Two-stage pulse tube refrigerator with step displacer as phase shifter

Similar documents
Cooling Characteristics of GM-type Pulse Tube Refrigerator with Neon as Working Gas

Oil-Lubricated Compressors for Regenerative Cryocoolers Using an Elastic Membrane

Experimental Investigation on Stirling type Thermally Coupled Three Stage Pulse tube Cryocoolers with U type Configuration

Thermal Testing of an EM Two-Stage Coaxial Pulse Tube Cold Finger for Earth Observation Missions

Development of a Two-Stage High -Temperature Pulse Tube Cooler for Space Applications

Development of High Efficiency 4K Two-Stage Pulse Tube Cryocooler

Continuously Variable Inertance Tubes for Pulse Tube Refrigerators

JT Micro Compressor Test Results

Cryogenic Engineering Prof. M. D. Atrey Department of Mechanical Engineering Indian Institute of Technology, Bombay

Correction of Pressure Drop in Steam and Water System in Performance Test of Boiler

Research of Variable Volume and Gas Injection DC Inverter Air Conditioning Compressor

CFD Simulation and Experimental Validation of a Diaphragm Pressure Wave Generator

Dynamic Operation of a 4 K Pulse Tube Cryocooler with Inverter Compressors

Study on Performance of Intersection Around The Underpass Using Micro Simulation Program

Vibration-Free Joule-Thomson Cryocoolers for Distributed Microcooling

CFD Analysis of the Anti-Surge Effects by Water Hammering

Cryogenic Engineering Prof. M. D. Atrey Department of Mechanical Engineering Indian Institute of Technology, Bombay

The Relationship between the Depth Embedded Pipe Pile and the Force of Clamping Jaw

CRYOGENIC REFRIGERATION USING AN ACOUSTIC STIRLING EXPANDER

An Investigative and Synoptic Review on Helium Liquefaction Using a Commercial 4 K Gifford- McMahon Cryocooler

Concept of modernization of input device of oil and gas separator

Physical explosion analysis in heat exchanger network design

A Numerical Study of the Performance of a Heat Exchanger for a Miniature Joule-Thomson Refrigerator

A Numerical Simulation of Fluid-Structure Interaction for Refrigerator Compressors Suction and Exhaust System Performance Analysis

Influencing Factors Study of the Variable Speed Scroll Compressor with EVI Technology

Laboratory studies of water column separation

A Study on the Punch Shape for Improving Tool Life in Shearing AHSS

Influence of Ambient Temperature on Performance of a Joule-Thomson Refrigerator

Earlier Lecture. In the earlier lecture, we have seen Kapitza & Heylandt systems which are the modifications of the Claude System.

CFD Analysis and Experiment Study of the Rotary Two-Stage Inverter Compressor with Vapor Injection

u = Open Access Reliability Analysis and Optimization of the Ship Ballast Water System Tang Ming 1, Zhu Fa-xin 2,* and Li Yu-le 2 " ) x # m," > 0

Performance Analysis of Centrifugal Compressor under Multiple Working Conditions Based on Time-weighted Average

AN EXPERIMENTAL INVESTIGATION ON HELIUM LIQUEFACTION USING TWO-STAGE GIFFORD McMAHON CRYOCOOLER

Trends in high performance compressors for petrochemical and natural gas industry in China

Reliability Growth of Stirling-Cycle Coolers at L-3 CE

CYCLE ANALYSIS OF LINEAR COMPRESSORS USING THREE- DIMENSIONAL CFD

Helium recovery at the National High Magnetic Field Laboratory

Efficiency Improvement of Rotary Compressor by Improving the Discharge path through Simulation

NUMERICAL ANALYSIS OF SINGLE STAGE PULSE TUBE REFRIGERATOR

Acoustical Modeling of Reciprocating Compressors With Stepless Valve Unloaders

Two-way Fluid Structure Interaction (FSI) Analysis on the Suction Valve Dynamics of a Hermetic Reciprocating Compressor

RESEARCH OF BLOCKAGE SEGMENT DETECTION IN WATER SUPPLY PIPELINE BASED ON FLUID TRANSIENT ANALYSIS ABSTRACT

Development of Scroll Compressors for R410A

Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance

Urban planning and traffic safety at night

Performance Analysis of a Twin Rotary Compressor

Heat Transfer Research on a Special Cryogenic Heat Exchanger-a Neutron Moderator Cell (NMC)

Experimental Study of an Air Lift Pump

Two-Stage Linear Compressor with Economizer Cycle Where Piston(s) Stroke(s) are Varied to Optimize Energy Efficiency

A NEW PROCESS FOR IMPROVED LIQUEFACTION EFFICIENCY

Spallation target cryogenic cooling design challenges at the European Spallation Source

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

The Estimation Of Compressor Performance Using A Theoretical Analysis Of The Gas Flow Through the Muffler Combined With Valve Motion

Cryocoolers for infrared Missile Warning Systems

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

TESTING AND ANALYZING ON P-V DIAGRAM OF CO 2 ROLLING PISTON EXPANDER

Performance Characterization of the ABI Cryocooler

PERFORMANCE AND CHARACTERISTICS OF COMPRESSOR/EXPANDER COMBINATION FOR CO 2 CYCLE ABSTRACT

Numerical simulation of radial compressor stages with seals and technological holes

Investigation of Suction Process of Scroll Compressors

Helium Management of the ESS Target and Monolith Systems

Performance Analysis of a Helium Turboexpander for Cryogenic Applications with a Process Modeling Tool: Aspen HYSYS

Influence of rounding corners on unsteady flow and heat transfer around a square cylinder

An Investigation of Liquid Injection in Refrigeration Screw Compressors

Modification and experimental research on vortex tube

Development of high pressure-high vacuum-high conductance piston valve for gas-filled radiation detectors

Results of mathematical modelling the kinetics of gaseous exchange through small channels in micro dischargers

Characterization and Performance Testing of Natural Gas Compressors for Residential and Commercial Applications

An Experimental Performance Study of Vortex Tube Refrigeration System

Numerical analysis of gas leakage in the pistoncylinder clearance of reciprocating compressors considering compressibility effects

Performance Testing of a High Capacity Compressor for a 20K 20W Cryocooler

University of Cincinnati

Helium-Liquefaction by Cryocooler for High-Field Magnet Cooling

Physical Fitness For Futsal Referee Of Football Association In Thailand

Designing Flexible Plants for Market Adaptation

Proceedings of the ASME th Biennial Conference on Engineering Systems Design and Analysis ESDA2014 June 25-27, 2014, Copenhagen, Denmark

Simulator For Performance Prediction Of Reciprocating Compressor Considering Various Losses

Development of a high vacuum sample preparation system for helium mass spectrometer

Capacity Modulation of Linear Compressor for Household Refrigerator

Optimization of Air compressor Motor speed for Reducing Power Consumption

Analytic and Experimental Techniques for Evaluating Compressor Performance Losses

Physiological Demands of Playing Field Hockey Game at Sub Elite Players

First Experimental Data of the Cryogenic Safety Test Facility PICARD

Effect of Hot End Obstruction and Nozzle on the Performance of Vortex Tube

Compressors. Basic Classification and design overview

Design Optimization for the Discharge System of the Rotary Compressor Using Alternative Refrigerant R410a

Study on the Influencing Factors of Gas Mixing Length in Nitrogen Displacement of Gas Pipeline Kun Huang 1,a Yan Xian 2,b Kunrong Shen 3,c

ME1251 THERMAL ENGINEERING UNIT IV AIR COMPRESSORS

Comparative Study of VISSIM and SIDRA on Signalized Intersection

Fuzzy modeling and identification of intelligent control for refrigeration compressor

RELIABILITY ASSESSMENT, STATIC AND DYNAMIC RESPONSE OF TRANSMISSION LINE TOWER: A COMPARATIVE STUDY

67. Sectional normalization and recognization on the PV-Diagram of reciprocating compressor

FABRICATION AND OPTIMIZATION OF PERFORMANCE OF VORTEX TUBE PARAMETERS

Aalborg Universitet. Published in: Proceedings of Offshore Wind 2007 Conference & Exhibition. Publication date: 2007

Effect of attack angle on flow characteristic of centrifugal fan

Mid InfraRed Instrument (MIRI) Cooler Cold Head Assembly Acceptance Testing and Characterization

SUBJECT INDEX. Dashpot load Dead space - 115, 118 Degrees of freedom - 51 Design guidelines for Ringboms

Special edition paper

SIMULATION OF THE FLOW FIELD CHARACTERISTICS OF TRANSIENT FLOW

University of Cincinnati

Transcription:

IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Two-stage pulse tube refrigerator with step displacer as phase shifter To cite this article: Shaowei Zhu 2015 IOP Conf. Ser.: Mater. Sci. Eng. 101 012183 View the article online for updates and enhancements. Related content - Displacer Diameter Effect in Displacer Pulse Tube Refrigerator Shaowei Zhu - The influence of pressure ratio on the regenerator performance Y Lin and S Zhu - A Validation System for the Complex Event Processing Directives of the ATLAS Shifter Assistant Tool A Santos, G Anders, G Avolio et al. This content was downloaded from IP address 148.251.232.83 on 15/05/2018 at 02:45

Two-stage pulse tube refrigerator with step displacer as phase shifter Shaowei Zhu Institute of Refrigeration and Cryogenics School of Mechanical Engineering, Tongji University 4800, Cao an Road, Shanghai, 201804, China E-mail: swzhu2008@yahoo.com Abstract. A two-stage pulse tube refrigerator with step displacer is discussed by numerical simulation. There is an optimum swept volume ratio of displacer over compressor and optimum phase angle difference between the displacer and the compressor. The volume of connecting tube between the pulse tube and the displacer can be used as a parameter to separate the mixing of the phase shifter effect and work distribution effect of the step displacer. 1. Introduction In order to get cooling power at lower temperature with high efficiency, two-stage pulse tube refrigerator is necessary [1-4]. Till now, Stirling type two-stage pulse tube refrigerator is still not comparable with two-stage Stirling refrigerator. One of the problems is that the phase shifter is not strong enough, powerful phase shifter is needed. One of the choices is to use solid phase shifter, such as step displacer [5]. For the second stage, solid phase shifter is effective [6]. If the second stage uses a solid phase shifter, then to make it as a step type to let both stages use a solid phase shifter is a natural choice. If a step displacer is used, the phase shifter effect and work distribution effect are mixed together. In this paper, we will use the volume of the connecting tube to separate the phase shifter effect and work distribution effect. 2. Structure Figure 1 is the schematic of the two-stage pulse tube refrigerator. An after cooler, a first stage regenerator, a second stage regenerator, a second stage cold head, a second stage pulse tube, a second stage gas distributor and a second stage connecting tube are connected serially. Between the first stage and the second stage regenerator, a first stage cold head, a first stage pulse tube, a first stage gas distributor and a first stage connecting tube are connected serially. Compared to pre-cooling type two-stage [5], the first stage regenerator can work at desired condition, and there is no pre-cooling heat exchanger. The disadvantage is the difficult gas distribution problem in the regenerator if the regenerator is very big for high cooling power. 3. Mixing problem of phase shifter effect and work distribution effect On the assumption of ideal pulse tube refrigerator, the swept volume for the first stage and second stage is related to the cooling power and refrigeration temperature, which depends on the mission and we cannot change. From the regenerator efficiency view point, the swept volume for the first stage and second stage have to be optimized to let the mass flow rate and pressure at the cold end of the pulse Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI. Published under licence by Ltd 1

tube have a suitable phase angle difference. In general case, the swept volume for cooling power and for regenerator efficiency is difficult to be the same. This is the mixing problem of the phase shifter effect and work distribution effect of the step displacer. In order to solve the problem, the swept volume ratio of the first stage displacer space and second stage displacer space is set for cooling power, while the swept volume of one displacer space is just fit for the pulse tube, the swept volume of another displacer space is bigger than the requirement and its over swept volume is balanced by the dead volume between the displacer head and the pulse tube. In this paper, connecting tube is used as the dead volume. Step displacer is the simplest type. Though we can use different displacers for different stages, the structure is complex. For two-stage, two independent displacers may be acceptable. For three-stage, three independent displacers are too complex compared to one step displacer with three steps. Compared to mixing phase shifter of solid phase shifter and inertia tube, step displacer is also simple. Figure 1. Schematic of two-stage pulse tube refrigerator with step displacer. 10. after cooler 11. first stage regenerator 12. first stage cold head 13. first stage pulse tube 14. first stage gas distributor 15. first stage connecting tube 16. first stage displacer space 21. second stage regenerator 22. second stage cold head 23. second stage pulse tube 24. second stage gas distributor 25. second stage connecting tube 26. second stage displacer space 31. compression space. 4. Numerical method The numerical method in reference [7] is used for the simulation. It is the first numerical model of pulse tube refrigerator, and is further improved with momentum effect [8]. This numerical method has an essential contribution to the pulse tube refrigerator in the pulse tube refrigerator history. The basic working mechanism of the pulse tube refrigerator is explained with the numerical data of this numerical method, even the invention of the double inlet pulse tube refrigerator is mainly from the numerical results of this numerical method. 5. Swept volume ratio and phase angle difference The basic data of the refrigerator is in table 1. The room temperature is 300K. The first stage temperature is 80K and the second sage temperature is 20K. Working medium is helium gas with 2MPa charge pressure. Operation frequency is 50Hz. The step ratio which is the swept volume of the first displacer space over the second displacer space is 4, which means that the input power for the first stage and second stage is the same at ideal condition. The swept volume of the compressor is 200cm 3. The swept volume ratio which is the total swept volume of the first displacer space and the second displacer space over the compression space and phase angle difference which is the phase angle delaying of the compression space over the displacer space are changed for finding the optimum swept volume ratio and phase angle difference. 2

Parts First stage regenerator First stage pulse tube First stage connecting tube Second stage regenerator Second stage pulse tube Table 1. Main parameters. Parameters 70mm 50mm, porosity70%, wire diameter 0.035mm 40mm 200mm 10mm 200mm 40 50, porosity62%, wire diameter 0.025mm 20mm 200mm Second stage connecting tube 5mm 200mm Figure 2 shows the effect of swept volume ratio and the phase angle difference. There is an optimum swept volume ratio to let the first stage regenerator loss and the second stage regenerator loss become minimized. Near the optimum swept volume ratio, the first stage regenerator loss and the second stage regenerator loss increase with the increasing of phase angle difference. Other loss, which includes loss of the compressor and pulse tubes, increases with the increasing of swept volume ratio and the decreasing of phase angle difference. There is an optimum phase angle difference and swept volume ratio for efficiency. In the simulation range, the input power and cooling power of the second stage increase with the increasing of the swept volume ratio and phase angle difference. The cooling power of the first stage increases with the increasing of the phase angle difference. At phase angle difference 30 and 40, the cooling power of the first stage increases with the increasing of the swept volume ratio. At phase angle difference 20, the cooling power of the first stage has a peak point with the increasing of the swept volume ratio. The pressure ratio increases with the increasing of swept volume ratio and with the decreasing of the phase angle difference. Figure 2a. First stage regenerator loss. Figure 2b.Second stage regenerator loss. Figure 2c. Other loss. Figure 2d. Efficiency. 3

Figure 2e. Input power. Figure 2f. First stage cooling power. Figure 2g. Second stage cooling power. Figure 2h. Pressure ratio. Figure 3 shows the equivalent PV diagrams in the pulse tubes, mass flow rate and pressure wave at the cold end of the pulse tubes at the optimum point. There is a distance between the PV diagrams of the warm end and the cold end. The mass flow rate lags the pressure wave, indicating good condition for regenerator efficiency. In this case, the mass flow rate at the cold end of the first stage pulse tube and the second stage pulse tube are almost the same and the PV diagrams are very similar.. Figure 3a. Equivalent PV diagrams. Figure 3b.Mass flow rate and pressure. 4

6. Connecting tube effect At step ratio 8, the input power to the first stage is two times that of the second stage. In this case, if the swept volume of the second stage is optimized, the swept volume of the first stage would be too big. The dead volume of the connecting tube of the first stage should be increased so that the big first stage displacer swept volume can be balanced by the volume of the connecting tube. Figure 4 shows the loss, cooling power of the first stage and second stage, efficiency, input power and pressure ratio vs. first stage connecting tube ratio, which is the volume of the first stage connecting tube over the volume of the first stage pulse tube. The loss of the first stage regenerator increases with the increasing of the first stage connecting tube ratio. The loss of the second stage and other loss decrease with the increasing of the first stage connecting tube ratio. There is an optimum first stage connecting tube ratio for efficiency and the cooling power of the second stage. The first stage cooling power, input power and pressure ratio decrease with the increasing of the first stage connecting tube ratio. The PV diagrams, mass flow rate and pressure at the cold end of the pulse tube with connecting tube ratio 0.0625 and 1 are shown in Figure 5 and Figure 6, respectively. It is shown that the first stage connecting tube can adjust the PV diagrams and mass flow rate. Figure 4a. Loss vs. first stage connecting tube ratio. Figure 4b. Cooling power and efficiency vs. first stage connecting tube ratio. Figure 4c. Input power and pressure ratio vs. first stage connecting tube ratio. At step ratio 2, the input power to the second stage is two times that of the first stage. In this case, if the swept volume of the first stage is optimized, the swept volume of the second stage would be too big. The volume of the connecting tube of the second stage should be increased so that the big second stage displacer swept volume can be balanced by the volume of the second stage connecting tube. 5

Figure 5a. PV diagrams at first stage connecting tube ratio 0.0625. Figure 5b. Mass flow rate and pressure at first stage connecting tube ratio 0.0625. Figure 6a. Diagrams at first stage connecting tube ratio 1. Figure 6b. Mass flow rate and pressure at first stage connecting tube ratio 1. Figure 7a. Loss vs. second stage connecting tube ratio. Figure 7b. Cooling power and efficiency vs. second stage connecting tube ratio. Figure 7 shows the loss, cooling power of the first stage and second stage, efficiency, input power and pressure ratio vs. second stage connecting tube ratio which is the volume of the second stage connecting tube over the volume of the second stage pulse tube. The loss of the first stage regenerator increases with the increasing of the second stage connecting tube ratio. The other loss decreases with the increasing of the second stage connecting tube ratio. There is an optimum second stage connecting tube ratio for efficiency, and second stage regenerator loss. The first stage cooling power, input power 6

and pressure ratio decrease with the increasing of the second connecting tube ratio. There is an optimum second stage connecting tube ratio for the second stage cooling power. The PV diagrams, mass flow rate and pressure at the cold end of pulse tubes with second stage connecting tube ratio 0.0625 and 1.75 are shown in Figure 8 and Figure 9, respectively. It is shown that the second stage connecting tube can adjust the PV diagrams and mass flow rate. Figure 7c. Input power and pressure ratio vs. second stage connecting tube ratio. Figure 8a. PV diagrams at second stage connecting tube ratio 0.0625. Figure 8b. Mass flow rate and pressure at second stage connecting tube ratio 0.0625. Figure 9a. PV diagrams at second stage connecting tube ratio 1.75. Figure 9b. Mass flow rate and pressure at second stage connecting tube ratio 1.75. 7

7. Conclusion There is an optimum swept volume ratio and phase angle difference for two stage pulse tube refrigerator with step displacer for efficiency, and the volume of the connecting tube can be used as an adjustable parameter to separate the phase shifter effect and power distribution effect to let the efficiency be optimized. Acknowledgment The author is thankful for the support of National Natural Science Foundation of China (Grant No. 51476117). References [1] Chan CK, Nguyen T, Jaco C,Tomlinson BJ, Davis T 2003 High Capacity Two-Stage Pulse Tube Cooler Cryocooler 12 219-224 [2] YAN P D, GAO W L, CHEN G B 2009 Development of a linear compressor for twostage pulse tube cryocoolers J Zhejiang Univ Sci A 10(11) 1595-1600 [3] Yang LW, Thummes G 2005 High frequency two-stage pulse tube cryocooler with base temperature below 20 K Cryogenics 45 155 159 [4] Radebaugh R 2000 Development of pulse tube refrigerator as an efficient and reliable cryocooler Proc. Institute of refrigeration, London [5] Zhu S W, Matsubara Y 2015 Pressure Ratio Effect to Warm Displacer Type Pulse Tube Refrigerator, Cryocooler 18 245-251 [6] Duval J M, Charles I, Coynel A, Gauthier A 2008 Development of 15 K Pulse Tube Cold Fingers for Space Applications at CEA/SBT, Cryocooler 16 45-50 [7] Zhu S W, Wu P Y, Chen Z Q 1990 Double inlet pulse tube refrigerators: an important improvement. Cryogenics 30 514 520 [8] Zhu S W, Matsubara Y 2004 Numerical method of inertance tube pulse tube refrigerator. Cryogenics 44 649 60 8