NGP-250/500 Nitrogen Generator Quick Start Guide

Similar documents
NGP-300D. Installation, Operation, & Service Manual

ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E)

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)

NGP-1000D-M1/M2/M3. Installation, Operation, & Service Manual

Type 1 - Nitrogen Generation System. Designed for: Dry or Pre-Action Fire Protection Systems (FPS) with a total capacity up to 750 gallons

Type 3 - PSA Nitrogen Generation System

ECS Protector Nitrogen Inerting Vent (PAV-WN)

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

INS-1500/2000 (EU) Nitrogen Generators Installation, Operation, and Instruction Manual

Potter Nitrogen Generators

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

INS-100/250 (EU) Nitrogen Generator Installation, Operation, and Instruction Manual

Inert Air (N2) Systems Manual

AUTOMATIC TIRE INFLATOR # MW-60, MW-60-4WAY & MW-64HP

Universal Valve Company Inc

Universal Valve Company Inc

APPS-160 Gen 2 User Manual

TECHNICAL INFORMATION

444C DUAL PERFORMANCE VALUE PACK

200 PSI COMPRESSORS - MODEL NUMBERS

100C Air Compressor Kit

400C & 450C DUAL PERFORMANCE VALUE PACKS

DEOX FPS 1 CORRISION INHIBITING SYSTEM O&M MANUAL. Revision 2 Date 02/04/16

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Portable Oil Lube Air Compressors

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

NTF-230 OPERATION MANUAL

IMPORTANT SAFETY INSTRUCTIONS

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

Marschalk Model # 94000

Avenger Model 33M Installation & Operation Instructions

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

INS-PV Potter IntelliPurge Nitrogen Purge Valve & INS-RA Remote Annunciator

Concentrate Distribution System (Stand Mounted) A-CDS-70-X & A-CDS-TANK-X-ST Industrial Drive, Orlinda, TN 37141

INSTRUCTION MANUAL FOR MODEL 7360V VERTICAL CURING CHAMBER Revision E May

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

R E D I C O N T R O L S

OPERATION MANUAL NTF-15

DESIGN DATA. Dry 105a. September 5, 2008

TECHNICAL DATA. Q = C v P S

CORROSION AT THE AIR-WATER INTERFACE REMOVE THE GAS

OPERATION MANUAL NTF-60 Plus

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

Technical Information

SPECIFICATIONS TABLE Maximum Air Pressure 115 PSI Air Tank Capacity 20 Gallons

INS-PV Potter IntelliPurge Nitrogen Purge Valve

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

200 PSI FAST-FILL AIR SOURCE KIT

200 PSI HIGH-FLOW AIR SOURCE KIT

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction.

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

SDS -Series 4C-D201/-D202 Supplemental Drying System User s Manual

2 GAL AIR COMPRESSOR OPERATOR S MANUAL 1/3HP/2-GALLON IMPORTANT: READ THIS OPERATOR S MANUAL BEFORE USING

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

FAULT CODE TROUBLESHOOTING INDEX

SPECIFICATIONS ATTENTION

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

450P AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

SWIRLFLO Refrigerated fountains with FLEXI-GUARD

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

TECHNICAL DATA. Q = C v P S

EGL-12 OIL-LESS COMPRESSOR

TECHNICAL DATA. Q = C v P S

TECHNICAL INFORMATION

N2 BLAST Datasheet Preaction single interlock electric c/w N 2 Blast Nitrogen generating system Remote controlled unit

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury.

Installation, Operation, and Maintenance Manual

Bermad Pressure Reducing. Model: 42T

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide

OPERATING INSTRUCTIONS

Installation, Operation, and Maintenance Manual

ACCU-PULSE Installation and Operation Instructions

TECHNICAL DATA. Q = C v P S

CS Controlled Dissolved Gas assembly with optional CS Air Aspirator assembly. Installation and Operation information

OPERATING INSTRUCTIONS Pressure Control System PCS-20 through PCS-100

BUBBLER CONTROL SYSTEM

Installation, Operation, and Maintenance Manual Parker Balston Model N2-04 Nitrogen Generator

450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

Data Sheet Issue A

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA. Q = C v P S

NTF-515. Operation Manual

OPERATION AND MAINTENANCE INSTRUCTION MANUAL

Nitrogen Advantage. Better Tire Pressure Retention. Improved Fuel Economy. Extended Tread Life. Elimination of Oxidation. Reduction in Tire Failures

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

TECHNICAL DATA. Trimpac 257a. September 16, 2013

ULTRA-LIGHT DUTY ONBOARD AIR SYSTEM

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA. Trimpac 244a. September 16, 2013

MANUAL BE SERIES Test Benches

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

with O 2 Controller Instruction Manual

KKT Training Series: ECO Series, Preventative Maintenance

Transcription:

NGP-250/500 Nitrogen Generator Quick Start Guide Version: A July 2013 Potter Electric Signal Company, LLC 5757 Phantom Dr., Suite 125 P. O. Box 42037 Hazelwood, MO 63042 Phone: (314) 595-6900

Document History Document Version A Description First official release of Quick Start Guide Additional Information For additional information, please see document #5403585 (Nitrogen Generator Manual)

Table of Contents 1. Before Going to the Jobsite... 5 2. Uncrating and Inspection... 6 3. Installation of Nitrogen Generator... 7 4. Wiring of NGP-250/500... 8 5. Installation of Nitrogen Purging System... 8 Start-up and Operation: 6. Standard Filling Method... 9 7. Nitrogen Purging Procedure... 12 8. Normal Operation... 16 9. NGP-250/500 Maintenance... 16 10. Troubleshooting FAQs... 17

Quick Start Guide: NGP-250/500 Nitrogen Outlet Valve Oil-less Air Compressor Nitrogen Membrane Nitrogen Bypass Valve Nitrogen Test Port Nitrogen Test Port Valve Drain Filters Drain Tube Port Pressure Switches Auto Drain Valve Nitrogen Inlet Valve Tank Pressure Gauge Page 4 of 17

1. Before Going To The Jobsite 1. Find a location for the nitrogen generator to be installed meeting these requirements: Dimensions 57 x 41 x 16 (H x W x D) Dry, clean, and well-ventilated Ambient temperatures above 50 F at all times Access to front for service Conveniently located near fire sprinkler system connections Conveniently located near drain 2. Run a dedicated electrical circuit with an electrical disconnect switch to sprinkler room. NOTE: The NGP-250 and 500 Nitrogen Generators operate at the same voltage but different amperage. Part # Model Phase Amperage Voltage 1119400 NGP-250-1A SINGLE 7.2A 115V 1119401 NGP-250-2A SINGLE 3.5A 208V 1119402 NGP-250-3A SINGLE 3.1A 230V 1119403 NGP-500-1A SINGLE 18.0A 115V 1119404 NGP-500-2A SINGLE 7.7A 208V 1119405 NGP-500-3A SINGLE 9.0A 230V Page 5 of 17

2. Uncrating and Inspection 1. On arrival, do a full inspection by checking all packages and crates in the shipment for damage. If damage is found, sign for the damage or refuse the shipment. Contact the carrier immediately and file a shipping damage claim with the carrier. 2. Check to ensure all components are contained and no visible damage has occurred during shipping. Important: Read all of the safety information in this manual before installing or operating this equipment. NGP-250/500 crate checklist: Item Nitrogen cabinet N2 storage tank N2 membrane (inside cabinet) Oil-less air compressor (inside cabinet) Nitrogen analyzer (inside cabinet) Manual and Quick Start Guide (inside cabinet) 10ft. 1/4 Condensation drain tube (inside cabinet) 3. Each nitrogen generator requires a minimum of one Air Maintenance Device and one Nitrogen Purge Valve (Model NGP-SPV or NGP-SPV AUTO). Check to see these components have arrived. NGP-250/500 required accessories: Item Air Maintenance Device (One per riser) NGP-SPV/AUTO (One per riser) AMD-1 NGP-SPV AUTO Required items supplied by sprinkler contractor: Item 4 anchor bolts (fit 7/16 holes on frame) NPT piping from generator to system (1/2 or greater) Dedicated electrical circuit with electrical disconnect 1/4 rubber drain tubing if more than 10ft. are needed Page 6 of 17

3. Installation of Nitrogen Generator 1. Ensure the location for installation of the NGP- 250/500 is a clean, dry, well-ventilated area with ambient temperatures above 50 F at all times. 2. Ensure that the dedicated electrical circuit with an electrical disconnect switch is the correct voltage and conveniently located for wiring. If not, contact a licensed electrican to install one. 3. Ensure the nitrogen generator is accessible at the front for servicing all major components inside the cabinet and near the fire sprinkler system connections. 7/16" holes 4. Install the NGP-250/500 by anchoring the unit to a level surface using the four 7/16 diameter holes on the frame. 5. Install 1/2 NPT pipe (or larger) from the nitrogen storage tank outlet connection to the sprinkler system air maintenance device using standard accepted installation practices. (Note: Tank comes with two 1/2 female NPT connections located on both sides. Choose either left or right side for use.) Install Drain Tube by pushing it into the Drain Tube port until it bottoms out. (Note: Tubing will need to be restrained, as air pressure from drain valve may cause the tubing to be displaced from drain.) 1/2 female NPT connector 6. Install 1/2 NPT pipe (or larger) from the air maintenance device to the sprinkler system using standard accepted installation practices. Additional system components may be required. (Note: AMD shown in closed position.) Page 7 of 17

4. Wiring of NGP-250/500 All wiring should be performed by a licensed electrician and conform to the NEC and all applicable local standards. For wiring instructions, refer to the Wiring Diagram. 5. Installation of Nitrogen Purging System Each riser requires a minimum of ONE Nitrogen Purge Valve to be installed prior to implementing the Nitrogen Purging Procedure. For installation instructions, refer to the NGP-SPV (Model # 1117984) bulletin (# 5401520) or NGP-SPV AUTO (Model # 1119799) bulletin (# 5401521) supplied with each purge valve. NGP-SPV (Nitrogen Generator Self Purge Valve) NGP-SPV AUTO (Nitrogen Generator Automatic Self Purge Valve) Purge Valves must be installed in a level horizontal position (shown above). Page 8 of 17

Quick Start Guide: NGP-250/500 6. Standard Filling Method 1. Before beginning, make sure the water supply is turned off. 2. Make sure all piping connections have been made according to installation instructions. 3. Close all air maintenance device valves. If multiple AMDs are used, ensure all valves are in closed position on each one. (Note: AMD shown in closed position.) 4. Fully open the nitrogen bypass valve. 5. Fully close the nitrogen inlet, outlet, and test port valves. Nitrogen outlet valve (Shown in closed position.) Nitrogen bypass valve (Shown in open position.) Nitrogen test port valve (Shown in closed position.) Nitrogen inlet valve (Shown in closed position.) Page 9 of 17

6. Power the air compressor system ON. 7. Allow tank pressure to reach 80 PSIG. 8. Check all piping connections for leaks. (Note: Check to see if pre-plumbed piping is leaking; fittings may have loosened during shipping.) Tank pressure gauge Note: While filling system with air, and after compressor shuts off, the air bleeder valve will continue to exhaust air. This minor pressure release is normal and will stop once valves are positioned to nitrogen purge mode. THE AIR BLEEDER VALVE IS FACTORY SET AND SHOULD NOT BE ADJUSTED Page 10 of 17

Quick Start Guide: NGP-250/500 9. After making sure there are no leaks, open the air maintenance device bypass valve to begin filling the sprinkler system. If there is more than one AMD on the system, then close the others. Fill one system at a time. 10. 11. Allow the sprinkler system to reach the desired pressure. (Note: This should finish in 30 minutes per the desired NFPA guidelines.) AMD Bypass valve shown OPEN. As soon as sprinkler system pressure is reached, put the sprinkler system back into service by placing the air maintenance device in the maintenance position (refer to the air maintenance device manual for proper operation). Maintenance Valves shown OPEN If there is more than one AMD on the system, then do EACH system individually and repeat steps 9 through 11 afterwards. Allow air compressor to run for a max of 40 minutes with a 20 minute rest before starting again. Page 11 of 17

7. Nitrogen Purging Procedure Once the system is at the desired supervisory pressure, it is time to start injecting nitrogen and purging the oxygen. 1. Close the nitrogen bypass valve. 2. Slowly open nitrogen outlet valve. 3. Slowly open the nitrogen inlet valve. Nitrogen outlet valve (Shown in open position) Nitrogen bypass valve (Shown in closed position) Nitrogen test port valve (Shown in closed position) Nitrogen inlet valve (Shown in open position) 4. Go to the end of the system and put the NGP-SPV / AUTO ball valve into the purge position. NGP-SPV shown in purge position. Page 12 of 17

5. Additional NGP-SPV AUTO Step --- Hit the TEST button on the timer. This restarts the timer and opens the solenoid valve. The NGP-SPV AUTO will now be open for 14 days, before it automatically shuts off. 6. While the air compressor is running, monitor the nitrogen generator membrane pressure. Pressure should remain steady at roughly 120 PSIG 7. The air compressor should automatically cycle OFF when the nitrogen storage tank pressure reaches 80 PSIG. 8. The air compressor should automatically turn ON when the nitrogen storage tank pressure drops to 60 PSIG. 9. Run the system for at least 5 ON/ OFF cycles. Take note that the system cuts off at 80 PSIG and turns on at 60 PSIG. (Note: The compressor should not run for longer than 15 minutes to reach 80 PSIG in the nitrogen tank.) Page 13 of 17

10. To decrease time cycle, bleed the tank pressure using the pressure relief valve located on the top of the tank. 11. Pull pressure relief valve ring and relieve air pressure until compressor starts running (this will happen once tank pressure drops below 60 PSIG). Once tank pressure reaches 80 PSIG, the compressor will turn off. Complete this process 5 times. Pressure Relief Valve 12. After five cycles, check the nitrogen purity at the TEST PORT on the cabinet using the nitrgen purity analyzer. The nitrogen purity should read 95-99%. (Note: Ensure the nitrogen test port valve is in the open position) Test Port 13. If the nitrogen purity levels are below 95% after 5 complete cycles, contact Potter Techncal Support. 14. Check the nitrogen purity level of the sprinkler system at the NGP-SPV / AUTO purge valve assembly using the portable nitrogen analyzer before leaving the jobsite. 15. Record purity level. (Note: On average it takes 14 days for the system to reach desired purity. Do not be alarmed by a low number if system has only been running a few hours.) 16. Turn off analyzer after use. Nitrogen Purity Analyzer Page 14 of 17

17. Continue the purging until acceptable nitrogen levels are reached. It is recommend that you return in 14 days and check the purge valve. 18. Close the purge valve after desired nitrogen purity level is achieved. (Note: This step will be done automatically if you are using the NGP-SPV AUTO only) Page 15 of 17

8. Normal Operation The nitrogen generator is controlled by pressure sensors that monitor the nitrogen tank pressure and automatically starts and stops the air compressor based on the control settings. Occasional start and stop operation of the Potter Nitrogen Generator is normal. Frequent start and stop operation (more than four times per hour) is not normal operation indicating service is required. Immediately turn off nitrogen generator and contact Potter Technical Support. When the air compressor is not running, the membrane pressure gauges will read 0. Only the tank pressure gauge indicates pressure while the compressor is not running. When the air com pressor is running, both pressure gauges read pressure and typically show different pressure readings this is normal. If the generator is running for more than 40 minutes continuously, immediately turn off the nitrogen generator and contact Potter Technical Support. 9. NGP-250/500 Maintenance Please Refer to the Nitrogen Generator manual ( # 5403585) for additional information. Page 16 of 17

10. Troubleshooting FAQs Question: The air compressor cycles frequently and/or continuously runs. Answer: 1) Check the pressure gauges on the nitrogen generator tank. If the pressure is above 80 PSI, then shut off the nitrogen generator system immdeiately. The potential problem could be a pressure switch failure. 2) Ensure all valves on the compressor are opened or closed where necessary. 3) Isolate the compressor from the nitrogen generator system if cycling continues. Check all of the fittings for leaks and repair accordingly. 4) If the cycling process continues and there are no leaks on the nitrogen generator side, check the sprinkler system for additional leaks. Question: Answer: The air compressor does not turn on. 1) Ensure the power switch is in the ON position and properly wired. 2) Check the pressure gauge on the Nitrogen Generator tank. (Note: The nitrogen generator system will not turn on unless the pressure is below 60 PSI.) 3) Make sure all valves are open or closed where necessary. Question: Answer: The air compressor takes too long to fill. 1) Confirm all valves are in the correct position. 2) Check the nitrogen generator system for leaks. 3) Check sprinkler system for leaks. Page 17 of 17