The Protection of Silos From Over. Pressurisation During Filling

Similar documents
White Paper: Preventing Disasters in Bulk Storage Silos through Comprehensive Servicing

from Thames Cryogenics Ltd Total Cryogenic Solutions Cryogenic Cluster Day 22/09/2010

MITIGATING PIPE AND RISER HYDRAULIC PIPELINE ISSUES WITH THE I-RISER PLUS

Guidelines for Delivery of Bulk Cementitious Products to Premixed Concrete Plants

GUIDELINES. Systems. Pressure

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module:

Method Statement: Testing Dry Riser System

PNEUMATIC CONVEYOR OVERVIEW

SILO SAFTEY EQUIPMENT. Silo Safety System KCS

Introduction. 1. Large oil-free screw compressor, Emeraude ALE series

Every things under control High-Integrity Pressure Protection System (HIPPS)

SILO SAFTEY EQUIPMENT. Silo Safety System KCS

Blowdown vessels Meeting the requirements of HSE PM60

PRESSURE SYSTEMS POLICY

Float Valve Function and Design Considerations

Unit 24: Applications of Pneumatics and Hydraulics

BLOCKAGE LOCATION THE PULSE METHOD

Oxygen Usage Best Practice Guide

Flex-Kleen CT Series Pulse-Jet Dust Collectors For high pressure/high vacuum applications

IS YOUR FLAP VALVE IN COMPLIANCE WITH NFPA ?

GUIDANCE IN-SERVICE INSPECTION PROCEDURES

VACUVENT Valve functions - benefits - flowpath - VG series - Sewage

New AQF Filter Polymer Filtration System

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

Journal of Applied Fluid Transients, Vol 1-1, April 2014 (3-1)

Experimental Investigation on Transient Response of Two Stage Pressure Relief Valve

SEMEMI SQA Unit Code H2AX 04 Carrying out scheduled maintenance tasks on fluid power equipment

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction.

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

OPERATION MANUAL NTF-15

PRESSURE REDUCING STATION INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

DC5A. Cyclone Separator Trap for Air. Copyright 2015 by TLV Co., Ltd. All rights reserved ISO 9001/ ISO MA-03 (DC5A) 19 June 2015

2 FUSION FITTINGS FOR USE WITH POLYETHYLENE PRESSURE PIPES DESIGN FOR DYNAMIC STRESSES

OIL AND GAS INDUSTRY

Noth American 7347 High Pressure Gas Regulators

MSC Guidelines for Review of Vapor Control Systems Procedure Number: C1-46 Revision Date: 01/08/2018

Data Sheet Issue A

SEMPEO SQA Unit Code FP2P 04 Maintaining fluid power equipment

SEMEM3-78 Testing and calibrating instrumentation and control equipment and circuits

TSS21 Sealed Thermostatic Steam Tracer Trap

Manual Actuated Boiler Blowdown Valves

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

VOLUME BOOSTER RELAYS YT-300 / 305 SERIES

Guidance on room integrity testing and its interpretation

Summary of the MRA LPG Codes of Practice

Examples of pressure systems and equipment are:

13. Evaporative Emission Control System

Spirax Compact FREME Flash Recovery Energy Management Equipment

RELIEF VALVES IN PARALLEL

Air Leakage Detailing & Awareness Services

OPERATION MANUAL NTF-60 Plus

I. CHEM. E. SYMPOSIUM SERIES NO. 85 MULTI-STAGE OVER PRESSURE PROTECTION AND PRODUCT CONTAINMENT ON HIGH PRESSURE POLYMERISATION REACTORS

RESOLUTION A.567(14) adopted on 20 November 1985 REGULATION FOR INERT GAS SYSTEMS ON CHEMICAL TANKERS

Pressure Systems Safety Regulation

SEMEM3-73 Maintaining medical gas pipeline systems and equipment

Lecture 19 PRESSURE-CONTROL VALVES [CONTINUED]

Tutorial. BOSfluids. Relief valve

User Information Sheet 024

AUTOMATED PNEUMATIC TANKER HATCH

PositionMaster EDP300 Extended Diagnostics. Compact, well-proven, and flexible

TECHNICAL DATA. Table 1 - Specifications

The benefits of the extended diagnostics feature. Compact, well-proven, and flexible

ANTI SHOCK RELIEF VALVE

Pipeline Flooding, Dewatering and Venting Dr Aidan O'Donoghue, Pipeline Research Limited, Glasgow, Scotland

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

INSTRUCTION MANUAL FOR POLYKEG DISPOSABLE KEG

SAMPLING SYSTEMS FOR LIQUIDS AND GASES FOR ALL TYPES OF APPLICATIONS

Frequently Asked Questions Directive 056 Facilities Technical

Features. Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes

STD Spray Type Desuperheater

JETTY LOADING SYSTEM

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

API Standard Venting Atmospheric and Low-Pressure Storage Tanks: Nonrefrigerated and Refrigerated

Sizing Pulsation Dampeners Is Critical to Effectiveness

GUIDELINES FOR SURVEY OF OIL FLOATING STORAGE VESSELS FIXED AT ANCHORAGE

Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel

Installation and operation Manual. Bermad Surge Anticipation Valve. Model No 435

APPS-160 Gen 2 User Manual

Overview IMPEM163S. Carry out preventative planned maintenance on instrumentation and control equipment used in food and drink operations

Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant

PROTEGO Braunschweiger Flammenfilter GmbH

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

COMMITTEE DRAFT. API 520 Part I 10 th Edition Ballot Item 2.1. This ballot covers the following item:

Hydraulic and Economic Analysis of Real Time Control

for Building facilities Industrial facilities etc.,multipurpose Pilot operated type(high capacity)

TECHNICAL DATA Q= C. Table 1 - Specifications

CONTROL VALVE TESTING

S300 Series. Valve Link. Features. Fisher Controls

Explosive Fittings Testing

MODELLING OF FUME EXTRACTORS C. R.

CAST IRON SAFETY VALVE TYPE 6301

Installation, Operation, and Maintenance Manual

MFP14-PPU (Vented) Automatic Packaged Pump Units

LIFTING MAGNETS ERIEZ MAGNETICS

Potable Water Truck Safe Work Procedure PTES_HSE_SWP_041. Name Date Signature. Author Geoff Selfe 25/01/2016. Reviewed Solomon Site 25/01/

INTERIM ADVICE NOTE 150/12. Guidance for Alternative Temporary Traffic Management Techniques for Relaxation Schemes on Dual Carriageways.

Pneumatic Conveying Principles BSH&E SEMINAR

6.6 Relief Devices. Introduction

PIG MOTION AND DYNAMICS IN COMPLEX GAS NETWORKS. Dr Aidan O Donoghue, Pipeline Research Limited, Glasgow

Transcription:

SHAPA Technical Bulletin No.11 The Protection of Silos From Over Pressurisation During Filling Page 1 of 8 August 2005

The Protection of Silos From Over Pressurisation During Filling By James Duggleby, Portasilo Ltd. Tel +44 1904 624872 E-mail: james.duggleby@portasilo.co.uk Abstract Within the construction industry there have been a number of serious accidents involving silos, which have been over-pressurised by tankers, this has resulted in the Health & Safety Executive (HSE) issuing a guidance note on this subject. These recommendations have largely been reflected in the process guidance note for bulk Cement silos, PG 3/1 (2001), issued by the Secretary of State. Although directed at the Cement, Concrete and Quarrying industries, these guidelines have obvious implications for all other industries, which utilise tanker filled silos. This paper will discuss the five key recommendations made by the HSE and identify the test work undertaken by Portasilo to support these recommendations with some alarming results. The paper will also look at the implications of the guidance notes with regards to the design and operation of tanker filled silos. Whilst tackling these five key points to ensure that all silos, new and existing, can be supplied or modified to meet the current standards by putting into place measures to prevent the over pressurisation of silos and by providing an ultimate basis of safety a pressure/vacuum relief valve (PRV). Background to the Guidance Notes In the case of each of these accidents, the silos became pressurised during pneumatic filling by a road tanker. The connection between the reverse jet filter and the silo roof was found to be the weak link and resulted in the 250kg filter unit being dislodged from the silo roof. In at least one case, this filter seriously injured the tanker driver. The underlying problem in each case was found to be the pressure relief valve, which was undersized for the maximum airflow entering the silo. The problem was also exacerbated by a significant lack of maintenance and by the overfilling of the silo. Page 2 of 8 August 2005

The guidance note makes recommendations for overall management control at the offloading point, together with a requirement for a documented maintenance regime for the filter unit and safety pressure relief valve. These recommendations are not particularly contentious; however, there is also a requirement to select a suitably sized vent filter Fig 1: Background to Guidance notes and pressure relief valve for the anticipated peak airflow rate. It is the quantification of this flow rate, which was contentious, together with the requirement for an automatic shut-off system in the silo fill line. Validation of the Air Flow Rate The peak airflow occurs when the tanker is allowed to depressurise in an uncontrolled manner at the end of the delivery. The higher the tanker pressure or the shorter the delivery line, the higher the air flow. This uncontrolled depressurisation of a road tanker is considered to be bad practice and management controls should be in place to prevent it; but its accidental occurrence is inevitable and must be taken into account. In the HSE guidance note, the peak flow is calculated using a formula for conventional fluid dynamics. A 2 bar g road tanker depressurising through a 10m long inlet pipe with one 90º bend would give rise to an airflow of up 13,000m³/hr. This figure is significantly higher than the 2000m³/hr conventionally allowed for by the industry; so it was widely disbelieved resulting in a slow adoption of the HSE s recommendations. Portasilo undertook a series of tests to try and understand what was really happening whilst a road tanker was discharging. The test work undertaken was designed to measure the airflow and the surge at the end of the conveying cycle. Although the measured results are less than those calculated, the differences can largely be accounted for by friction losses caused by an unpolished inlet pipe, plus losses through the onboard pipework and the flexible connecting hose. Given that a highly polished pipe can be expected after some months service and that the other losses are likely to be vehicle dependant, these calculated figures appear to present a conservative, but realistic basis for sizing equipment Page 3 of 8 August 2005

The surge in flow experienced at the end of the cycle is clearly not a transient peak; therefore, it cannot be disregarded due to its short duration. Flow rates in excess of 2000m³/hr, the figure conventionally used for design, are sustained for many minutes. The results of these tests and a comparison with calculated figures are shown in Fig 2. Air flow from a depressurising tanker Fig 2: Airflow rate from a depressurising tanker Implications on silo design and operation Silo vent filter The implications for filter sizing are not as onerous as might be expected, despite this large airflow because nothing has changed! Filters are conventionally sized on empirical rules that take into account the large surge in airflow on completion of the tanker s discharge. Although the numbers have changed, they have changed on both sides of the equation. Portasilo surveyed a large number of OPC silo installations and the results indicated that filter size was not so important as might be first thought. Bag filters as small as 10m² were giving excellent performance after 20 years service, whilst much larger filters less than a year old were performing badly. Filter media area is obviously important, but the filter must also be well engineered, well maintained and installed on a generously sized silo. Page 4 of 8 August 2005

Pressure/vacuum relief valve Unlike a silo filter, pressure relief valves are typically sized by calculation. If the maximum airflow is under estimated, then even the best quality valve will be undersized and will fail to provide adequate protection for the silo to which it is fitted. As part of the tests undertaken by Portasilo, direct tests were conducted on a number of pressure relief valves. These trials consisted of a road tanker with a pressure relief valve coupled directly to the end of the filling pipe. The tanker was depressurised and the pressure accumulation was measured. Although this was an extreme test, this scenario is similar to a full silo with a blocked filter; which was a common factor on all the damaged silos. It quickly became evident from these tests that the valves capacities were significantly less than those claimed by the manufacturer. Further investigations revealed that both calculation errors and an effect known as pressure piling were to blame. The shape of the valve seat and proximity of the weather cover are critical and can give rise to a very significant reduction in valve capacity. These test results are shown in Fig 3 along with the manufacturer s claimed capacity. Performance test for a spring operated PRV Fig 3: Performance test for a spring operated pressure relief valve Page 5 of 8 August 2005

It was also evident that the spring loaded valves have a limited opening, due to short springs; which severely restricts the out breathing capacity and gives them a poor tolerance to powder build up. At first the dead weight valves seemed to fare better as pressure relief valves, but as their name suggests they use dead weight to provide the correct pressure relief setting. Therefore, the inertia required to lift the weight is great, resulting in transient pressure peaks greater that the silo s design pressure, which can be potentially damaging. They also suffer a similar problem of powder build up when utilised for vacuum relief. From the results obtained, it was concluded that an ideal valve should be spring-loaded for both pressure and vacuum relief with long travel springs to maximise the valve s opening. A weather cover should be designed to prevent powder build up, which should also minimise the effects of isokinetic crashing and facilitate the weekly test required by the HSE. Therefore, It should also be fitted and easily removed without tools. Most importantly, the valve must be tested at peak flow rates and certified to confirm this! Certificates should be carefully scrutinised to ensure that tests were conducted at the peak flow rate and at specified pressure set points. Finally the pressure accumulation of the valve must be taken into account. The valve must relief the maximum flow rate whilst ensuring that the pressure build up within the silo is less than that of the silo s design pressure. Automatic shut off system The automatic shut-off system stipulated by the guidance note comprises of an actuated valve in the fill pipe, operated by both pressure and level sensors. In addition, to preventing damage to the silo filter, such a system can prevent nuisance operation of the pressure relief valve and hence, emission of dust to the atmosphere. It is conceivable that such a system could be used as the basis of safety for the silo, instead of the relief valve. However, all components and circuitry need to be arranged to fail-safe and the level of risk involved would justify duplicate instrumentation with cross checking safety circuitry. It is therefore, more realistic to use a suitably sized pressure relief valve for protection of the silo, and to provide a simpler version of this shut-off system to protect the silo filter from the damaging surges and to prevent dust release to atmosphere. In order to give the tanker driver a chance to carry out a controlled shutdown prior to the automatic closing of the shut off valve, a two-stage alarm system for both silo level and pressure should be provided. Page 6 of 8 August 2005

Management Control at the unloading point It is important that clear instructions are provided for the tanker driver at the offloading point. These should prohibit uncontrolled venting of the tanker through the silo and instruct the driver to carry out a controlled shut down in the event of an alarm prior to the automatic closing of the shut off valve. Documented maintenance Weekly maintenance checks should include the operation of the pressure relief valve and to confirm the operation of the reverse jet filter. The condition of the filter bags is easily monitored by measuring the differential pressure across the filter; however, the reading must be taken during the silo filling operation. An analogue gauge or digital display of silo filter s differential pressure is therefore, best mounted adjacent to the filling point rather than located on the silo roof. Summary 1) A reverse jet filter in the order of 20m² should be considered for new projects. Exact area and filter media choice will depend on the dust being handled. Of equal importance is the number of cleaning valves and a generously sized casing to allow separation of the dust and air. 2) A combination pressure/vacuum relief valve sized for the peak flow rate needs to be provided. The set pressure must be high enough to prevent accidental dust leakage (typically around 500m WG) and the pressure accumulation must be less than the silo design pressure. (Typically in the order of 1000mm WG). The valve must be certified for this maximum airflow (13,000m³/hr) and must be tolerant of dusty air. 3) An automatic shut-off system should be provided, comprising of a control unit and an actuated valve in the silo fill line. This is operated by both pressure and level transducers installed in the silo. A digital/analogue display for the filter s differential pressure will indicate the condition of the reverse jet filter and facilitate its maintenance. If this is supplied in addition to the pressure relief valve, fail-safe circuits are not required. 4) Clear instructions should be provided at the offloading point for the tanker driver. Page 7 of 8 August 2005

5) A documented maintenance regime should be introduced to ensure regular inspection of the relief valve, the filter and the automatic shut-off system. Fig 4: Summary Page 8 of 8 August 2005