Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems. J.C.M. VAN ROSSUM * Prysmian Group NL The Netherlands

Similar documents
FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO

MECHANICAL ASPECTS OF SUBMARINE CABLE ARMOUR

Inert Air (N2) Systems Manual

Experiences and Challenges of Combined HV & EHV Qualifications to IEC, AEIC and IEEE 48 & 404

About ABB Micafil Facts

HV Spiker Kit - CSTE. 30 th April 2014

TECHNICAL DATA. Q = C v P S

User Information Sheet 015

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers

C I R E D 18 th International Conference on Electricity Distribution Turin, 6 th to 9 th June 2005

Micafil RIP bushings High-voltage Resin Impregnated Paper bushings. Power and productivity for a better world TM ABB

TECHNICAL DATA. Q = C v P S

AUTOMATIC HOSE TEST UNIT, TYPE SPU

Axpo Power Ltd. 2) GE Grid Solutions

Micafil RIP bushings High-voltage Resin-Impregnated Paper bushings. Power and productivity for a better world TM ABB

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS

TECHNICAL DATA. Q = C v P S

A SURVEY OF THE RELIABILITY OF HVDC SYSTEMS THROUGHOUT THE WORLD DURING On behalf of Study Committee B4

Umbilicals Experience and Challenges, Tie Back installations

Periodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels

RCP3 service performance measures: additional information on the proposed HVDC energy availability target

Section 2 Safety, Tools and Equipment, Shop Practices Unit 4 General Safety Practices. Unit Objectives. Pressure Vessels and Piping (1 of 2)

TECHNICAL DATA. Q = C v P S

A hose layline contains important information for specifying the replacement assembly: manufacturer, hose trade name, working pressure and hose ID.

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

User Manual MFCS TM -EZ

RULES PUBLICATION NO. 119/P

TECHNICAL DATA. Q = C v P S

CRANE WITH WINCH USE AND MAINTENANCE MANUAL. Code Rev. Release MD /03

BENNEX Advanced Cable Termination ACT Subsea Electrical Termination

Distribution Transformer Instruction Manual

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

PART Q CONTROL OF HAZARDOUS ENERGY (LOCKOUT-TAGOUT)

CIRCUIT BREAKER POLE MERLIN AND GERRIN MAKE AT TATA POWER COMPANY

DW Module 8: Distribution Answer Key

NATURAL GAS MAINTENANCE. Part 192 Subpart "M"

Innovation Electrical Industry

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Assessing Permeation of Gas through Polyethylene Pipe

Rejuvenation Instructions

TECHNICAL DATA OBSOLETE

KMU SUBSTATION WORKSHOP

ELECTRIC OPERATING PROCEDURES Date: 11/01/06

Engineering Technical Report 128. Risk Assessment for BT Operators Working In a ROEP Zone. Draft for Approval

Installation, Operating, Maintenance and Safety Instructions for. Pressurised water systems for boats

Neil Kane Managing Director EMT UK

Improving distillation tower operation

TECHNICAL DATA. Q = C v P S

On-Stream Tightness Testing of Vacuum Process Installations

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS

Position switches FP series

Operating instructions Binary level sensor LI / / 2013

Delayed Coker Safe Sampling Tar or Spalled Coke

Pressure independent control valve (PICV) FLOWMATIC

CO 2. (R744) Service Station Presentation. Contents. Goals Basic functions Specification Recovery R477 Vacuum Charge Safety Other features Prototype

Hydraulic and Economic Analysis of Real Time Control

Further technical information is available on

E 441 E 451 E 461 E 641 E 700 Tank mounting Nominal flow rate up to 800 l/min

Underwater pressure resistant. cables and harnesses for outboard use

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

ON-LINE MONITORING OF REGULATOR TRANSFORMER AT THE MARGEM DIREITA SS IN ITAIPU. M. E. G. ALVES* Treetech Sistemas Digitais Ltda.

Flamco Flamco-Fill STA Flamco-Fill STM

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

The Discussion of this exercise covers the following points:

23.1 Functions, Basic Configuration, and Interfaces

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption

Materials Performance November Nitrogen generator inhibits corrosion within fire protection systems

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell:

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications

Cold-acclimatised pipelines

E 094 E 103 E 143 Tank top mounting Connection up to G1 / -16 SAE Nominal flow rate up to 135 l/min / 35.7 gpm

PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS

LOCK-OUT/TAG-OUT (LO/TO) SAFETY PROGRAM

TECHNICAL PAPER PRESENTATION

Cycle Isolation Monitoring

CABLE ENTRIES IN HAZARDOUS AREAS CORRECT SELECTION, INSTALLATION AND MAINTENANCE

CFSW. Hinges with built-in safety multiple switch

B kv pilot installation with a ketone based insulation gas with first experience from operation in the grid. D. TEHLAR ABB - Switzerland

Development of a High Pressure, Oil Free, Rolling Piston Compressor

OPERATING PROCEDURES

OPERATION. Estimated kerf width compensation. HPR260 Manual Gas Instruction Manual 4-9

Visualize Nitrogen Gas Consumption

How To Deal With Pre-Charge Loss In Bladder Accumulators Due To Gas Permeation

Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module:

OPERATION MANUAL NTF-15

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

Unit 24: Applications of Pneumatics and Hydraulics

Recent Developments in Pressure Management

LO/TO LOCKOUT/TAGOUT PROGRAM

OPERATION MANUAL NTF-60 Plus

Installation, Operating, Maintenance and Safety Instructions for MAXI-SYSTEM Pressurised water systems for boats

Operating Manual ALU 7 - ALU 10 - ALU 20 - ALU 26 ALU 35 - ALU 60 - ALU 100

Monitoring transformers with infrared cameras

A Rationale for Pressure Relief Device(s) Qualification Requirements (LH2)

SPECIFICATIONS PARTICLE SENSOR KS-18F Higashimotomachi, Kokubunji, Tokyo , Japan

IEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031)

Controlling Cabin and Envelope Air Flows & Pressure Differentials

Transcription:

21, rue d Artois, F-75008 PARIS CIGRE US National Committee 2012 Grid of the Future Symposium http : //www.cigre.org Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems J.C.M. VAN ROSSUM * C. G. N. DE JONG Alliander B. WEGBRANS R. BARTHOLOMEUS J. C. SMIT Alliander N. Crane Prysmian Group UK United Kingdom T. HERMANS A. STEENIS Alliander N. Robertson Prysmian Group UK United Kingdom SUMMARY HV and EHV XLPE insulated cable systems are widely installed nowadays but the backbones of most transmission grids are Fluid-filled cable systems. The high performance of these Fluid-filled systems is guaranteed for decades under the condition that the hydraulic system is intact: leakages, even small ones, may shorten the life-time of such cables (systems) and can have a negative impact on the environment. PFT (PerFluorocarbon Tracers) technology is added to the cable fluid in minimal quantities and where the cable system is damaged, the fluid with the volatile PFT compounds permeate through the ground and can be detected using highly sophisticated detection equipment. The advantages of PFT detection are that small leakages can be found, the environmental impact is reduced, detection when circuit is in service and single excavation to repair the leak. The PFT compatibility with HV LPOF cable systems is underlined by a successful type test, in full accordance with IEC60141, and a pilot project where a small oil leak (18 liter per week) was detected at 6m depth, underneath railroad tracks. KEYWORDS LPOF, end of life time, NO 2 freezing, fatigue, PerFluorocarbon Tracers, PFT, environmental * jos.vanrossum@prysmiangroup.com 1

1 - INTRODUCTION Around the world the backbone of underground electricity transmission has been borne by fluid filled cables generally operating between 33kV and 400kV, some of which are still in service since the 1930 s [1]. Fluid filled technology has largely been superseded by XLPE type cables. However, most utilities and transmission operators have significant quantities of fluid filled systems within their networks and will continue to do so for many years [2]. Fluid filled cables have proven to be reliable, provided the fluid pressure is maintained via the integrity of the metallic sheath and associated accessories. Leaks can occur on fluid filled cables for a number of reasons but typically through metal fatigue, external corrosion or third party damage. Once a leak occurs it is generally identified by the cable operator through the activation of low pressure alarms and to ensure that the cable remains operational new cable fluid is pumped into the system pressure tanks to keep pace with the leak volume. Traditionally the main method for locating cable fluid leaks has involved de-energizing of the cable circuit, excavation to gain access and then applying a liquid nitrogen freeze (photo 1). Photo 1 freezing of 36/50kV fluid filled cable in urban area photo 2 Equipment for injecting PFT in LPOF system during service Fluid pressures are monitored to determine on which side of the freeze the leak is occurring. This process is then repeated at different locations until the leak is found. It is not uncommon for this process to take between 3 & 7 attempts before the leak is located. Many old lead sheath cables have porosity and the cable leaks when high loadings are applied. When the circuit is de-energized and the temperature decreases, the leaks often close up making them difficult to find. 2 PFT TECHNIQUE Perfluorocarbon tracers (PFT) are highly volatile compounds, with excellent electrical insulation properties which are added to the cable fluid in minute quantities. If the cable system is damaged, the fluid with the volatile PFT compounds permeates through the ground and can be detected using highly sophisticated detection equipment [3]. The advantages of this system are: - small leakages, < 5 liter/day, can be found, - reduction environmental impact, - detection is possible with cable circuit in service, - extend the cable circuit life time, - only single excavation is needed to repair oil leakages 2

Injection methods For now there are two methods of injection available, being the full flush method and the PFT injection during service (photo 2). When the full-flush method is applied, the cable circuit is deenergized and the pressure tanks are closed. The free cable fluid is then flushed with PFT cable fluid. This is the quickest way to tag a cable circuit. With the PFT injection during service method a cable circuit is injected with an extra high concentration of PFT cable fluid during routine maintenance. This method can take a number of injection s before the PFT Tracers reach the cable leak depending on the location of the leak in relation to the distance from the injection valve and the leak rate. A new, more efficient, method for injecting PFT cable fluid is under development in cooperation with one of the largest utilities of the Netherlands Alliander, see chapter 4. Detection Perfluorocarbons are a man-made substance which are present in the atmosphere at very low background levels, typically 2-3 parts per quadrillion (ppq). An advanced mobile laboratory (photo 3) has developed which can detect the background levels of perfluorocarbon in the atmosphere. Photo 3 PFT mobile laboratory for detecting small quantities of PFT in the atmosphere Upon arrival at site the air over the cable route is sampled (when possible) by driving along the cable route or by handheld sampler. Any PFT which has permeated through the subsoil from the leaking cable fluid will be detected. When a high level of PFT is identified by the PFT van, a handheld sampler is used to pin point the location within one-two metres of the cable leak. 3 LABORATORY TESTS In order to demonstrate the compatibility of PFT with HV LPOF cable system technology, a type test at 87/150kV level was initiated. For this, 30 m of 87/150kV fluid filled cable, with 800 mm 2 Cu conductor and lead sheath, was installed with one 180 o bend and terminated into porcelain outdoor terminations. The tested cable was produced and installed in 1969 and was in service for almost 40 years. Before the type test was started, the test loop was injected with PFT and measures were taken to ensure the PFT had impregnated the cable main insulation. An adaptor was installed on one of the terminations which made it possible to inject the PFT directly into the oil channel of the cable (figure 1). 3

Figure 1 Detail of termination modification in order to inject oil with PFT concentrate directly into the cable oil channel 1 2 PFT pressure vessel Empty barrel Oil tap point Photo 4 87/150kV LPOF cable injected with PFT type test loop figure 2 scheme for injecting PFT in the type test loop A pressure tank filled with PFT was connected to one of the terminations. After the pressure tank with PFT oil was opened, the oil channel of the cable was flushed with PFT (figure 2). Please note that the oil filled system was under atmospheric pressure during this procedure as the termination could not be closed due to oil injection modification (figure 1). An oil extraction point was created for easy oil sampling in the middle of the test loop (figure 2). The tap point was opened, leaking about one drop of oil per minute resulting in ~ 1 liter per 24 hours. Oil samples were taken on a regular basis for PFT measurements. After one and a half day PFT was found in the oil from the tap point and after 4 days the value of the PFT concentration was stable, confirming the presence of PFT inside the cable insulation as this is the only path for PFT injected oil to reach the tap point. In conclusion: The test setup was under atmospheric pressure. PFT oil was injected only into the oil channel of the LPOF cable. After one and a half day, PFT penetrated through the paper layers of the LPOF cable. After this experiment the test setup was restored for type test by closing the termination and increasing the oil pressure to normal values. Type test The Type Test program is based on IEC 60141-1 (1993) [4] and is summarized hereunder: 1. Dielectric loss angle/ temperature test, IEC 60141-1 4.3, U=87kV, tan δ measured at 20, 75, 60, 40 and 20 o C, requirement: tan δ < 33x10-4. 4

2. Heating Cycle Voltage test, U=174kV, 10 heat cycles (8/16h), conductor temperature between 75 80 o C for at least 2 hours in hot condition, 3. Dielectric loss angle/ temperature test, IEC 60141-1 4.3, U=87kV, tan δ measured at 20, 75, 60, 40 and 20 o C, requirement: tan δ < 33x10-4. 4. Dielectric security test, IEC 60141-1 4.4, U = 220kV / 24hours, requirement: no breakdown. 5. Lightning Impulse voltage test, IEC 60141-1 4.5.2, Impulse voltage = 550kV 10+/10-, conductor temperature between 75 80 o C for at least 2 hours, requirement: no breakdown. 6. A.C. voltage test after the impulse test, IEC 60141-1 4.5.4, U = 184kV for 15min, requirement: no breakdown. All tests were passed successfully without remarks. 4 PILOT PROJECT The PFT pilot project is implemented in the 50kV grid of Alliander (Dutch DSO): in their 50kV grid a total of 1000 km three core LPOF cable is still in active service installed from the 1950 s until the late 70 s. A picture of a typical three core LPOF cable is shown in photo 5. Table 1 50kV LPOF cable systems data Photo 5 example 36/50kV 3core LPOF cable Photo 6 typical defects of lead sheathed LPOF cables after ageing Small leakages (<5ltr/day) are non-detectable with traditional freezing methods, therefore a new strategy with the use of PFT technology was adapted by Alliander. After careful considerations the pilot project was initiated on four cable oil sections. Relevant data may be found in table 1. These four sections have leakage history over the last decade with non-detectable cause. See photo 6 for typical leaking defects that can occur in LPOF cable lead sheath due to fatigue. Each selected section was surveyed and an appropriate PFT injection plan was created. A different PFT injection method was developed for each section; the plan depending on height profile, number of pressure tanks and number of joints in the oil section. Basically this PFT injection method consists of injecting and withdrawing oil for a minimum amount, but not according to the full flush method. It is anticipated with this method that due to the cyclic rating of the cable circuit, and hence cable temperature variations, the PFT enriched oil will be distributed along the cable circuit in time. This new injecting method saves PFT enriched oil, time and minimizes disturbances for the grid. The pilot test is still running. 5

One remarkable result was found on a pilot project on a 150kV LPOF cable system. This circuit was leaking oil at a slow leakage rate: 18 ltr per week. Detection was initiated, using Prysmian detection van, see photo 3, but no leakages were found along the cable route. Railroad tracks highest PFT concentration measured Pressure tank Armoured oil feeding pipe ~ 6 m (20 ft) leak location 150kV spare LPOF cable Photo 7 hand held PFT sampler figure 3 detected oil leakages in armoured oil feeding pipe under rail track Eventually, with the aid of the hand-held PFT sampler (see photo 7), the leakage was detected in an oil feeding pipe between a pressure tank and LPOF joint connected to a 150kV LPOF spare cable, despite the fact that: The leak was located underneath a railway crossing at ~ 6 m (20 feet) depth, thus the PFT had to diffuse through 6m of soil before it could be detected and the busy traffic on the railroad tracks disturbed the PFT detection, see figure 3. It proves the effectivenes of PFT as a oil leakage detection system for small leakages. Further application of PFT injection into LPOF cable systems will be roll-out in order to allocate small leakages, full-filling their obligation for environmental enterprising. 5 UNITED KINGDOM PFT EXPERIENCE The PFT technique was developed and fine-tuned in the UK a few years before it was introduced in the Netherlands. In the UK the regional electricity companies have been slow in taking on board the merits of topping up slow leaking circuits with PFT injection during service solution during routine cable system pumping. Generally the method employed so far has been to flush an equivalent oil volume to the loose cable circuit oil volume with new degasified cable oil mixed with a controlled dosage of PFT. To allow time for the PFT to permeate through to the ground level before the survey is carried out PFT detection is normally carried out after a period of about 14 days. To date Prysmian UK have successfully tagged 14 cable circuits and have located more than 25 leaks with a 100 % detection success rate. The full flush method with known final concentration of PFT allows very quick leak detection on circuits not previously tagged that suddenly increase in leakage. BIBLIOGRAPHY [1] Cigre technical brochure 338 Statistics of AC underground cables in power networks, October 2008. [2] Cigre technical brochure 358 remaining life management of AC underground lines, December 2007 [3] R. Ghafurian et al Leak Location in Fluid filled Cables Using the PFT Method, IEEE Vol.14, no.1, January 1999 [4] IEC60141-1 Oil-filled, paper insulated, metal sheathed Cables and Accessories for Alternating Voltages up to and including 400kV 6