Rapidmain Installation Guide

Similar documents
SIMPLAIR PIPING TOOL. JXT Company

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

tubepress press procedure

Materials : Stainless steel ASTM A351 CF8M

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

k valve 2 (50)HF 2½ (65)SF installation guide aylesbury For valve sizes (DN): tel fax

COMPACT TRIPLE WALL OUTLET STATION MODEL INSTALLATION AND OPERATING INSTRUCTIONS

Pressure Dump Valve Service Kit for Series 3000 Units

// ADapters GUIDelines

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

Pressure Dump Valve Service Kit for Series 2300 Units

Instrument Operating Manual

COMPRESSED AIR DISTRIBUTION SYSTEMS

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

ACCURACY, PERFORMANCE, AND HANDLING OF OIL-FILLED DIGIQUARTZ PRESSURE INSTRUMENTATION

Translation of the original Operating Instructions for HKS rubber compensators

SEries 29 Hydrant valves installation, operation & maintenance manual

Mounting and Operating Instructions EB EN. Type Supply Pressure Regulator. with increased air capacity

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

SERIES 500 VARIABLE RANGE PNEUMATIC DIFFERENTIAL PRESSURE TRANSMITTER

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

PRO SINK -R 1 and 2. Dilution system CONTENTS

Installation, operation & maintenance manual - original version

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

PC3_ and PC4_ Pipeline Connectors

FILTER REGULATORS MODEL NO: CAT155 & CAT156 FITTING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS

COMPRESSION TUBE FITTINGS

book : t95575.fm Seite 1 Mittwoch, September 20, :10 AM. Avensys. Exposed Single Lever Mixer

ATS430 turbidity sensor Retractable insertion assembly

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES

Thermocirc Installation and Maintenance Instructions

CA10S, CA14 and CA14S Air and Gas Traps

Installation and commissioning instructions 255 series and 256 series

Corrugated Hose Loop Calculations

INFLATOR TDUX-IT-16 AND GAS CYLINDER E

Air Operated Hydraulic Pumping Systems to 50,000 psi

GLAUNACH THE SILENCER HANDBOOK INSTALLATION GLAUNACH GMBH ALL RIGHTS RESERVED -

Manual Actuated Boiler Blowdown Valves

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

HYDRALECTRIC LIMITED,

HYDRALECTRIC LIMITED,

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

INSTRUCTION MANUAL. January 23, 2003, Revision 0

ML3M Monnier Miniature Compressed Air Lubricator

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

Poollift Delphin. Version: February, 2015 MANUAL AND OPERATING INSTRUCTIONS

User guide DIAPHRAGM SEALS. Industrial instrumentation for Pressure and Temperature

Latvin Luxury Shower Panel. Telephone Product Specification. ~ Minimum Working Pressure 1.0 bar ~ Maximum Working Pressure 3.

AVK SERIES 601, 602, 603 & 605 UNIVERSAL COUPLINGS, ADAPTORS & END CAPS INSTALLATION, OPERATION & MAINTENANCE MANUAL

General Performance Data Hose Ref Minimum Bend. Safety Pressure at 20 C (BAR) Working Pressure at. Flow Rate at 3 bar (lit/min) Working Pressure

Instruction Manual. Standard Surge Eliminator. Standard X. Flushable X - X

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

PANACEA P125 USER MANUAL

M03 WUNDATRADE. Heat Pump Manifold. Before you start: Check the contents. Optional. ...a division of WUNDA GROUP PLC

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

Aquor House Hydrant V2

differential pressure regulating valve - threaded

Maximum 0.85 MPa pressure setting Long-life, high flow perfect for balancer applications

DN 1/2" to 2" Female BSP + 0 C C Max Pressure : 16 Bars Specifications : Stainless steel removable filter Female / Female With draining valve

CARTRIDGE FILTERS TECHNICAL MANUAL MT 080. Installation, commissioning and maintenance instructions. 08/02 Edition

Materials : Dichromate zinc plated steel flanges or AISI 316

SRI Jigger Tubes System

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

Erection, maintenance and disposal Inverted installation. Zinc oxide silicone-housed surge arresters PEXLIM R-X, Q-X and P-X

LEAK TROUBLESHOOTING

Introduction GUIDELINES FOR INSTALLATION PREINSULATED TUBE UNITHERM... Principal of Operation

Installation and Use Manual

DN 3/8" to 4" Female BSP - 10 C C Max Pressure : 16 Bars up to DN 2 Specifications : Removable stainless steel filter Female / Female

Installation and Training Manual

FIREFIGHTING EQUIPMENT

DN 1/4" to 3" Female BSP - 10 C C Max Pressure : 25 Bars ( up to DN 1 ) Specifications : Anti blow-out stem With PTFE packing Full bore

Installation, Operation, and Maintenance Manual. Welker Constant Pressure Cylinder With Solid Indicator (Non-mixer) Model CP-30SI

RS Pro 300mm Long EPDM 15bar Braided Stainless Steel Hose RS Stock No

THE OWNER'S MANUAL IS IN TWO VOLUMES: VOLUME 2 TECHNICAL SPECIFICATIONS - ASSEMBLY PROCEDURE ZODIAC

SAILTEC, INC CONGER COURT, OSHKOSH, WI USA

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

k valve ½ (15) ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF installation guide aylesbury For valve sizes (DN):

Series SFD. Clean Air Filter. Variations. Made to Order. Type. Cartridge (replaceable element) Disposable (non-replaceable element) Up to 100

09 - Choosing /sizing a cylinder and valve

AVM7 Stainless Steel Thermostatic Air Vent

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

Data sheet Pressure switch type CS December 2001 DKACT.PD.P10.A B1119

BIMBAR INFLATABLE PACKERS AND ACCESSORIES

Dri-Line Mk3 Monnier Compressed Air Drain Trap

KAX VALVE ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF INSTALLATION GUIDE AYLESBURY FOR VALVE SIZES (DN):

DISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING COMPRESSORS

SCA Series Inverted Bucket Steam Traps

Calculation tables for thermal expansion.

PN LINE. Technical remarks PN 11 PN 13 PN 14 PN 15 PN 17 PN 18 PN 20 PN 23 PN 25 PN 26 PN 27 PN 28 PN 29 PN 37 PN 38 PN 39 PN 40 PN 43 PN 10 8_9 10_12

IMPORTANT PLEASE READ BEFORE COMMENCING INSTALLATION

CRANKSET 1 - TECHNICAL SPECIFICATIONS. 44,5 mm 8 mm

PANACEA P100 LOW PRESSURE USER MANUAL

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

Airmate TS1.5/6 Oil-less Air Compressor

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

30T A/Manual Hydraulic Shop Press

Installation Instructions for the AlphaDeck Staging System

Transcription:

Rapidmain Installation Guide Aluminium Compressed Air Pipe Work Installation Guide Trafalgar Court, Waterloo Ind Estate, Widnes Cheshire. UK. Ref: Rapidmain installation guide 4b

Index 1. Rapidmain fittings: Assembly and locking torque setting. 3-5 2. Calculating compressed air flow... 6 4. Design layout for thermal expansion.. 7 5. Pipe work fall and further points to consider.... 8-9 6. Pipe work bracket support. Bracket types and their use... 10 7. Take-offs lines (branch lines) and the use of flexible pipe. 11 Brief Specification Working Pressure - 0.6 to 13 bar (- 8 to 191 PSI) Media Compressed Air and other Neutral Gas Flow Range 20 to 63 mm 0.73 to 26.8 M/min (26 to 948 cfm) * Temperature Range -20 to +70 C * Flow rate calculated over 100 metres Single run line P1@ 8bar We suggest that both the installer and the user of the Rapidmain pipe installation carefully read this manual before its use and before carrying out any installation or modification work. Please also refer to the local health and safety guidelines and accident prevention rules and regulations. Page 2

Rapidmain Installation Guide Aluminium Compressed Air Pipe Work Installation Rapidmain fittings: Assembly and locking torque settings Tightening of locking collars on fittings Assemble by hand or use our spanner set the correct torque. Black for the body and blue for the nut: See table B below Table B O D 20 25 32 40 50 63 Torque 9-11 11-13 12-15 15-17 17-20 18-22 L = mm 45 55 60 70 85 95 Use the depth gauge on the spanner to mark the outside of the pipe: See below. Push the fitting up to the mark on the pipe and then rotate the blue locknut to secure. Page 3

Rapidmain Installation Guide Aluminium Compressed Air Pipe Work Installation Guide Rapidmain fittings: Assembly and locking torque settings Chamfer Pipe If you choose to use a vice to clamp the Aluminium pipe when cutting or chamfering leave clear at least 50mm of pipe to avoid damaging the radius diameter and pipe sealing surface. On larger pipe if required use a neutral lubricant or soap. Trafalgar Court, Waterloo Ind Estate, Widnes Cheshire. WA8 OSZ.UK. Page 4

Rapidmain fittings: Assembly and locking torque settings WARNING: to avoid O-Ring damage, the tube end must be chamfered before inserting the tube into the fittings. R-Range of Compressed Air distribution fittings Sizes DN 20 to 63 OD 1.1 Before use check that all the fitting connection parts are correctly assembled. Ensure you check the orientation of the locking clip; if this is incorrectly assembled the integrity of the connection cannot be guaranteed (See Table A). 1.2 Before inserting the tube into the fitting rotate the light-blue coupling ring until a slight mechanical stop is felt and no further. 1.3 The tube must be inserted into the fitting until the tube bottoms. This can be checked by previously marking on the tube the length L indicated in Table B. 1.4 Once the tube has been correctly inserted into the fitting, rotate the coupling ring completely over the first mechanical stop described in Section 1.2 above until fully tight. For best results it is advisable to use the C type spanners shown in the catalogue. 1.5 Table B shows the torque (N/m) required for each fitting size to provide the optimum mechanical operation and seal. 1.6 Table C illustrates the correct alignment for installation. Misalignment of more than 5 o from the horizontal could compromise the integrity of the fitting seal. 1.7 Please refer to the specifications shown in the present catalogue for pipe and fittings compatibility with chemical substances that could be present in the compressed air. 1.8 Rapidmain will not be held responsible for any damage caused by improper use of their products and/or non-compliance of the manufacturers assembly instructions here within. Table A How to calculate an air system pipe size 2.1 Pressure drop through fittings Although fittings are smooth inside and have the same tube internal diameter, they nonetheless cause a resistance to air flow, particularly when tubes change direction as in the case of elbows, tees, couplings and reduction fittings. Table E refers to pressure drops caused by fittings. Every fitting or change of direction has an equivalent pipe length of tube indicated in this table. 2.2 Air System pipe sizing Once the compressed air consumption (l/min) and the allowable pressure drop have been calculated, refer to Table D to select the correct tube dimension. After having examined the plant and considered the changes of direction as well as the pressure drop of fittings you can then refer to Table E to complete and correct previous calculations. Page 5

Calculating Compressed air flow Table C Table D Pressure drop for 100 m (in bars) Effective Absolute Pressure (in bars) Delivery SRA * (in l/min) Outside diameter of the tube (mm) Referential axis Delivery SRA * Actual delivery at the effective pressure (P) x absolute pressure (P+1) in bars Temperature Correction: 0 degrees + 273 Air delivery at 0 degrees C = delivery 15 degrees C x * SRA: Standard Reference Atmosphere 288 Using the Nomogram The tube diameter can be determined by first finding the flow rate in l/m and the allowable pressure drop. a. We have chosen the working pressure on the C axis. A straight red line has then been drawn connecting the working pressure to the pressure drop value on the A axis. b. Drawing this straight line allows us to locate a point on the R referential axis. c. A green line has then been drawn from the referential R axis to the value on the A axis which indicates plant delivery in l/min. d. This green line intersects on the B axis which shows the suitable tube diameter. Trafalgar Court, Waterloo Ind Estate, Widnes Cheshire. WA8 OSZ.UK. Page 6

Design layout for thermal expansion DL = DT x 0,02 x L A = DL x 23 B = 0.7 x A Variation due to thermal expansion Introduction The theoretical calculations and design criteria in this manual are only relevant where the installation ambient temperature is between 15 o C and 25 o C. Attention! Where the installation is outside of the recommended ambient temperatures indicated above, it may be necessary to take corrective action such as thermal insulation of the pipe or the inclusion of expansion/contraction loops. Calculating expansion loop dimensions On long straight runs of pipe it may be necessary to insert expansion loops in the line to prevent damage to the pipe, due to thermal movement (expansion or contraction) of the pipe. Example L1 = 40 mt L2 = 40 mt DT = 50 o C DL = DT x 0.02 x L = 50 x 0.02 x 40 = 40 mm A = DL x 23 = 40 x 23 = 920 mm B = 0.7 x A = 0.7 x 920 = 640 mm Legend A-B = Quote (mm) L-L1-L2 = Lengths (mt) DL = Expansions (mm) DT = Thermal range ( o C) M = Mobile bracket F = Fix bracket Examples of Expansion Loops Vertical layout (Upwards) Horizontal Vertical layout (Downwards) Fixed brackets hold the pipe firmly while sliding brackets allow axial movement. Page 7

Pipe work fall and further points to consider Fall of pipes Where possible horizontal runs should be designed to have a slight fall of (1-2%) in the direction of air flow to encourage drainage and collection of condensate at lower levels or at drop legs built within the air system, from which the condensate can be drained as required. Direction of air flow Install drains at low points where ever possible. Example Pipe Fall Trafalgar Court, Waterloo Ind Estate, Widnes Cheshire. WA8 OSZ. UK. Page 8

Pipe work fall and further points to consider To allow for system maintenance, install an adequate quantity of isolation valves in the pipe work. Valve Ball Valve Fixing of Pipes To allow for thermal movement of the pipe and to avoid stress points, the pipe should be installed and fixed to a secure surface of building, such as a wall, brickwork, roof support (direct or with hanging brackets) or the building framework using suitable fixed and sliding brackets as required. Fixed bracket Fixed bracket Sliding bracket Fixed bracket Page 9

Rapidmain Installation Guide Aluminium Compressed Air Pipe Work Installation Guide Pipe work bracket support. Bracket types and there use Bracket and Pipe support centres It is important to install the pipe work brackets with correct spacing. Always try to support the pipe joint with a bracket located within 200 to 500 mm from the pipe joint. Please refer to the diagram below for examples of preferred installation Install brackets by each joint to support the pipe joint Suggested Maximum Support Centres) DN 20/25 32 40 50 63 P (MT) 2.5 3 3.5 4 4.5 Legend L = Length (mt) P = Brackets support centre (mt) M = Bracket G = Joint An alternative to the standard aluminium expansion loop, is to use suitable flexible hose assembly as shown below. DL = DT x 0,2 x L B = (2 x R) + DL 1 + DL 2 Legend L1-L2 = Lengths (mt) DL1-DL2 = Expansion (mm) DT = Thermal range ( o C) M = Bracket R = Radius (mm) A-B = Quotes (mm) Quote R A (mm) DN 20 25 32 40 50 63 R (mm) 70 85 100 130 160 200 A (mm) 370 390 500 560 600 800 Attention! Tables are valid only for stainless steel flexible hoses type 1REX/INOX/N/321/DN. For other types refer to the manufacturer s technical documentation Page10

Take-off lines (branch lines) and the use of flexible pipe DL = DT x 0,2 x L A = DL x Y Legend A = Quote (mm) L1-L2 = Lengths (mt) DL = Expansion (mm) DT = Thermal range ( o C) F = Fixed bracket U = Use Y = Calculation factor Calculation Factor Y DN 20 25 32 40 50 63 Y 20 20 25 28 33 40 Bends using flexible hose. Using a flexible hose in corners is also acceptable. They can be used for the change of direction and at the same time to compensate for any thermal movement. L min = 1000 mm At the end of a pipe run always terminate the pipe and the fitting to an fixed anchored point eg: Wall Legend L1-L2 = Lengths (mt) DL1-DL2 = Expansion (mm) M = Bracket R = Radius (mm) L = Length of flexible pipe (mm) Pd 20od=0.2 b(3 psi) 6m/sec Pd 63od=2.5%(3 psi) 12m/sec Avoid installing flexible hoses with to tight a radius or where the hose is subject to, too much stretch Page 11