Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

Similar documents
COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

S Surge Arresters

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

Effective March 2015 Supersedes S August 2002

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

Erection, maintenance and disposal Inverted installation. Zinc oxide silicone-housed surge arresters PEXLIM R-X, Q-X and P-X

Effective May 2017 Supersedes August 2005 (S )

Norrsken Family Booklet

Permanent Roof Anchors

Inspection Recommendations

DEEPSEA POWER & LIGHT. Operator s Manual. SeaLite Six. Original Instruction Ruffin Road San Diego, CA USA

Sub-Base Assembly For Type-ML 32 & VR-1 Step Voltage Regulator Single-Phase Liquid-Filled Part # GEK 35171

Vertical Lifeline. Ladder Climb. User Instructions. 3M Occupational Health and Environmental Safety. Fall Protection Equipment

SIX R (P ) AND SEVEN R (P ) POSITION CYLINDERS Service Information

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

USER INSTRUCTION MANUAL CONCRETE BOLT ANCHORAGE CONNECTOR

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

INSTRUCTIONS FOR USE

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

BS Series Basket Strainer

WHEATLEY Series 500 Swing Check Valve

Instruction Manual. Model TC1-S TopSide Clamp. top side clamp. For your personal safety READ and UNDERSTAND instructions before using tools.

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

S Loadbreak Apparatus Connectors WARNING: WARNING:

3M Liqui-Cel EXF-14x28 and 14x40 Series Membrane Contactor

2000 lb manual winch

INSTRUCTIONS FOR MODELS UPH & UPHS HIGH FLOW, HIGH PURITY GAS REGULATORS

INSTRUCTIONS FOR USE

GRAVITY BIKE RACK ASSEMBLY & OPERATING INSTRUCTIONS

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

User Instructions 1789 Parapet Wall Anchor

Tripod. System. User Instructions. 3M Occupational Health and Environmental Safety. Fall Protection Equipment

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm)

Type BBS-03, BBS-05, BBS-06, BBS-25

RGC-IR Remote Gas Calibrator for IR400

OPERATION AND INSTRUCTION MANUAL Swivel Anchor Model: HD26248

60 farm jack. Distributed exclusively by Harbor Freight Tools Mission Oaks Blvd., Camarillo, CA 93011

INSTALLATION COMMISSIONING, OPERATION & MAINTENANCE MANUAL

OPERATION AND INSTRUCTION MANUAL Swivel Anchor Model: SWY100N

New AQF Filter Polymer Filtration System

Model C Pipe Line Strainer 6, 8 & 10 Inch (DN150, DN200 & DN250) 250 psi (17,2) General Description. Technical Data. Page of 6 MAY, 2006 TFP1644

User Instruction Manual Fixed Beam Anchor

GALISO SOAP OPTION FOR PCT-ADW-D

STYLE 3414/3416 & 3421/3423 Apollo Monitor with Foldaway Legs OPERATING & MAINTENANCE INSTRUCTIONS

E X R A D I N Spherical Ion Chambers A3. A4 REF DOC #

OWNERS MANUAL. Model Shown with optional Primary Mooring Cleats. Portable Mooring System SAFETY OPERATION MAINTENANCE PARTS

OPERATION AND INSTRUCTION MANUAL

INSTRUCTION MANUAL Pressure Relief Device LPT

Instruction Manual No. 742, 8/98

Installation, Operation and Maintenance Manual. TSV Temperature Shut-off Valve SPD Rev. 6 10/07

TRAVSMART permanent single-cable horizontal lifeline system

RollGliss Rescue Emergency Descent Device. This manual is intended to be used as part of an employee training program as required by OSHA.

3M Liqui-Cel EXF-4x13 and 4x28 Series Membrane Contactors

This document to be used with Hurley traditional Davits

OPERATION AND INSTRUCTION MANUAL Flat Roof Anchor Model: FRA250L-10X-CTS

WHEATLEY Series 822/820 Swing Check Valve

PLEASE READ CAREFULLY BEFORE INSTALLING OR USING MEGA POOL SAVER MPS 1100

3" UC Ultra-Chuck Durable Lightweight Air Inflated Bladder Chuck Operation/Repair Manual. (76.2 mm) DOUBLE E COMPANY, INC.

453 Series Steam Heated Vaporizing Regulator

SPECIFICATIONS ATTENTION

SECURITY AND CONFIDENCE AT HEIGHT

CP-D/CP-M Circular Polarizer for Phoroptor. User s Guide

Transcription:

Surge Arresters MN235014EN Effective January 2017 Supersedes July 2011 (I235-84-1) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions COOPER POWER SERIES Olean, NY USA Va ristar SURGE ARRESTER Cat. No. AZG4 Ser. No. Rating MCOV/COV Pres Relief 63 kv rms kv rms ka rms sym Class Cert. 4/20 ka IEC 60099-4 Year Frequency 50-60 Hz Alt. 0-12000 Ft. 0-3600 M

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... I SAFETY INFORMATION... III Safety instructions...iii PRODUCT INFORMATION.... 1 Introduction...1 GENERAL APPLICATION RECOMMENDATIONS.... 1 IDENTIFICATION... 1 ASSEMBLY.... 1 Base or Foundation Mounting...2 Bracket or Structure Mounting...2 Suspension Mounting...2 ELECTRICAL CONNECTIONS.... 2 MAINTENANCE....3 ii

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. iii

Eaton s Cooper Power series VariSTAR Type AZG4 Surge Arrester is designed to be operated in accordance with safe operating procedures. These instructions are not intended to supersede or replace proper safety and operating procedures. Read all instructions before installing the arrester. Surge arresters should be installed and serviced only by personnel familiar with good safety practice and the handling of high voltage electrical equipment Product information Introduction Eaton s Cooper Power series VariSTAR AZG4 Class 4, 20 ka Surge Arresters incorporate the latest in metal oxide varistor (MOV) technology. These arresters are totally gapless and are constructed of a single series column of 76 mm diameter MOV disks. The arrester is designed and tested exclusively to the requirements of the international standard IEC 60099-4 and is available in ratings for the overvoltage protection of high voltage systems through 400 kv. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user s purpose, please contact your Eaton representative. Initial inspection The factory takes special precautions to ship the arresters in well-designed containers that reduce the possibility of damage, which may occur during transit. Carefully inspect each arrester for physical damage. In case of improper handling or shipping damage, immediately file a claim with the carrier and promptly notify Eaton or your local representative. Do not install arresters that have evidence of external damage. Handling and storage If the arrester is to be stored for an appreciable time before installation, provide a clean, dry storage area. Locate the arrester so as to minimize the possibility of physical damage. Quality standards ISO 9001 Certified Quality Management System General application recommendations Eaton s Cooper Power series product application engineers are available to make specific application recommendations. Identification A nameplate attached to the base casting of each VariSTAR Arrester indicates its catalog number, voltage rating (Ur), continuous operating voltage (Uc), rated frequency, pressure relief rated current, class, reference to the type test standard, altitude range, serial number, and year of manufacture. For multiple unit arresters, a nameplate attached to the top casting of each unit indicates the catalog number and serial number of the complete arrester of which the unit forms a part. The unit nameplate also indicates the total number of units comprising the complete arrester and references the position of this unit in the complete assembly. Olean, NY USA VariSTAR SURGE ARRESTER Cat. No. AZG4 Ser. No. Rating MCOV/COV Pres Relief 63 kv rms kv rms ka rms sym Class Cert. 4/20 ka IEC 60099-4 Frequency 50-60 Hz Figure 1. Unit Nameplate. Alt. 0-12000 Ft. 0-3600 M Year Always handle surge arresters carefully. Dropping or jarring an arrester may cause serious damage to the porcelain and/or internal parts and may cause catastrophic failure upon energization. Assembly VariSTAR Type AZG4 Arresters rated 3- through 120 kv are shipped ready for installation. Assemble multiunit VariSTAR Type AZG4 Arresters in a series stack as indicated on the nameplate attached to the top casting of each unit. A grading ring is supplied for standard arresters rated 172 to 360 kv and some arresters of lower voltage rating having extra leakage housings. Grading ring assembly instructions are shown in Figure 8. Choose a permanent location so that the arresters will be installed as (electrically) close as possible to the equipment being protected. Minimum clearance distances between 1

any line potential surface to an arrester and to any ground plane are listed in Table 1. Figures 2 and 3 show alternate mounting arrangements. See Table 1 and Figure 7 for standard arrester height and leakage distance information. The values shown in Table 1 are the minimum clearances recommended by Eaton. These minimum clearances may be increased to meet local or system requirements for spacing of energized equipment. Safe operating practices must always be followed. Make electrical connections so that no mechanical stress is applied to the arrester. Base or foundation mounting Pier footings should extend below the frost line. Elevate the foundation sufficiently above the ground line for personnel safety and to prevent contamination from ground splash, drifting snow, floodwater, or other contaminating conditions. If the top of the foundation is not level, shims will be required for leveling. Layout mounting dimensions for the foundation are shown in Figure 6. The base section (unit #1) shall be bolted to the foundation. Units #2, #3 and #4 (as applicable) shall be bolted in place, one unit at a time, until all arrester units and grading ring (if supplied) are assembled. Electrical connections Install the arrester as close as possible (electrically) to the apparatus being protected. Line and earth connections must be short and direct. Make the earth connection to a solid, effective and permanent low resistance earth. Equipment protection will be improved by always interconnecting the arrester earth connections with the transformer tank and system neutral whenever possible. The standard line terminal (Figure 4) and earth terminal (Figure 5) include connector clamps that accommodate 14-335 mm 2 stranded copper or aluminum conductor. This is equivalent to a maximum conductor diameter of 21 mm or 500 mcm. The line and earth terminals allow the connector clamp to be positioned for vertical or horizontal conductor takeoff; in addition, they accommodate industry standard two- or four-hole connectors. C C 0.5 C C 0.866 C The vent port in the base must be directed away from adjacent equipment to prevent ionized gases from damaging other equipment in the unlikely event of arrester failure. Bracket or structure mounting When bolting arresters directly to structures, or mounting brackets, make the assembly rigid enough to prevent mechanical failure. Suspension mounting Arresters rated through 168 kv can be suspension mounted. Either the top or bottom of suspension mounted arresters can be connected to the line as long as the sheds on the porcelain housings are not inverted. For additional information regarding suspension mounting, contact your Eaton factory representatives. Figure 2. Three-phase triangular mounting. Refer to Table 1, page 7, for Dimension C. C C DIRECTED VENT POINT Figure 3. Three-phase in-line mounting. D DIRECTED VENT PORT Refer to Table 1, page 7, for Dimensions B and C. D To prevent strains on the arrester when suspension mounting, suspend it freely. Always make flexible connections to line and earth terminals. 2

1.11 cm DIA HOLES ON 4.44 cm CENTERS STAINLESS STEEL CLAMP 7.62 cm TYPICAL 4 PLACES GALVANIZED STEEL BOLTS Maintenance WARNING Before working on arresters, disconnect all line leads. Consider any part of an arrester dangerous when connected to the line, including a base not solidly earthed. 1.90 cm ALUMINUM ALLOY 4.44 cm 9.52 cm (3) 16 x 32 mm LG. MTG. SLOTS (120 APART) 222 254 mm DIA. BOLT CIRCLE* 60 1.43 cm DIA HOLES ON 4.44 cm CENTERS 120 Figure 4. Line terminal cap. Line and earth terminals (suitable for copper or aluminum conductors up to 335 mm 2 (up to a maximum diameter of 20 mm)). THICKNESS OF MOUNTING FEET IS 22 mm TYPICAL 4 PLACES GALVANIZED STEEL BOLTS 7.62 cm 4.44 cm 9.52 cm Figure 6. Base mounting details. * To develop rated cantilever strength use 254 mm bolt circle mounting diameter and 12 mm hardened bolts and flat washers. GALVANIZED STEEL VariSTAR Type AZG4 Arresters require no special maintenance under normal conditions. If the arrester is installed in an area of severe contamination, keep the arrester housing clean by washing periodically. Keep line and earth connections tight. 1.43 cm DIA HOLES ON 4.44 cm CENTERS STAINLESS STEEL WARNING Arresters can be washed while energized provided standard live washing procedures are followed. Figure 5. Earth terminal. Line and earth terminals (suitable for copper or aluminum conductors up to 335 mm 2 (up to a maximum diameter of 20 mm)). 3

1070 DIA 1070 DIA 1400 DIA 600 DIA (508*) 600 600 770 390 (300*) A A A A A A VIEW1 VIEW2 VIEW3 VIEW4 VIEW5 VIEW6 *FOR 172 kv ONLY Figure 7. Dimensions of VariSTAR Type AZG4 Surge Arrester. Refer to Table 1, page 7, for Dimension A. MOUNTING TABS U r =172-240 kv U r =258-294 kv U r =300-360 kv PLACE THE (3) GRADING RING MOUNTING TABS UNDER LINE TERMINAL CAP. Part No. Digits 6 & 7 of Arrester Catalog No. AT76Y1 60-61 AT76Y2 62-65 AT76Y3 67-69 AT76Y4 70-72 AT76Y5 74-75 Figure 8. Grading ring assembly. Arresters with extra leakage housings may require grading rings in different voltage ratings. 4

Table 1. Catalog Numbers and Dimensional Information for Standard Arresters. (Contact Eaton Representative for Catalog Numbers of Non-standard Arresters) Ur Arrester Rating (kv rms) Dimension B Minimum Phase-to-Earth Clearance (mm) Dimension C Minimum Phase-to-Phase Clearance (mm) Housing Leakage Distance (mm) Uc Arrester COV (kv rms) Catalo Number Dim A (mm) Figure 7 View Number 3 2.55 AZG4041G002003 471 1 163 308 234 19 6 5.10 AZG4041G005006 471 1 165 309 234 19 9 7.65 AZG4041G007009 471 1 173 317 234 20 10 8.40 AZG4042G008010 535 1 176 320 406 23 12 10.2 AZG4042G010012 535 1 186 330 406 24 15 12.7 AZG4042G012015 535 1 202 347 406 24 18 15.3 AZG4043G015018 630 1 223 367 665 28 21 17.0 AZG4043G017021 630 1 237 382 665 29 24 19.5 AZG4043G019024 630 1 241 385 665 30 27 22.0 AZG4044G022027 725 1 261 406 922 35 30 24.4 AZG4044G024030 725 1 282 426 922 35 33 27.5 AZG4044G027033 725 1 308 452 922 36 36 29.0 AZG4044G029036 725 1 320 465 922 36 39 31.5 AZG4045G031039 852 1 341 486 1267 43 42 34.0 AZG4045G034042 852 1 347 492 1267 43 45 36.5 AZG4045G036045 852 1 367 512 1267 44 48 39.0 AZG4045G039048 852 1 387 531 1267 44 54 42.0 AZG4046G042054 929 1 411 556 1646 52 60 48.0 AZG4046G048060 929 1 458 603 1646 53 66 53.0 AZG4047G053066 1002 1 496 641 1872 59 72 57.0 AZG4047G057072 1002 1 529 674 1872 59 78 62.0 AZG4048G062078 1219 1 568 712 2540 70 84 68.0 AZG4048G068084 1219 1 617 762 2540 72 90 70.0 AZG4048G070090 1219 1 634 778 2540 72 96 76.0 AZG4048G076096 1219 1 680 825 2540 73 108 84.0 AZG4049G084108 1436 1 743 888 3226 93 120 98.0 AZG4049G098120 1436 1 853 998 3226 96 132 106 AZG4052G106132 1817 2 919 1064 3518 110 138 111 AZG4052G111138 1817 2 960 1105 3518 111 144 115 AZG4053G115144 1890 2 991 1135 3744 117 162 130 AZG4054G130162 2034 2 1109 1253 4186 125 168 131 AZG4055G131168 2107 2 1117 1261 4412 130 172 140 AZG4061G140172 2116 3 1374 1704 4412 136 180 144 AZG4062G144180 2261 3 1407 1737 4872 150 192 152 AZG4062G152192 2261 3 1467 1797 4872 152 198 160 AZG4063G160198 2333 3 1533 1863 5098 158 204 165 AZG4064G165204 2550 3 1571 1902 5766 169 216 174 AZG4064G174216 2550 3 1646 1976 5766 171 228 182 AZG4065G182228 2768 3 1706 2036 6452 191 240 190 AZG4065G190240 2768 3 1772 2102 6452 193 258 209 AZG4067G209258 3149 4 2126 2659 6744 214 264 212 AZG4067G212264 3149 4 2151 2684 6744 214 276 220 AZG4069G220276 3366 4 2211 2745 7412 226 288 230 AZG4069G230288 3366 4 2293 2827 7412 228 294 235 AZG4070G235294 3438 5 2332 2865 7638 237 300 239 AZG4070G239300 3438 5 2365 2898 7638 238 312 245 AZG4071G245312 3583 5 2411 2945 8098 253 330 267 AZG4074G267330 3872 6 2750 3448 8992 274 336 269 AZG4074G269336 3872 6 2763 3462 8992 275 360 289 AZG4075G289360 4090 6 2925 3624 9677 297 Arrester Mass (kg) 1. Position #5 designates nameplate options: 0=English 1=Spanish 2=Portuguese 2. All arresters are available in grey (standard) or brown porcelain glaze. For brown glaze, substitute B for G in the eighth position of the catalog number. 3. Digits 6 and 7 housing designation may be modified for arresters requiring leakage distance other than the standard arresters shown. Extended leakage may require additional clearances for phase-to-phase and phase-to-earth. Contact your sales representative for this information. 4. Cantilever strength for ratings 3-48 kv=10,200 NM and for ratings 54-360 kv=13,550 NM. Maximum working load should not exceed 40% of this value. 5. Refer to Figure 7 for Dimension A. 5

This page is intentionally left blank. 6

This page is intentionally left blank. 7

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. MN235014EN/Rev 0117 January 2017 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.