinders should eliminate the potential for incorrect filling, or product withdrawal from cryogenic liquid container by using connectors specific either for each gas or for each type of gas such as the same connection for the inert gases argon and nitrogen. 3.5 Modification to Liquid and Gas Outlet Connections To protect against unsafe conditions arising from the filling of a container with an incorrect product, and the potential impact of product integrity being compromised, the following procedures should be adopted for all liquid, and gas, withdrawal and filling connections of cryogenic liquid containers. Use of coupling adapters shall be strictly prohibited. A controlled procedure must be developed and implemented, that ensures only authorised and competent personnel undertake any modifications to liquid and gas connections on a cryogenic liquid container owned/operated by the responsible filling company. These modifications are done under the responsibility of the gas filling company and records must be maintained of all changes of service. Medical liquid cylinders. The outlet shall be either: - a threaded or socket connection, silver brazed, welded, or attached by other methods to the valve body in a manner that prevents removal or would render the connection or valve body outlet unusable if removal was attempted or accomplished; or: - a permanent and integral part of the valve body. For containers used in fixed installations the connections can be permanently fixed when the container is next refurbished. Industrial liquid cylinders shall have any of the above outlet connections or a threaded connection with a device that deters removal of the fitting and provides indication that removal was attempted. 3.6 Identification and Labelling It is recommended that the following labels are securely affixed to the body of the container in addition to any statutory requirements. Clear product identification which can be easily read at a safe distance and comply with the guidelines for the labelling of gas cylinders. Additional product labels should be securely affixed at the inlet and outlet connections To further increase the product identification, a label visible from all directions may be fixed on the cylinder. Actions to be taken by the user s personnel in the event of an emergency should be simply and clearly displayed 3.7 Storage of gases Clearly separated and marked storage areas should be provided at filling plants, sales outlets and customers for medical and industrial gases. 2