FV Flash Vessel Installation and Maintenance Instructions

Similar documents
DF1 and DF2 Diffusers

TSS21 Sealed Thermostatic Steam Tracer Trap

TP1 and TP2 Temporary Cone Shaped Strainers

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

CP10 Sensor Installation and Maintenance Instructions

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

Dri-Line Mk3 Monnier Compressed Air Drain Trap

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

BDV60 Blowdown Vessel Installation and Maintenance Instructions

PV4 and PV6 Piston Valves

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

Manual Actuated Boiler Blowdown Valves

MF2M Monnier Miniature Compressed Air Filter

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

Spirax Compact FREME Flash Recovery Energy Management Equipment

DCV6 Disc Check Valve

CVS10 Sanitary Check Valves

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

AVC32 Carbon Steel Air Vent for Steam Systems

AVM7 Stainless Steel Thermostatic Air Vent

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

APT14, APT14HC and APT14SHC Spares 2

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

ML3M Monnier Miniature Compressed Air Lubricator

SRV66 Sanitary Pressure Reducing Valve

S and SF Inverted Bucket Steam Traps

PC10HP Pipeline Connector (ASME 600)

MFP14-PPU (Vented) Automatic Packaged Pump Units

CA44, CA44S, CA46 and CA46S Air and Gas Traps

BCV31 DN40 - Blowdown Control Valve

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

CS10-1 Stainless Steel Clean Steam Separator

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

Airodyn, BRair and BRoil Compressed Air Drain Traps

BPT13 Balanced Pressure Thermostatic Steam Traps

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

TW Temperature Control Valve

QuickHeat TM Packaged Heat Exchanger Solutions

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

CA10S, CA14 and CA14S Air and Gas Traps

BCV31 DN20 - Blowdown Control Valve

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

Vane Flow Switches Colima FLU Series

M111 Spiraflo Transducer

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

BDV1 and BDV2 Blowdown / Depressurisation Valves

Thermocirc Installation and Maintenance Instructions

SRV2S Pressure Reducing Valve

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

SCA Series Inverted Bucket Steam Traps

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

BRV71 and BRV73 Pressure Reducing Valves

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

LP10-4 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance IM-P402-92

BCVi43 Blowdown Control Valve

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

STD Spray Type Desuperheater

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

Colima TOR Magnetic Level Switches

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

RJ check valves Installation and Maintenance Instructions

Transcription:

4041050/5 IM-P404-10 EMM Issue 5 FV Flash Vessel Installation and Maintenance Instructions 1. Safety information 2. Specific product safety information 3. Product information 4. Installation 5. Commissioning 6. Operation 7. Maintenance 8. Spare parts FV6 shown Copyright 2017 IM-P404-10 EMM Issue 5 1 Printed in GB

2 IM-P404-10 EMM Issue 5

1. Safety information Safe operation of the unit can only be guaranteed if it is properly installed, commissioned and maintained by a qualified person (see Section 1.10) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. 1.1 Intended use Referring to these Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended use / application. The products listed below comply with the requirements of the Pressure Equipment Directive (PED) and carry the Pressure Equipment Directive categories: mark. The products fall within the following Product Group 2 Gases Flash vessel, FV6 and FV8 Category 2 Flash vessel, FV12, FV15 and FV18 Category 3 i) The products have been specifically designed for use with steam which is in Group 2 of the above mentioned Pressure Equipment Directive. The products use on other fluids may be possible but, if this is contemplated, Spirax Sarco should be contacted to confirm the suitability of the products for the application being considered. ii) Check material suitability, pressure and temperature and their maximum and minimum values. If the maximum operating limits of the product are lower than those of the system in which it is being fitted, or if malfunction of the product could result in a dangerous overpressure or over temperature occurrence, ensure a safety device is included in the system to prevent such over-limit situations. iii) Determine the correct installation situation and direction of fluid flow. iv) Spirax Sarco products are not intended to withstand external stresses that may be induced by any system to which they are fitted. It is the responsibility of the installer to consider these stresses and take adequate precautions to minimise them. v) Remove transit protection covers from all connections before installation. 1.2 Access Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting to work on the product. Arrange suitable lifting gear if required. IM-P404-10 EMM Issue 5 3

1.3 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. 1.4 Hazardous liquids or gases in the pipeline Consider what is in the pipeline or what may have been in the pipeline at some previous time. Consider: flammable materials, substances hazardous to health, extremes of temperature. 1.5 Hazardous environment around the product Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive noise, moving machinery. 1.6 The system Consider the effect on the complete system of the work proposed. Will any proposed action (e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel at risk? Dangers might include isolation of vents or protective devices or the rendering ineffective of controls or alarms. Ensure isolation valves are turned on and off in a gradual way to avoid system shocks. Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that the system has depressurised even when the pressure gauge indicates zero. 1.7 Temperature Allow time for temperature to normalise after isolation to avoid danger of burns. 1.8 Tools and consumables Before starting work ensure that you have suitable tools and / or consumables available. Use only genuine Spirax Sarco replacement parts. 1.9 Protective clothing Consider whether you and / or others in the vicinity require any protective clothing to protect against the hazards of, for example, chemicals, high / low temperature, radiation, noise, falling objects, and dangers to eyes and face. 1.10 Permits to work All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to these installation and maintenance instructions. Where a formal 'permit to work' system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibility is safety. Post 'warning notices' if necessary. 4 IM-P404-10 EMM Issue 5

1.11 Handling Manual handling of large and/or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. 1.12 Residual hazards In normal use the external surface of the product may be very hot. If used at the maximum permitted operating conditions the surface temperature of flash vessels may reach a temperature approaching 198 C (390 F). Many products are not self-draining. Take due care when dismantling or removing the product from an installation (refer to Section 7 - 'Maintenance instructions'). 1.13 Freezing Provision must be made to protect products which are not self-draining against frost damage if they are inoperative in environments where they may be exposed to temperatures below freezing point during shutdown. The vessel should be thoroughly defrosted prior to use. Trace heating should be considered under servere environmental conditions, in order to prevent the operating temperature of the vessel dropping below -10 C (14 F) during service. 1.14 Disposal This product is recyclable and no ecological hazard is anticipated with its disposal providing due care is taken. 1.15 Returning products Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination resides or mechanical damage which may present a health, safety or environmental risk. This information must be provided in writing including Health and Safety data sheets relating to any substances identified as hazardous or potentially hazardous. IM-P404-10 EMM Issue 5 5

2. Specific product safety information The following information is specific to FV type flash vessels and should be read in conjunction with the 'Safety information', Section 1 2.1 Overpressure protection Flash vessels must be protected against overpressure situations and provision is made for fitting a safety valve. However, it should not be assumed that the safety valve will be the same size as the connection. Safety valve sizing must be in accordance with National Standards. A connection is also provided for a pressure gauge. Safety valves and pressure gauges are both available from Spirax Sarco. Warning If this product is not used in the manner specified by this IMI, then the protection provided may be impaired. 6 IM-P404-10 EMM Issue 5

3. Product information 3.1 General information Spirax Sarco products are designed, manufactured and tested to exacting standards to meet modern system requirements. Where applicable, they satisfy current safety and design codes and users can expect long service life when products are selected, installed and maintained in accordance with Spirax Sarco recommendations. The FV type flash vessels are designed and constructed to comply with the Pressure Equipment Directive (PED), these vessels are particularly suited to boiler heat recovery systems where efficient separation of flash steam from blowdown is essential to prevent contamination of the boiler feedtank and/or heat transfer surfaces. Spirax Sarco flash vessels are equally suited to condensate steam flash applications. This Installation and Maintenance Instruction document provides comprehensive information on operation, installation and maintenance and should be read prior to commencing work on the product. Flash steam outlet Safety valve connection Pressure gauge connection Inspection cover Inlet Installation supports Inspection cover Condensate/residual blowdown outlet Fig. 1 Typical features of the FV type flash vessel (model FV15/FV18 shown) IM-P404-10 EMM Issue 5 7

3.2 Technical data Designed for use with saturated steam. Material of construction: Paint finish Carbon steel Temperature resistant silver paint Maximum design pressure 14 bar g (203 psi g) Maximum design temperature 198 C (390 F) Minimum design (operating) temperature Designed for a maximum cold hydraulic test pressure -10 C (14 F) In accordance with the Pressure Equipment Directive (PED). Note : Maximum design Pressure and temperature can be further limited, lower than that stated on the nameplate depending on the chosen flange rating of the system. PN16 Class A150 13.3 bar g @ 198 C (192.9 psi g @ 390 F) 13.8 bar g @ 198 C (200.1 psi g @ 390 F) Note: These vessels will withstand full vacuum conditions. Conforms to Ped 2014/68/EU Category Fig. 2 Typical FV type flash vessel name-plate details 8 IM-P404-10 EMM Issue 5

4. Installation Note: Before actioning any installation observe the 'Safety information' in Sections 1 and 2. FV type flash vessels are supplied with integral support brackets. Brackets should be fastened firmly to secure mounting points. It is important that external stresses are not introduced into the vessel and shims should be used beneath the support brackets if necessary to obtain accurate pipeline alignment during installation. Ensure that the blanking plugs supplied with the vessel are fitted securely, both at ambient and operating temperatures. The vessel must be mounted with the flash steam outlet uppermost, (see Figure 1). Each vessel incorporates a " BSP screwed boss for a pressure gauge, U-syphon gauge and cock. A separate connection is provided to accommodate a safety valve* and it is recommended that a float trap is fitted beneath the condensate/residual blowdown outlet. Fitment of a vacuum breaker may be required to counteract the creation of vacuum conditions by steam condensation. * It must not be assumed that the safety valve will be the same size as the connection - refer to 'Overpressure protection', Section 2.1. 5. Commissioning Before putting the unit into service, ensure that: - Blanking plugs are tight; check for tightness also when vessel has reached operating temperature. Caution:- Maximum operating temperature is 198 C (390 F). - All connections to adjoining pipework/plant are sound and secured so that no external stresses are introduced into the unit - No extraneous objects / material are present within the vessel. - Any associated safety accessory (e.g. safety valve) has been correctly sized, adequately tested and is in working order. - Check allowable pressure/temperature rating of flanges used and ensure operation and safety accessories are set within this limit. IM-P404-10 EMM Issue 5 9

6. Operation Operation of flash vessels is inherently simple and no special operating instructions are required. The vessel allows for the safe expansion of saturated water from high to lower pressures with the accompanying production of flash steam. On a precautionary note, vessels are designed to operate at high temperatures and care should be taken to avoid personal injury if vessels are unlagged. Operating conditions Spirax Sarco flash vessels are designed to operate under saturated steam conditions up to 14 bar g @ 198 C (203 psi g @ 390 F). They have a minimum design operating temperature of -10 C (14 F). Note : Maximum design Pressure & Temperature can be further limited, lower than that stated on the nameplate depending on the chosen flange rating of the system. PN16 13.3 bar g @ 198 C (192.9 psi g @ 390 F) Class A150 13.8 bar g @ 198 C (200.1 psi g @ 390 F) 7. Maintenance Flash vessels require no routine maintenance; however, blanking plugs should be checked periodically for tightness and, where used, insulation for security. Vessels should be included in a written scheme of examination including regular internal visual inspection for signs of excessive corrosion, by a suitably qualified competent person who is responsible for determining the frequency of examination. 8. Spare parts No spare parts are required or available for flash vessels. Repairs to pressure vessels are not recommended as specialist design procedures and welding operations are required, together with reinspection by a qualified competent person. 10 IM-P404-10 EMM Issue 5

IM-P404-10 EMM Issue 5 11

12 IM-P404-10 EMM Issue 5