Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Similar documents
Bermad Pressure Reducing. Model: 42T

Model 420-HY Pressure Regulating Hydrant Valve

Model: 43T. Bermad Pressure Relief Valve

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

WW-730. Pressure Sustaining/Relief Control Valve

WW-720. Pressure Reducing Control Valve

WW-720. Pressure Reducing Control Valve

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Bermad Model:

INSTALLATION OPERATION MAINTENANCE

Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve

TECHNICAL DATA. Page 1 of 12

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

TECHNICAL DATA Q= C. Table 1 - Specifications

Pressure Reducing Control Valve w/ Hydraulic Check Feature

TECHNICAL DATA CAUTION

TECHNICAL DATA. Table 1 - Specifications

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

End Connection. Thread x Thread N/A N/A N/A N/A Flange x Flange N/A

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

Model GPR Primary Pressure Regulating Valve. Instruction Manual

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

DS06D,G Dial Set Pressure Regulating Valve

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

DS05C,D,G Dial Set Pressure Regulating Valves

D05 Pressure Regulating Valves

SINGER MODEL 106/206-RPS-L&H

TECHNICAL DATA CAUTION

Pressure Regulators. Operating Instructions. Instrumentation

Operation Manual. Diaphragm Sensed Gas Pressure Regulators

V43 Pressure Actuated Water Regulating Valve

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

Models 106-RF / 206-RF Rate of Flow Control Valve

Anti-flood device Model B-1

Speed control assembly model A-1

Pressure Reducing Valve for Steam Type 2333 A

Regulator from 1800 B series

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Installation Troubleshooting Maintenance Instructions Installation / Start-up

TECHNICAL DATA. Q = C v P S

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

D05T Compact Design Pressure Regulating Valves

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation. Size: inch / mm

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

Installation and operation Manual. Bermad Surge Anticipation Valve. Model No 435

MEGR-1627 Instruction Manual

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

1800C and 1800C-HC Series Service Regulators

OPERATING AND MAINTENANCE MANUAL

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE. 4. TECHNICAL DATA Approvals:

TECHNICAL DATA ACCELERATOR MODEL E-1

RS(H)20, 25 USER MANUAL

Installation Instructions for NP100 Series Nitrogen Control Panels

1200B2 Series Service Regulators. Instruction Manual

Discharge Relief Valve Operation & Maint.

Types 749B and R130 Changeover Manifolds

Maximum 0.85 MPa pressure setting Long-life, high flow perfect for balancer applications

Waterous Relief Valve

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA DELUGE VALVE, MODEL F-1 STRAIGHT THROUGH STYLE

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

Mounting and Operating Instructions EB 2555 EN. Self-operated Pressure Regulators. Pressure Reducing Valves Type 50 ES Type 50 EM.

TECHNICAL DATA. than the water inlet pressure to the concentrate

Mounting and Operating Instructions EB 3017 EN. Self-operated Regulators

Installation, Operation and Maintenance Manual for Back Pressure Regulator

HIGH RATE BASKET STRAINER

LRS(H)4 Pressure-Reducing Regulator User Manual

Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections

Anderson Greenwood Series 93 Positive Pressure POSRV Installation and Maintenance Instructions

Needle valve. Contents. User s Manual. (1) Be sure to read the following warranty clauses of our product 1. (2) General operating instructions 2

RD(H)20/25 Pressure-Reducing Regulator User Manual

Temperature Controllers

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

BERMAD Waterworks. Level Control Valve with Altitude Pilot. 700 Series. Model X. Features and Benefits. Major Additional Features

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

Mounting and Operating Instructions EB EN. Self-operated Pressure Regulators. Type 2335 Excess Pressure Valve with pilot valve

PN-DR. Pneumatic Direct-acting Pressure Reducing Valve for Steam and Air. Copyright 2018 by TLV CO., LTD. All rights reserved

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

TECHNICAL DATA OBSOLETE

CAST IRON VALVES FLOAT VALVE

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

Combination Air Valve

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

S & M Water Consultants

A-DR20-2/A-DR20-6/A-DR20-10

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

BERMAD Waterworks. Pressure-Reducing Valve. 700 Series. Model 720. Features and Benefits. Major Additional Features

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

TECHNICAL DATA. Dry 132a. October 1, 2008

Transcription:

Bermad Pressure Reducing Valve Model: 720-UL INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD

1. Safety First BERMAD believes that the safety of personnel working with and around our equipment is the most important consideration. Please read all safety information below and from any other relevant source before attempting to perform any maintenance function. Comply with all approved and established precautions for working with your type of equipment and/or environment. Authorized personnel should perform all maintenance tasks. Prior to performing a procedure, read it through to the end and understand it. If anything is not clear, ask the appropriate authority. When performing a procedure, follow the steps in succession without omission 2. Description BERMAD s Model 720UL Pressure-Reducing Valve is an automatic pressure control valve that reduces higher inlet pressure to lower constant outlet pressure, regardless of fluctuating flow-rates and/or varying inlet pressure. It is a pilot-operated, diaphragm-actuated, low pressure-loss valve. Valve differential pressure powers the diaphragm actuator open or closed. The double-chambered actuator design enables quick and smooth valve action Models and Sizes Models and Sizes covered by this document include the BERMAD Pressure-Reducing Valve 720UL, sizes 2, 2.5, 3, 4, 6 and 8. It is available in either the Globe Y or Angle pattern. Operating Pressure Rating Sizes 2, 2.5, 3, 4 and 6 have a maximum rated inlet pressure of 300 psi (21 bar). Size 8 have a maximum rated inlet pressure of 175 psi. (12 bar). Outlet pressure setting for all sizes is psi. When setting the outlet pressure, the inlet pressure should be at least 15 psi (1 bar) higher than the set outlet pressure. In cases where the inlet pressure falls below or is equal to the intended outlet pressure, the outlet pressure and flow will be as described in Tables 2 through 7. In the case of zero (static) flow through the valve, the maximum increase in the downstream (outlet) pressure above the set pressure of the valve will not exceed 8 psi (0.5 bar). Flow Capacity Table Valve Size [in (mm)] 2 (50) 2.5 (65) 3 (80) 4 (100) 6 (150) 8 (200) Max. Inlet pressure [psi (bar)] 175 (12) Outlet pressure adjustable range [psi (bar)] (2-12) Maximum flow-rate [GPM (LPM)] 150 (568) 500 (1892) 800 (3028) 1800 (6813) 4000 (15140) Minimum required flow-rate for Pilot Setting [GPM (LPM)]* 75 (284) 250 (946) 400 (1514) 900 (3406) 2000 (7570) Table 1 *Required flows to be established through the valve to properly adjust the set pressure.

3. UL Listed BERMAD 720-UL Deluge Valve is UL Listed when installed with specific components & accessories. Refer to the current UL Directory. Consult the manufacturer for any component approval recently to appear in the UL fire protection equipment directory. 4. Installation 4.1 Allow enough room around the valve assembly for any adjustments and future maintenance/disassembly work. 4.2 Before the valve is installed, flush the pipeline to remove any dirt, scale, debris, etc. Failure to do this might result in the valve being inoperable. 4.3 Listed indicating valves should be installed upstream and downstream of the BERMAD Model 720UL valve to allow future maintenance. See figure 1. 4.4 Install the valve in the pipeline with the valve flow arrow on the body casting in the proper direction. Use the lifting eye provided on the main valve cover for lifting and lowering the valve. 4.5 The Model 720UL is intended for horizontal installation only. Ensure that the valve is positioned so that the actuator can be easily removed for future maintenance. 4.6 After installation, carefully inspect/correct any damaged accessories, piping, tubing, or fittings. 4.7 Install a UL listed sprinkler system pressure relief valve sized in accordance with NFPA 13. 4.8 Install a UL listed pressure gauge on both the upstream & downstream of the Pressure Reducing Control Valve. See installation drawing, figure 1, for indicated installation. 4.9 Install the Model 720UL valve in accordance with the Standard for Installation of Fire Sprinkler Systems, NFPA 13, or the Standard for Installation of Standpipe and Hose Systems, NFPA 14, as appropriate. The Model 720UL valve is to be tested after installation in accordance with NFPA 13. 4.10 The Model 720UL valve is to be inspected, tested and maintained in accordance with the Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems, NFPA 25.

Figure 1: Installation Drawing

5. Operation The pressure-regulating pilot senses downstream pressure and modulates the upper control chamber causing the main valve to throttle, thus maintaining constant downstream pressure. When the downstream pressure falls below the pilot setting, the pilot opens, pressure in the upper control chamber decreases, and the main valve modulates open to increase downstream pressure and maintain pilot setting. If the downstream pressure rises above the pilot setting, the pilot closes, pressure in the upper chamber increases and the main valve throttles close to decrease downstream pressure to the pilot setting. The pressure-reducing pilot is equipped with an adjusting screw to preset the desired downstream pressure and an internal adjustable needle valve to control the closing speed. Starting-up When performing this procedure refer to figure 1. 5.1 Open a hydrant, relief valve, drain valve, or other flow-consumer downstream of the Model 720UL Pressure- Reducing Valve, creating a system demand. 5.2 Fully open upstream indicating valve (2a). 5.3 Gradually open downstream indicating valve (2b) to fully open, allowing flow through the Model 720UL Pressure-Reducing (1) Valve. 5.4 Wait for downstream pressure stability. 5.5 Slowly close the flow-consumer that was opened in step #1 above to fully close. There is no flow; the pressure on the downstream side of the system that is reflected through the pressure gauge (3b) should be according to the factory pre-set adjusted pressure plus up to an additional 10%. Readjusting The pilot valve is factory pre-set according to the stated demands of the customer. The pre-set is clearly indicated on the pilot valve tag. If readjustment to either the pressure or valve response is required, follow the following steps. 5.6 Ensure that there is minimum flow through the main valve.(for Pilot setting flow rate see Table1, item Minimum flow rate for pilot setting.) 5.7 Free the tension between the adjusting screw on the pressure reducing pilot valve (2 in figure 2) and the fastening nut by turning the fastening nut counterclockwise. 5.8 By alternately turning the adjusting screw on the pilot valve a half turn and then reading the downstream pressure, gradually adjust the pressure: Counterclockwise to decrease (-) the downstream pressure or Clockwise to increase (+) the downstream pressure. 5.9 Repeat the Starting-up procedure, section 0 steps 1-5. Caution: Small changes in the adjustment of the needle valve have great impact on the valve performance. The needle valve is factory set at one-half turn open to one and one-half turn open. The maximum number of turns is 3 from fully closed to fully open. More than 3 turns toward open might cause the valve to perform at less than optimal functioning. Perform step #5 with this in mind. 5.10 By turning the needle valve (in figure 2) on the pilot valve bottom adjust the valve response. Turn: Clockwise to decrease (-) the closing speed of the main valve or Counterclockwise to increase (+) the closing speed of the main valve. 5.11 Repeat the Starting-up procedure, steps 1-5. Note: Valve response adjustment affects pressure adjustment. Any adjustment to valve response requires rechecking pressure adjustment. See section Error! Reference source not found., steps 1-4.

6. Figure 2: Operation Drawing 7. Maintenance and Inspection Test WARNING: Do not turn off the water supply to make repairs without placing a roving fire patrol in the area covered by the system. The patrol should continue until the system is back in service. 7.1 Prior to turning off any valves or, notify local security guards. 7.2 In any of the following inspections or testing procedures, if an abnormal condition exists, see Troubleshooting for possible cause and corrective action. 7.3 The Model 720UL valve is to be inspected, tested and maintained in accordance with the Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems, NFPA 25. Normal Conditions 7.4 All main isolating valves should indicate a fully open position. 7.5 Upstream pressure gauge should (3a figure 2) reflect the upstream pressure supplied to the valve. 7.6 Down stream pressure gauge (3b) should be according to the system design criteria.

8. Quarterly Inspection 9.1 The system should be checked for normal condition. 9.2 Check that the main valve, pilot system, accessories, tubing & fittings, are all in good condition, damage free and not leaking. 9.3 The fastening nut, of the pilot valve (2 figure 2) adjusting screw, should be fastened tightly. 9. Annual Inspection and Test 9.4 Complete Quarterly Inspection. 9.5 Conduct a flow test in systems nominal flow. The down stream pressure gauge should show the adjusted down stream pressure, and according to the system design criteria, this pressure should be stable. If re-adjusting is needed it should be according to 4.1. 10. Abnormal Conditions SYMPTOM PROBABLE CAUSE REMEDY Valve fails to regulate Valve fails to open Needle valve (21) not properly adjusted. Pulsates or hunts. Air trapped in main valve cover. Filter screen (4) blocked. Insufficient inlet pressure. No downstream demand. Factory set at ½ or 1½ open. Adjust. Slowly adjust needle valve (21) until pulsation stops. Loosen cover tube fitting at the highest point, allow the air to escape and re-tighten. Remove filters cap and screen to clean. Check/create inlet pressure. Create demand/flow. Insufficient pilot spring compression. Turn adjusting screw CW on pilot (8). Valve fails to hold set static outlet pressure Indicating valves closed. Filter screen (4) blocked. Debris trapped in main valve. Diaphragm in main valve is leaking. Open. Remove filters cap and screen to clean. Remove and inspect actuator assembly. Check seat and disc seal. Caution: This test will cause the valve to go fully open. Close downstream indicating valve or omit this test if this may cause damage. Test for leakage. Close indicating valves and remove the plug in the main valve cover. If a continuous flow exists, the diaphragm is damaged or loose. Note: Mark F Large Filter In cases where the filter screen frequently becomes blocked, install a filter with filtration capacity of at least 80 mesh, 250 µm. We recommend replacing the standard filter with BERMAD s Large Filter Mark F. 11. Difficulty in Performance Where difficulty in performance is experienced, the manufacturer or his authorized representative should be contacted if any field adjustment is to be made.