Instruction Manual. PLT Series. 1. General Specification. 2. Installation. 3. Wiring. 4. Function. 5. Setting & Calibration

Similar documents
DPC-30 DPC-100. Reference Manual

Sensoric 4-20 ma Transmitter Board Operation Manual

SSL. Smart Valve Positioner.

INSTRUCTION MANUAL. FLOAT TYPE LEVEL TRANSMITTER HT-100R Series HITROL CO., LTD.

Installation, operating and maintenance Instructions for Seemag bypass level indicator

SSR. Smart Valve Positioner.

Installation and Operation Manual

INSTRUCTION MANUAL STATION CONTROLLER SC100 MOTOR PROTECTION ELECTRONICS, INC.

Electro-Pneumatic Converter YT-940 SERIES

陕西创威科技有限公司. Shaanxi Creat Wit Technology Co., Ltd. Precision pressure calibrator-cwy300 Operating Manual

BI-680 Online Dissolved Oxygen Controller Instruction Manual

Hand-held pressure calibrator with integrated pump Model CPH6600

Pressure Transmitters 36 F-27839

SPD310/SPD360 Air Differential

T EK-SUB 4800C 19 mm Submersible Level Transmitter

ACV-10 Automatic Control Valve

SPECIFICATIONS ATTENTION

PX3005. Rangeable Industrial Pressure Transmitter M-5721/1018

[Instruments for vacuum measurement, checking and adjustment] 3

Instruction Manual Differential Pressure Transmitter

TEL/jlRE" Introduction. Display Features and Modes. Startup Procedure. Power-Up Procedure. Adjustment Modes

Integral type Differential pressure flowmeter VNT Series

AMS 2710 PCB pressure sensor module with V output

BUBBLER CONTROL SYSTEM

Precision pressure sensor Basic version Model CPT6020

10 switches simultaneously. The settings of the master sensor (source of copy) can be copied to the slave sensors. Reducing setting labor

3.0 Pressure Transmitter Selection

Pressure transmitter PASCAL Ci4

Preferred Instruments Danbury, CT USA

KING-GAGE. Calibration Instruction Manual. D/P LiquiSeal Purge Control and D/P Purge Control

MANUAL KPS Pressure Control Valve

86BSD Backside Digital Output

Manual Weighingblock VB2 series and Uniscale

OEM Manual MODEL 2305 ECONOMICAL DIGITAL SINGLE CYLINDER SCALE

Additel 780 Series Pressure Controller

P9000 DESCRIPTION. For parts requiring RoHS compliance, please contact factory. P February /6

TH-1800-T TRX-700-CNG Converter

Digital Vacuum Regulator

Features. Description

Installation and Operation Manual

KERN EG/EW Version /02

OEM Manual. MODEL ½ Digit DRUM SCALE

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05

DM01. Please visit our website: Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

BUBBLER CONTROL SYSTEM

OPTIBAR P 1010 C Technical Datasheet

DM01. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION SPECIFICATIONS. CE (EMC) Compliant

Troubleshooting Guide: 640 Pediatric Exam Table with Midmark Scale

ETd 04. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. Type: ETd 04. class 0.05

SAPCON. User Manual. Capacitance Continuous Level Indicator. . Introduction. . General Description. . Principle of Operation. .

For a similar sensor with o-ring mounting, refer to the 85BSD digital output pressure sensor.

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm)

User's Manual. Heavy Duty Dissolved Oxygen Meter. Model

High-performance submersible pressure transmitter For level measurement Model LH-10

Table of Contents. Sensor Calibration and Troubleshooting CDS4000 CO 2. Introduction 1. Handling Information. Calibration 2.

CDS-2000 CO 2 Sensor Verification, Calibration, and Troubleshooting Bulletin

Design Features. General Description

Digital Pressure Gauge Main features: Data Sheet: DFP.418.R4.EN

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES

Pneumatic high-pressure controller Model CPC7000

Additel 780 Series Pressure Controller

TEK-SUB 4800B. Submersible Level Transmitter. Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys LEVEL

User s Guide. Pressure Controller for liquid delivery systems

High-performance submersible pressure transmitter For level measurement Model LH-20

IPH 2 & IPX 2. Features Type 4X & Explosion-Proof Current-to-Pressure (I/P) Transmitters. Approved for Use with Natural Gas.

P-5215 Differential Pressure Transmitter

High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20

Digital Pressure Gauge Main features: Data Sheet: BIT02B.417.R6.EN COVER on request

Maintenance Manual. Liquid Level Transmitter CT801-SI, CT801-TA

CDP-100S Pressure Type Level Transmitter

IP65 Air Differential Pressure Switch

GASGUARD VENT LINE3 Ammonia Sensor OPERATING & INSTALLATION MANUAL

The M-Series Eletta Flow Meter High accuracy DP Flow Meter with multiple functions

HS653 Negative Pressure Ventilation Controller

Operating Instructions Part No

STARLOG. Capacitive Water Depth Probe

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1)

Digital Indicating Dissolved Oxygen Meter AER-102-DO. Instruction Manual

P900. P900, Datenblatt Seite 1 DESCRIPTION

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

2600T Series Pressure Transmitter Models 264DC Differential and 264HC Gage Level Transmitters. Kent-Taylor

Inductive Linear Displacement Transducers Model IW 260 Measuring strokes: 80 mm, 170 mm, 240 mm, 360 mm

RAI-M series RUDDER ANGLE INDICATOR SYSTEM

JUMO dtrans p30 Pressure Transmitter

Wing Union/Hammer Union Pressure Sensors. Datasheet. Models 435/437

T EK-COR 1100A Coriolis Mass Flowmeter

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

SDI mA Pressure Transducer (Submersible + Dry) Model WL2100 Operating Manual

WIKA INSTRUMENT CORPORATION

VR46.5V(A)/VR86.5V(A) SERIES

High-performance submersible pressure transmitter For level measurement Model LH-20

SX150A. Features. Typical Applications. Description

MPM426W/436W Submersible Level Transmitter

Datasheet May, 2017 HPSD 4000 Pressure Transducer 1/5. Applications

210 Series Transmitter with External Electrochemical Sensor

Operator: Save these instructions for future use!

Heavy Duty Dissolved Oxygen Meter

EASIDEW TRANSMITTER with Current Source Output

Transcription:

4 Digit Display, 4-20mA Output Instruction Manual (Digital Differential Pressure Transmitter) 1. General Specification 2. Installation 3. Wiring 4. Function 5. Setting & Calibration 1

4 20 1 Differential Pressure Transmitter Model : 100 92 Range : Max Pressure : S / N : 1 2 3 4 EXT. 18-35V + OUT _ ULFA TECHNOLOGY CO.,LTD HIGH LOW MADE IN KOREA unit: mm 5 75 General PLT Series pressure transmitter are measures and controls positive, negative(vacuum) and differential pressure of air or non corrosive gases, and for the variously choice of ranges available to suit your needs precisely. The PLT Widely used to measure fan and blower pressures, filter resistance, pressure drop across orifice plates, liquid levels in storage tanks and many other applications. The PLT model has four functions of gauge, peak pressure detection, Offset(p) pressure and transmitter. It is very easy to set and use by front pad key. Accuracy is +/-0.25% of full scale. Specification GENERAL Maximum Pressure: Rated Range x 3 Media Compatibility: Air and non corrosive gas Pressure Range: Refer to range table ELECTRICAL Power Supply: Connections: Display: Warm up Time: TRANSMITTER Connections: Output Signal: Loop Resistance: Zero & Span Adj: DC24V(100-.220VAC 50~60Hz) 2 screw terminal block 4 Digit LED 15 minutes 2 Screw terminal block 4-20mADC(limited at 30mADC) 0-1100 One touch Adjustable on Panel PERFORMANCE AT 23 Range Table Zero Output: 4 ma Model No Range Resolution Full Span Output: 20 ma Accuracy: ±0.25 % FSO(Includes -B15M ±15.0 mmh 2O 0.1 mmh 2O Linearity, Hysteresis & Repeatability) -B150M ±150.0 mmh 2O 0.1 mmh 2O Operating Temperature: 0 to 70 -B1500M ±1500 mmh 2 O 1 mmh 2 O -B760H ±760 mmhg 1 mmhg MECHANICAL -D30M 0~30.0 mmh 2 O 0.1 mmh 2 O Pressure Connections: 1/8" PT female -D300M 0~300.0 mmh 2 O 0.1 mmh 2 O Materials: Aluminum Case -D3000M 0~3000 mmh 2O 1 mmh 2O Weight 600g -B01K ±1.000 kg/cm 2 0.001 kg/cm 2 STANDARD ACCESSARIES -B07K ±7.00 kg/cm 2 0.01 kg/cm 2 Tow(2) 1/8" PT plugs for duplicate/ Snap ring We can apply to other user specification Mounting ring, four(4) mounting screws (Pressure units and range) 2

Installation LOCATION : Select your site location, Clean and dry, no shock and vibration, proper to the ambient temperature and humidity in use. PANEL MOUNTING The PLT Series Digital Pressure Transmitter is designed for panel mounting in a single 93mm diameter hole. FIG.1 SNAP RING SNAP RING GROOVE SCREW MOUNT RING A panel mounting fastening kit is provided with all PLT Series Pressure Transmitter. 1. Select your site location, mark the appropriate panel cutout and complete the necessary panel cut. 2. Carefully insert the Pressure Transmitter through the hole from front of the panel. 3. Carefully insert the mount ring through the body of PLT from back side. 4. Insert the snap ring to the snap ring groove. 5. Tightening four mount screw through the mount ring from back side. PRESSURE PORT CONNECTION 93mm HOLE PANEL Tow(2) PT 1/8" barbed nipples are provided with all PLT Series Pressure Transmitter 1. Wind teflon seal tape 3 or 4 times on the screw of the nipple and tightening it in the pressure port high and low 2. If you use the PLT to measure differential pressure, high pressure is connect to 'HIGH" port, and low pressure is connect to "LOW" port. 3. If you use PLT to measure single pressure, positive pressure is connect to "HIGH" port and negative pressure(vacuum) is connect to "LOW" port. (In this case, another port is open to air) 4. Standard pressure connections are barbed fittings for 3/16" I.D. tubing. Wiring POWER CONNECTION The following procedures are to be used to install a standard 24V DC main power source. 1. Before connection, the user must first confirm that the power specification is DC24V or AC100-220V. 2. Verify that the facility's main power source is turned off or disconnected. 3. Connect lead cable to power terminal matching polarity as shown in FIG.2 below. Take care that wrong wiring will damage the Instrument and malfunction (AC220V is not concerned to polarity) CURRENT OUT CONNECTION(4-20mA) The PLT sends a standard 2wire 4-20mA current out 1. Connect lead cable to current out terminal matching polarity as shown in FIG.2 below. 2. Do not run the signal cable along with any high voltage or power cable or put them in the same race way. It may cause malfunction due to induction. 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 50 Receiver Resistance(Ω ) 1 2 3 4 Receiver ma Vps-12.0 R Max = 20mADC FIG.2 POWER SUPPLY 24VDC 4~20mA The ranges of optimum receiver resistance is refer to below graph. Max Value 0 5 10 15 20 25 30 35 40 Supply Voltage(VDC) 3

Function Zero setting : Optimize display and current out to zero automatically by front key pressed. Peak pressure Measurement : This mode is display for peak pressure by supplied pressure. And the display is cleared by press enter key in the peak Offset(p) pressure Measurement : This mode is display the changed pressure based on the current pressure. Current pressure is turned into "0" when offset mode selected. This mode does not concern to 4-20mA current out put. Sampling time setting : Sample rate is 0.1sec of this product. Sampling time is measuring time by sample rate. For example, if setting time is 2 sec, PLT measures 20 times for 2 seconds and out to display and 4-20mA out put by average of 20 times measured value. Setting and Calibration Hear by describe key function and setting methode. Please read this section carefully for the correct and optimum use of this product. Key functions UP DOWN MODE ENTER Peak mode - Increase setting value - Offset mode set/reset - Decrease setting value - Peak pressure mode set/reset - Entering into the setting mode - Setting item circulation - Save setting value - Clear peak value in the peak mode - Release setting mode Press the (down) key once to set peak mode Transmitter : PLT has 4-20mA current out put. Span (20mA) range can be changed within original "PEA" displayed like left while press peak key range. Communication(option) : Measurement pressure can be sent by RS232 or RS485 for option Press the ENTER to reset peak value and newly start specification. ID setting : This mode set identification number for communication. Press the (down) key once more to release peak mode Over pressure warning : PLT displays warning on LED for over pressure (positive and negative). Upper 4 elements of segment(" ") blink for warning when measurement pressure over 10% for high pressure(factory setting value), And under 4 elements of segment(" ") blink for warning when measurement pressure under 10% for low pressure(factory setting value), Factory setting recovery : The parameters are changed all to factory setting value and all user setting value is cleared. Offset mode Press the P(UP) key once to set offset mode "delt" displayed like left while press P key Press the P(UP) key once more to release offset mode 4

User setting mode Entering User setting mode : Press MODE key for more than 3seconds till appear "I n t" on LED into the user setting Press the MODE key once in user setting mode to change setting item. The setting item circulate " I n t " " PoFS " " P 4 " " P20 " " Id " " FACt " " I n t " while mode key press repeated. Each item setting methode is refer to next pages. Save : If you complete your setting in the each mode, save and exit to measure Press ENTER for more than 3 seconds to save and exist in the setting Release User setting mode : If you are not operate this instrument for about 1 minute, It's released user setting mode automatically and return to measuring Sampling time setting It can be set 0.1~5.0 seconds by 0.1 sec resolution. PLT reading pressure 0.1sec interval for a setting time and calculate average pressure to display and 4-20mA output. (ex) setting time : 2 sec PLT reading pressure 20 times for 2 seconds and calculate average of measured 20 data to display and 4-20mA current output. This functions is useful to measure hunted pressure Zero setting Optimize zero to display and current out automatically by front key pressed. CAUTION : Release pressure port free before zero set 4mA current setting Press than MODE for more 3 seconds till display till appear LED "PoFS" on set zero and exit to measure "PoFS" blink for about 5 seconds to calculate zero. more than 5 seconds till display to save and exist in the setting This function is set pressure level to 4mA current out. Generally pressure zero is setting to 4mA current out. By the way, negative pressure is setting in another case. PLT can be set any pressure level to 4mA current out between low and high pressure range. Low and high pressure ranges are setting in factory. display like left. Release MODE key then appear current set time on LED display (default set time is 0.5 sec) Set your sampling time use up/down key appear "SAvE" on display to save and exist in the sampling time setting mode till appear "P4" on LED Set your pressure level to 4mA out use up/down key display to save and exist in the setting mode 5

20mA current setting This function is set pressure level to 20mA current out, That is set span. PLT can be set any pressure level to 20mA current out between low and high pressure ranges. Low and high pressure ranges are setting in factory. Recall to Factory setting value This function is recall to initial states of factory out from unmatched user parameters that zero, span etc. till appear "P20" on LED till appear "FACt" on LED Set your pressure level to 20mA current out use up/down key recall and exit to measure to save and exist in the setting mode to recall and exist in the setting mode ID No setting ID number is use for address for communication to master. It's concern to PLT communication function installed.(option) till appear "ID" on segment. Set your ID No use up/down key(0~255) default set is 0. to save and exist in the setting ULFA TECHNOLOGY CO.,LTD 344, industrial zone,201 haan 3-dong kwang myung-city, kyung ki-do 423-754 KOREA TEL:02-806-4403 FAX:02-806-4406 ulfatech@ulfatech.com Copyright c 2003.08 ULFA TECHNOLOGY CO.,LTD 6 http://www.ulfatech.com