V/LNV SERIES. Installation, Operation, and Service Manual WARNING IC /08

Similar documents
H/SERIES. Installation, Operation, and Service Manual WARNING IC /09

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

Table Of Contents. Profire MTH. Burner Gas Only. Installation Operation Maintenance

GM Series Dual-Block Multi-Function Gas Control Valves

Installation Instructions

SPECIFICATIONS ATTENTION

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h

Operator: Save these instructions for future use!

Your safety and the safety of others are very important.

PGM PREPIPED GAS MANIFOLD

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

IPG IGNITION GAS PILOTS BACK-LOADED GAS

INSTRUCTION MANUAL. Gas Salamander

C645A-E Pressure Switches

GAS SUPPLY DESIGN GUIDE

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Float Operated Level Controllers

SZ, RZ & SRZ Series*

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

Propane Conversion Kit Instruction

Valve Proving System VDK 200 A S06*

Propane Conversion Kit Instruction

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

Propane Conversion Kit Instruction

INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER BG600 GAS BURNER 1,200,000 thru 2,400,000 Btu/h

G96 Series BASOTROL Dual Operator Valve

TECHNICAL DATA. than the water inlet pressure to the concentrate

High-Pressure Boiler Inspection Procedures: A Complete Checklist

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

Valve Proving System VDK 200 A S02

Required Indoor Draft Hood. Optional Outdoor Vent Cap

INSTALLATION OPERATION MAINTENANCE

GAS SUPPLY APPLICATION GUIDE

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

WW-730. Pressure Sustaining/Relief Control Valve

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

O.K. Safety first CDN USA. Table of Contents. Approvals. Attention IFGC CSA UL ANSI NFPA

KC Series Gas Components and Supply Design Guide

Temperature Controllers

36H SERIES Combination Gas Valve

Operator: Save these instructions for future use!

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

Installation Instructions

Propane Conversion Kit Instructions

Installation Instructions For Natural Gas Conversion

SINGLE VALVE WITH LOW-FLOW BYPASS

Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage.

/2004 US/CA

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

Instructions for High Altitude Conversion

Automatic Valve Proving Control

GENERAL DESCRIPTION MODEL RCW DRY SYSTEM CONFIGURATION. Technical Support Airpark Dr. Standish, MI 48658

Model: 43T. Bermad Pressure Relief Valve

Discharge Relief Valve Operation & Maint.

Standard Gas Countertop Griddle

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

USER S INFORMATION MANUAL

Installation and Maintenance Instructions

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Steam System Best Practices 14 Best Practices for Guide Lines for Boiler Plant Log Books

GAS FUEL VALVE FORM AGV5 OM 8-03

Job Number Plant Location 123 Roadrunner Avenue, Tombstone, AR Fuel Devices

Installation and Maintenance Instructions

V5197A. Firing Rate Gas Valve APPLICATION FEATURES PRODUCT HANDBOOK

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

TECHNICAL DATA. Q = C v P S

BGA158 Series CE Approved Class B Shutoff Gas Valve

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.

BGA158 Series CE Approved Class A Shutoff Gas Valve

Operator: Save these instructions for future use!

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation.

Thank You for Attending Today s Webinar. Today s Featured Speaker

Installation and Maintenance Instructions

INSTALLATION & OPERATION MANUAL FOR Stockpot Range

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

Dual Solenoid Gas Valve Installation

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Operator: Save these instructions for future use!

SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation. Size: inch / mm

Installation Instructions

WW-720. Pressure Reducing Control Valve

WARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY

Bermad Pressure Reducing. Model: 42T

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

COMBUSTION. Webster Combustion Technology 619 Industrial Road, Winfield, KS Installation, Startup, Operation and Maintenance Manual

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

200 PSI FAST-FILL AIR SOURCE KIT

BERMAD Waterworks. Level Control Valve with Altitude Pilot. 700 Series. Model X. Features and Benefits. Major Additional Features

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

OPERATING AND MAINTENANCE MANUAL

Power Flame Incorporated. Nova Premix. Installation and Operation Manual

Transcription:

V/LNV SERIES Installation, Operation, and Service Manual WARNING ONLY FACTORY AUTHORIZED BURNER SERVICE PERSONNEL SHOULD START- UP, ADJUST, OR SERVICE THIS EQUIPMENT. IC-1511 07/08

V SERIES TABLE OF CONTENTS PAGE SECTION 1. INTRODUCTION A. GENERAL INFORMATION... 3 B. DESCRIPTION... 3 C. OPERATING CONTROLS... 3 D. FLAME SAFEGUARD CONTROLS... 3 E. COMBUSTION AIR HANDLING SYSTEM... 4 F. SYSTEM... 4 G. PILOT SYSTEM... 4 H. GAS SYSTEM... 4 SECTION 2. INSTALLATION A. DRAFT CONDITIONS... 7 B. COMBUSTION AIR SUPPLY... 7 C. COMBUSTION CHAMBER DESIGN... 7 D. BURNER INSTALLATION... 10 E. GAS PIPING... 11 F. FUEL PIPING... 11 G. INSTALLATION CHECKLIST... 16 H. FIRING MODES...17 SECTION 3. STARTING AND OPERATING A. PREPARATION FOR INITIAL START-UP... 25 B. FIRING PREPARATIONS... 25 C. SEQUENCE OF OPERATION... 26 D. ELECTRICAL INTERFERENCE TEST... 26 E. START-UP AND OPERATION... 27 F. NORMAL OPERATION... 29 G. SHUTDOWN... 29 PAGE SECTION 5. MAINTENANCE A. GENERAL... 39 B. CONTROL SYSTEM... 39 C. GAS SYSTEM... 39 D. SYSTEM... 40 E. DRAWER ASSEMBLY... 40 F. IGNITION ELECTRODE, CABLE, AND PILOT... 40 G. FLAME SCANNER... 40 H. BURNER MOUNTING INSPECTION... 40 I. EXTENDED SHUTDOWN... 40 J. MAINTENANCE FLOW CHART... 41 SECTION 6. TROUBLE SHOOTING BURNER DOES NOT START... 42 NO IGNITION... 42 PILOT BUT NO MAIN FLAME... 43 BURNER STAYS IN LOW FIRE... 43 SHUTDOWN DURING FIRING...44 MODULATING MOTOR DOES NOT OPERATE... 44 WARRANTY POLICY...46-47 START-UP AND SERVICE REPORT... 48 PRODUCT SATISFACTION SURVEY... 49 SECTION 4. ADJUSTMENTS A. GENERAL... 30 B. COMBUSTION ADJUSTMENTS AND GAS... 30 C. GAS PILOT ADJUSTMENT... 31 D. DIRECT SPARK PILOT ADJUSTMENT... 31 E. BURNER SETTINGS... 31 F. PILOT TURN DOWN TEST... 33 G. ON-OFF BURNER ADJUSTMENTS... 33 H. LOW-HIGH BURNER ADJUSTMENTS... 34 I. FULL MODULATION BURNER ADJUSTMENTS... 36

OPERATING PRECAUTIONS This operating manual presents information that will help to properly operate and care for the equipment. Study its contents carefully. The unit will provide good service and continued operation if proper operating and maintenance instructions are followed. No attempt should be made to operate the unit until the principles of operation and all of the components are thoroughly understood. Only trained and authorized personnel should be allowed to operate, adjust or repair this equipment. If you are operating a burner(s), it is your responsibility to ensure that such operation is in full accordance with all applicable safety requirements and codes. Placed on all Industrial Combustion burners are warning or caution labels designed to inform the operator of potential hazards and stress important information. These symbols and their meanings are as follows: WARNING FAILURE TO INSTALL AND OPERATE THIS EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURERS RECOMMENDED INSTRUCTIONS AND INDUSTRY STANDARDS AND PRACTICES CAN RESULT IN FIRE, EXPLOSION, PROPERTY DAMAGE AND/OR PER- SONAL INJURY!! READ THIS MANUAL IN IT S ENTIRIETY PRIOR TO ANY ATTEMPT TO COMMISSION THIS EQUIPMENT. INSTALLATION, STARTUP, OPERATION AND MAINTE- NANCE OF THIS EQUIPMENT MUST BE PERFORMED ONLY BY FACTORY AUTHORIZED, EXPERIENCED AND QUALIFIED PERSONNEL. WARNING HAZARD OF ELECTRIC SHOCK!!! MORE THAN ONE DISCONNECT MAY BE RE- QUIRED TO DISCONNECT ALL POWER TO THIS PANEL. SERIOUS PERSONAL INJURY OR DEATH MAY RESULT. WARNING TO AVOID PERSONAL INJURY FROM MOVING PARTS, SHUT OFF ALL ELEC- TRICAL POWER BEFORE SERVICING THIS EQUIPMENT. WARNING READ PRODUCT MANUAL AND FULLY UNDERSTAND ITS CONTENTS BEFORE- ATTEMPTING TO OPERATE THIS EQUIP- MENT. SERIOUS PERSONAL INJURY OR DEATH MAY RESULT. CAUTION PROVIDE SUPPORT FOR THIS PANEL TO PREVENT DAMAGE TO THE ELEC- TRICAL COMPONENTS. CAUTION ONLY FACTORY AUTHORIZED BURNER SERVICE PERSONNEL SHOULD START- UP, ADJUST, OR SERVICE THIS EQUIP- MENT. CAUTION AFTER FINAL FUEL INPUT ADJUST- MENTS ARE MADE, VERIFY FUEL IN- PUT BY METER IF POSSIBLE. 1

Further warning and caution references have been made in this manual and should be adhered to for smooth operation of the burner. WARNING CAUTION NOTE This symbol precedes information which, if disregarded, may result in injury to the user of the burner or to others. This symbol precedes information which, if disregarded, may result in damage to the burner. This symbol precedes information which is vital to the operation or maintenance of the burner. Model designations are based on the type of fuel(s) to be fi red and the amount of furnace pressure to be overcome. Burner size is based on fi ring rate (rated input in BTU/HR). MODEL FUEL ATOMIZATION VG/LNVG GAS VL #2 PRESSURE VLG/LNVLG #2 GAS/ PRESSURE EXAMPLE: Model number on nameplate is VLG-45, indicating it is a combination No. 2 oil and Gas burner with input rated at 4,500 MBTU per hour, against furnace pressures up to 2.0 W.C. BURNER SIZE AND RATED FURNACE PRESSURE - V/BURNER: SIZE 1 - V13 to 34 1.0 W.C. SIZE 2 - V35 to 55 2.0 W.C. SIZE 3 - V60 to110 3.0 W.C. SIZE 4 - V120 to 168 4.0 W.C. BURNER SIZE AND RATED FURNACE PRESSURE - LNV BURNER: SIZE 1 - LNV13 to 25 1.5 W.C. SIZE 2 - LNV30 to 50 2.5 W.C. SIZE 3 - LNV54 to 90 4.0 W.C. SIZE 4 - LNV100 to 147 4.5 W.C. NOTE: Firing at higher furnace pressures de-rates the burner by appoximately 5% per one half inch of additional pressure. Consult with Factory. RATED BURNER INPUT SIZE MBTU/HR US GPH 13 1,300 9.3 15 1,500 10.7 17 1,700 12.1 20 2,000 14.3 21 2,100 15.0 25 2,500 17.9 30 3,000 21.4 34 3,400 24.3 35 3,500 25.0 40 4,000 28.6 42 4,200 30.0 45 4,500 32.1 50 5,000 35.7 54 5,400 38.6 55 5,500 39.3 60 6,000 42.9 63 6,300 45.0 70 7,000 50.0 80 8,000 57.1 84 8,400 60.0 90 9,000 64.3 100 10,000 71.4 105 10,500 75.0 110 11,000 78.6 120 12,000 85.7 126 12,600 90.0 147 14,700 105.0 168 16,800 120.0 * Gas input based on natural Gas at 1,000 Btu/cu.ft. and 0.60 specifi c gravity. ** Oil input based on 140,000 Btu/gal. *** Refer to burner nameplate data for correct manifold pressures. THE INSTALLATION OF A BURNER SHALL BE IN ACCORDANCE WITH THE REGULATIONS OF AUTHORITIES HAVING JURISDICTION. THE EQUIPMENT MUST BE INSTALLED IN ACCORDANCE WITH APPLICABLE LOCAL, STATE OR PROVINCIAL INSTALLATION REQUIREMENTS INCLUDING THE NATIONAL ELECTRICAL CODE (NEC) AND ASSOCIATED INSURANCE UNDERWRITERS. AND GAS BURNING EQUIPMENTS SHALL BE CONNECTED TO FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES, TO ASSURE SAFE AND PROPER OPERATION OF THE BURNER. THE V SERIES BURNERS ARE DESIGNED TO BURN EITHER GAS OR LIGHT No.1 OR 2 AS DEFINED BY ASTM D396-1978 SPECIFICATIONS. DO NOT USE GASOLINE, CRANKASE, OR ANY CONTAINING GASOLINE. 2

SECTION 1 INTRODUCTION A. GENERAL INFORMATION Industrial Combustion V/Series burners are assembled, wired and tested at the factory. The V/series burner line is listed by the Underwriters Laboratory for the U.S. and Canada, and bears the UL and cul markings when ordered as such by the customer. Compliance with other regulatory agencies such as CSD-1, I.R.I./GE GAP, F.M., etc., is available at time or order. Optional controls and control systems are also available. The operator of this equipment must be familiar with the individual functioning of all controls to understand the operations and procedures described in this manual, and supplementary instructions provided with optional controls. Identify and locate each item in the illustrations as they are described in the following sections. CAUTION ONLY FACTORY AUTHORIZED BURNER SERVICE PERSONNEL SHOULD START-UP, ADJUST, OR SERVICE THIS EQUIPMENT B. DESCRIPTION The Industrial Combustion V/Series burners are designed to operate with gas and light oil. The burners are designed for automatic, unattended operation except for periodic inspection and maintenance. The control panel components require little attention except for occasional cleaning. The burners are available in the following confi guration SIZE 1 -V13-34 - On-Off (Optional: Low-High-Off, Low- High-Low, Full Modulation) SIZE 2 - V35-55 - Low-High-Off (Optional: Low-High-Low, Full Modulation) SIZE 3 - V60-63 - Low-High-Off (Optional: Low-High-Low, Full Modulation) SIZE 3 & 4 - V70-168 - Full Modulation C. OPERATING CONTROLS - PANEL The burner control panel my be integral to the burner or remote, and contains a fl ame safeguard programming control, motor relays (starters), and terminal strips mounted internally on a panel subbase. Lights, switches, a control circuit breaker are mounted externally on the panel. 1. ON-OFF BURNER SWITCH 2. FUEL SELECTOR SWITCH - Gas - Off - Oil Gas position: Selects gas as the fi ring fuel Off position: Burner off Oil position: Selects oil as the fi ring fuel 3. CONTROL CIRCUIT BREAKER Supplementary low overcurrent protection only. No larger than 15 amps. 4. AUTO-MANUAL MODULATION SELECTOR SWITCH Auto Position: Selects boiler modulation control. In this position, the burner will operate automatically in response to load demand. Manual Position: Selects 135 ohm potentiometer for manual modulating control. 5. MANUAL MODULATING CONTROL 135 ohm (For full modulation burners only) Increases or decreases the burner fi ring rate manually. 6. SIGNAL LAMPS. a. POWER ON (white) illuminates when the control circuit is energized (powered). b. IGNITION (amber) illuminates when the ignition transformer is powered, and pilot valve is energized (opened). c. MAIN FUEL (green) illuminates when the main fuel valve or valves are energized (open). d. FLAME FAILURE (red) illuminates when the fl ame safeguard system fails to detect pilot or main fl ame. 7. MODULATING MOTOR Operates the air damper and fuel rate valves through a linkage system to adjust air-fuel ratios under all load conditions. 8. IGNITION TRANSFORMER Provides high voltage spark for ignition of gas pilot or main fl ame direct spark models. D. FLAME SAFEGUARD CONTROLS The flame safeguard controls the operating sequence of the combustion system (prepurge, pilot, fi ring and shutdown). The fl ame safeguard programmer incorporates a fl ame sensing cell (scanner) to shut down the burner in the event of pilot fl ame or main fl ame failure. Other safety controls shut down the burner based on sequence of operation as shown in the manufacturers fl ame safeguard manual. 3

When a parallel positioning system is furnished, the fl ame safeguard may be incorporated as an integral component to the parallel positioning control. Consult burner and component technical documentation. E. COMBUSTION AIR HANDLING SYSTEM 1. MOTOR AND BLOWER - The impeller is directly driven by the motor at 3450 rpm. A heavy-duty forward curved, multi-blade centrifugal impeller supplies combustion air. 2. AIR VOLUME REGULATOR - Air dampers are located in the air inlet housing. The dampers are mechanically linked and actuated by a two-position motor or hydraulic cylinder for on-off operation. Low-high-off, low-high-low or full modulation burners have the dampers mechanically linked to the modulating motor. 3. COMBUSTION AIR PROVING SWITCH - A pressure sensitive, differential switch actuated by air pressure created by the blower fan. Contacts close to prove combustion air fl ow. 4. DIFFUSER - An air fl ow diffuser stabilizes fl ame front. OPERATION Air from the impeller fl ows through the blast tube and diffuser to mix with fuel in the ignition zone. Combustion air fl ow rate is determined by the position of the air regulating blades at the inlet of the impeller. Linking the air fl ow with fuel fl ow provides effi cient combustion at all fi ring rates. F. SYSTEM Models VL - VLG are high pressure atomizing burners using fuel pressure for atomization. Atomized fuel is discharged from the nozzle as a fi ne conical spray. 1. FUEL UNIT - Size 1 & 2 Direct driven from the blower motor with a fl exible coupling at 3450 rpm, and set for 300 psi operation, fuel unit is two stage (two sets of gears) and must be installed for a two pipe installation, one suction and one return line. Separately driven oil pumps are available as option to the standard arrangement. Size 3 & 4 A separately driven oil pump is standard. 2. NOZZLE - The nozzle meters oil flow delivering a specified amount at a specific pressure. Fuel pressure (mechanical) atomizes oil in a fi ne conical spray pattern from the nozzle orifice. The burner is supplied with nozzle(s) to fire to its maximum rate unless a different firing rate was specified. VL & VLG models 13-34 are supplied with simplex nozzles, models 35-168 are supplied with return fl ow nozzles. 3. NOZZLE ADAPTOR - The nozzle adaptor provides the means for connecting fuel lines with the nozzle. 4. SOLENOID S - Two normally closed (N.C.) and one normally open (N.O.) solenoid valves are part of the oil system on LO-HI-OFF and LO-HI-LO burners. The two N.C. valves provide positive shut off of fuel oil while the one N.O. valve cycles the burner to HI fi re when closed. 5. METERING - The fi ring rate is controlled by an adjustable metering valve in the return line. At low fi re, the metering valve is open, and is closed at high fi re. 6. FILTER - Prevents foreign matter from entering the burner oil system. This item is provided optional and shipped loose with burner. OPERATION Fuel oil is delivered to the fuel unit, either by gravity, fuel unit suction, or by a circulating pump, through a fuel oil fi lter. Pressurized fuel returns to the storage tank until the two solenoid valves open. On direct spark ignited burners, (VL-13 to 55) ignition occurs when the oil valves open. Where gas pilots are provided (Models VG and VLG), the oil valves open after the pilot is proven. Oil input rate is controlled by the oil metering valve, which varies the fl ow to meet load demands. The low fi re positions bypass oil back to the storage tank. At high fi re, the metering valve is in the closed position. The modulating motor positions the metering valve and the air damper simultaneously. G. IGNITION SYSTEM Oil only models VL-13 to 55 are supplied with direct spark ignition. Models VL-60 to 168 are supplied with a gas pilot system. Gas and combination Gas-Oil models are supplied with a gas ignition system. The standard pilot gas train consists of a manual shutoff cock, a gas pressure regulator and a solenoid operated gas shutoff valve. H. GAS HANDLING SYSTEM Depending upon the requirements of the regulating authority, the gas control system and gas train may consist of some, or all, of the following items. MAIN GAS TRAIN COMPONENTS 1. GAS VOLUME - The butterfl y type valve is positioned by linkage from the modulating motor and controls the rate of fl ow of gas. 2. MAIN GAS S - Electrically operated safety shutoff valve(s) that open to admit gas to the burner. Standard U.L. burners include: -Models: 13-25; Diaphragm gas valve & solenoid valve -Models: 30-50; One motorized gas valve w/proof of closure or two safety shutoff valves. -Models: 55-120; One motorized gas valve w/proof of closure and one safety shutoff valve. -Models: 126-168; Two motorized gas valves (Two motorized gas valves can be optionally provided on all models) 3. MAIN GAS REGULATOR - Regulates gas train pressure to specifi ed pressure required at the burner manifold. Input is set by main gas pressure regulator adjustment. 4

4. MAIN GAS COCKS - Used for manual shutoff of the gas supply upstream of the pressure regulator. A second shutoff cock downstream of the main gas valve(s) provides a means of testing for leakage through the gas valve(s). 5. HIGH GAS PRESSURE SWITCH. (Models 30-168) A pressure actuated switch that remains closed when gas pressure is below a selected setting. Should the pressure rise above the setting, the switch contacts will open causing main gas valve(s) to close. This switch requires manual reset after being tripped. 6. LOW GAS PRESSURE SWITCH. (Models 30-168) A pressure actuated switch that remains closed when gas pressure is above a selected setting. Should the pressure drop below this setting, the switch contacts will open, causing main gas valve(s) to close. This switch requires manual reset after being tripped. OPERATION Metered gas fl ows through the main gas shutoff cock, through the pressure regulator to the automatic gas valves and butterfl y valve to the gas manifold.the butterfl y gas valve modulates fl ow to burner input demand. The butterfl y valve is positioned through mechanical linkage by the modulating motor. The air control damper is positioned simultaneously by the modulating motor. The automatic gas valve(s) cannot be energized unless the combustion air proving switch is closed. The low and high gas pressure switches must be closed to prove proper gas pressure. A normally open vent valve, if required, is located between the two automatic gas valves. This valve is shut when the automatic gas valves are open. When the automatic valves are closed, the vent valve is open for venting gas to the outside, should any be present. NOTE GAS TRAIN COMPONENTS UP- STREAM OF THE BUTTERFLY ARE SHIPPED LOOSE TO BE MOUNTED BY THE INSTALLER. NOTE PILOT GAS SUPPLY CONNECTION MUST BE UPSTREAM OF THE MAIN GAS PRES- SURE REGULATOR GAS PILOT TRAIN SCANNER ELECTRICAL ENCLOSURE SOLENOID IGNITION TRANSFORMER BLOWER MOTOR GAS BUTTERFLY MODULATING MOTOR METERING F.G.R. (Low NOx Only) AIR HOUSING 656-00001 Figure 1-1 5

GAS MANIFOLD DIFFUSER AIR BAFFLE MOUNTING FLANGE CHOKE RING NOZZLE BODY AND TIP RADIAL GAS SPUDS 656-00002 Figure 1-2 A J B C K DIA. C L 4X Ø3/4 L B.C. M C L D C L I U T N G H F E S R P 656-00037 BURNER STANDARD CONFIGURATION - REAR MOUNTED PANEL, GAS PILOT LINE PANEL MOUNTED MODEL A B C D E F G H I J K L M N P R S T U SIZE 1 32 7/8 12 3/8 4 8 1/4 3 3/4 15 9 3/4 30 9 3/4 7 3/8 12 7/8 11 1/4 6 1/2 14 3/8 13 12 5 /14 7 1/4 11 3/4 SIZE 2 37 1/3 13 5/8 4 10 4 18 1/8 8 34 1/2 10 1/2 7 3/8 15 13 1/4 7 1/2 15 1/8 12 1/2 12 3/4 6 1/4 9 14 1/2 SIZE 3 44 3/8 16 1/8 4 11 1/2 3 3/4 17 1/2 15 3/4 41 3/4 15 1/4 7 3/8 16 3/4 15 1/4 8 3/8 17 3/8 12 1/2 14 1/8 6 1/4 10 1/4 18 5/8 SIZE 4 54 3/8 24 7/8 5 13 5/8 4 25 1/4 12 45 7/8 13 1/2 7 3/8 17 1/2 15 3/8 8 3/4 20 1/8 14 1/2 16 7 1/2 12 1/4 19 1/4 *Dimensions are in inches Figure 1-3 6

A. DRAFT CONDITIONS A boiler or other heating vessel fired with a V Series burner does not depend on chimney draft for proper combustion air. Combustion air is supplied by the burner forced draft blower providing adequate air for any normal combustion condition. Since draft control is essential to maximum effi ciency, a draft regulator may be required when the vessel is connected to a tall stack or where wind conditions may cause erratic draft. Excessive furnace draft contributes to inefficient burner operation. Sealed boilers may be operated under positive fi rebox pressure within the capability of the burner. B. COMBUSTION AIR SUPPLY The space in which a burner operates must be supplied with adequate fresh air for combustion and ventilation purposes. Fresh air supply must meet or exceed all code requirements. Consult with insurance carrier and/or local authorities for specifi c regulations. WARNING THE BER ROOM PRESSURE MUST BE AT LEAST EQUAL TO THE OUTDOOR ATMO- SPHERIC PRESSURE. WHERE FAN VENTILA- TION IS USED, AIR MUST BE FORCED INTO THE BER ROOM. NEVER EXHAUST AIR FROM THE BER ROOM. ADJOINING AREAS HAVING EXHAUST FANS MUST BE POSITIVILY ISOLATED FROM THE BER ROOM. C. COMBUSTION CHAMBER DESIGN It is not possible to include a complete design and construction combustion chamber manual in this section, but the following may be helpful in arranging burner applications in typical boilers. Combustion chambers are of fi ve basic types: 1. Commercial Flex tubes watertube type boilers. 2. Conventional Cast Iron sectional boilers. 3. Conventional dry bottom fi rebox boilers having a refractory fl oor and full water walls. 4. Full refractory combustion chambers in ash pit type installations where a complete fi rebox is required below the level of the boiler water walls. 5. Commercial Fire Tubes scotch marine type boilers. SECTION 2 INSTALLATION The V series burners are of the forced draft fl ame retention type. Refractory is required only to protect surfaces not adequately protected by free circulating water. Four basic objectives are: 1. Provide adequate combustion space. 2. Avoid fl ame impingement. 3. Protect surfaces not adequately water cooled. 4. Seal openings. BURNER COMBUSTION CHAMBER MODEL LENGTH WIDTH CL HEIGHT 13 56 26 12 15 56 26 12 17 56 26 12 20 56 26 12 21 56 26 12 25 56 26 12 30 62 30 13.5 34 62 30 13.5 35 62 30 13.5 40 62 30 13.5 42 62 30 13.5 45 62 30 13.5 50 83 33 15 54 83 33 15 55 83 33 15 60 83 33 15 63 83 33 15 70 83 33 15 80 104 39 18.5 84 104 39 18.5 90 104 39 18.5 100 128 39 18.5 105 128 39 18.5 110 128 39 18.5 120 128 39 18.5 126 128 39 18.5 147 142 44 22 168 142 44 22 Figure 2-1 Suggested Minimum Combustion Chamber Dimensions in Figure 2-1 are based on the rated capacity of the burner. 7

While these dimensions are typical for good practice, satisfactory results may be achieved with modifi cations to suit some conditions. Factors such as fuel properties, total combustion volume, length of flame travel often make fixed requirements impractical. When in doubt, consult the factory. Insulation should be provided between the refractory and the boiler base. Mineral wool, or other material not likely to settle is preferred. The chamber front wall may be constructed of fi rebrick or insulating fi rebrick. Insulation should be used between refractory and front plate. Firebrick, or insulating fi rebrick should be set in high temperature bonding mortar with provision for expansion. CAUTION GASKET MUST BE RESILIENT TO SEAL ANY UN- EVEN AREAS BETWEEN THE BURNER FLANGE AND THE BER FRONT PLATE TO PREVENT LEAKAGE OF COMBUSTION GASES. L CL W Firetube Boiler SUPPORT BURNER HERE 656-00006 FIGURE 2-2 L CL W SUPPORT BURNER HERE Cast Iron Boiler 656-00007 FIGURE 2-3 8

L CH W SUPPORT BURNER HERE Firebox Boiler 656-00008 FIGURE 2-4 L CH SUPPORT BURNER HERE Commercial Watertube FIGURE 2-5 9

FIGURE 2-6 D. BURNER INSTALLATION Prepare the boiler front plate as follows: 1. Determine burner mounting height. Locate and scribe a level horizontal centerline across the mounting face. 2. Locate and scribe vertical centerline. Be sure stud locations line up where studs will have full support. If they don t or if opening is too large, a steel adapter plate, 3/8 minimum may be welded or bolted in place. Suitable anchors should be provided to hold refractory in place. Adapter plate must be properly sealed (use insulating rope gasket) to prevent leakage of combustion gases. fl ange. Refer to the general arrangement drawings in the Introduction section of the manual. 5. Permanently support the burner using the pipe support connections. 6. The space between the boiler refractory, water leg, or fi re tube and outside diameter of the blast tube must be packed with plastic refractory, Kaiser Refractory Mono T- Air Set or equal. Ram plastic refractory from front to rear, parallel to outside surface of blast tube. 3. Using insulating rope gasket, wrap rope on the inside of the bolt circle, looping rope around the four mounting studs. 4. Set burner into position for mounting and tighten into place. All burners are equipped with a four-hole mounting 10

E. GAS PIPING Gas service and house piping must supply the quantity of gas demanded by the unit at the pressure required at the burner gas train inlet. All piping must be in strict accordance with applicable codes, ordinances and regulations of the supplying utility. In the absence of other codes, piping should be in accordance with the following standards: National Fuel Gas Code NFPA No. 54, ANSI No. Z223-1. Gas train components upstream of the butterfl y valve are shipped loose. These components should be mounted by the installer as close to the butterfl y valve as practical. Normally, the control train is ordered to suit a particular code or insurance regulation - such as Underwriters Laboratories / Canadian Underwriter s Laboratories (UL / cul) Factory Mutual, or Industrial Risk Insurance. See Figure 2-7 through 2-10 for component arrangement. Arrange gas piping at the burner so that the burner is accessible for servicing without disassembly. The pilot gas train is supplied with the burner, and is factory installed. The gas pilot supply line must be connected upstream of the main gas regulator. If a reducing bushing is required between the house piping and the burner piping, it should be close to the burner shutoff valve. The gas piping must be internally clean and free of foreign material. Before using in service, a leak test must be performed. (SEE SECTION 3-E) F. FUEL PIPING PRESSURE ATOMIZATION PIPING The VL and VLG model burners use pressure atomization. Fuel oil is provided by a burner mounted fuel unit directly coupled to the blower motor via a fl exible coupling on Size 1 & 2 Burners, Remote Pump on Size 3 & 4 Burners. The suction and return line sizes (two-pipe system) are based on the suction rate of the fuel unit and not the burner fi ring rate. Pipe size must be selected so that suction vacuum is within suitable limits. TWO PIPE - SINGLE BURNER OPERATION. A two-pipe system is essential. The suction and return between the storage tank or supply source and the burner must be sized to supply the required quantity of oil circulated, including excess oil returned to the storage tank. SUCTION LINE SIZING. The Suction load is determined by: 1. The vertical lift from the oil level in the tank to the pump. 2. Pressure drop through valves, fi ttings, strainers, etc. 3. The friction loss due to oil fl ow. This loss varies with: a. Quantity of oil pumped (gph). b. Length of suction line (feet). c. Diameter of the suction line. d. Number of fi ttings. Although the gear type pumps used on the V series burners are capable of developing higher suction, it is not desirable to operate above 15 inches of mercury vacuum. If the vacuum is greater, fl ow may be erratic. Refer to the manufacturers table for line sizing 1. Check suction capacity. 2. Measure total pipe length (horizontal and vertical). 3. Read up from line total feet of copper tube to the intersection line of the specific suction capacity in g.p.h. 4. Read left to column inches of vacuum at fuel unit. This is vacuum required to draw oil through pipe listed at given length. 5. Add 1 of vacuum for every foot of lift. 6. Total inches of vacuum (frictional tube loss plus lift). 7. If total exceeds 15, check next larger pipe size. RETURN LINE SIZING. Generally, the return line should be sized the same as the suction line. TWO PIPE - MULTIPLE BURNER SYSTEM. Several options exist for a multiple burner installation. In Figure 2-16 a typical installation showing separate suction lines for each burner with a common return line. Figure 2-17 shows multiple burners with oil supplied by a transfer pump. The circulating pump is sized, in this case for the total suction capacity of all burners. Note that a special pressure regulating valve is required if the fuel unit inlet pressure is above 3 psi. Figure 2-18 shows an installation using a day tank. A pump supplies oil to the day tank. Figure 2-19 shows a fl ooded loop system. The circulating pump is sized according to the maximum burner fi ring rate for all burners plus a 30% service factor. The burner return lines feed into the common supply line. NOTE INDUSTRIAL COMBUSTION RECOMMENDS THAT ALL FIRING BURNERS BE EQUIPPED WITH AN STRAINER (IF NOT INCLUDED WITH THE BURN- ER) TO PREVENT PARTICLES FROM CLOGGING THE NOZZLE. IT IS ESSENTIAL TO FOLLOW THE STRAINER MANUFACTURER S MAINTENANCE SCHEDULE TO ENSURE PROPER FILTRATION. 11

OUTPUT TO BURNER SHUTOFF COCK MAIN GAS MAIN GAS A REGULATOR SHUTOFF COCK TO BURNER PILOT A PILOT REGULATOR INPUT FROM SUPPLY PILOT SHUTOFF COCK 571-0012 Typical U.L. Gas Train - On-Off System - Size 1 V13 to V34 FIGURE 2-7 OUTPUT TO BURNER SHUTOFF COCK A MAIN GAS MAIN GAS REGULATOR SHUTOFF COCK TO BURNER PILOT A PILOT REGULATOR INPUT FROM SUPPLY PILOT SHUTOFF COCK 571-0013 Typical U.L. Gas Train - Low-High-Off System - Size 1 V13 to V34 FIGURE 2-8 12

OUTPUT TO BURNER BUTTERFLY SHUTOFF COCK A MAIN GAS REGULATOR MAIN GAS SHUTOFF COCK TO BURNER PILOT A PILOT REGULATOR INPUT FROM SUPPLY PILOT SHUTOFF COCK 571-0014 Typical U.L. Gas Train - Full Modulation System - Size 1 V13 to V34 FIGURE 2-9 A OUTPUT TO BURNER BUTTERFLY HIGH GAS PRESSURE SWITCH LOW GAS PRESSURE SWITCH SHUTOFF COCK A MAIN GAS A REGULATOR MAIN GAS SHUTOFF COCK TO BURNER PILOT A PILOT REGULATOR INPUT FROM SUPPLY PILOT SHUTOFF COCK 571-0015 Typical U.L. Gas Train - Low-High-Off, Low-High-Low, Size 2 V35 to V63 Full Modulation System - Size 2-3-4 V35 to V168 FIGURE 2-10 13

NOZZLE PRESSURE TAP NOZZLE PRESSURE TAP N.C. S NOZZLE N.C. S NOZZLE MODULATING MOTOR FUEL UNIT PRESSURE TAP FUEL UNIT PRESSURE TAP FUEL UNIT FUEL UNIT SUPPLY SUPPLY RETURN TO TANK RETURN TO TANK FIGURE 2-11 On-Off Oil System Size 1 - V13 to V34 656-00011 FIGURE 2-12 Low-High-Off, Low-High-Low Oil System Size 2 - V35 to V55 656-00012 MODULATING MOTOR N.C. VLAVES SUPPLY NOZZLE PRESSURE TAP NOZZLE Remote Pump System FIGURE 2-13 RETURN TO TANK PRESSURE SWITCH METERING FUEL UNIT PRESSURE TAP CHECK 656-00014 N.C. S NOZZLE PRESSURE TAP NOZZLE MODULATING MOTOR NOZZLE PRESSURE TAP N.C. S MODULATING MOTOR FUEL UNIT PRESSURE TAP FUEL UNIT PRESSURE TAP FUEL UNIT PRESSURE TAP RETURN TO TANK FUEL UNIT FUEL UNIT NOZZLE SUPPLY METERING CHECK SUPPLY FIGURE 2-14 METERING FUEL UNIT PRESSURE TAP Full Modulation Oil System Size 1 - V13 to V34 Simplex Nozzle 656-00013 14 FIGURE 2-15 RETURN TO TANK Full Modulation Oil System Size 2- V35 to V55 Return Flow Nozzle 656-00029

RETURN TO TANK SUPPLY TANK CHECK SUPPLY TO BURNERS CHECK CHECK CHECK GATE BURNER NOZZLE GATE GATE BURNER NOZZLE GATE RETURN RETURN 571-0016 FILTER INLET FUEL UNIT METERING FILTER Multiple Burners with separate suction lines INLET FUEL UNIT METERING FIGURE 2-16 CHECK GATE RETURN TO TANK CHECK CHECK BACK PRESSURE SET BELOW 3 PSI SUPPLY TO BURNERS VOLUME CONTROL BY-PASS CHECK PRESSURE GAUGES W/ISOLATORS GATE BURNER NOZZLE RETURN PRESSURE GAUGE W/ISOLATOR GATE BURNER NOZZLE RETURN SUPPLY TANK GATE FILTER INLET GATE FUEL UNIT CHECK METERING VACUUM OR COMPOUND GAUGE W/ISOLATOR FILTER INLET RELIEF FUEL UNIT METERING 571-0017 STRAINER TRANSFER PUMP Typical Oil Loop for Multiple Burners with Transfer Pump FIGURE 2-17 CHECK BURNER NOZZLE DAY TANK SUPPLY TANK 571-0018 GATE STRAINER GATE VACUUM OR COMPOUND GAUGE W/ISOLATOR CHECK RELIEF Typical Installation Using Day Tank TRANSFER PUMP GATE RETURN STRAINER INLET FUEL UNIT METERING FIGURE 2-18 15

VACUUM BREAKER 6" MINIMUM CHECK CHECK BURNER NOZZLE CHECK BURNER NOZZLE PRESSURE GAUGE GATE PRESSURE GAUGE GATE RETURN RETURN STRAINER INLET FUEL UNIT METERING STRAINER INLET FUEL UNIT METERING SUPPLY TANK GATE STRAINER VACUUM GAUGE W/ISOLATOR GATE STRAINER VACUUM GAUGE W/ISOLATOR GATE TRANSFER PUMP 571-0019 DUPLEX PUMP SYSTEM Typical Flooded Loop System GATE TRANSFER PUMP FIGURE 2-19 G. INSTALLATION CHECKLIST 1. All burners are carefully assembled and tested at the factory, but before being placed in service all connectors should again be checked for looseness caused during shipment. Check: a. Electrical terminals in the control panel and on all electrical components. b. Pipe fi ttings and unions. c. Tubing connections. d. Nuts, bolts, screws. 2. Open all necessary oil shutoff valves. Do not run pumps or fuel unit without oil. 3. Before connecting electrical current to any component, be sure the voltage is the same as that specifi ed on component nameplates. CAUTION BEFORE OPENING THE MANUAL GAS SHUT-OFF S, READ THE REGULA- TOR INSTRUCTIONS CAREFULLY. THE INSTRUCTIONS ARE IN THE REGULATOR BOX. FOLLOW THE MANUFACTURER REC- OMMENDATIONS. OPEN SHUT-OFF ON THE INLET SIDE OF THE REGULATOR SLOWLY AND CAREFULLY TO ALLOW IN- LET PRESSURE TO BUILDUP SLOWLY IN THE REGULATOR UNTIL IT IS FULLY PRES- SURIZED. OPENING THE SHUT-OFF QUICKLY WILL DAMAGE THE REGULATOR. DO NOT EXCEED THE REGU- LATOR PRESSURE RATINGS. 4. Before burner operation, be sure all motors are rotating in the proper direction. 5. Before fi ring, make sure the burner fi ring head and dry areas of the boiler are protected with refractory. The burner mounting fl ange must be properly sealed against the vessel front plate. 6. Make certain that the operator in charge is properly instructed in operation and maintenance procedures. 16

H. FIRING MODES ON-OFF OPERATION Combustion Air Gas Oil Pressure Atomization: Two solenoid type safety shut off oil valves initiate the flow of oil from the high pressure pump to the nozzle. Oil flow rate is fixed based on pump oil pressure and the simplex nozzle's flow rating. COMPONENTS DESCRIPTION: Fixed two bladed damper. Two safety shut of valves are provided to initiate the flow of gas. The primary is a diaphragm or motorized type valve. On diaphragm gas valve the time to open can be adjusted by a bleed valve. On models with motorized valves the time to open is fixed at 13 seconds. A manually adjusted gas regulator limits firing rate. PRE-PURGE: Valves are closed. STARTUP, IGNITION: RUN, MODULATE: SHUT DOWN, POST-PURGE: The damper provided on a on-off is adjusted at the time the burner is installed and fixed in place. The open damper position allows a fixed rate of air flow during all aspects of burner operation while the blower motor is operational. Valves open. To prevent a surge of gas from reaching the manifold, the primary gas valves open at a slowed rate. Valves remain open. Valves remain open. On shut down all gas valves close within 1 second. The valves are closed. The oil pump is operating with pre-purge, but oil is flowing through an internal relief and returning to the supply system. The valves open allowing pressurized oil to flow from the pump to the nozzle. Valves close immediately. The oil pump is operating with postpurge, but oil is once again relieved to the supply system. OPERATION VARIATIONS: None None None 17

LOW-HIGH-OFF OPERATION - LOW or 60% DAMPER PURGE COMPONENTS DESCRIPTION: A two blade damper which is controlled by a two position, spring return actuator with mechanical linkage. For 60% damper purge a mechanical stop is provided on the damper to ensure sufficient air flow is provided during prepurge. Damper position is controlled by a two position, spring return actuator with mechanical linkage. The actuator also contains a limit switch which is used to actuate the second stage of the oil supply system. (see oil at right) Two safety shut of valve are provided to initiate the flow of gas. The primary is a diaphragm or motorized type valve which have delayed opening rates to prevent an "in rush" of gas. A butterfly type gas metering valve is linked directly to the damper actuator and provides gas flow metering during the drive to the high position. A manually adjusted gas regulator limits maximum firing rate. PRE-PURGE: Damper is in it's closed or low fire position. For 60% damper purge this would be against the mechanical stop. Valves are closed. STARTUP, IGNITION: RUN, MODULATE: Damper remains in it's low fire starting position. Damper is driven open in 30 seconds by the two position actuator. Low-High-Off burners have no provision to modulate the burner once high fire rate has been achieved. Valves open. To prevent a surge the primary gas valve opens at a slowed rate. Gas flow to the manifold is metered based on the butterfly valves low fire setting. The gas valves remain in their open position. The actuator begins it's travel to the high fire position opening the gas metering valve. The burner will remain at high fire until demand is satisfied. SHUT DOWN, POST-PURGE: Damper returns to its start position based on the 25 second closure speed of the mechanical actuator. On shut down all gas valves close within 1 second. The butterfly valve closes in 25 seconds with the two position actuator. VARIATIONS: None None Pressure Atomization: Two solenoid type safety shut off oil valves initiate the flow of oil from the high pressure pump to the nozzle. The oil pump has a built in solenoid controlled two level pressure regulating system. Low and high flow rates are set on the pump based on pressure and the nozzle's flow rating. The pump is operational but the valves are closed. Oil is flowing through an internal relief valve and returning to the supply system. Safety shut off valves open allowing oil to flow from pump to nozzle. Oil pressure at the nozzle is based on the pump's low pressure setting. Excess oil is flowing through an internal relief valve and returning to the supply system. The safety shut-off oil valves remain open. The pump's solenoid is energized by the auxiliary switch within the damper actuator as it opens the air damper. Oil pressure is then increased based the pumps high pressure setting. The burner will remain at high fire until demand is satisfied. All valves immediately return to their startup or de-energized position. The oil pump is operating with post-purge, but oil is flowing through an internal relief valve and returning to the supply system. For pumps without the internal dual pressure solenoid an external pressure relief valve and normally open solenoid valve are used. OPERATION 18

LOW-HIGH-OFF OPERATION - OPEN DAMPER PURGE COMPONENTS DESCRIPTION: A two blade damper which is controlled by a two position, spring return actuator with mechanical linkage. The actuator also contains a limit switch which is used to actuate the second stage of the oil supply system. (see oil at right) A second external switch ensures the damper has returned to the low fire position before ignition is initiated. Two safety shut of valve are provided to initiate the flow of gas. The primary is a diaphragm or motorized type valve which have delayed opening rates to prevent an "in rush" of gas. A butterfly type gas metering valve is linked directly to the damper actuator and provides gas flow metering during the drive to the high position. A manually adjusted gas regulator limits maximum firing rate. PRE-PURGE: From it's closed position the damper is driven open by the flame safeguard control where it remains for the duration of the prepurge cycle. Valves are closed. STARTUP, IGNITION: RUN, MODULATE: Damper returns to the low fire position which is proven through the external switch. The burner is now ready for startup. Damper is driven open in 30 seconds by the two position actuator. Low-High-Off burners have no provision to modulate the burner once high fire rate has been achieved. Valves open. To prevent a surge the primary gas valve opens at a slowed rate. Gas flow to the manifold is metered based on the butterfly valves low fire setting. The gas valves remain in their open position. The actuator begins it's travel to the high fire position opening the gas metering valve. The burner will remain at high fire until demand is satisfied. SHUT DOWN, POST-PURGE: Damper returns to its start position based on the 25 second closure speed of the mechanical actuator. On shut down all gas valves close within 1 second. The butterfly valve closes in 25 seconds with the two position actuator. VARIATIONS: None None Pressure Atomization: Two solenoid type safety shut off oil valves initiate the flow of oil from the high pressure pump to the nozzle. The oil pump has a built in solenoid controlled two level pressure regulating system. Low and high flow rates are set on the pump based on pressure and the nozzle's flow rating. The pump is operational but the valves are closed. Oil is flowing through an internal relief valve and returning to the supply system. Safety shut off valves open allowing oil to flow from pump to nozzle. Oil pressure at the nozzle is based on the pump's low pressure setting. Excess oil is flowing through an internal relief valve and returning to the supply system. The safety shut-off oil valves remain open. The pump's solenoid is energized by the auxiliary switch within the damper actuator as it opens the air damper. Oil pressure is then increased based the pumps high pressure setting. The burner will remain at high fire until demand is satisfied. All valves immediately return to their startup or de-energized position. The oil pump is operating with post-purge, but oil is flowing through an internal relief valve and returning to the supply system. For pumps without the internal dual pressure solenoid an external pressure relief valve and normally open solenoid valve are used. OPERATION 19

LOW-HIGH-LOW MOD - LOW or 60% DAMPER PURGE COMPONENTS DESCRIPTION: A two blade damper which is controlled by a two position, spring return actuator with mechanical linkage. For 60% damper purge a mechanical stop is provided on the damper to ensure sufficient air flow is provided during prepurge. Power to drive the actuator is routed through a low/auto switch and a remote located modulating control. The actuator also contains a limit switch which is used to actuate the second stage of the oil supply system. (see oil at right) Two safety shut of valve are provided to initiate the flow of gas. The primary is a diaphragm or motorized type valve which have delayed opening rates to prevent an "in rush" of gas. A butterfly type gas metering valve is linked directly to the damper actuator and provides gas flow metering during the drive to the high position. A manually adjusted gas regulator limits maximum firing rate. PRE-PURGE: Damper is in it's closed or low fire position. For 60% damper purge this would be against the mechanical stop. Valves are closed. STARTUP, IGNITION: RUN, MODULATE: Damper remains in it's low fire starting position. Damper is driven open in 30 seconds by the two position actuator. Low-High-Low burners will modulate from the low to high rate positions based on the signal from the modulating control and the selection of the low/auto switch. Valves open. To prevent a surge the primary gas valve opens at a slowed rate. Gas flow to the manifold is metered based on the butterfly valves low fire setting. The gas valves remain in their open position. The actuator begins it's travel to the high fire position opening the gas metering valve. The burner will then modulate from low to high as described in the combustion air column. SHUT DOWN, POST-PURGE: Damper returns to its start position based on the 25 second closure speed of the mechanical actuator. On shut down all gas valves close within 1 second. The butterfly valve closes in 25 seconds with the two position actuator. VARIATIONS: None None Pressure Atomization: Two solenoid type safety shut off oil valves initiate the flow of oil from the high pressure pump to the nozzle. The oil pump has a built in solenoid controlled two level pressure regulating system. Low and high flow rates are set on the pump based on pressure and the nozzle's flow rating. The pump is operational but the valves are closed. Oil is flowing through an internal relief valve and returning to the supply system. Safety shut off valves open allowing oil to flow from pump to nozzle. Oil pressure at the nozzle is based on the pump's low pressure setting. Excess oil is flowing through an internal relief valve and returning to the supply system. The safety shut-off oil valves remain open. The pump's solenoid is energized by the auxiliary switch within the damper actuator as it opens the air damper. Oil pressure is then increased based the pumps high pressure setting. The burner will then modulate from low to high as described in the combustion air column. All valves immediately return to their startup or de-energized position. The oil pump is operating with post-purge, but oil is flowing through an internal relief valve and returning to the supply system. For pumps without the internal dual pressure solenoid an external pressure relief valve and normally open solenoid valve are used. OPERATION 20

LOW-HIGH-LOW MOD - OPEN DAMPER PURGE COMPONENTS DESCRIPTION: A two blade damper which is controlled by a two position, spring return actuator with mechanical linkage. Power to drive the actuator is routed through a low/auto switch and a remote located modulating control. The actuator also contains a limit switch which is used to actuate the second stage of the oil supply system. (see oil at right) A second external switch ensures the damper has returned to the low fire position before ignition is initiated. Two safety shut of valve are provided to initiate the flow of gas. The primary is a diaphragm or motorized type valve which have delayed opening rates to prevent an "in rush" of gas. A butterfly type gas metering valve is linked directly to the damper actuator and provides gas flow metering during the drive to the high position. A manually adjusted gas regulator limits maximum firing rate. PRE-PURGE: From it's closed position the damper is driven open by the flame safeguard control where it remains for the duration of the prepurge cycle. Valves are closed. STARTUP, IGNITION: RUN, MODULATE: Damper returns to the low fire position which is proven through the external switch. The burner is now ready for startup. Damper is driven open in 30 seconds by the two position actuator. Low-High-Low burners will modulate from the low to high rate positions based on the signal from the modulating control and the selection of the low/auto switch. Valves open. To prevent a surge the primary gas valve opens at a slowed rate. Gas flow to the manifold is metered based on the butterfly valves low fire setting. The gas valves remain in their open position. The actuator begins it's travel to the high fire position opening the gas metering valve. The burner will modulate from low to high as described in the combustion air column. SHUT DOWN, POST-PURGE: Damper returns to its start position based on the 25 second closure speed of the mechanical actuator. On shut down all gas valves close within 1 second. The butterfly valve closes in 25 seconds with the two position actuator. VARIATIONS: None None Pressure Atomization: Two solenoid type safety shut off oil valves initiate the flow of oil from the high pressure pump to the nozzle. The oil pump has a built in solenoid controlled two level pressure regulating system. Low and high flow rates are set on the pump based on pressure and the nozzle's flow rating. The pump is operational but the valves are closed. Oil is flowing through an internal relief valve and returning to the supply system. Safety shut off valves open allowing oil to flow from pump to nozzle. Oil pressure at the nozzle is based on the pump's low pressure setting. Excess oil is flowing through an internal relief valve and returning to the supply system. The safety shut-off oil valves remain open. The pump's solenoid is energized by the auxiliary switch within the damper actuator as it opens the air damper. Oil pressure is then increased based the pumps high pressure setting. The actuator begins it's travel to the high fire position opening the gas metering valve. The burner will modulate from low to high as described in the combustion air column. All valves immediately return to their startup or de-energized position. The oil pump is operating with post-purge, but oil is flowing through an internal relief valve and returning to the supply system. For pumps without the internal dual pressure solenoid an external pressure relief valve and normally open solenoid valve are used. OPERATION 21

FULL MODULATION - LOW or 60% DAMPER PURGE COMPONENTS DESCRIPTION: Combustion Air Gas Oil A two blade damper's position is controlled by a proportional modulating actuator (or motor) with mechanical linkage. The modulating actuator is capable of stopping at any point along it's 90 degree stroke based on a signal from a remotely connected modulating control or from a burner mounted manual potentiometer which is selected through an auto/manual modulation selector switch. The actuator also contains an internal switch that ensures the damper is in the low fire position before ignition is initiated. For 60% damper purge a mechanical stop is provided on the damper to ensure sufficient air flow is provided during prepurge. Two safety shut of valve are provided to initiate the flow of gas. The primary is a diaphragm or motorized type valve which have delayed opening rates to prevent an "in rush" of gas. A butterfly type gas metering valve is linked directly to the damper actuator and provides gas flow metering relative to the actuators position. A manually adjusted gas regulator limits maximum firing rate. Pressure Atomization: Two solenoid type safety shut off oil valves initiate the flow of oil from the high pressure pump to a return flow nozzle. In the return line from the nozzle is an adjustable oil metering valve which limits the amount of oil allowed to return to the pump. The metering valve is connected to the damper actuator with mechanical linkage. PRE-PURGE: STARTUP, IGNITION: RUN, MODULATE: Damper is in it's closed or low fire position. For 60% damper purge this would be against the mechanical stop. Damper remains in it's low fire starting position. The burner is now ready for startup. Damper is driven by the modulating actuator to a firing rate position as determined by the modulating control or manual potentiometer. The actuator can complete full travel to high fire in 30 seconds. The actuator will then continue to adjust the firing rate position based on signals from the modulating control until demand is satisfied. Valves are closed. Valves open. To prevent a surge the primary gas valve opens at a slowed rate. Gas flow to the manifold is metered based on the butterfly valves low fire setting. The gas valves remain in their open position. As the actuator begins it's travel to the firing rate position it is also adjusting the butterfly gas metering valve increasing the flow of gas to the manifold. The burner will continue to modulate as described under the combustion air heading until demand is satisfied. The pump is operational but the valves are closed. Oil is flowing through an internal relief valve and returning to the supply system. Safety shut off valves open allowing oil to flow from pump to nozzle. Oil pressure at the nozzle is based on the pump's pressure setting less the volume of oil returning through the metering valve. The safety shut-off oil valves remain open. As the actuator begins it's travel to the firing rate position it is also adjusting the oil metering valve decreasing the amount of oil allowed to return to the pump. This in turn is increasing the pressure and volume of oil at the nozzle. The burner will continue to modulate as described under the combustion air heading until demand is satisfied. OPERATION SHUT DOWN, POST-PURGE: Damper returns to its starting position based on the 30 second closure speed of the mechanical actuator. On shut down all gas valves close within 1 second. The butterfly valve closes in 30 seconds with the damper actuator. All valves immediately close. The metering valve opens to it's low fire position in 30 seconds with the damper actuator. The oil pump is operating with post-purge, but oil is flowing through an internal relief valve and returning to the supply system. On models with a simplex nozzle oil is diverted from the supply line through the meter and back to the pump before the first safety shut-off valve. VARIATIONS: Options are available for 4-20amp modulating signal conversion or 4-20 proportional modulating actuators. Also optional is an actuator with dual low fire start switch positions for improved "turn down" in dual fuel situations. None 22