Technical Information

Similar documents
TECHNICAL INFORMATION

Installation, Operation, and Maintenance Manual Parker Balston Model N2-04 Nitrogen Generator

TECHNICAL INFORMATION

TECHNICAL INFORMATION

Nitrogen Generation Systems

N2-14, N2-22, N2-35, N2-14A, N2-22A, N2-35A

TECHNICAL INFORMATION

TECHNICAL INFORMATION

Nitrogen Generation Systems

Balston Nitrogen Generation Systems

OPERATION MANUAL NTF-15

OPERATION MANUAL NTF-60 Plus

Membrane modules for nitrogen and oxygen generator systems. Technology Overview ENGINEERING YOUR SUCCESS.

SERVICE MANUAL MODEL BA600AMST-S1 BREATHING AIR PANEL

Nitrogen Generators. PMNG Commercial Series. Section 50 Bulletin A -20

SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL

SERVICE MANUAL MODEL BA020AMST BREATHING AIR PANEL

ON-SITE INDUSTRIAL GASES. Nitrogen & Oxygen Generators

NTF-230 OPERATION MANUAL

Atlas Copco. On-site Industrial Gases Nitrogen & Oxygen Generators

Nitrogen Supply System

/ /

SERVICE MANUAL MODEL BA200AA-S1 BREATHING AIR PANEL

ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E)

4-7 kw/ hp. Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward

Potter Nitrogen Generators

Nitrogen Advantage. Better Tire Pressure Retention. Improved Fuel Economy. Extended Tread Life. Elimination of Oxidation. Reduction in Tire Failures

SERVICE MANUAL MODEL BA100BMST 100 SCFM PORTABLE AIR PANEL

SERVICE MANUAL MODEL BA200AMST-S1 BREATHING AIR PANEL

NTF-515. Operation Manual

SERVICE MANUAL MODEL BA020ANM-S1 BREATHING AIR PANEL

Instruction Bulletin Addendum For Pressure-Balanced In Situ Oxygen Probes

Workhorse-15 Oxygen Generator

Applied Compression s nitrogen generator packages offer users a cost-effective alternative to costly bottled nitrogen.

Model Series 62 Constant Differential Relay

Genie Supreme TM Model 123HP Installation & Operation Instructions

Workhorse 8 Oxygen System Model No 5665, 5673, 5679

Atlas Copco. On-site Industrial Gases Nitrogen & Oxygen Generators

OX SCFH Oxygen Concentrator. Installation and Operation Manual

Analytical Gas Systems Product Catalog


ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

DF-550E PROCESS ANALYSERS APPLICATIONS FEATURES

NGP-250/500 Nitrogen Generator Quick Start Guide

Genie Supreme Model 123 Installation & Operation Instructions

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER

Customer Responsibilities. Important Customer Information. Cary 4000/5000/6000i UV-Vis spectrophotometer Site Preparation Checklist

1020 Industrial Drive, Orlinda, TN fax

CAPITAL CONTROLS SERIES NXT3000

Air Eliminators and Combination Air Eliminators Strainers

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

Inert Air (N2) Systems Manual

Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability.

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

USER S MANUAL. N2-MISTRAL-0 / 25 L/min NITROGEN GENERATOR. Rev. 3 - August 2008

PRO-50 Instrument Supply Regulator

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

Pressure Regulators. Operating Instructions. Instrumentation

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

MARITIME PROTECTION NITROGEN SYSTEM

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

AirSep PSA Nitrogen Systems

Electropneumatic Transducer (I/P) Installation, Operation and

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

2 Sentry MCL Installation, Operation & Maintenance

NGN Series nitrogen generator

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

94270 Vapor Guard Tank Blanketing Valve Vapor Guard Tank Blanketing Valve What is Tank Blanketing? Features How does it work?

Nitrogen Tyre Inflator Owner s Manual

SERIES 30. Spring Operated Tank Blanketing Valve PROTECTOSEAL.

Integrity Testing LifeASSURE BNA045 and BNA065 Series Filter Cartridges

CS Controlled Dissolved Gas assembly with optional CS Air Aspirator assembly. Installation and Operation information

MEDICAL EQUIPMENT CATALOG

MODEL RP050BMST RESPIRATORY PROTECTOR MANUAL

AIR DRIVEN. Gas Boosters & SYSTEMS. Accepting VISA, MasterCard and American Express

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

The Shand & Jurs Model Vapor Guard Tank Blanketing Valve

Assembly and Installation Procedures

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

Avenger Model 33M Installation & Operation Instructions

Detector Carrier Gas Comments Detector anode purge or reference gas. Electron Capture Nitrogen Maximum sensitivity Nitrogen Argon/Methane

ADVANCED AIRLINE FILTER INSTRUCTION MANUAL

MEGR-1627 Instruction Manual

3M TM Versaflo TM AP-600 Series Air Filtration Panels For use with 3M TM Versaflo TM Supplied Air Respirator Systems. Work. in a World of.

CSA Sample Draw Aspirator Adapter Operator s Manual

SDS -Series 4C-D201/-D202 Supplemental Drying System User s Manual

Operating Guidelines for PermSelect Modules Liquid Contacting

RD(H)20/25 Pressure-Reducing Regulator User Manual

Type ACE95jr Tank Blanketing Valve

BREATHING AIR PURIFIER

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

OPERATING AND MAINTENANCE MANUAL

V DGX Series. Direct-Operated Regulators Manual D103834X012

System Pressure Manager Standard & System Pressure Manager Plus

Sullair Air Systems. *Assessment of the market for compressed air efficiency services. Technical report, U.S. Department of Energy, June 2001

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

THE GUIDE TO MEMBRANE NITROGEN GENERATORS

Float Operated Level Controllers

Oxygen Concentrator. Installation and Operation Manual. ClearWater Tech, LLC. Integrated Ozone Systems

Transcription:

Technical Information Installation, Operation, Installation, Operation and Maintenance and Maintenance Manual Manual Balston Model 75700-K728 Nitrogen Generator Figure 1-75700-K728 Overall Dimensions These instructions must be thoroughly read and understood before installing and operating this product. If you have any questions or concerns, please call the Technical Services Department at 800-343-4048, 8AM to 5PM Eastern Time (North America only). For other locations, please contact your local representative.) Please save product packaging for future use. General Description Engineered System Oxygen Monitoring! The Balston 75700-K728 Nitrogen Generator is a completely engineered system which will convert a compressed air supply into 95% to 99.5% purity compressed nitrogen. The generator is based on state-of-the-art membrane technology. Compressed air flows through the hollow fiber membrane module and is separated into a concentrated nitrogen output stream and an oxygen enriched permeate. The compressed nitrogen is delivered to the process or equipment downstream. The permeate is vented to the atmosphere. The Balston 75700-K728 Nitrogen Generator includes all the components required to convert compressed air into high purity nitrogen. The flow schematic (see Figure 2) shows all of the major components of the system. The system can be broken down into three primary functional groups. These are: prefiltration, air separation, and flow controls. An oxygen analyzer is also available as a separate accessory for the 75700- K728 (P/N 72-730). In hazardous applications where the oxygen content in nitrogen is critical (i.e. blanketing explosive chemicals or packaging food for extended shelf life), an oxygen monitor or trace analyzer should be used in conjunction with safety interlocks and/or alarm systems to assure proper nitrogen purity levels at all times. Bulletin TI-75700-K728 1

Description Prefiltration Air Separation Controls Two stages of coalescing prefiltration and an activated carbon hydrocarbon adsorber, and a particulate filter are supplied with the Balston 75700-K728 Nitrogen Generator to protect the membrane module from contamination. The filters are equipped with float drains which automatically open to empty any liquids which accumulate inside the filter housing. The carbon adsorber protects the membrane module from hydrocarbon buildup. The particulate filter traps any carbon dust which may escape from the carbon adsorber. Air separation takes place in the membrane module. The module consists of bundles of hollow fiber membranes. The inlet air enters the center bore of these fibers and travels the length of the fibers. As the air passes through these hollow fibers, oxygen and water molecules pass through the membrane wall at a higher rate than nitrogen molecules. This results in a high purity, dry nitrogen gas stream exiting the membrane module The oxygen enriched permeate stream exits the generator through the vent port on the right side of the unit. The controls on the Balston Nitrogen Generator consist of an outlet pressure gauge, a flowmeter and a flow control valve, (see Figure 1). Proper use of these controls will assure the user of a 95% to 99.5% nitrogen outlet stream, depending on operating pressure and flow rate. The pressure gage, which is mounted on the front panel, measures outlet pressure. The flowmeter measures the flow rate of nitrogen exiting the membrane module. The scale on this flowmeter is dimensionless because the operating pressure can range from 60 psig to 145 psig (4 barg to 10 barg). The Nitrogen Purity information on page 9 is used to convert the dimensionless flowmeter reading to SCFH, based on inlet air pressure and required purity. The flow control valve is used to set the flow rate through the system. FINAL STAGE GRADE DX PRE-FILTER Figure 2 - Flow Schematic 2

General Location Utilities!! Installation The Balston 75700-K728 Nitrogen Generator is a free-standing unit. Do not suspend the Nitrogen Generator from a wall or ceiling. Its considerable weight and size could pose a falling hazard. The inlet and outlet ports on the 75700-K728 are 1/4" female NPT. A 1/4" male connector rated for 145 psig (10 barg) should be used to connect to the Nitrogen Generator. The nitrogen sample port is 1/4" NPT and can be piped to an oxygen analyzer or trace analyzer. Pressure Regulator - A pressure regulator and gage should be installed directly upstream from the nitrogen generator to set and maintain the inlet air pressure. Maintaining a constant inlet air pressure is critical to the performance of the system. Flow Controller - If the application requires nitrogen at pressures higher than 10 psig (0.7 barg), install a flow controller downstream from the nitrogen generator, close to the point of use (see Adjustment Procedure section, page 4). The Balston 75700-K728 Nitrogen Generator should be located in an area where the ambient temperature is between 35 F and 104 F (2 C and 40 C). Installation of the unit in an area where the ambient temperature exceeds 104 F (40 C) or falls below 35 F (2 C) may affect the performance and/or life of the system. The environment surrounding the nitrogen generator should also be adequately ventilated. The 75700-K728 creates a 30% to 40% oxygen permeate stream which may pose a flammability problem in an oxygen-sensitive environment. Compressed Air - The Balston 75700-K728 Nitrogen Generator requires a source of clean, dry compressed air for operation. The incoming air should be between 35 F and 100 F (2 C and 38 C), with a pressure dewpoint of 35 F (1.7 C) and free of water, compressor oil, hydrocarbons, organic solvent vapors, and particulate matter. The compressed air consumption varies with inlet pressure and nitrogen purity. Consult chart on page 8 to ensure an adequate supply of compressed air is available for the generator. Drain Lines - The waste drained from the first two stages of prefiltration will consist of water and compressor oil and should be piped away to an appropriate disposal container using 1/4" OD plastic tubing. Figure 3 - Recommended Installation 3

Receiving Tank Installations Recommended Accessories In many applications, the process flow requirements for nitrogen fluctuate with time. As noted earlier, if the flow rate of the emergent nitrogen stream varies, the purity level of the nitrogen stream also varies; therefore, it is important to keep the nitrogen flow as constant as possible. A receiving tank can be installed between the nitrogen generator and the process to accommodate fluctuations in nitrogen demand and maintain nitrogen purity. If a receiving tank is to be used, a back pressure regulator and a check valve should be installed between the Balston Nitrogen Generator and the receiver tank (see Figure 4). The Balston 72-460 Back Pressure Controller contains both of these components and may be ordered as an accessory for the 75700-K728 Nitrogen Generator. The adjustable back pressure regulator, when set to the appropriate pressure, will maintain a constant pressure drop across the flow control valve. By controlling the pressure drop across the flow control valve, the nitrogen flow and purity will be kept constant and the variability in purity of the nitrogen process stream will be minimized. The check valve, when installed properly, will prevent any flow of nitrogen from the receiver upstream toward the generator, providing a more effective means of storing the emergent nitrogen. The Balston 72-730 Oxygen Analyzer (Product Bulletin PK-62) monitors the oxygen content of the nitrogen process stream from the Balston 75700-K728 Nitrogen Generator. The oxygen analyzer also has adjustable alarms to signal high or low oxygen concentrations, and alarm relay contacts for additional process controls. The oxygen analyzer can be connected to the sample outlet port (See Figure 1). A shutoff valve should be installed directly upstream from the analyzer and opened only when readings are being taken. The valve should be closed at all other times to maintain maximum output flow of nitrogen. Figure 4 - Receiver Tank Installation Operation Startup System Adjustment for Desired Outlet Purity The inlet and outlet connections to the Balston 75700-K728 Nitrogen Generator must be checked for leaks prior to system start-up. After the system is properly installed and checked for leaks, the inlet gate valve can be opened to introduce compressed air to the system. During start-up and adjustment of the system, the nitrogen produced by the unit will be of variable purity. If the application for the nitrogen is critically dependent on purity, the nitrogen produced during start-up or adjustment should be vented. If the outlet nitrogen flow is closed, the system will still consume compressed air. The inlet air is simply vented to atmosphere through the permeate ports of the membrane module. The user must determine the nitrogen purity, flow rate, and pressure required by the application prior to adjusting the system for desired outlet nitrogen purity and flow rate. The inlet air pressure must be constant in order for the system to supply nitrogen of 4

consistent purity to the application. The inlet pressure to the Balston Nitrogen Generator should be maximized (within process and generator parameters) to optimize the operation of the membrane module. The required inlet air flow rate and all flow and purity specifications for different operating conditions are shown in the specifications listing on page 9. Note: There will be a 10 psig to 15 psig pressure differential between the pressure of the compressed air supply at the inlet and the operating pressure of the membrane module. All flow rate/purity charts are based on the operating pressure of the membrane module. This pressure loss must be taken into account when determining the inlet pressure which will deliver the desired purity and flow of nitrogen from the generator. Atmospheric Pressure Applications (<10 psig/0.7 barg) Elevated Pressure Applications (<10 psig/0.7 barg) If the Balston 75700-K728 Nitrogen Generator System is being used to deliver nitrogen at or near atmospheric pressure (e.g. purging or blanketing applications), use the following procedure for start-up and adjustment of the system 1 Open the shutoff valve located on the front panel of the generator. 2 Adjust the (customer installed) inlet air pressure regulator. 3 Adjust the (customer installed) outlet pressure regulator to <10 psig (0.7 barg). 4 Consult the Nitrogen Purity Information on Page 9 to determine the proper flowmeter setting for the required process nitrogen purity and inlet air pressure. Adjust the flow regulator valve on the front panel (see Figure 1) to yield the proper flowmeter reading. 5 Allow the system to reach equilibrium at the desired flow rate, pressure, and purity parameters. This should take approximately 15 minutes. 6 If an oxygen analyzer (P/N 72-730) has been installed to monitor nitrogen purity, the readings should be checked and the analyzer re-calibrated on a routine basis. If the nitrogen purity level falls below the desired level, readjust the flow control valve until the proper nitrogen purity level is reached. (Note: If more than minor adjustments of the flow control valve are required to reach the desired purity level, please see the Troubleshooting section of this manual for further guidance.) If the Balston 75700-K728 Nitrogen Generator is being used to deliver nitrogen at an elevated pressure (>10 psig/0.7 barg), use the following procedure for start-up and adjustment of the system. (Note: In elevated pressure applications, the customer should install a flow controller downstream from the nitrogen generator, as detailed in the Installation section of this manual.) 1 Open the shutoff valve. 2 Adjust the (customer installed) inlet air pressure regulator. 3 Turn the Flow Control Valve to its fully open position. 4 Set the (customer installed) outlet pressure regulator (see Figure 1) to the desired outlet nitrogen pressure. 5 Consult the Nitrogen Purity information on Page 9 to determine the proper dimensionless flowmeter setting for the required process nitrogen purity and generator operating pressure. Adjust the (customer installed) flow controller until the dimensionless flowmeter shows the correct reading (based on the Nitrogen Purity Label). 6 Allow the system to reach equilibrium at the desired flow rate, pressure, and purity parameters. This should take approximately 15 minutes. 7 If an oxygen analyzer (Balston P/N 72-730) has been installed to monitor nitrogen purity, the readings should be checked and the analyzer re-calibrated on a routine basis. If the nitrogen purity level falls below the desired level, readjust the downstream flow controller until the proper nitrogen purity level is reached. (Note: If more than minor adjustments of the downstream flow controller are required to reach the desired purity level, please see the Troubleshooting section of this manual for further guidance.) 5

Receiver Tank Applications Temperature Equilibrium After all the components have been properly installed (see Figure 4), the following procedure should be followed to ensure optimal operation of the entire nitrogen supply system. 1 Open the shutoff valve. 2 Adjust the (customer installed) inlet air pressure regulator. 3 Set the flow regulator valve to its fully open position. The nitrogen flow meter reading should be at the top of the scale. 4 Close the shutoff valve to the process and open the vent valve downstream from the receiving tank to prevent substandard nitrogen from entering the process. 5 Adjust the back pressure controller until the pressure gauge on the nitrogen generator reads 10 psig (0.7 barg) less than the desired nitrogen storage pressure. Maximize the storage pressure in order to maximize the storage capacity of the selected receiving tank. 6 Set the flow control valve on the front panel of the nitrogen generator to the proper reading, as specified by the Nitrogen Purity Label. 7 Purge the entire system for 5 minutes, venting the initial nitrogen stream through the vent valve to atmosphere. 8 Close the vent valve, open the process shutoff valve, and Initiate the flow of nitrogen to the process. The use of a receiving tank upstream from the process, as detailed in this literature, significantly reduces the effects of fluctuating nitrogen demand on the purity of the nitrogen process stream from the Balston Nitrogen Generator. A 5 minute purge of the system (see Step 7 above) is needed each time the unit is started. If the temperature of the inlet air to the Balston Nitrogen Generator differs from the temperature of the module (i.e. ambient temperature), the system must be allowed to reach temperature equilibrium before a constant purity of nitrogen is delivered from the system. If the temperature difference is 10 F-20 F (5 C-10 C), this equilibrium period may be as long as 60 minutes. The inlet air temperature should not be higher than the ambient temperature, or condensation of water within the system may occur, resulting in inefficient performance of the generator. Performance of the Balston 75700-K728 Nitrogen Generation System is highly dependent on the temperature of the inlet air. The data on purity and flow rate presented in this bulletin is based on an inlet air temperature of 68 F (20 C). If the temperature of the inlet air at the point of use for this system varies from 68 F (20 C) by more than 5 F (3 C), the factory must be consulted for flow and purity information. If the temperature of the inlet air is expected to vary, recommends installing an Oxygen Analyzer (P/N 72-730) to provide assurance that the application is supplied with the desired purity of nitrogen. Evaluation System Upsets The performance and operating conditions of the Balston 75700-K728 Nitrogen Generator should be checked at least once per month. This routine system check should include correcting any changes in the flowmeter reading, confirming pressure gauge reading stability and operating pressure setting, and checking the downstream flowmeter (if applicable) to ensure flows are consistent with the required nitrogen purity level. The optimum performance of the nitrogen generator is dependent on system parameters remaining stable and accurate; as such, the use of an oxygen analyzer to monitor system performance is highly recommended. The Balston 72-730 Oxygen Analyzer is designed for this purpose (see Product Bulletin PK-62). System upsets relative to pressure or flow rate will result in variations in purity of the outlet gas. System upsets relative to temperature, dewpoint, hydrocarbon (e.g., organic solvent) vapor content of the inlet compressed air may result in variations of the system performance or damage to the membrane module. These types of upsets should be 6

eliminated from the compressed air delivery system to assure consistent performance of the Balston Nitrogen Generation System. Shutting Down Proper shutdown of the Balston Nitrogen Generator can be accomplished by simply closing the shutoff valve on the inlet line. If this valve is left open, the system will continue to consume compressed air. Closing the flow control valve will not prevent air consumption because the membrane module permeate ports are open to atmosphere. Maintenance! Before servicing the Balston Nitrogen Generator, isolate the unit from the compressed air supply and fully depressurize the system. All maintenance activities for the Balston 75700-K728 Nitrogen Generator should be performed by suitable personnel using reasonable care. Required maintenance for the Balston 75700-K728 Nitrogen Generator consists of changing the prefilter cartridges and final filter cartridge, replacing the carbon absorbent, and calibrating the performance of the system. The recommended service schedule and replacement part numbers are outlined at the end of this section. To ensure consistent product performance and reliability, use only genuine Balston replacement parts and filter cartridges. Replacement coalescing filter cartridges and carbon adsorbent for the nitrogen generator have been assembled into a maintenance kit (P/N MK76081-K728) which may be purchased through a local representative. The MK76081-K728 Maintenance Kit provides 6 months of filtration replacement components and consists of: two DuraDRY Grade DX coalescing filter cartridges, one DuraDRY Grade BX coalescing filter cartridge (prefilter and particulate filter), and an activated carbon adsorbent. The total time required for filtration replacement is 30-45 minutes. Filter Cartridge Replacement Activated Carbon Adsorbent Replacement Follow-up The filter cartridges in the coalescing and particulate filter assemblies are removed by: loosening the collar from the filter assembly, lowering the filter bowl away from the filter head, and unscrewing the element retainer from the base of the cartridge. Insert the new filter cartridge and reassemble the housing in reverse order. Make sure the proper grade filter is installed in the proper filter housing (housings are labeled on the front). In order to replace the activated carbon adsorbent material, the filter/adsorber assembly must be removed from the back of the nitrogen generator. Remove the inlet and outlet tubing from the filter/adsorber assembly and remove the two screws which hold the assembly to the generator. Remove the plugs from the carbon adsorber towers and invert over a waste container to empty the spent adsorbent. Re-fill with new adsorbent, seal and re-mount filter/adsorber assembly to the generator. Re-connect tubing to filter/ adsorber assembly. Pressurize the generator and check for leaks. The performance of the system should be reviewed on a monthly basis. This review should include checking the settings for inlet pressure, outlet flow rate, and outlet pressure. If these readings have changed from the original settings, adjustments must be made as described in the Adjustment Procedure section of this bulletin. Calibration must be performed routinely on any oxygen analyzer being used with the system. Consult the manufacturer for procedure and frequency of calibration. 7

Figure 5 - Maintenance Items Service Schedule 1st Stage 2nd Stage Carbon Adsorber Particulate filter Replacement Element 100-12-DX 100-12-BX See Note (1) 100-12-DX Change Frequency 6 Months 6 Months 6 Months 6 months 1 A maintenance kit MK76081-K728 is available and includes a new carbon tower assembly and filter elements. The recommended service life for carbon tower and filter elements on the 75700-K728 and K729 is six months. Recommended service life on the 75700-K511 is one year. 2 To ensure consistent product performance and reliability, use only genuine DuraDRY replacement parts and filter cartridges. System Specifications Inlet air consumption required @ indicated pressure and N 2 Purity Model 75700-K728 Operating Pressure (psig) Purity (% N 2 ) Inlet Air Required (SCFM) 100 97 5-10 8

Balston Nitrogen Generation System Model Number 75700-K728 Purity (% Nitrogen) 95.0-99.5 Flow Capacity Atmospheric Dewpoint Particles > 0.01µm Suspended Liquids Commercially Sterile Max. Operating Pressure Maximum Pressure Drop Ambient Operating Temperature Range Recommended Ambient Operating Temp. Inlet Air Temp. Range Maximum Recommended Inlet Air Temp. Electrical Requirements Dimensions Shipping Weight See Purity/Flow Charts below -58 F (-50 C) None None Yes 145 psig (10 barg) 15 psig (0.7 barg) 35 F - 104 F (2 C - 40 C) 68 F (20 C) 35 F - 100 F (2 C - 38 C) 68 F (20 C) None 16"w x 36"h x 10"d (40 cm x 92 cm x 26 cm) 75 lbs. (34 kg) Type 75700-K728 NITROGEN PURITY/FLOW CHART (Flow at indicated Operating pressure, Psig/Barg, @ 68 F/20 C) Approximate Nitrogen Purity 145 Psig/ 10 Barg 125 Psig/ 8.6 Barg 110 Psig/ 7.6 Barg 100 Psig/6.9 Barg 90 Psig/6.2 Barg 80 Psig/5.5 Barg (Percent, %) METER SCFH METER SCFH METER SCFH METER SCFH METER SCFH METER SCFH 95 76 237 68 197 61 169 55 147 49 128 43 108 96 66 204 58 170 52 145 47 127 42 110 36 93 97 52 165 47 138 41 118 37 103 33 89 28 75 98 45 143 40 119 35 102 31 89 27 77 23 65 99 27 94 23 78 21 67 17 58 15 50 13 43 99.5 13 55 10 46 * 39 * 34 * 30 * 25 1 THE READING, TAKEN DIRECTLY FROM THE FLOW METER ON THE CONTROL PANEL, IS DIMENSIONLESS. READ FLOW METER AT THE MIDDLE OF THE BALL. 2 PURITY SHOWN IS APPROXIMATE. ALL PURITIES ARE +/- 0.5%. IF A MORE ACCURATE READING IS REQUIRED, AN OXYGEN ANALYZER IS RECOMMENDED. ALL DATA SHOWN IN THE TABLE IS BASED ON AN OPERATING TEMPERATURE OF 68 F (20 C). * AN OXYGEN ANALYZER IS RECOMMENDED FOR SETTING THESE POINTS. 9

Notes & Cautions Notes Cautions! 1 The flow meter reading is dimensionless. Read flowmeter at the top of the ball. The actual flow at various operating pressures is converted into SCFH (standard cubic feet per hour) in the purity flow chart on Page 9. 2 Minimum purity shown on the purity label in percent nitrogen. All nitrogen purities are ± 0.5%. If a more accurate reading is required, use the Balston 72-730 Oxygen Analyzer or a trace analyzer. 3 All data shown in the flow chart is based on an operating temperature of 68 F (20 C). 4 At inlet air temperatures less than 68 F (20 C) or greater than 82 F (28 C) consult factory for flow rates. 1 The Balston 75700-K728 Nitrogen Generator should be installed in an area with adequate ventilation to reduce the flammability of the oxygen-rich permeate stream. The system should not be located in an area where the permeate stream poses the risk of explosion or combustion. 2 Nitrogen is nontoxic and largely inert. It can act as a simple asphyxiant by displacing oxygen in air. Inhalation of nitrogen in excessive concentrations can result in unconsciousness without any warning symptoms such as dizziness, fatigue, etc. 3 The maximum operating pressure of the system is 145 psig (10 barg). Operating the nitrogen generator at pressures above 145 psig (10 barg) will result in damage to the membrane. 4 The recommended operating inlet air temperature for the nitrogen generator is 68 F (20 C) or less. If the inlet air temperature will be higher than the ambient temperature, the compressed air should be cooled and filtered, to remove water and oil, prior to heating for introduction to the nitrogen generator. Inlet air must have a pressure dewpoint of 35 F (1.7 C) and be free of compressor oil, hydrocarbons, organic solvent vapors, and particulate matter. Do not use high temperature compressed air directly from the compressor. 5 The maximum operating inlet air temperature of the Balston 75700-K728 Nitrogen Generator is 100 F (38 C). If the inlet air temperature is above 100 F (38 C), the longevity of the membrane will be reduced and the warranty will be void. 6 The drain lines from the prefilters should be piped away to an appropriate collection vessel or waste treatment system (open to atmospheric pressure) to avoid any possible re-entrainment of liquid in the air which feeds the membrane module. 7 Changes in inlet pressure or outlet flow demand will alter the nitrogen purity. 10

Troubleshooting and Service! All troubleshooting and service activities should be performed by suitable personnel using reasonable care. Symptom Course of Action Loss of outlet pressure Loss of outlet flow Purity is lower than specified for operating conditions Air leak through drains of prefilters Check that the flow control valve on the generator is fully open and control the flow with a valve at the process. Check operating pressure to assure that it is greater than 60 psig (4.1 barg). Check the system for leaks. Check operating pressure to assure that it is greater than 60 psig (4.1 barg). Check setting of flow control valve. Adjust if necessary. Check the system for leaks. Check setting of flow rate compared to specification. Check the operating pressure to assure that it has not varied from the original reading. Check the system for leaks. Measure the temperature and dewpoint of the inlet air. The recommended temperature is 68 F (20 C) and the recommended dewpoint 60 F (15 C) or lower. Calibrate oxygen analyzer (if needed). Remove tubing from the drain and hold finger over drain opening for a few seconds to allow pressure to build, and drain to seal. Check inlet pressure. It should be greater than 15 psig (1 barg) to seal drain. Remove bowl from filter assembly and rinse with water. If leak persists, replace automatic float drain. (P/N 21552) 11

Don t Forget To: Serial Numbers 1 Complete and mail your registration card. 2 Keep your product certification in a safe place. 3 Call the Technical Services Department at 800-343-4048, 8AM to 5PM Eastern Time with any questions (North America only). For other locations, please contact your local representative. The serial number label for the unit is on the lower right hand side of the right side panel. For your own records, and in case service is required, please record the following: DATE IN SERVICE SERIAL NO. Please have the serial number available when calling for assistance. 100 Ames Pond Drive, P.O. Box 1262 Tewksbury, MA 01876-0962 Phone (978) 858-0505 Fax (978) 858-0625 For additional information call toll-free (800) 343-4048 or Visit our website 12 2000 Printed in U.S.A. Bulletin TI-75700-K728 All trade marks acknowledged