Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection

Similar documents
Dimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

Dimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection

Dimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

Dimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

Technical Data. Dimensions

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 10 mm

Technical Data. Dimensions

Technical Data. General specifications Switching element function Rated operating distance s n 1.5 mm

Technical Data. Dimensions

Technical Data. Dimensions

Technical Data. General specifications Switching element function Rated operating distance s n 2 mm

Technical Data. General specifications. Rated operating distance s n 5 mm

Technical Data. Dimensions

Technical Data. Dimensions

Inductive slot sensor

Technical Data. Dimensions

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 5 mm

Technical Data. Dimensions

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Technical Data. General specifications. Rated operating distance s n 2 mm

LMP 307. Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % / 0.

OPTIBAR P 1010 C Technical Datasheet

DMK 458. Pressure Transmitter for Marine and Offshore. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.25 % FSO option: 0.

Relative pressure transmitter type 520

DK46 - DK800 Supplementary instructions

Pressure switch, Differential pressure switch and Thermostat RT-E

Level sensing relative and absolute pressure transmitter type 712

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Miniature flowmeters DK 46, DKR 46 DK 47, DK 48, DK 800

Pressure control, differental pressure control and thermostat Type RT

1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure

IA CERTIFICATE (Revision 3 Revised for Annual Review) Hazel Grove Stockport Cheshire SK14 6NG United Kingdom

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition

Pressure Measurement Single-range transmitters for general applications

OSAT Series. Intrinsically Safe Infrared Temperature Sensor Operator's Guide

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition

Certificate of Compliance

II 2G EEx ia IIC T6. Ignition protection class

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765

Pressure switch KP-E. Data sheet

IA CERTIFICATE (Annual review required by MASC covered by an additional letter) (Revision 2- Review & Review)

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI

SITRANS P measuring instruments for pressure

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

x act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0.

2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure

x act i Precision- Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor

Level transmitter LT 100

Pressure Measurement Single-range transmitters for general applications

Safety Instructions Liquiphant FailSafe FTL80, FTL81, FTL85

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Type N-10, N-11 Hazardous Area Non-incendive Transmitters

User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] IM 01C25A00-12E

Single and double acting, magnetic, self-centering Bores: ø 16, 20, 25, 32, 40 mm

High-performance submersible pressure transmitter For level measurement Model LH-20

ATM.1ST/Ex - High Precision Transmitter

Liquid level instruments BM 24 /BM 51

SITRANS. Pressure transmitter SITRANS P, Z series for gauge and absolute pressure. Introduction. Safety instructions 2.

Operating instructions Pressure sensor. PN422x / / 2013

Monitoring device NTS 30

Pressure Measurement Single-range transmitters for general applications

Pneumatic pressure switch 20DD

ATM.ECO/IS - Analog Transmitter with Temperature compensation

Position switches FP series

ATM/Ex - Intrinsically Safe Analog Pressure Transmitter - ATEX / IECEx Certified

Smart performance with innovative and ever-strong coil drive even under harsh working environments

KTE6000 / KTU6000 Series OEM pressure transmitters for industrial media

High-performance submersible pressure transmitter For level measurement Model LH-20

ATM/Ex - Analog Pressure Transmitter

Prewired position switches FA series

Electronic relative and differential pressure switch type 616

RTD temperature probes

CERTIFICATE OF COMPLIANCE

High-performance submersible pressure transmitter For level measurement Model LH-20

DSL, DSH: Specially designed pressure limiter

Relative pressure switch type 521

Model range*1) Switching pressure difference

Pressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview

Zelio Relays RSL Slim Interface Plug-In Relays

Siemens AG psi (6 bar) 145 psi (10 bar) 464 psi (32 bar) 1450 psi (100 bar) 3626 psi (250 bar) 8700 psi (600 bar) psi (800 bar)

VG5 Supplementary instructions

High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20

Level switches Series LD Vibrating fork level switch for liquids and solids

EX-RECESSED CEILING LIGHT FITTINGS

Level switches Series LD Vibrating fork level switch for liquids and solids

Pressure Switches Application Guideline

Prewired position switches FA series

Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC

Gas density monitor With integrated transmitter Model GDM-100-TI

UHrasonic Sensor VEGASON60 type series SN6*.CI**H***

Torque Tube TB300 Digital Transmitters

TeSys protection components

High-performance submersible pressure transmitter For level measurement Model LH-10

I/P Transducer Positioner Module

Manual Power relay SR853

ED 701 Hygenic Pressure Transmitter

better measurement Simply a question of

sitrans p Operating Instructions (de/en) Edition 03/2004

BA307C & BA308C Intrinsically safe loop-powered 3½ digit panel mounting indicators issue 9

Transcription:

0102 Model Number Features Direct mounting on standard actuators Compact and stable housing Fixed setting EC-Type Examination Certificate TÜV99 ATEX 1479X Usable up to SIL2 acc. to IEC 61508 Accessories BT65A BT65X BT115A BT115X BT65B BT115B V18-W Cable socket in M18 format, ready for make up Technical Data specifications Switching element function DC Dual NC Rated operating distance s n 3 mm Installation flush mountable Output polarity NAMUR Assured operating distance s a 0... 2.4 mm Actuating element Stainless steel 1.4305 / AISI 303 8.5 mm x 8.5 mm x 0.5 mm Reduction factor r Al 0.5 Reduction factor r Cu 0.4 Reduction factor r 304 1 Reduction factor r St37 1.3 Reduction factor r Brass 0.6 Nominal ratings Nominal voltage U o 8 V Switching frequency f 0... 3 khz Hysteresis H typ. 5 % Reverse polarity protection reverse polarity protected Short-circuit protection yes Suitable for 2:1 technology yes, Reverse polarity protection diode not required Current consumption Measuring plate not detected 3 ma Measuring plate detected 1 ma Time delay before availability t v 1.1 ms Switching state indicator LED, yellow Functional safety related parameters MTTF d 1470 a Mission Time (T M ) 20 a Diagnostic Coverage (DC) 0 % Ambient conditions Storage temperature -40... 100 C (-40... 212 F) Mechanical specifications Connection type Connection (system side) V18 connector Housing material PBT Sensing face PBT Degree of protection IP67 information Use in the hazardous area see instruction manuals Category 1G; 2G; 3G Compliance with standards and directives -25... 100 C (-13... 212 F) Note: Under the same product name but with a different part no., this product has a predecessor with a restricted temperature range (up to +70 C). The temperature range specified here (up to +100 C) only applies to sensors with part no. 2239**. Standard conformity NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999 Electromagnetic compatibility NE 21:2007 Standards EN 60947-5-2:2007 IEC 60947-5-2:2007 Approvals and certificates UL approval culus Listed, Purpose CSA approval ccsaus Listed, Purpose CCC approval CCC approval / marking not required for products rated 36 V Dimensions 65 33,5 36 5 7 5,4 9 LED 30 I II M18x1 14 25 S 1

Electrical Connection Pinout 1 4 2 3 Wire colors in accordance with EN 60947-5-2 1 BN 2 WH 3 BU 4 BK (brown) (white) (blue) (black) 2

ATEX 1G Device category 1G EC-Type Examination Certificate TÜV 99 ATEX 1479 X II 1G Ex ia IIC T6 T1 Ga Standards EN 60079-0:2012, EN 60079-11:2012, EN 60079-26:2007 Ignition protection "Intrinsic safety" Appropriate type NCN3-F31.-N4... 100 nf A cable length of 10 m is considered. 100 µh A cable length of 10 m is considered. and in this instruction manual. The EC-Type Examination Certificate has to be observed. The special conditions must be adhered to! Directive and hence also EC-Type Examination Certificates apply in general only to the use of electrical apparatus under atmospheric conditions. The use in ambient temperatures of > 60 C was tested with regard to hot surfaces by the mentioned certification authority. If the equipment is not used under atmospheric conditions, a reduction of the permissible minimum ignition energies may have to be taken into consideration. The temperature ranges, according to temperature class, are given in the EC-Type Examination Certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. Note: Use the temperature table for category 1!!! The 20 % reduction in accordance with EN 1127-1:2007 has already been accounted for in the temperature table for category 1. must be observed. The intrinsic safety is only assured in connection with an appropriate related apparatus and according to the proof of intrinsic safety. The associated apparatus must satisfy the requirements of category ia. Due to the possible danger of ignition, which can arise due to faults and/or transient currents in the equipotential bonding system, galvanic isolation of the power supply and signal circuit is preferable. Associated apparatus without electrical isolation must only be used if the appropriate requirements of IEC 60079-14 are met. Install the device in such a way that the resin surface is not exposed to mechanical hazards. Electrostatic charge Additional requirements for gas group IIC. Avoid electrostatic charges that can cause electrostatic discharge when installing or operating the device. Information on electrostatic hazards can be found in the technical specification IEC/TS 60079-32-1. 3

ATEX 2G Device category 2G EC-Type Examination Certificate TÜV 99 ATEX 1479 X II 1G Ex ia IIC T6 T1 Ga Standards EN 60079-0:2012, EN 60079-11:2012 Ignition protection "Intrinsic safety" Appropriate type NCN3-F31.-N4... 100 nf ; a cable length of 10 m is considered. The value is applicable for one sensor circuit. 100 µh ; a cable length of 10 m is considered. The value is applicable for one sensor circuit. and in this instruction manual. The EC-Type Examination Certificate has to be observed. The special conditions must be adhered to! Directive and hence also EC-Type Examination Certificates apply in general only to the use of electrical apparatus under atmospheric conditions. The use in ambient temperatures of > 60 C was tested with regard to hot surfaces by the mentioned certification authority. If the equipment is not used under atmospheric conditions, a reduction of the permissible minimum ignition energies may have to be taken into consideration. The temperature ranges, according to temperature class, are given in the EC-Type Examination Certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. must be observed. The intrinsic safety is only assured in connection with an appropriate related apparatus and according to the proof of intrinsic safety. Install the device in such a way that the resin surface is not exposed to mechanical hazards. 4

ATEX 3G (ic) Device category 3G (ic) Certificate of Compliance PF 13 CERT 2895 X Standards Maximum permissible ambient temperature T Umax at Ui = 20 V for Pi=34 mw, Ii=25 ma, T6 for Pi=34 mw, Ii=25 ma, T5 for Pi=34 mw, Ii=25 ma, T4-T1 for Pi=64 mw, Ii=25 ma, T6 for Pi=64 mw, Ii=25 ma, T5 for Pi=64 mw, Ii=25 ma, T4-T1 for Pi=169 mw, Ii=52 ma, T6 for Pi=169 mw, Ii=52 ma, T5 for Pi=169 mw, Ii=52 ma, T4-T1 Connection parts II 3G Ex ic IIC T6 T1 Gc EN 60079-0:2012, EN 60079-11:2012 Ignition protection category "ic" 100 nf ; A cable length of 10 m is considered. 100 µh ; A cable length of 10 m is considered. and in this instruction manual. The data stated in the data sheet are restricted by this operating instruction! The special conditions must be observed! must be observed. The sensor must only be operated with energy-limited circuits, which satisfy the requirements of IEC 60079-11. The explosion group depends on the connected, energy-limited power supply circuits. Install the device in such a way that the resin surface is not exposed to mechanical hazards. Each sensor circuit van be operated with the stated maximum values. 67 C (152.6 F) The sensor must not be mechanically damaged. The connection parts are to be installed, such that a minimum protection class of IP20 is achieved, in accordance with IEC 60529. 5