HORNE 20 THERMOSTATIC MIXING VALVE TYPE H-2003

Similar documents
Horne Engineering Ltd

Installation Instructions and User Guide 15mm & 22mm Thermostatic Mixing Valve

HORNE T109A/306A/307A THERMOSTATIC SHOWER VALVE FOR SURFACE MOUNTING WITH TIMED FLOW CONTROL INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Installation Instructions and User Guide

PEG402, PEG402UA & PEG402UAX TMV3 / TMV2 Combined

Twin & Triple Control Concealed Thermostatic Shower Valve

TEMPERATURE STABILISED THERMOSTATIC SHOWER PANEL

Installation Instructions and User Guide

Intamix Thermostatic Mixing Valve

Issue date: July 2012 Issue 1

THERMOSTATIC MIXING VALVES

Self-help Temperature Adjustment

SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER

Installation Guide - C01202 & C01203 Thermostatic Mixing Valve TMV2

In Line Thermostatic Controller. Copper x Copper


TMV3 Requirements IMPORTANT Installer:

Issue date: April 2017

bathrooms.com Concentric Thermostatic Shower Mixers Cleaning and Care Installation Manual Contents

SMV-001 Thermostatic Shower Mixer Valve Installation Instructions & Adjustment Settings

Scald Protection Three-Way Thermostatic Mixing Valve

Installation, commissioning and servicing instructions

Deluge Optimo Shower valve and kit 10032CP

Scald Protection 3-Way Thermostatic Mixing Valve

Thermostatic Mixing Valves 61022CPB & 61028CPB Intamix Pro V

3.5 litr es per INSTALLATION INSTRUCTIONS. Avon 21 Self-closing taps (Push button) B0992AA Self-closing basin pillar tap

Combination Air Valve

Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections

Installation, commissioning and servicing instructions

INSTALLATION, OPERATING AND MAINTENANCE GUIDE FOR EXPOSED AND CONCEALED MODELS MODERN, TRADITIONAL AND MINIMALISTIC

PRODUCT MANUAL IMPORTANT

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

Crosby style JCE Safety Valve Installation, Maintenance and Adjustment Instructions CROSBY

System Pressure Manager Standard & System Pressure Manager Plus

Tempering valve for solar and instantaneous applications Installation, commissioning and servicing instructions 2522HP series

15/3 THERMOSTATIC MIXING VALVE PRODUCT MANUAL IMPORTANT

Rada-Presto TF2020 and TF2020S

LNVx Gas Conversion Kit Instructions

553 Series.

Anti-flood device Model B-1

TMV20 THERMOSTATIC MIXING VALVE

1. Introduction. The Easy Guide to TMV3 Approval

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

Engineering Data Sheet

k valve 2 (50)HF 2½ (65)SF installation guide aylesbury For valve sizes (DN): tel fax

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

National Health Service Model engineering Specification

MODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

book : t95575.fm Seite 1 Mittwoch, September 20, :10 AM. Avensys. Exposed Single Lever Mixer

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

hydraulic valve 1 Introduction

TECHNICAL DATA. Q = C v P S

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Installation Troubleshooting Maintenance Instructions Installation / Start-up

MANUAL FOR INSTALLATION, COMMISSIONING AND MAINTENANCE FOR

BASIN AND WALL MIXER INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

AQUABLEND MM THERMOSTATIC MIXING VALVE

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

Instruction Sheet. SUPERSEDES: New EFFECTIVE: August 1, 2013

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES

PRODUCT MANUAL IMPORTANT

TECHNICAL INSTRUCTIONS

MAINTENANCE PROCEDURE FOR X 650

OWNER S GUIDE DUAL CONTROL THERMOSTATIC SHOWER VALVE. Shower Control. may differ depending on choice of Model. Concealing Plate. Handles and ISSUE 01

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

215 and 222 Series PRODUCT MANUAL

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

Installation, commissioning and servicing instructions. General

Regulator from 1800 B series

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

Installation, commissioning and servicing instructions

PO Box 370 Phone: Swansea NSW 2281 Fax: AUSTRALIA Mobile: Web:

AREA VALVE SERVICE UNITS

Model: 43T. Bermad Pressure Relief Valve

Latvin Luxury Shower Panel. Telephone Product Specification. ~ Minimum Working Pressure 1.0 bar ~ Maximum Working Pressure 3.

MUELLER GAS. No-Blo Operations Using D-5. Drilling Machine. Reliable Connections. General Information 2

AQUABLEND 1500 THERMOSTATIC MIXING VALVE WITH THERMAL FLUSH

TECHNICAL DATA. Q= Cv S

Training. Testor Training Manual

THE MF-400 SERIES. Operating and Service Manual. Series includes all variants of MF-400/401

INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

Vegas Easyfit Kitchen Sink Mixer

1800C and 1800C-HC Series Service Regulators

Combination Air Valve Model

KTM 50 (DN ) Installation, maintenance and operating instructions

MARKWIK SEQUENTIAL LEVER OPERATED THERMOSTATIC MIXERS. INSTALLER: After installation please pass this instruction booklet to user

USER INSTRUCTIONS. NAF Duball DL Ball Valves. Installation Operation Maintenance. Experience In Motion. flowserve.com

TECHNICAL DATA DELUGE VALVE, MODEL F-1 STRAIGHT THROUGH STYLE

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Bar valve with fixed shower head Installation guide

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

776 Cryogenic Safety Valve

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual

WE SAY: CLEANLY SEPARATED SYSTEMS = ELKO-MAT EDER!

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

Installation, Operation & Maintenance Manual for Flo-Max Coupler Bracket Model FM150

Transcription:

PO Box 7, Rankine Street Johnstone, Renfrewshire Scotland. PA5 8BD Tel: 01505 321 455 Fax: 01505 336 287 Email: technical@horne.co.uk Web: www.horne.co.uk HORNE 20 THERMOSTATIC MIXING VALVE TYPE H-2003 INSTALLATION, COMMISSIONING, OPERATING AND MAINTENANCE INSTRUCTIONS APPROVAL The HORNE 20 TMV Type H-2003 has been independently tested by WRc-NSF and approved to all the requirements of NHS Model Engineering Specifications D 08 Thermostatic Mixing Valves (Health Care Premises) to the following designations and for the following applications. APPLICATION BATHS DESIGNATION -HP-T44 -HP-T46 -LP-T44 HOT AND COLD WATER PRESSURES 1-5 bar 1-5 bar 0.2-1 bar SHOWER -LP-S 0.2-1 bar WASHBASIN -LP-W 0.2-1 bar The hot and cold pressures do not need to be equal. See 1.3 overleaf. The HORNE 20 TMV Type H-2003 is a Type 3 Thermostatic Mixing Valve according to NHS Estates Health Guidance Note "Safe" hot water and surface temperatures. Normal Conditions of Use for Type 3 Valves High Pressure Low Pressure Maximum Static Pressure 10 bar 10 bar Flow Pressure, Hot & Cold 1 to 5 bar 0.2 1 bar Hot Water Supply Temperature 52 65C 52 65C Cold Water Supply Temperature 5 20C 5 20C Minimum Temperature Differential 1. INSTALLING THE HORNE 20 TMV 5K 5K 1.1 Check that the HORNE 20 TMV is approved for the intended application (see table on Page 1). 1.2 Install the HORNE 20 TMV as close as possible to the outlet to comply with HTM 04-01. The dead leg from the HORNE 20 TMV to the outlet should not exceed 2 metres. 1.3 Check that the supply pressures are within the ranges given above. If the hot and cold water supplies are of unequal pressures, then the lower of the two pressures should not be less than 0.2 bar maintained pressure. 1.4 Check that the supply temperatures are within the ranges stated above. Mar 2012 Page 1 of 10

1.5 Isolating valves must be fitted to the hot and cold water supply pipes close to the inlets of the TMV. The isolating valve on the cold water supply pipe may also be used to isolate the cold water tap. 1.6 The HORNE 20 TMV can be fitted in any attitude with the mixed water outlet pointing upwards, downwards, horizontally or any angle between these planes. 1.7 Connect the hot water supply to the port on the valve with the RED dot, and the cold water supply to the port with the blue dot. 2. FLUSHING OF PIPEWORK TO THE WATER SUPPLY (Water Fittings Regulations 1999, schedule 2 G13.1) The most common cause for complaint regarding the performance of any Thermostatic Mixing Valve is traced to dirt or debris in the TMV or check valves. Before a HORNE 20 TMV is commissioned, the hot and cold water pipework should be thoroughly flushed using the FLUSHING KIT shown in the diagram below. The FLUSHING KIT comprises a screwed adaptor to fit the strainer body and a plastic pipe to enable water to be flushed to drain. Only one or two kits are required on each site. The kit must be ordered separately. DO NOT FLUSH THE PIPEWORK BY REMOVING THE STRAINER BASKETS AND OPENING THE TAPS. DO NOT OPEN the hot water tap before flushing the hot and cold water pipework. The flushing procedure is as follows: 2.01 During this procedure, keep the hot and cold water taps closed. 2.02 Close the hot and cold water ISOLATING VALVES. 2.03 Unscrew the END CAP (18) and remove the STRAINER BASKET (16) from the strainer at the hot inlet. 2.04 Screw the FLUSHING KIT into the STRAINER BODY (15). 2.05 Place the outlet of the flushing pipe where it can drain freely. If draining into a wash basin or bath, make sure that the drain plug is NOT in place and that water passing through the flushing pipe is free to drain. 2.06 Open the hot water ISOLATING VALVE and allow any air in the pipework to escape until water begins to flow to drain. Allow water to flow to drain until it is perfectly clean and free from any dirt or debris. 2.07 Close hot water ISOLATING VALVE. 2.08 Remove the Flushing Kit and replace the strainer basket and end cap. 2.09 Repeat 2.03 to 2.08 at the cold water inlet with the cold water ISOLATING VALVE. 2.10 Re-open both ISOLATING VALVES. The flushing procedure has now been completed. Mar 2012 Page 2 of 10

3. COMMISSIONING A NEW HORNE 20 TMV 3.1 Open the hot water tap and allow water to run through the HORNE 20 TMV. 3.2 Check that hot and cold water supplies stabilise at or near to their designed temperatures and pressures. 3.3 Measure the temperature at the hot water tap. This is the temperature of the mixed water. Set the Mixed Water Temperature as in the table below: Application Bath (44C Fill) Bath (46C Fill) Shower Washbasin Mixed Water Temp. 44C 46C 41C 41C A TMV with multiple designations should be reset on site to suit the appropriate designation. Notes Bath fill temperatures of more than 44C should only be available when the bather is always under the supervision of a competent person (e.g. nurse or care assistant) For washbasins, washing under running water is assumed. 3.4 If necessary, make minor adjustments to the temperature setting as described in Section 4 below. 3.5 CARRY OUT A COLD WATER ISOLATION TEST AS BELOW. 3.5.1 Close the cold water isolating valve and simultaneously measure the mixed water temperature. The flow of mixed water should immediately stop and then a drip or trickle may be seen. The temperature of any water coming from the tap should not be more than 2 C above the mixed water set temperature measured in 3.3 above. 3.5.2 If the HORNE 20 TMV performs satisfactorily, close the hot water tap and open the cold water isolating valve. 3.5.3 If the water coming from the tap is at a temperature of more than 2 C above the mixed water temperature setting, then the HORNE 20 TMV is not cutting off the hot water supply properly. The most likely cause for this to happen is dirt inside the TMV. It should be dismantled and thoroughly cleaned and the pipework flushed again. See 6.3.1 to 6.3.9. 3.6 The HORNE 20 TMV is supplied with WRAS approved DN20 integral single check valves located in each of the swivel inlet assemblies. To ensure that the check valves are working properly, proceed as follows. 3.6.1 Start with both hot and cold taps closed and both hot and cold isolating valves open. 3.6.2 Close the cold supply isolating valve. 3.6.3 Remove the strainer cap (18) at the cold inlet to the HORNE 20 TMV. After some initial draining of water, there should be no flow whatever. This indicates that the check valve at the cold inlet is giving a tight shut off. 3.6.4 Replace the strainer cap (18) at the cold inlet and open the cold supply isolating valve. 3.6.5 Close the hot supply isolating valve. 3.6.6 Remove the strainer cap (18) at the hot inlet. After initial draining of water, there should be no flow of water whatever. This indicates that the check valve at the hot inlet is giving a tight shut off. 3.6.7 Replace strainer cap. 3.7 The HORNE 20 TMV has now been commissioned. Mar 2012 Page 3 of 10

4. TEMPERATURE ADJUSTMENT The HORNE 20 TMV is set at the factory to control the mixed water temperature at approximately 42 C. The range of temperature adjustment is 35-46 C. To alter the temperature setting, carry out the following procedure: 4.1 Check that hot and cold water supplies are at or near to their designed temperature and pressure. 4.2 Open the mixed water outlet and allow water to flow until the mixed water temperature has stabilised. Make sure that the dead leg from the HWS to the HORNE 20 TMV and from the HORNE 20 TMV to the outlet has fully cleared. 4.3 Using the ADJUSTING KEY (1), turn the ADJUSTING SCREW (2) clockwise to reduce the mixed water temperature or anti-clockwise to increase it. Adjustments of not more than half a turn at a time should be made. The temperature at the outlet should be measured and allowed to stabilise before any further adjustments are made. 4.4 After making an adjustment, close the hot water supply isolating valve for ten seconds then re-open it and measure the mixed water temperature again. If a further adjustment is required, repeat the procedure. 5. IN-SERVICE TESTING 5.1 The purpose of In-Service Testing is to regularly monitor and record the performance of the TMV. Periodic testing should be carried out to check whether any deterioration has occurred in the performance of the HORNE 20 TMV. The results of these tests, and the equipment used, should be recorded on the Commissioning, Maintenance and In-Service Testing Sheet at the back of these instructions. Note that instrumentation to the same specification should be used each time when measurements are taken to ensure consistency of results. Record all the information requested on the In-Service Testing sheet at the back of these instructions. 5.2 A COLD WATER ISOLATION TEST should be carried out as described in 3.5.1 above. If the water coming from the tap is at a temperature of more than 2 C above the mixed water temperature setting then the HORNE 20 TMV is due for maintenance. NOTE: A Thermostatic Mixing Valve in need of maintenance can be undetectable in normal use and only become apparent when a disruption occurs in the hot or cold water supply pressures or temperatures. 5.3 The frequency of in-service testing depends upon the condition of the water passing through the TMV. In-service testing must be carried out more frequently in hard water areas than in soft water areas. As a general guide, inservice testing should be carried out at intervals somewhere between 6 months and 12 months. In-service testing should be carried out at least every 12 months and, where the water is hard, the interval may be less than 6 months. Experience of local conditions and the in-service testing record will dictate the frequency of in-service testing. In the absence of practical experience of this, a first check 6 8 weeks after commissioning should be performed. If no problems are detected (and mixed water temp is within 1C of the commissioning temp) then checking again 12 15 weeks after commissioning will help to build up a history. The results should be recorded on the attached sheet. Any requirement to reset the mixed water temperature should be noted. If no such adjustments are required, then the next in-service tests can be scheduled for 24 28 weeks after commissioning. If small adjustments (1 to 2 K) are required then check the strainers for cleanliness, make sure the isolating valves are fully open and verify the check valves are operating correctly (see Maintenance Section). The next in-service test should be conducted 18-21 weeks after commissioning. If larger adjustments are required (>2K), then service work is required and the in-service tests should be repeated 18 21 weeks after commissioning. Note that the pressure and temperatures of the supplies must be identical to those during commissioning for the in-service tests to be meaningful. 6. MAINTENANCE Maintenance of all Thermostatic Mixing Valves is essential to ensure the product continues to operate to specification after installation, and continues to offer scald protection. Record all maintenance carried out on the attached Commissioning & Maintenance Record sheet at the back of these instructions. The frequency of maintenance depends upon the condition of the water passing through the TMV. The remarks in 5.3 regarding in-service testing apply equally to maintenance. All 'O' Ring Seals should be replaced at least every three years. The Thermostat Element (6) should be replaced at least every six years. All other parts should be replaced only if physical damage has occurred. Mar 2012 Page 4 of 10

MAINTENANCE PROCEDURES 6.1 Close hot and cold water inlet isolating valves and open the outlet to allow pipework to drain. 6.2 CLEANING STRAINERS - Unscrew END CAPS (18) and withdraw STRAINER BASKETS (16). Clean the baskets and de-scale them, if necessary. 6.3 THERMOSTATIC MIXING VALVE MECHANISM (Minor maintenance carried out with the HORNE 20 in situ.) 6.3.1 Unscrew VALVE COVER (3). Remove THERMOSTAT ELEMENT (6), SLIDE VALVE ASSEMBLY (7), RETURN SPRING (8) AND BAFFLE TUBE (9). 6.3.2 The SLIDE VALVE ASSEMBLY (7) is a precision part and must be handled with care. 6.3.3 Remove the ADJUSTING SCREW (2) by turning it clockwise until the thread disengages. 6.3.4 The SLIDE VALVE SEAL (10) can be removed by piercing the rubber with a sharp pointed probe. Take care not to bruise the edges of the groove. 6.3.5 If the SLIDE VALVE SEAL (10) has been removed, then it MUST be replaced with a new one. NEVER re-use an 'O' Ring. 6.3.6 Thoroughly clean all components. 6.3.7 Flush out the valve body by replacing the VALVE COVER (3) and ADJUSTING SCREW (2) and opening the isolating valves and allowing water at full bore to pass through the body to the outlet. 6.3.8 If dirt is seen during flushing then carry out FLUSHING PROCEDURE in Section 2. 6.3.9 Re-assemble the HORNE 20 TMV. (See 6.5) 6.4 MAJOR MAINTENANCE. For this, remove the HORNE 20 TMV from the pipework. 6.4.1 Unscrew PIPE COUPLING NUTS (13) and the OUTLET PIPE COUPLING. 6.4.2 Lift the valve out of the pipework. 6.4.3 DO NOT grip the valve body in a vice. This could distort the body and jam the internal parts. 6.4.4 Remove the valve cover and internal parts as referred to in 6.3.1 to 6.3.4 above. 6.4.5 If the valve body requires de-scaling, remove all O-Ring seals and use a proprietary fluid for this purpose. Do not put the THERMOSTAT ELEMENT (6) or the BAFFLE TUBE (9) in de-scaling fluid. 6.4.6 Inspect the condition of the "HOT VALVE FACE" and "COLD VALVE FACE". If the valve faces show signs of deterioration, they can be resurfaced as follows. 6.4.7 Using a mandrel (Tool No. 6356), lap the hot valve face using a water soluble scouring paste. Use 800 Grade wet abrasive paper on a flat surface to lap the "COLD VALVE FACE". 6.4.8 Reassemble the HORNE 20 TMV. 6.5 RE-ASSEMBLY 6.5.1 When fitting new O-Rings, it is advisable to smear them sparingly with a WRAS listed silicone grease. 6.5.2 Insert the components into the HORNE 20 TMV in the order shown on Drawing 6355. NOTE: The flanged end of the BAFFLE TUBE (9) must be inserted first into the valve body. 6.5.3 Insert the ADJUSTING SCREW (2) into the VALVE COVER (3) and turn anti-clockwise until the top of the Adjusting Screw is approximately 5mm below the top of the Lockshield. 6.5.4 When the internal components have been located loosely in the valve body, place the VALVE COVER (3) over the ELEMENT ASSEMBLY (6) then push gently and turn until the thread on the Valve Cover engages with the valve body. The internal components are self-aligning. 6.6 CHECK VALVES Check valves are located within the STRAINER BODY (15). They are not removable. They are designed for a long, maintenance free life. Mar 2012 Page 5 of 10

Mar 2012 Page 6 of 10

FAULT FINDING CHART SYMPTOM POSSIBLE CAUSE ACTION Mixed water temperature too high Temperature setting too high. Temperature has been set when the hot water temperature is too low Re-adjust temperature setting 4 REFER TO SECTION Hot water has migrated into cold water supply Inspect Check Valve at cold inlet If the check valve leaks replace the strainer body and check valve sub-assembly 3.6.1 to 3.6.6 See Drg.6355 Thermostat Element has failed. This can be checked by carrying out a hot or cold water failure test. Replace element (6) 6 Mixed water temperature too low Temperature Setting too low Re-adjust temperature setting 4 Hot water supply temperature has fallen Check hot water supply system 3.2 Cold water has migrated into hot supply Inspect Check Valve at hot inlet If the check valve leaks replace the strainer body and check valve sub- assembly. 3.6.1 to 3.6.6See Drg 6355 Cold valve face requires cleaning Remove valve Cover (3) and service valve face 6.4.7 Mixed water flow rate too low. Partly blocked strainers Clean strainers 6.2 Unusually high pressure drop in supply pipework Check all valves are full open. Check Pressurisation unit Check mains supply Extra Demand added to system Check pipe sizing Mixed water temp does not respond to adjusting screw Slide-Valve (7) is seized Valve requires de-scaling 6.4.5 Mixed water temp changes and is not steady Water at outlet runs full hot or full cold Hot and cold inlets reversed Remove HORNE 20 TMV from pipes and reverse connections. Connect inlet with red dot to hot pipe Slide-Valve (7) is seized Valve requires De-Scaling 6.4.5 Thermostat element has failed (This can be checked by carrying out a hot or cold water failure test) Hot and cold inlets are reversed Replace element (6) 6 Hot inlet is marked with Red dot Cold inlet is marked with Blue dot Valve continues to pass cold water when hot supply is isolated Cold valve face requires cleaning Remove valve cover (3) and service cold valve face 6.4.7 Fouling at hot valve seat Clean hot valve face 6.4.7 Valve continues to pass hot water when cold supply is isolated Slide-Valve seal is damaged Replace Slide-Valve Seal (10) 6.3.4 & 6.3.5 Element has failed Replace Element (6) 6 Mar 2012 Page 7 of 10

COMMISSIONING, MAINTENANCE & IN-SERVICE TESTING RECORD Establishment: Type of Valve: Horne 20 Thermostatic Mixing Valve Date Installed: Installed by: Location of Valve: Commissioning Details Note: Fill in ALL information during commissioning. Hot Water Supply : HW Temp C HW Pressure Bar Temp: Instrumentation: Cold Water Supply: CW Temp C CW Pressure Bar Pressure: Mixed Temp at max draw-off: Mixed Temp: C Flowrate at max draw-off: l/min Mixed Temp at low draw-off: Mixed Temp: C Flowrate at low draw-off: l/min Instrumentation Used: Temp: Press: Flow: Cold Water Isolation Test Max Mixed Water Temp during CW Isolation test: C Mixed Water Temp on restoration of CW Supply: C Note: MWT should return within 2 degrees of set temp, and be no greater than 43C after this test. Comments: In-Service Testing Record Date: Hot Water Supply : HW Temp C HW Pressure Bar Instrumentation: Temp: Used: Cold Water Supply: CW Temp C CW Pressure Bar Pressure: Mixed Temp at max draw-off: Mixed Temp: C Flowrate at max draw-off: l/min Mixed Temp at low draw-off: Mixed Temp: C Flowrate at low draw-off: l/min Instrumentation Used: Temp: Press: Flow: Cold Water Isolation Test Max Mixed Water Temp during CW Isolation test: C Mixed Water Temp on restoration of CW Supply: C Note: MWT should return within 2 degrees of set temp, and be no greater than temp shown below* for this test. Comments: Recommended Date of Next In-Service Test: *Max stabilised Mixed Water Temperatures: Bath (44C fill) = 46C, Bath (46C fill) = 48C, Washbasin = 43C, Shower = 43C Mar 2012 Page 8 of 10

IN-SERVICE TESTING RECORD (Note: Photocopy this page) In-Service Testing Record Establishment: Location of Valve: Date: Type of Valve : Horne 20 Thermostatic Mixing Valve Hot Water Supply : HW Temp C HW Pressure Bar Temp: Instrumentation: Cold Water Supply: CW Temp C CW Pressure Bar Pressure: Mixed Temp at max draw-off: Mixed Temp: C Flowrate at max draw-off: l/min Mixed Temp at low draw-off: Mixed Temp: C Flowrate at low draw-off: l/min Instrumentation Used: Temp: Press: Flow: Cold Water Isolation Test Max Mixed Water Temp during CW Isolation test: C Mixed Water Temp on restoration of CW Supply: C Note: MWT should return within 2 degrees of set temp, and be no greater than 43C after this test. Comments: Recommended Date of Next In-Service Test: In-Service Testing Record Establishment: Location of Valve: Date: Type of Valve : Horne 20 Thermostatic Mixing Valve Hot Water Supply : HW Temp C HW Pressure Bar Temp: Instrumentation: Cold Water Supply: CW Temp C CW Pressure Bar Pressure: Mixed Temp at max draw-off: Mixed Temp: C Flowrate at max draw-off: l/min Mixed Temp at low draw-off: Mixed Temp: C Flowrate at low draw-off: l/min Instrumentation Used: Temp: Press: Flow: Cold Water Isolation Test Max Mixed Water Temp during CW Isolation test: C Mixed Water Temp on restoration of CW Supply: C Note: MWT should return within 2 degrees of set temp, and be no greater than 43C after this test. Comments: Recommended Date of Next In-Service Test: Mar 2012 Page 9 of 10

Brochure Ref: L-02 PO Box 7 Rankine Street Johnstone SCOTLAND PA5 8BD Tel: +44 (0)1505 321455 Fax: +44(0)1505 336287 Email: Technical@horne.co.uk www.horne.co.uk Mar 2012 Page 10 of 10