THERMOSTATIC MIXING VALVES

Similar documents
Installation Instructions and User Guide 15mm & 22mm Thermostatic Mixing Valve

Installation Instructions and User Guide

PEG402, PEG402UA & PEG402UAX TMV3 / TMV2 Combined

Installation Instructions and User Guide

Twin & Triple Control Concealed Thermostatic Shower Valve

In Line Thermostatic Controller. Copper x Copper

Self-help Temperature Adjustment

Installation Guide - C01202 & C01203 Thermostatic Mixing Valve TMV2

Intamix Thermostatic Mixing Valve

TMV3 Requirements IMPORTANT Installer:

CONSTANT FLOW REGULATOR (CFR)

TEMPERATURE STABILISED THERMOSTATIC SHOWER PANEL

SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER

Issue date: July 2012 Issue 1

PRESSURE INDEPENDENT CONTROL VALVE (PICV)

Issue date: April 2017

HORNE 20 THERMOSTATIC MIXING VALVE TYPE H-2003

INSTALLATION, OPERATING AND MAINTENANCE GUIDE FOR EXPOSED AND CONCEALED MODELS MODERN, TRADITIONAL AND MINIMALISTIC

Deluge Optimo Shower valve and kit 10032CP


1. Introduction. The Easy Guide to TMV3 Approval

Scald Protection Three-Way Thermostatic Mixing Valve

Pressure Independent Control Valve (PICV) Fig DN15-32

SMV-001 Thermostatic Shower Mixer Valve Installation Instructions & Adjustment Settings

DB 61 Dolphin TMV3 Integrated Thermostatic Mixing Valve

Scald Protection 3-Way Thermostatic Mixing Valve

Thermostatic Mixing Valves 61022CPB & 61028CPB Intamix Pro V

Installation, commissioning and servicing instructions

National Health Service Model engineering Specification

bathrooms.com Concentric Thermostatic Shower Mixers Cleaning and Care Installation Manual Contents

Tempering valve for solar and instantaneous applications Installation, commissioning and servicing instructions 2522HP series

WHTM Supplement

Installation, commissioning and servicing instructions

Horne Engineering Ltd

Installation, commissioning and servicing instructions. General

V12 THERMOSTATIC SHOWER VALVE PRODUCT MANUAL

15/3 THERMOSTATIC MIXING VALVE PRODUCT MANUAL IMPORTANT

215 and 222 Series PRODUCT MANUAL

PRODUCT MANUAL IMPORTANT

INSTALLATION INSTRUCTIONS 1/2 THERMOSTATIC VALVE AND TRIM

3.5 litr es per INSTALLATION INSTRUCTIONS. Avon 21 Self-closing taps (Push button) B0992AA Self-closing basin pillar tap

Issue 1. Air Valves OUR GENIUS IS FITTINGS.

OWNER S GUIDE DUAL CONTROL THERMOSTATIC SHOWER VALVE. Shower Control. may differ depending on choice of Model. Concealing Plate. Handles and ISSUE 01

HORNE T109A/306A/307A THERMOSTATIC SHOWER VALVE FOR SURFACE MOUNTING WITH TIMED FLOW CONTROL INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

These instructions must be left with the user.

Bar valve with fixed shower head Installation guide

These instructions must be left with the user.

Thermostatic Concentric Mixer Valve. with Exposed and Concealed Fitting Options. Fitting Instructions

Options Concentric Petite

Thermocirc Installation and Maintenance Instructions

PRODUCT MANUAL IMPORTANT

RA-N radiator valves with integrated presetting and self-sealing tailpiece

Installation, commissioning and servicing instructions

INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

High Performance BSP Dial Up Pattern Pressure Reducing Valve

Atmos Low Pressure Thermostatic Bar Mixer Valve

Rada-Presto TF2020 and TF2020S

TECHNICAL CATALOGUE PRESSURE REDUCING VALVES EUROPRESS

MANUAL FOR INSTALLATION, COMMISSIONING AND MAINTENANCE FOR

TECHNICAL CATALOGUE PRESSURE REDUCING VALVES EUROPRESS

Engineering Data Sheet

valves Total Control.

book : t95575.fm Seite 1 Mittwoch, September 20, :10 AM. Avensys. Exposed Single Lever Mixer

Dynamic Valve Type RA-DV Pressure Independent Radiator Valve

Atmos Fusion. Thermostatic Concentric Mixer Valve with Riser Rail. Fitting Instructions

OPERATING INSTRUCTIONS

Latvin Luxury Shower Panel. Telephone Product Specification. ~ Minimum Working Pressure 1.0 bar ~ Maximum Working Pressure 3.

FILTER REGULATORS MODEL NO: CAT155 & CAT156 FITTING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

TMV20 THERMOSTATIC MIXING VALVE

M03 WUNDATRADE. Heat Pump Manifold. Before you start: Check the contents. Optional. ...a division of WUNDA GROUP PLC

These instructions must be left with the user

Atmos Zone. Thermostatic Concealed Concentric Mixer Valve with Fixed Head. Fitting Instructions

BASIN AND WALL MIXER INSTALLATION INSTRUCTIONS

CALEFFI. Pre-adjustable pressure reducing valves with self-contained cartridge series 01085/17 GB. replaces 01085/14 GB

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6

DS05C,D,G Dial Set Pressure Regulating Valves

ASSE International Product (Seal) Listing Program

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

320 c PRODUCT MANUAL IMPORTANT

hydraulic valve 1 Introduction

Materials : Brass body dezincification-resistant up to DN1 1/4

SHOWER FITTINGS INSTRUCTIONS AND MAINTENANCE GUIDE. Please read carefully before use

INSTALLATION INSTRUCTIONS

THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER

ACCREDITED. Technical specifications series

Pre-adjustable pressure reducing valves with self-contained cartridge

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

SCA Series Inverted Bucket Steam Traps

HUPF Series DESCRIPTION APPLICATION INSTRUCTION SHEET GAS PRESSURE REGULATOR WITH INCORPORATED FILTER EN1C-0003NL05 R1205.

Function. Code Automatic filling units with pressure gauge connection Size 1/2 Code Automatic filling units with pressure gauge Size 1/2

DS06D,G Dial Set Pressure Regulating Valve

Rada Sense Shower T3 DMV PRODUCT MANUAL IMPORTANT

LNVx Gas Conversion Kit Instructions

KTM 50 (DN ) Installation, maintenance and operating instructions

CALEFFI. Reduced pressure zone backflow preventer. 574 series 01022/18 NA D E C F B D E. Function

AQUABLEND MM THERMOSTATIC MIXING VALVE

WORCESTER GREENSTORE. Indirect Unvented Cylinder with Solar Coil FOR USE WITH WORCESTER GREENSTORE SYSTEM HEATPUMP ONLY GB/IE

System Pressure Manager Standard & System Pressure Manager Plus

HYDRALECTRIC LIMITED,

Transcription:

THERMOSTATIC MIXING VALVES D1088 & D1089 INTRODUCTION Are self-acting Thermostatic Mixing Valves designed to blend hot and cold water, to ensure a constant, safe outlet temperature and prevent scalding. Design and manufactured to comply with BS EN1287 and BS EN1111. Have been independently tested and certified as meeting the requirements of the D08 specification under the TMV3 scheme. The D1089 includes right angle isolation valves. Both the D1088 & D1089 thermostatic mixing valves are certified under the BuildCert TMV2 & TMV3 schemes and are WRAS approved products listed in the WRAS Approvals Directory: D1088 - BuildCert Approval Number (TMV3): BC1802/1016 (for TMV3) FM311 ISO 9001 - BuildCert Approval Number (TMV2): BC1801/1016 (for TMV2) CRANE HOUSE, EPSILON TERRACE, WEST ROAD, IPSWICH, SUFFOLK IP3 9FJ TELEPHONE: +44 (0)1473 277300 FAX: +44 (0)1473 277301 EMAIL: enquiries@cranefs.com www.cranefs.com Designed and manufactured under quality management systems in accordance with BS EN ISO 9001:2008 Every effort has been made to ensure that the information contained in this publication is accurate at the time of publishing. Crane FS assumes no responsibility or liability for typographical errors or omissions or for any misinterpretation of the information within the publication and reserves the right to change without notice. CFS_D1088_D1089_1016 0ED17254D_V1 - WRAS Scheme Approval Number: 1301096 (WRAS) D1089 www.cranebsu.com

TECHNICAL SPECIFICATION Table 1 Factory Setting 41 C Temperature Setting Range 30 C to 50 C Minimum Hot to Mix Temperature 10 C Temperature Stability ±2 C Maximum Working Pressure 10 Bar Min Flow Rate 5 l/min GENERAL INSTALLATION TMV2 & TMV3 These instructions are issued as guidelines only and may not cover all installation conditions if unsure please contact our Technical Helpline before installation. Crane FS products are designed for installation and use within suitably designed systems reflecting CIBSE, BSRIA and HVAC guidelines. Particular care should be taking with regards to accessibility to valve for setting/adjustment, tube cutting, jointing & bracketing/supports. The thermostatic mixing valve must be installed in accordance with the regulations of the local water company and the Water Supply (Water Fittings) Regulations 1999. The D1088 & D1089 are suitable for single outlet applications only. The D1088 & D1089 can be installed in any orientation. Flush hot & cold supply pipework before connection. For the D1088, where isolation valves are not supplied, isolation valves in the water supply inlets should be fitted as close as practical to the TMV. For D1088, wafer strainers are supplied as shown in figure 5. For D1089, strainers are supplied and located in the isolation valve body. TMV3 The D1088 and D1089 have been approved as TYPE 3 valves under the TMV3 scheme. They have been designed and manufactured for use in Healthcare and Commercial installations and complying with NHS Estates requirements D 08. LIMITS OF USE The D1088 & D1089 have been approved for use on the following designated systems. Table 2 - Mixed Water Temperature Code Operating Pressure Application HP-S, LP-S High Pressure Shower Temperature 41ºC HP-W, LP-W High Pressure Washbasin Temperature 41ºC HP-B, LP-B High Pressure Bidet Temperature 38ºC HP-T44, LP-T44 High Pressure Bath Fill Temperature 44ºC HP-T46, LP-T46 High Pressure Bath Fill (assisted) Temperature 46ºC Note 1 - HP: High Pressure LP: Low Pressure Note 2-15mm not acceptable for LP Tub Fill, LP-T44 & LP-T46. CONDITIONS OF USE Table 3 - Normal Conditions of Use for Type 3 Valves Operating Pressure Range High Pressure Low Pressure Maximum Static Pressure 10 - Flow Pressure - Hot & Cold 1 to 5 bar 0.2-1 bar Hot Supply Temperature 52 to 65ºC 52 to 65ºC Cold Supply Temperature 5 to 20ºC 5 to 20ºC Note 1: The valve may perform adequately outside the conditions in table 3 but the TMV3 scheme approval does not apply. Note 2: The highest flow rates will be achieved under balanced pressure conditions, but the pressure at the valve inlets must be within a ratio of 2:1 under flow conditions and the size and layout of pipe work and fittings must take this into account. PRE-COMMISSIONING CHECKS Follow this method for adjusting the water temperature: 1. Remove the maroon plastic protective cap on top of the valve with a screw-driver. 2. Back-out the nut, using a monkey spanner: - To increase the temperature turn anti-clockwise - To decrease the temperature turn clockwise - To set the valve to a maximum mixed water temperature in accordance with the valve application (See Table 4). Once the correct outlet temperature is set the internal mechanism must be tested at least 3 times by: Alternately isolate the hot & cold water supply. This causes the internal piston to travel its full stroke and will ensure correct operation of the valve. With hot & cold isolation valves and the terminal outlet fully open retest the flow temperature. If the set temperature has moved, repeat the commissioning process. A fail safe test must be carried out by isolating the cold supply. Once isolated, the flow must reduce, within a couple of seconds, to a trickle - depending on site conditions, supply temperature/pressure. Then repeat fail safe test isolating the hot supply. Once isolated, the flow must reduce to a trickle within a couple of seconds depending on site conditions. If either the cold or hot fail safe function does not operate, check; - Supply pressures - Supply temperatures - Hot water supply is at least 10ºC above required mix temperature, i.e. minimum hot to mix temperature Screw driver Screw The blue plastic protective cap Nut Figure 1 - D1088 pictured, cap removal Figure 2 - D1088 pictured, temperature setting 3 THERMOSTATIC MIXING VALVES: D1088 & D1089 THERMOSTATIC MIXING VALVES: D1088 & D1089 4

COMMISIONING Since the installed supply conditions are likely to be different from those applied in the laboratory tests, it is appropriate, at commissioning, to carry out some simple checks and tests on each mixing valve to provide a performance reference point for future in-service tests. a) The designation (TMV3) of the Thermostatic Mixing Valve matches the intended application. b) The supply pressures are within the range of operating pressures for the designation of the valve. c) The supply temperatures are within the range permitted for the valve and within guidance information on the prevention of legionella etc. d) Record the temperature of the hot and cold water supplies. e) Record the temperature of the mixed water at the largest draw-off flow rate. f) Record the temperature of the mixed water at a smaller draw-off flow rate. g) Isolate the cold water supply to the mixing valve and monitor the mixed water temperature. h) Record the maximum temperature achieved as a result of (g) and the final stabilised temperature. Note: The final stabilised mixed water temperature should not exceed the values in the following table. i) Use recording equipment such as a thermometer etc. used for the measurements. Table 4 - Guide to Maximum Stabilised Temperatures Recorded During Site Tests Application Mixed Water Temperature Bidet 40 C Shower 43 C Washbasin 43 C Bath (44 C Fill) 46 C Bath (46 C Fill) 48 C IN SERVICE TESTING Purpose The purpose of in-service tests is to regularly monitor and record the performance of the Thermostatic Mixing Valve. Deterioration in performance can indicate the need for service work on the valve and/or the water supplies. Service Work Procedure Using the same measuring equipment or equipment to the same specification as used in the commissioning of the valve, adjust the temperature of the mixed water in accordance with the requirement of the application. Carry out the following sequence: a) Record the temperature of the hot and cold water supplies. b) Record the temperature of the mixed water at the largest draw-off flow rate. c) Record the temperature of the mixed water at a smaller draw-off flow rate, which shall be measured. If the mixed water temperature has changed significantly from the previous test results (e.g.> 1 K), record the change and before re-adjusting the mixed water temperature check: a) That any in-line or integral strainers are clean. b) Any in-line or integral check valves or other anti-back siphonage devices are in good working order. c) Any isolating valves are fully open. With an acceptable mixed water temperature, complete the following procedure: a) Record the temperature of the hot and cold water supplies. b) Record the temperature of the mixed water at the largest draw-off flow rate. c) Record the temperature of the mixed water at a smaller draw-off flow rate, which shall be measured. d) Isolate the cold water supply to the mixing valve and monitor the mixed water temperature. e) Record the maximum temperature achieved as a result of (d) and the final stabilised temperature. f) Record the equipment, thermometer etc. used for the measurements. If at step (e) the final mixed water temperature is greater than the values in the above table and/ or the maximum temperature exceeds the corresponding value from the previous results by more than about 2 K, the need for service work is indicated. Note: In-service tests should be carried out with a frequency, which identifies a need for service work before an unsafe water temperature can result. In the absence of any other instruction or guidance, the following procedure described in Annex F of D08 may be used. 5 THERMOSTATIC MIXING VALVES: D1088 & D1089 THERMOSTATIC MIXING VALVES: D1088 & D1089 6

FREQUENCY OF IN-SERVICE TESTS (Annex F of D08) General In the absence of any other instruction or guidance on the means of determining the appropriate frequency of in-service testing, the following procedure may be used: a) 6 to 8 weeks after commissioning carry out the tests detailed in In-Service Tests. b) 12 to 15 weeks after commissioning carry out the tests detailed in In-Service Tests. Depending on the results of the above tests, several possibilities exist: a) If no significant changes (e.g. 1 K) in mixed water temperatures are recorded between commissioning and 6 to 8 week testing, or between commissioning and 12-15 week testing the next in-service test can be deferred to 24 to 28 weeks after commissioning. b) If small changes (e.g. 1 to 2 K) in mixed water temperatures are recorded in only one of these periods, necessitating adjustment of the mixed water temperature, then the next in-service test can be deferred to 24 to 28 weeks after commissioning. c) If small changes (e.g. 1 to 2 K) in mixed water temperatures are recorded in both of these periods, necessitating adjustment of the mixed water temperature, then the next in-service test should be carried out at 18 to 21 weeks after commissioning. d) If significant changes (e.g. > 2 K) in mixed water temperatures are recorded in either of these periods, necessitating service work, then the next in-service test should be carried out at 18 to 21 weeks after commissioning. The general principle to be observed after the first 2 or 3 in-service tests is that the intervals of future tests should be set to those which previous tests have shown can be achieved with no more than a small change in mixed water temperature. TMV2 The valves covered by these instructions have been specifically designed and manufactured as being in compliance with BS EN1287 and BS EN1111. It has been independently tested and approved as a TYPE 2 valve under TMV2 scheme for use in domestic situations. LIMITS OF USE The D1088 & D1089 have been approved for use on the following designated systems. Table 5 - Mixed Water Temperature Code Operating Pressure Application HP-S, LP-S High Pressure Shower Temperature 41ºC HP-W, LP-W High Pressure Washbasin Temperature 41ºC HP-B, LP-B High Pressure Bidet Temperature 38ºC HP-T44 High Pressure Bath Fill Temperature 44ºC Note 1: HP: High Pressure LP: Low Pressure Note 2: 46 C is the maximum permissible mixed water temperature from the bath tap. The maximum temperature takes account of the allowable temperature tolerances inherent in thermostatic mixing valves and temperature losses in metal baths. 46 C is not a safe bathing temperature for adults or children. Note 3: The British Burns Association recommends 37 to 37.5 C as a comfortable bathing temperature for children. In premises covered by the Care Standards Act 2000, the maximum mixed water outlet temperature is 43 C. CONDITIONS OF USE Table 6 - Normal Conditions of Use for Type 2 Valves Operating Pressure Range High Pressure Low Pressure Maximum Static Pressure 10 bar 10 bar Flow Pressure - Hot & Cold 0.5 bar to 5.0 bar 0.1 bar to 1.0 bar Hot Supply Temperature 55 to 65ºC 55 to 65ºC Cold Supply Temperature 25 C 25 C Note 1: Valves operating outside table 6 s conditions cannot be guarantees by the Scheme to operate as Type 2 valves. Note 2: Valves approved for designation of use H.P only, must state: - If a water supply is fed by gravity then the supply pressure should be verified to ensure the conditions of use are appropriate for the valve. Note 3: Valves approved for designation of use LP Tub applications that only achieve the minimum flow rate requirement at a supply pressure of 0.2 bar must indicate that the minimum supply pressure for LP Tub application is 0.2 bar. 7 THERMOSTATIC MIXING VALVES: D1088 & D1089 THERMOSTATIC MIXING VALVES: D1088 & D1089 8

PRE-COMMISSIONING CHECKS Follow this method for adjusting the water temperature: 1. Remove the maroon plastic protective cap on top of the valve with a screw-driver. 2. Back-out the nut, using a monkey spanner: - To increase the temperature turn anti-clockwise - To decrease the temperature turn clockwise - To set the valve to a maximum mixed water temperature in accordance with the valve application (See Table 7). Once the correct outlet temperature is set the internal mechanism must be tested at least 3 times by: Alternately isolate the hot & cold water supply. This causes the internal piston to travel its full stroke and will ensure correct operation of the valve. With hot & cold isolation valves and the terminal outlet fully open retest the flow temperature. If the set temperature has moved, repeat the commissioning process A fail safe test must be carried out by isolating the cold supply. Once isolated, the flow must reduce, within a couple of seconds, to a trickle depending on site conditions, supply temperature/pressure Then repeat fail safe test isolating the hot supply. Once isolated, the flow must reduce to a trickle within a couple of seconds depending on site conditions. If either the cold or hot fail safe function does not operate, check; - Supply pressures - Supply temperatures - Hot water supply is at least 10ºC above required mix temperature, i.e. minimum hot to mix temperature TMVs shall be located in such a way that it can be easy accessed for maintenance and commissioning purposes. Screw driver Screw The blue plastic protective cap Nut Figure 3 - D1088 pictured, cap removal Figure 4 - D1088 pictured, temperature setting COMMISIONING Since the installed supply conditions are likely to be different from those applied in the laboratory tests, it is appropriate, at commissioning, to carry out some simple checks and tests on each mixing valve to provide a performance reference point for future in-service tests. a) The designation (TMV2) of the Thermostatic Mixing Valve matches the intended application. b) The supply pressures are within the valves operating range. c) The supply temperatures are within the range permitted for the valve and within guidance information on the prevention of legionella etc. d) Record the temperature of the hot and cold water supplies. e) Record the temperature of the mixed water at the largest draw-off flow rate. f) Record the temperature of the mixed water at a smaller draw-off flow rate. g) Isolate the cold water supply to the mixing valve and monitor the mixed water temperature. h) Record the maximum temperature achieved as a result of (g) and the final stabilised temperature. i) NOTE: The final stabilised mixed water temperature should not exceed the values in the following table. j) Use recording equipment, such as a thermometer etc. k) The mixed water temperature at the terminal fitting must never exceed 46 C. Table 7 - Guide to Maximum Stabilised Temperatures Recorded During Site Tests Application Mixed Water Temperature Bidet 40 C Shower 43 C Washbasin 43 C Bath (44 C Fill) 46 C 9 THERMOSTATIC MIXING VALVES: D1088 & D1089 THERMOSTATIC MIXING VALVES: D1088 & D1089 10

IN SERVICE TESTING It is a requirement that all TMV2 approved valves shall be verified against the original set temperature results once a year. When commissioning/testing is due the following performance checks shall be carried out: 1. Measure the mixed water temperature at the outlet. 2. Temperature readings should be taken at the normal flow rate after allowing for the system to stabilise. 3. The sensing part of the thermometer probe must be fully submerged in the water that is to be tested. 4. Carry out the cold water supply isolation test by isolating the cold water supply to the TMV, wait for five seconds if water is still flowing check that the temperature is below 46 C. 5. Any TMV that has been adjusted or serviced must be re-commissioned and re-tested in accordance with the manufactures instructions. 6. If there is no significant change to the outlet temperature (±2 C or less change from the original settings) and the fail-safe shut of is functioning, then the valve is working correctly and no further service work is required. Note: If there is residual flow during the commissioning or the annual verification (cold water supply isolation test), then this is acceptable providing the temperature of the water seeping from the valve is more than 2 C above the designated maximum mixed water outlet temperature setting of the valve. The installation of thermostatic mixing valves must comply with the requirements of the Water Supply (Water Fittings) Regulations 1999. MAINTENANCE - TMV2 & TMV3 Most domestic water supplies contain calcium which will separate out when the water is heated in a system. The degree and speed of scaling may vary depending on factors such as water flow rates, system design, the hardness of the water and the temperature to which the water is heated. Deposits of scale may over time form in the valve, particularly at the hot inlet. The formation of the scale may adversely affect the performance of the valve which will be detected during the in-service testing. If this occurs it will be necessary to remove the valve for de-scaling and service. If required, the internal working parts can be removed and cleaned as follows: Fixing Screw Protective Cap Headwork Thermal element and piston assembly Flow guide Main spring O-ring Check Valve Figure 5 - D1088 pictured, exploded views Sealing Gaskets Tailpiece Union Nut Wafer Strainer Olives Compression Nut Tailpiece Assembly 1. Isolate hot and cold water supply. 2. Remove the valve to a clean working area. 3. Remove the protective cap. 4. Unscrew the headwork of the valve. 5. Carefully remove the temperature-sensitive and piston assembly, put to one side. 6. Remove the main spring and flow guide, carefully put to one side. 7. Inspect the components for contamination or damage. 8. Clean or replace as necessary. 9. Remove the O-ring. 10. Clean the valve body and Headwork using a propriety de-scaler (approved for use on potable water applications). 11. Thoroughly rinse the body and headwork in clean potable water. 12. Carefully fit new O-ring to body. 13. Carefully re-fit all components and perform the commissioning sequence. If after cleaning the valve and replacing the O-ring seals the valve does not function correctly, it may be necessary to replace the thermal element. 11 THERMOSTATIC MIXING VALVES: D1088 & D1089 THERMOSTATIC MIXING VALVES: D1088 & D1089 12