Sinorix PRESCODEM400, PRESCODEM400/220 Sinorix CDT-V, Sinorix H2O Jet Removable contact pressure gauge with electrical connector Allows to visually check the pressure of the cylinder on which it is mounted Electrically monitors loss of pressure via the integrated switch connected to the extinguishing control unit (ECU) Allows disassembly when the cylinder is pressurised Is compatible with VFR300-S valves Product codes: PRESCODEM400 - A6E60200527 PRESCODEM400/220- A6E60200441 2017-08-08 Control Products and Systems
Application Functions This product is used with the Sinorix TM CDT-V automatic gas extinguishing systems and with the Sinorix TM H2O Jet automatic water mist extinguishing systems. The pressure gauge gives a direct indication of the pressure in the cylinder on which it is mounted. The table on the operating instructions label allows for comparison of the pressure indicated by the pressure gauge with the theoretical pressure values, taking into account the room temperature at the time of performing the check. Thus any loss of extinguishing agent (i.e. a loss of pressure) is easily identifiable. The switch integrated in the pressure gauge is electrically connected to the extinguishing control unit (ECU). The ECU indicates a "Loss of extinguishing agent" fault when the pressure of the cylinder has decreased by 10% Type summary Item Designation Item Designation 1 Rotating switch 4 Contact pressure gauge 2 Connection cable 5 Rotating nut M22 x 1,5 3 Dial - - Equipment combinations Designation Description Product code BOUT80-CDT Extinguishing agent cylinder A6E60200465 OUTEX MANO pressure gauge removal tool FR2:LB704350008 TOR-UNIT unit connection cable loom FR2:LB704220008 TOR-MULTI multiple connection cable loom FR2:LB704210008 Product documentation Type Title Document ref. Installation, Commissioning, Maintenance, Cylinder handling and safety Installation, Commissioning, Maintenance, Cylinder handling and safety Sinorix CDT-V Fixed gas automatic extinguishing systems Sinorix H2O Jet Single sector fixed automatic water mist system A6V10780127 A6V10780312 2
Notes Security This product may only be installed by Siemens-authorized specialized installers, with experience in the design, installation and maintenance of automatic extinguishing systems. Installers must ensure that this product is used as intended, that any danger to themselves or to others is avoided, and that Siemens requirements are met (assembly instructions, technical instructions, commissioning, and operating instructions). Furthermore, the installation must comply with the accident prevention regulations and national regulations in force. Installers must also ensure that the operators have read and understood the information related to this product. CAUTION Country-specific safety requirements Failure to comply with country-specific safety requirements may result in bodily injury or damage to equipment. Comply with the provisions applicable for each country and observe the corresponding safety instructions Mounting Apply fluorosilicone grease sparingly to the O-ring of the pressure gauge. Screw up fully the rotating nut of the pressure gauge on the pressure port of the valve using a 30 mm open-end wrench Direct the pressure gauge for reading: screw the square clockwise using a 14 mm openend wrench. WARNING Risk of breaking the sealing Never unscrew the pressure gauge with the square. Connect the connector of the connecting cable of the pressure gauge to a junction box via a TOR-x connection cable loom. WARNING Fragile precision instrument to be handled with caution Never use the unit to screw the pressure gauge on. Always use the tightening nut located at the back of the unit and a 30 mm open-end wrench toscrew the pressure gauge on. Replace any pressure gauge after an impact, e.g. a fall. 3
Maintenance Storage Store in its original packaging, protected from shocks. Inspection every six months Check that the product is in a good condition. Check by hand that the product is corrected tightened and re-tighten if necessary. Wipe the glass of the pressure gauge with a clean lint-free cloth. 4
CTechnical data PRESCODEM400 Technical data Operating pressure 300 bar Voltage 4,5 à 24 V DC / AC Current 5 à 100 ma Breaking capacity 24 Vcc/Vac / 100mA Resistance of the contact (under pressure) 1,6 Ω to 3,0 Ω Switch normally closed above 270 bar Precision class: Pressure gauge 1.6 ± 6,4 bar Precision class: Pressure gauge 2.5 ± 6,75 bar Thread M22 x 1,5 Protection index IP54 Materials Brass, Elastomer, Plastic, Aluminium Operating temperature - 20 C to + 50 C Storage temperature - 40 C to + 70 C Weight 0,19 kg PRESCODEM400/220 Technical data Operating pressure 300 bar Voltage 4,5 à 24 V DC / AC Current 5 à 100 ma Breaking capacity 24 Vcc/Vac / 100mA Resistance of the contact (under pressure) 1,6 Ω to 3,0 Ω Switch normally closed above 220 bar Precision class: Pressure gauge 1.6 ± 6,4 bar Precision class: Pressure gauge 2.5 ± 5,5 bar Thread M22 x 1,5 Protection index IP54 Materials Brass, Elastomer, Plastic, Aluminium Operating temperature - 20 C to + 50 C Storage temperature - 40 C to + 70 C Weight 0,19 kg Marking Code Index SS/AA (Week/Year) EN 837-1 PGS 11040 CE0786 VdS CI 1.6 Standards, directives and authorizations Regulation No. 305/2011 Product standard: EN 12094-10 Conformity with CPR VdS certification Recognized associativity G309002 With DECT Siemens XC10 5
Dimensions Dimensions in mm Issued by Siemens SAS ZI-BP20 617 rue Fourny FR-78531 Buc cedex Tel. +33 1 85 57 01 00 www.siemens.com/buildingtechnologies Siemens SAS, 2017 Technical specifications and availability subject to change without notice. 6 Control Products and Systems Document ID 2017-08-08 Edition 2017-08-08