Fan and air movement essentials

Similar documents
Session #: Selection of Explosion Protected Equipment for Hazardous Locations

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps

Applied Fluid Mechanics

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS

The System Curve, the Fan Curve, and the Operating Point

OSAT Series. Intrinsically Safe Infrared Temperature Sensor Operator's Guide

An Impeller Blade Analysis of Centrifugal Gas Compressor Using CFD

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

TRZ 03-K Volumeter. Proven Technology. Superior Performance. TRZ 03-K Volumeter is a Turbine Gas Flowmeter for Secondary Gas Metering.

AXIAL FLOW FANS GENERAL INFORMATION

NZQA registered unit standard version 3 Page 1 of 7. Plan electrical installations for explosive atmospheres

Hazardous (Classified) Locations

Guidance on room integrity testing and its interpretation

Understanding Lobe Blowers Roots Blowers. Article written by Technical Team of EVEREST GROUP

TABLE OF CONTENTS PART 2 - CONFINED SPACES

Models EXN and OLG. General Description. Features and Benefits. Pressurizer for Vertical Air Conditioners Increased Safety for Hazardous Locations

Models EXN and OLG. General Description. Features and Benefits. Pressurizer for Vertical Air Conditioners Increased Safety for Hazardous Locations

Introduction to Pumps

Technical information

Vision Painting Inc Safety Management System

Compressors. Basic Classification and design overview

Numerical Fluid Analysis of a Variable Geometry Compressor for Use in a Turbocharger

ENGINEERING AUSTRALIA PTY. LTD.

INDICATIONS FOR CHOICE OF ATEX FANS

SMOKE EVACUATION FANS OUTSIDE THE HAZARDOUS AREA

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

Turbo Blowers. Combustion Excellence Since Features. Benefits

INDICATIONS FOR CHOICE OF ATEX FANS

2012 SYLLABUS FOR IFE LEVEL 2 CERTIFICATE FIRE SCIENCE, OPERATIONS AND SAFETY 500/5925/7.

CHAPTER 3 : AIR COMPRESSOR

NZQA registered unit standard version 2 Page 1 of 7. Conduct a conformity assessment of explosion-protected apparatus

EFFECTS OF WATER SPRAYS AND SCRUBBER EXHAUST ON FACE METHANE CONCENTRATIONS

(Refer Slide Time: 2:16)

Third measurement MEASUREMENT OF PRESSURE

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

Quick Reference Technical Data

Working Environment Safety Assessment

Goaf Inertisation and Sealing Utilising Methane from In-Seam Gas Drainage System

Unit 9 Packet: Gas Laws Introduction to Gas Laws Notes:

SAFETY IN CONFINED SPACES AND HEALTH SAFETY EXPLOSION HAZARD - TOXIC HAZARD

The evolution of the Ex-proof flame path

APPLICATION OF DRYACIDE DUST FOR THE STRUCTURAL TREATMENT OF GRAIN SILOS, BINS AND GRAIN STORES

Lab # 03: Visualization of Shock Waves by using Schlieren Technique

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Senior mechanical energy conversion trends

TExT Thorough Examination & Test of LEV Local Exhaust Ventilation Systems

In Vessel Composter Installation & Commissioning Manual

PROCESS ROTATING EQUIPMENT (CENTRIFUGAL PUMPS )

This test shall be carried out on all vehicles equipped with open type traction batteries.

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

CTG Certification Protocol -- Version 3.0 SUMMARY

VACUUM TESTING PRECAST CONCRETE MANHOLES

Another convenient term is gauge pressure, which is a pressure measured above barometric pressure.

AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller.

Title: Abrasive Blasting Effective Date: 11/17/2014 Control Number: THG_0034 Revision Number: 1 Date: 10/22/2015 Annual Review Completed: 5/13/2015

The principal mechanism for taking medium air velocity measurement is the Anemometer.

PRODUCT CONFIGURATOR AT mcr Monsun. smoke extraction and air supply axial-flow fans

Level 3 Certificate in Fire Science, Operations, Fire Safety and Management (All Examinations)

OPTIMIZATION OF SINGLE STAGE AXIAL FLOW COMPRESSOR FOR DIFFERENT ROTATIONAL SPEED USING CFD

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS

Understanding Centrifugal Compressor Capacity Controls:

TECHNICAL DESCRIPTION

Operating Instructions Part No

Simple Set Max. Pressure Independent Control Valves 2 Way 2-1/ /09/18

Mass Flow Controller (MFC) for Gases

The routine maintenance and inspection of local exhaust ventilation (LEV)

Inerting System Design for Medium Speed Vertical Spindle Coal Pulverizers TABLE OF CONTENTS

Series 6517 Katharometers. The ideal equipment for Process Monitoring and Control. Robust no moving parts. Designed for continuous industrial use

INTRODUCTION 1.0 GENERAL

6-5 Maintenance Manual

STORAGE OF COMPRESSED GAS CYLINDERS (SAF-SPI-15)

PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS

FAN ENGINEERING. Field Testing of Fans FE-900. Introduction. Testing Equipment. Testing Standards. Prior to Testing

TACTICAL VENTILATION Graeme Bowser, Tyne & Wear Fire Brigade, U.K.

Supplementary Operator s Manual 42/24-14 EN Rev. 3

EFFECTIVE DESIGN OF CONVERTER HOODS. 111 Ferguson Ct. Suite 103 Irving, Texas U.S.A. 400 Carlingview Dr. Toronto, ON M9W 5X9 Canada.

EXPERIMENTAL ANALYSIS OF FLOW OVER SYMMETRICAL AEROFOIL Mayank Pawar 1, Zankhan Sonara 2 1,2

1 PIPESYS Application

Flow Through Axial and Centrifugal Compressors by Kartik Sharma Mentors Prof. Gautam Biswas Prof. Subrata Sarkar

MATERIAL SAFETY DATA SHEET COMPRESSED METHANE

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

Chapter 16 Test. Directions: Write the correct letter on the blank before each question.

Spray Finishing Self-Inspection Checklist

Pump Selection and Sizing (ENGINEERING DESIGN GUIDELINE)

LAB 13: FLUIDS OBJECTIVES

THEORETICAL EVALUATION OF FLOW THROUGH CENTRIFUGAL COMPRESSOR STAGE

NZQA unit standard 7145 version 9 Page 1 of 5. Design and maintain effective ventilation systems for an underground coal mine

Thermo Probe, Inc. TP-5 TP-7 TP-8. Instruction Manual English. Switch. Display. Carry Strap. Probe. Ground Clip. Switch. Display.

Vacuum Systems and Cryogenics for Integrated Circuit Fabrication Technology 01

Effect of Inlet Clearance Gap on the Performance of an Industrial Centrifugal Blower with Parallel Wall Volute

SAMPLE QUESTIONS AND INFORMATION FOR CANDIDATES

Flow in a shock tube

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR

CHAPTER 31 IDEAL GAS LAWS

Pressure Control. where: p is the pressure F is the normal component of the force A is the area

Smoke and heat Ventilator Testing

Vertex VP Operation and Maintenance

CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER

Transcription:

1 Properties of air For the purposes of this section we will assume that it is air that will be moved by the various types of fans. The air we breathe is made up of a mixture of gasses - nitrogen 78%, oxygen 1% and 1% trace gasses including carbon dioxide. All of these gasses have mass In the atmosphere, the weight of these gasses produce a pressure (approx, 101,35 Pa at sea level depending on the weather). The mass and pressure result in air having a density 1.kg m 3 which is considered the standard density of air. Air Density changes with conditions and can be affected by temperature as well as atmospheric variations due to high and low pressure systems. Higher or lower altitude also correspond with higher or lower density and pressure. Air flow and air pressure As fans provide the means to move air, the relevant variables are the volume flow rate required and the pressure that must be overcome in order to deliver the volume. The graphical intersection of volume air flow and pressure required (in an X Y scatter chart) describes the fan performance duty needed for a particular application..1 Measurement of air flow Air flow is the measurement of the quantity of air that is conveyed in a given time period; L/s (litres per second) m 3 s -1 (cubic metres per second) m 3 hr -1 (cubic metres per hour) CFM (cubic feet per minute). Measurement of air pressure Air pressure is the force per unit area exerted by air; Pa (Pascals) KPa (Kilopascals) In.WG (Inches Water Gauge) Mm.HO (mm water gauge) PSI (Pounds per square inch) In relation to fans and air movement there are five pressure variables to be considered. Static pressure The difference between the absolute pressure at a point in an airstream, usually inside a duct and the pressure of the outside atmosphere. Static pressure acts equally in all directions, is independent of velocity and is a measure of the potential energy available in an air stream. Velocity pressure Is the measure of energy available in an airstream and is always positive. Total Pressure The sum of static and velocity pressure. It is a measure of the total energy available in an air stream. Pacific HVAC Engineering 016 www.pacifichvac.com Tel. Australia 1300 733 833 NZ 0800 100 36

Fan total pressure The difference between the mean total pressure at the fan outlet and the total pressure at the fan inlet. Fan impeller types Fan static pressure The fan static pressure is a defined quantity used in rating fans and cannot be measured directly. It is the fan total pressure minus the velocity pressure corresponding to the mean air velocity at the fan outlet. Note that it is not the difference between the fan static pressure at the outlet and the static pressure at the inlet; that is, it is not the external system static pressure. 3 How fans work A fan is a rotating bladed device which continuously applies energy to air or gas passing through it. There are three main components to a fan; the impeller, a means to drive the impeller and the casing. Energy is transferred to the air by rotation of the impeller being one of the three main types commonly used; centrifugal, axial or mixed flow. Centrifugal In the centrifugal type, it is the centrifugal force generated by the mass of air contained within the impeller at any given instance, as well as the force exerted by the angle of the blades to the entering air which gives it both static and velocity pressure and therefore moves air through the system. In the axial type there is little or no centrifugal action; the blades being set at an angle relative to the direction of air entry generate a lift or pressure difference. In the mixed flow type, energy is imparted to the air by a combination of centrifugal force and lift. As the name suggests, this type of fan displays a mix of characteristics seen in both axial and centrifugal fans. Axial (sickle blade type) The casing is not simply an enclosure for the impeller to channel air in a certain direction. It plays an important part in the aerodynamic performance particularly in the case of centrifugal and mixed flow fans when it is often the major element which converts velocity energy to useful potential energy (static pressure) and in axial fans where impeller tip clearance is important. 4 Fan type characteristics 4.1 Centrifugal Mixed Flow Air enters the impeller axially and is discharged radially into a volute or scroll shaped casing. These fans offer medium to low volume flow rates at moderate to high pressures. The main varieties are characterised by the type and angle of the impeller blades. A) Backward types may consist of aerofoil sections or single thickness blades, the latter being either curved or straight. These impellers typically have few blades. The pressure curve generated by this impeller type is relatively steep over the working range and the power curve has a nonoverload characteristic. Very good efficiencies are possible with this type of impeller. B) Forward curve types are characterised by a larger number of shallow blades sloping forward in the direction of rotation. The power curve for this type of fan rises steeply from zero to maximum flow making this type prone to overloading its driving motor if operated beyond the rated duty point. It will handle relatively large volumes of air at lower operating speeds however, overall efficiency is less than backward inclined blading. Pacific HVAC Engineering 016 www.pacifichvac.com Tel. Australia 1300 733 833 NZ 0800 100 36

C) Radial blades produce a near straight power curve from a minimum at zero flow to a maximum at maximum air flow although the curve is not as steep as for a forward curve impeller. The blades tend to be self cleaning and can handle moderately dirty conditions. 4. Axial In this type, air enters and leaves the fan axially in a straight through configuration. Duties are usually medium to high volume flow at medium to low pressures. In its simplest form a single impeller is direct driven by a motor in a cylindrical casing. The discharge flow embodies a pronounced swirl or twist to the airstream which may, if not corrected, materially increase the resistance of the downstream portion of the system. This swirl can be removed by fitting guide vanes either upstream or downstream of the fan. The removal of swirl increases the efficiency of the fan. A further variation to remove swirl is the use of two independently driven contra-rotating impellers within a single casing. Axial types have non overloading power characteristics and can display very good efficiencies. 4.3 Mixed Flow This type of fan has an air path through the impeller which has characteristics of both axial and centrifugal types. Mixed flow impellers are designed to provide both axial and radial discharge. Higher fan static pressures are achievable with this type of impeller compared to axial fans. 5 Presenting Fan Performance Fan performance is typically represented graphically using x-y scatter charts with points plotted at intersections of static pressure and air flow. Data series presenting the working range of the fans are plotted to graphically illustrate performance as a line or curve. Multiple fans of similar type, for example axial flow fans with adjustable pitch blades, are presented as groupings of curves within the one graph. Pacific HVAC Engineering 016 www.pacifichvac.com Tel. Australia 1300 733 833 NZ 0800 100 36

5 Fan Duty The points along the fan curve represent the outflow of air at varying levels of system resistance (static pressure). The required fan performance for flow rate at the designed pressure level is the duty point that the fan is required to meet. Represented graphically, the duty that is required is a point along a calculated curve known as the system curve. It should be remembered that the fan performance presented in this catalogue has been derived through testing to recognised standards. In arriving at duty requirements for fans, designers are advised to pay close attention when determining overall system resistance to ensure that fans perform to published levels. 6 Fan Applications Although typically thought of as a means to provide airflow in airconditioning systems, fans are applied to a diverse range of air movement tasks in a wide range of environments. The following sections provide an overview of more specialised fan applications. 6.1 Smoke Spill Such systems are intended to limit and control the movement of smoke during a fire. The most common technique involves pressurizing the areas on either side of the compartment where the fire is located and exhausting from the fire area. This method creates a pressure sandwich which tends to move air (and thus smoke) from the protected areas towards the fire whilst moving smoke out of the fire area. Although this does introduce fresh oxygen to the fire area, most systems are aimed at protecting the occupants and equipment in the compartments adjacent to allow evacuation and to allow fire personnel clear access to the fire to extinguish it. Generally in Australia, smoke spill fans fall into two categories. Tested to withstand 00 C for two hours. Tested to withstand 300 C for one half of one hour. If an area that requires smoke spill fans has fire sprinklers serving it, then fans tested for 00 C for two hour are acceptable. Smoke-spill fans have to be tested to Standard AS449:1999 and conform with the requirements of AS/NZS1668.1:015. Pacific HVAC Engineering 016 www.pacifichvac.com Tel. Australia 1300 733 833 NZ 0800 100 36

6.1 Smoke Spill Fans (continued) Smoke spill fans can be roof mounted, plate mounted, in line axial, in line centrifugal. For 300 C 30min smoke spill Fans in buildings without sprinkler systems, dampers shall remain open in the event of fire. 6. Hazardous Location Fans The selection of fans in hazardous locations has to take into account four sets of information. The area classification. The gas group. The T rating or ignition temperature of the hazard. The required IP rating of the apparatus. 6..1 Area Classification The areas are classified into ZONES, and these zones are based on the frequency of the appearance of an explosive atmosphere and the duration for which it can last. Summarized as follows: Gases and Vapours Zone 0 Area in which an explosive gas-air mixture is continuously present or present for long periods. Zone 1 Combustible or conductive dusts are present. Area in which an explosive gas-air mixture is likely to occur for short periods in normal operation. Zone Area in which an explosive gas-air mixture is not likely to occur, and if it occurs it will only exist for a very short time due to an abnormal condition. Dust Zone 0 Area in which an explosive dust-air mixture is continuously present or present for long periods. Zone 1 Combustible or conductive dusts are present and is likely to occur for short periods in normal operation. Zone Area in which an explosive dust mixture is not likely to occur, and if it occurs it will only exist for a very short time due to an abnormal condition. Pacific HVAC Engineering 016 www.pacifichvac.com Tel. Australia 1300 733 833 NZ 0800 100 36

6.. Gas Groups Gas Groups are divided into two categories. Group 1. Coal Mining Industry. (Methane) Group II Other Industries. Group II is further subdivided as follows and the representative gases for each group are shown as well: Group I - Methane Group IIA - Propane Group IIB - Ethylene Group IIC - Hydrogen 6..3 Temperature or T rating The source of ignition in a hazardous area can be an arc or a spark or even a hot surface. Since electrical equipment generates heat in normal operation we need to ensure that a hot surface on electrical apparatus cannot ignite a surrounding explosive gas atmosphere or a dust cloud or layer. All hazardous materials have what is known as an Ignition Temperature. This is the minimum temperature at which the hazardous material when mixed with air will ignite and sustain combustion, without an ignition source (auto-ignition or spontaneous ignition). The temperature of a layer on the surface of the equipment. Eg. if the ignition temperature of the dust layer is 75 C then the equipment T rating must not exceed 00ºC or T3. 6..4 Ingress Protection (IP) Ratings Designation First digit protection against contact and ingress of foreign bodies. Second digit protection against water. IP44 IP54 IP55 IP56 IP65 IP66 Protection against contact with parts inside the enclosure by foreign objects including wires with a diameter greater than 1mm. Protection against contact with parts inside the enclosure by foreign objects including dust. Protection against dust ingress is not total but not in amounts that will interfere with the operation of the equipment. Complete protection against contact with parts inside the enclosure by foreign objects including dust. Protection against water sprayed from any direction. Protection against water sprayed from any direction. Protection against beamed water directed by a nozzle. Protection against strongly beamed water jets or heavy seas. Protection against beamed water directed by a nozzle. Protection against strongly beamed water jets or heavy seas. Pacific HVAC Engineering 016 www.pacifichvac.com Tel. Australia 1300 733 833 NZ 0800 100 36

6..5 Types of motors used in Hazardous locations Temperature Classification To prevent ignition of gases, dust or vapours in hazardous areas it is essential that external motor components do not exceed the flash point of ignitable materials. Group I Gases - Max. surface temp. 150 C Group II Gases and Dusts are assigned a Temp. Class (T) in relation to the maximum equipment surface* temperature allowable: T1-450 C T - 300 C T3-00 C T4-135 C T5-100 C T6-85 C * For EXD motors, the temperature relates to the external surface of the motor. For protection levels above EXD, the internal temperature is also taken into account. Levels of Protection - Motors EXN Is a level of protection that states the motor will in normal operation not ignite a surrounding area, and that any ignition is unlikely to happen. DIP These motors use suitable enclosures to prevent arcs and sparks or heat to be liberated inside the enclosure to ignite any exterior dust on or near the motor. Used in heavily dust laden environments. EXD These are motors that are built to withstand an internal explosion within the motor casing and will not transmit any flame or spark that could ignite surrounding gas or vapours. They also operate at external surface temperatures that do not allow ignition of surrounding gas or vapours. Three Phase Motors EXD motors are certified to Class I, Zone 1 protection (including Gas groups IIA and IIB). EXE Exe protection is also known as increased safety, this level of protection is such that the motor does not produce arcs or sparks under normal use. Generally used in spray booth applications. Motors hold certification to EXE Class I, Zone I protection (including Gas groups IIA, IIB, IIC. Temperature classification T3 and ingress protection IP66 Specification Range EXD, EXE Three Phase Motors Insulation: Class F Type: TEFC Ingress Protection: Up to IP66 Voltage: Up to 500 Volts Frequency: 50Hz - 60Hz Standards Met Motors certified are compliant with AS/NZS60079.0:005, AS/ NZS60079.7:006 which also covers classifications EXN and DIP. Pacific HVAC Engineering 016 www.pacifichvac.com Tel. Australia 1300 733 833 NZ 0800 100 36

6.3 Fresh Air Supply Fans Fresh air is introduced to air conditioned spaces to maintain adequate ventilation rates and to flush out contaminants. The level of fresh air introduced depends mainly on the type and function of the space and the number of occupants utilising the area at any given time. These fans should deliver fresh air ventilation rates in accordance with Australian Standard (AS) 1668.-01. These fans are also known as supply air fans and can be roof units, in line axial, centrifugal or any type of fan depending on the design. 6.4 Car Park Exhaust and Supply Fans Compliance with AS1668. requires that the internal environment of a car park is safe for occupants and that if the internal air quality is acceptable to health, it is concluded that the air quality of any discharges either through mechanical or natural ventilation are equal to or better than that in the car park. Car park exhaust fans should always have aluminium impellers, F class motors are acceptable. Car park supply fans can have plastic, glass reinforced nylon or fibre reinforced plastic impellers, again class F motors are acceptable. 6.5 Stairwell Pressurisation Stairwells are frequently the primary escape routes for the occupants of a building in a fire emergency. In addition, the stairwells may be the primary access routes for the fire fighting teams responding to the emergency. Thus, it is critical that they remain clear of smoke for as long as is necessary to safely evacuate the building and bring the fire under control. Most high rise buildings employ a stairwell pressurization system to keep the stairs clear of smoke while operating at a low enough pressure that an average person can open the doors to enter or exit the stairwell on their way to safety. Stairwell pressurization fans are fairly standard in construction and are usually in line axial type, but not limited to this type of fan. Standard motors meet the code requirements. Pacific HVAC Engineering 016 www.pacifichvac.com Tel. Australia 1300 733 833 NZ 0800 100 36

7 Fan Laws 7.1 About Fan Laws It is not practical to test fans of every size with differing variables such as gas density or rotational speed. Fortunately, by the use of fan laws, the performance of geometrically similar fans of different sizes or speeds can be predicted with sufficient accuracy for practical purposes. These laws are most often used to calculate changes in flow rate, pressure, sound and power of a fan when size, rotational speed or gas density is changed. In the following laws, the suffix 1 has been used for the initial known values and the suffix for the changed values and the resulting calculated value. 7.1.1 Fan Law for Volume Volume Speed. Volume flow changes in direct proportion to fan speed. Q N = Q D 1 N1 D1 3 Where: Q = flow rate, N = fan rotational speed, D = impeller diameter 7.1. Fan Law for Pressure Pressure Speed. Pressure changes in direct proportion to the square of the fan speed ratio. N P = P1 N 1 D D1 ρ ρ1 Where: P = pressure N = fan rotational speed, D = impeller diameter, ρ = density of air 7.1.3 Fan Law for Power Power Speed 3 Power required changes in direct proportion to the cubed power of fan speed. W N = W 1 N 1 3 D D1 5 ρ ρ1 Where: W = power N = fan rotational speed, D = impeller diameter, ρ = density of air 7.1.4 Fan Law for Sound Power Log (speed) N D Lw = Lw1 + 50Log 10 + 70Log 10 + 0Log N 1 D1 Where: Lw = sound power level, N = fan rotational speed, D = impeller diameter, ρ = density of air 10 ρ ρ1 Pacific HVAC Engineering 016 www.pacifichvac.com Tel. Australia 1300 733 833 NZ 0800 100 36