Equipment, Design, and Installation of Closed-Circuit Ammonia Mechanical Refrigerating Systems

Similar documents
IRC 2011 All Rights Reserved

Single & Headered Relief Vent Piping Analysis

ASHRAE made significant changes in 2001 to the calculations. Fundamentals of Safety Relief Systems

Ammonia Refrigeration Valves

Application Worksheet

Pressure-Relief Valves

Air Eliminators and Combination Air Eliminators Strainers

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

CONTROL VALVE SEAT LEAKAGE

PROCEDURES FOR REPAIRS TO ASME NV STAMPED PRESSURE RELIEF DEVICES OF NUCLEAR SAFETY RELATED PRESSURE RELIEF VALVES

plumbing SAFETY AND RELIEF VALVES PART II

Si C132. Safety valves for pressure relief in accordance to PED, DIN/EN and ASME. Engineering GREAT Solutions

COMMITTEE DRAFT. API 520 Part I 10 th Edition Ballot Item 2.1. This ballot covers the following item:

What is pressure relief valve? Pressure relief valve

Modeling a Pressure Safety Valve

VBS-9263 Series. Application. Features. Applicable Literature

Installation Operation Maintenance

MSC Guidelines for Pressure Vessels

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

VB-7263 Series. Application. Features. Applicable Literature

Horizontal Bladder Tanks

Vertical Bladder Tanks

VB-7212 Series. Application. Features. Applicable Literature. 5/8" O.D., 45 SAE Flared Stem Up Open, Two-Way Valves General Instructions

VB-7273 Series. Application. Features. Applicable Literature

Standard Pneumatic Test Procedure Requirements for Piping Systems

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

ACCESSORY KIT INSTALLATION INSTRUCTIONS

VB-7213 Series. Application. Features. Applicable Literature. 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions

****** * EX * ****** DWN W.W.POWELL CALCULATION OF FLOW LOSSES IN INLET CHK D.PAPA AND DISCHARGE HEADERS ASSOCIATED WITH

Specifications, Applications, Service Instructions & Parts EZ-SRV CARTRIDGE PRESSURE-RELIEF VALVES. For Ammonia and Halocarbon Refrigeration Systems

GUIDANCE IN-SERVICE INSPECTION PROCEDURES

Model MTB-ASME Vertical Bladder Tanks

MAKING MODERN LIVING POSSIBLE. Pilot operated internal safety valves type POV REFRIGERATION AND AIR CONDITIONING DIVISION.

Model MTB-ASME Horizontal Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks

Technical Committee on LP-Gas at Utility Gas Plants

Regulated Oil and Gas Companies under National Energy Board Jurisdiction

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

Technical data. Back pressure limit: 27.5% of set pressure. Capacity certification: ASME Boiler & Pressure Vessel Code Section I and VIII

STANDARD FOR CONTROL VALVE SEAT LEAKAGE

Pressure Relief Valves

29 SERIES - SAFETY VALVE

VB-7211 Series. Application. Features. Applicable Literature. 1/2" to 1-1/4" Union End NPT Stem Up Open, Two-Way Valves General Instructions

API Standard Venting Atmospheric and Low-Pressure Storage Tanks: Nonrefrigerated and Refrigerated

44 (0) E:

Dimensioning of Safety Valves Auditorium Tecnimont

TECHNICAL DATA. Page 1 of 12

Type EZH Relief or Backpressure Regulator

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

BACK PRESSURE / SUSTAINING

Model Series 62 Constant Differential Relay

SIZING AND CAPACITIES OF GAS PIPING

Wet pipe low flow foam/water system

PRESSURE RELIEF DEVICES. Table of Contents

SIZING AND CAPACITIES OF GAS PIPING

Storage Systems and Accessories

North American Orifice Metering System

Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators

Sizing, Selection, and Installation of Pressure-relieving Devices in Refineries

BACK PRESSURE / SUSTAINING

The Electronic Newsletter of The Industrial Refrigeration Consortium

Type R622 Pressure Reducing Regulator

MSC Guidelines for Compressed Air Systems

TECHNICAL DATA Q= C. Table 1 - Specifications

ANDERSON GREENWOOD SERIES 9000 POSRV INSTALLATION AND MAINTENANCE INSTRUCTIONS

Noth American 7347 High Pressure Gas Regulators

BRITISH STANDARD BS 341-4: Transportable gas container valves. Part 4: Pressure relief devices ICS

Leak testing of Valves. Standards for acceptable Rates of Valve Leakage

SERIES SAFETY VALVE

S300 Series. Valve Link. Features. Fisher Controls

Regulating valves REG-SA and REG-SB

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller.

Vertical and Horizontal Bladder Tanks

The Shand & Jurs Model Vapor Guard Tank Blanketing Valve

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

The Discussion of this exercise covers the following points:

Safety relief valves SFV 20-25

TECHNICAL DATA CAUTION

North American 7339 High Pressure Gas Regulators

PRO-50 Instrument Supply Regulator

Hand-operated regulating valves in stainless steel Types REG-SA SS and REG-SB SS

Safety Selector Valves Dual Pressure Relief Device System

RELIEF VALVES IN PARALLEL

BASICS OF RELIEF VALVES

SCA Series Inverted Bucket Steam Traps

ACCESSORY KIT INSTALLATION MANUAL

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

SERIES 30. Spring Operated Tank Blanketing Valve PROTECTOSEAL.

SIZING AND CAPACITIES OF GAS PIPING

Safety relief valves Type SFA 15 and SFA 15-50

TECHNICAL DATA. Table 1 - Specifications

Safety relief valves, type SFA 15 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Regulating valves Type REG 6-65 Type REG-SS REFRIGERATION AND AIR CONDITIONING. Technical leaflet

COMBINATION AIR RELEASE DEGASSING (CARD) VALVES INSTALLATION AND MAINTENANCE MANUAL

Limited quantities of compressed gases.

Transcription:

American National Standard For ANSI/IIAR -1999, Addendum A-005 Equipment, Design, and Installation of Closed-Circuit Ammonia Mechanical Refrigerating Systems Approved by the American National Standards Institute: October 5, 005 Supersedes ANSI/IIAR -1999, in part, as noted

Forward (Informative) This standard was first issued in March of 1974 by the International Institute of Ammonia Refrigeration (IIAR) as IIAR 74-. The standard was intended to be a reference document covering the minimum requirements for specific aspects of industrial ammonia refrigerating systems to supplement existing refrigeration safety standards issued by other organizations such as ASHRAE, ASME and ANSI. The standard was first approved as an American National Standard by the American National Standards Institute (ANSI) in March 1978 as ANSI/IIAR 74- - 1978. Subsequent revisions to the standard were approved by ANSI in July 1985 (ANSI/IIAR -1984), December 199 (ANSI/IIAR -199), and August 1999 (ANSI/IIAR -1999). This revision, an addendum designated as ANSI/IIAR -1999, Addendum a- 005, received approval from ANSI in October 005. This revision shall be used in conjunction with ANSI/IIAR -1999. Changes shown in this revision supersede information found in ANSI/IIAR -1999 as noted herein. Review of Substantive Changes from Addendum a-005: In ANSI/IIAR -1999a, Addendum a-005, IIAR appended both informative and normative sections to ANSI/IIAR -1999, and amended certain normative sections of the standard. These changes include: Section 3.0: Revised the definition of proof test Section 5.10.3: Modified language to allow duplicate nameplates to identify equipment Section 7.3.4: Amended language regarding protecting vessels from hydrostatic overpressure due to the thermal expansion of liquids Section 7.3.7: Revised language regarding allowable length of discharge piping installed on the outlet of pressure-relief devices and fusible plugs discharging to the atmosphere Table 5: Replaced old Table 5 based on Table 3 from ANSI/ASHRAE 15-004, after corrected erroneous values Appendix A: Removed Figures A-1 and A- as an editorial change Appendix F: Added an informative appendix regarding hydrostatic pressure relief Appendix G: Added an informative appendix on duplicate nameplates on pressure vessels Appendix H: Added a normative appendix based on the Appendix H from ANSI/ASHRAE 15-004 This standard was prepared using the ANSI Canvass Method whereby organizations and individuals recognized as having an interest in the subject of the standard were contacted prior to the approval of this revision. Consensus was achieved by use of the Canvass Method. It was prepared and approved for submittal to ANSI by the IIAR Standards Review Committee. At the time of approval of this revision of the standard, the Committee had the following members: G. Robert Shriver, Chair - EVAPCO, Inc. Rex Brown - ALTA Refrigeration, Inc. Dennis R. Carroll - Cimco Refrigeration Inc. Robert J. Czarnecki - Campbell Soup Company Wayne D. Davis - M & M Refrigeration, Inc. Eduardo A. Ford - ColdWorks Engineering, Inc. Gregory P. Klidonas - FES Systems, Inc. Daniel R. Kuespert - Snowy Owl LLC Thomas A. Leighty - Refrigeration Systems Co. Michael J. Lynch U.S. Cold Storage, Inc. Brian M. Marriott - York International Corp. Richard P. Merrill - EVAPCO, Inc.

Page 4 Section 3.0: Revised the definition of proof test Proof test: Design confirmation by testing a production sample to verify that it will not fail when exposed to a predetermined pressure that exceeds its rated design pressure.

Page 16 Section 5.10.3: Modified language to allow duplicate nameplates to identify equipment 5.10.3 Equipment Identification 5.10.3.1 Manufacturers producing pressure vessels shall provide data in accordance with the requirements of the relevant "UG" sections of the latest edition of Section VIII, Division 1, ASME Boiler and Pressure Vessel Code (8.6), but in any case shall provide the following minimum data on a metal nameplate affixed to the equipment as specified in 5.10.3.: a. ASME stamp (where applicable) b. National Board Number (where applicable) c. Manufacturer's name (preceded by the words "certified by," if the vessel is ASME stamped) d. Maximum allowable working pressure at temperature e. Minimum design metal temperature at pressure f. Manufacturer s serial number g. Year of manufacture h. Model number i. Test pressure applied j. Type of construction (in accordance with 8.6, where applicable) k. Additional pressure and temperature stamping with reference to vessels used below minimum design metal temperature (in accordance with 8.6, where applicable) 5.10.3. Nameplate mounting 5.10.3..1 The original nameplate shall be affixed to the equipment as specified in the governing edition of Section VIII, Division 1, ASME Boiler and Pressure Vessel Code (8.6) paragraph UG-119(e). 5.10.3.. Duplicate nameplates 5.10.3...1 Duplicate nameplates shall comply with the governing edition of Section VIII, Division 1, ASME Boiler and Pressure Vessel Code (8.6) paragraph UG-119(e). 5.10.3... A duplicate nameplate, if used, shall be installed on the skirt, supports, jacket, or other permanent attachment to a vessel. 5.10.3...3 Duplicate nameplates shall be permanently marked DUPLICATE. 5.10.3...4 Duplicate nameplates shall be obtained only from the original equipment manufacturer or its assignee. 5.10.3...5 The installer shall certify to the manufacturer that the duplicate nameplate has been applied to the proper vessel, in accordance with the governing edition of Section VIII, Division 1, ASME Boiler and Pressure Vessel Code (8.6) paragraph UG- 119(d). The installer shall provide a copy of the certification to the owner, who shall retain the copy with the U1a form for the vessel. Appendix G provides further information on duplicate nameplates.

Page 8 Section 7.3.4: Amended language regarding protecting vessels from hydrostatic overpressure due to the thermal expansion of liquids 7.3.4 Piping in the system and other components required to comply with this paragraph that may contain liquid refrigerant or other incompressible fluids and that can be isolated from the system shall be protected from hydrostatic pressure due to the thermal expansion of such liquids during periods of normal operation, maintenance or standby by one of the following provisions: a. Installation of a pressure-relief device (see Appendix F) anywhere between isolation devices with discharge piping to relieve hydrostatic pressure to an acceptable location, or b. Use of trained technicians to isolate liquid-containing parts of the system.

Page 8 Section 7.3.7: Revised language regarding allowable length of discharge piping installed on the outlet of pressure-relief devices and fusible plugs discharging to the atmosphere 7.3.7 The maximum length of the discharge piping installed on the outlet of pressurerelief devices and fusible plugs discharging to the atmosphere shall be determined by the method in Appendix H. See Table 5 for the allowable flow capacity of various equivalent lengths of discharge piping for conventional safety relief valves.

Page 9 Table 5: Replaces old Table 5 based on Table 3 from ANSI/ASHRAE 15-004, erroneous values corrected Table 5. Pressure Relief Discharge Line Capacity of Various Discharge Line Lengths Discharge Line Capacity (lb/min of air, note 3) Set Length Nominal Pipe Size, NPS/schedule (note 4) (psig) (feet) 1-1- 1-1- (note 1) (note ) 1/ 1/ 3/4 3/4 1 1 1/4 1/4 1/ 1/ -1/ 3 4 5 6 8 80 40 80 40 80 40 80 40 80 40 40 40 40 40 40 40 40 150 1 10.4 13.8 0.1 5.1 34.3 41.5 6.4 73. 86.8 100 167 40 37 644 1015 1469 549 150 9.4 1.6 18.5 3.3 3. 39. 59.6 70.1 83.5 96.8 163 34 366 636 1006 1458 535 150 3 8.6 11.6 17. 1.8 30.4 37. 57.1 67.4 80.6 93.6 158 30 360 68 996 1447 51 150 4 7.9 10.8 16. 0.6 8.9 35.5 54.9 65.0 77.9 90.7 155 5 354 61 987 1436 507 150 5 7.4 10. 15.3 19.6 7.6 34.0 5.9 6.8 75.5 88.0 151 1 348 614 978 145 494 150 6 7.0 9.6 14.6 18.7 6.5 3.7 51.1 60.8 73.3 85.6 148 16 343 607 969 1415 481 150 8 6.3 8.8 13.4 17.3 4.6 30.5 48.1 57.4 69.4 81.3 14 09 333 593 95 1395 455 150 10 5.8 8.1 1.4 16.1 3.0 8.7 45.5 54.5 66.1 77.5 136 0 34 581 937 1375 49 150 16 4.8 6.8 10.5 13.6 19.7 4.7 39.7 47.9 58.4 68.8 13 185 301 548 893 13 358 150 5 4.0 5.6 8.7 11.4 16.6 1.0 34.1 41.3 50.6 60.0 109 166 74 507 838 153 6 150 40 3. 4.5 7.1 9.4 13.7 17.3 8.4 34.6 4.6 50.7 93.6 144 4 456 766 1158 15 150 60.7 3.8 5.9 7.8 11.4 14.5 4.0 9. 36. 43.1 80.5 15 1 407 693 1060 1976 150 100.1.9 4.6 6.1 9.0 11.5 19.1 3.3 8.9 34.6 65.3 10 176 343 593 90 1753 150 160 1.7.3 3.7 4.9 7. 9. 15.3 18.8 3.3 7.9 53.1 83.6 145 86 50 787 156 150 50 1.3 1.9 3.0 3.9 5.8 7.4 1.4 15. 18.9.6 43. 68.3 119 38 40 664 1307 00 1 1.0 15.9 3.0 8.7 39.1 47.3 71.0 83. 98.7 114 189 7 41 78 1148 1660 880 00 10.9 14.6 1.4 6.9 37.0 45.1 68.3 80. 95.5 111 185 67 415 71 1139 1649 867 00 3 10.1 13.6 0.1 5.4 35.3 43.1 65.8 77.5 9.5 107 181 6 409 713 1130 1639 853 00 4 9.4 1.8 19.0 4. 33.7 41.3 63.6 75.1 89.9 104 177 57 404 706 111 169 840 00 5 8.8 1.1 18.1 3.1 3.4 39.8 61.5 7.9 87.4 10 174 53 398 699 111 1618 87 00 6 8.4 11.5 17.3.1 31.1 38.4 59.7 70.9 85. 99.3 170 49 393 69 1104 1608 815 00 8 7.6 10.5 16.0 0.5 9.1 36.0 56.5 67.3 81.1 94.9 164 41 384 679 1087 1589 790 00 10 7.1 9.8 14.9 19. 7.4 34.0 53.7 64. 77.6 90.9 159 34 374 667 107 1570 765 00 16 5.9 8. 1.7 16.5 3.7 9.6 47.4 57.0 69.3 81.6 145 17 351 634 109 1518 696 00 5 4.9 6.8 10.6 13.9 0.1 5.3 41.0 49.6 60.7 71.8 130 196 3 59 973 1448 601 00 40 4.0 5.6 8.7 11.4 16.7 1.1 34.5 41.9 51.5 61. 11 17 87 538 897 1351 463 00 60 3.3 4.6 7. 9.6 14.0 17.7 9. 35.6 44.0 5.3 97.4 151 54 484 80 147 309 00 100.6 3.6 5.7 7.5 11.1 14.1 3.4 8.6 35.4 4.3 79.5 14 13 413 710 1096 07 00 160.0.9 4.6 6.0 8.9 11.3 18.8 3.1 8.6 34. 64.9 10 177 347 606 946 183 00 50 1.6.3 3.7 4.9 7. 9.1 15. 18.7 3. 7.8 53.0 83.7 146 90 510 805 1575 Notes: 1. To convert psig to kpa gauge, multiply psig by 6.895.. To convert feet to meters, multiply feet by 0.3048. 3. To convert lb air/min to grams air/sec, multiply lb air/min by 7.559. 4. To convert inches to millimeters, multiply inches by 5.4. Table 5 is reprinted by permission from ANSI/ASHRAE Standard 15-004: Safety Standard for Refrigeration Systems. Copyright 004, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. www.ashrae.org.

Table 5. Pressure Relief Discharge Line Capacity of Various Discharge Line Lengths Set (psig) (note 1) Length (feet) (note ) Discharge Line Capacity (lb/min of air, note 3) Nominal Pipe Size, NPS/schedule (note 4) 1/ 1/ 3/4 3/4 1 1 1-1/4 1-1/4 1-1/ 1-1/ -1/ 3 4 5 6 8 80 40 80 40 80 40 80 40 80 40 40 40 40 40 40 40 40 50 1 13.5 17.9 5.8 3.1 43.8 5.9 79.4 9.9 110 17 11 303 469 811 177 1847 303 50 1.4 16.5 4. 30.4 41.7 50.7 76.6 89.9 107 14 07 98 463 803 168 1836 3190 50 3 11.5 15.5.9 8.8 39.9 48.7 74.1 87. 104 11 03 93 457 796 159 186 3177 50 4 10.8 14.6 1.7 7.5 38.3 46.9 71.8 84.8 101 118 199 88 45 789 150 1816 3164 50 5 10. 13.9 0.7 6.4 36.9 45.3 69.8 8.5 98.8 115 196 84 446 78 14 1806 315 50 6 9.7 13. 19.9 5.4 35.6 43.8 67.8 80.4 96.5 11 19 80 441 775 134 1796 3139 50 8 8.9 1. 18.4 3.6 33.4 41.3 64.5 76.7 9.3 108 186 7 431 76 117 1777 3114 50 10 8. 11.3 17.3. 31.6 39.1 61.5 73.4 88.6 104 180 65 4 750 10 1758 3090 50 16 6.9 9.6 14.8 19.1 7.5 34.3 54.7 65.6 79.7 93.7 166 47 398 716 1159 1706 301 50 5 5.7 8.0 1.4 16.3 3.5 9.5 47.7 57.5 70.3 83.0 149 5 368 673 110 1635 96 50 40 4.7 6.6 10. 13.4 19.6 4.7 40.3 48.9 60.1 71. 130 199 331 616 103 1535 785 50 60 3.9 5.5 8.6 11.3 16.5 0.9 34.3 41.8 51.5 61.3 114 175 95 558 940 146 66 50 100 3.0 4.3 6.8 8.9 13.1 16.6 7.5 33.6 41.7 49.7 93.3 145 48 479 81 163 375 50 160.4 3.4 5.4 7.1 10.5 13.4. 7. 33.8 40.4 76.5 10 07 406 705 1098 105 50 50 1.9.8 4.3 5.8 8.5 10.8 18.0.1 7.5 3.9 6.6 98.7 17 340 597 940 1831 300 1 15.0 19.8 8.6 35.5 48.4 58.4 87.5 10 11 140 3 333 516 891 1404 030 350 300 13.8 18.4 6.9 33.7 46. 56.1 84.7 99.4 118 137 8 38 510 884 1395 019 3507 300 3 1.9 17.3 5.5 3.1 44.4 54.1 8. 96.7 115 133 4 33 504 877 1386 009 3494 300 4 1.1 16.4 4.3 30.8 4.7 5. 79.8 94.1 11 130 0 319 499 870 1377 1999 3481 300 5 11.5 15.6 3.3 9.6 41. 50.5 77.7 91.8 110 18 17 314 493 863 1369 1989 3469 300 6 11.0 14.9.4 8.5 39.9 49.0 75.7 89.6 107 15 13 310 488 856 1360 1979 3456 300 8 10.1 13.8 0.8 6.6 37.6 46.3 7. 85.7 103 10 07 30 478 843 1344 1960 3431 300 10 9.3 1.9 19.5 5.1 35.6 44.1 69.1 8.3 99. 116 01 95 469 830 138 1941 3407 300 16 7.9 10.9 16.8 1.8 31.1 38.8 61.8 74.0 89.8 105 186 76 443 796 184 1888 3338 300 5 6.6 9. 14. 18.6 6.8 33.6 54.1 65.3 79.7 93.9 168 53 41 751 16 1816 341 300 40 5.4 7.5 11.7 15.4.4 8. 46.0 55.7 68.4 81.0 148 5 37 691 1144 171 3097 300 60 4.5 6.3 9.8 1.9 18.9 3.9 39.3 47.8 58.9 70.0 19 199 334 630 1056 1598 93 300 100 3.5 4.9 7.8 10.3 15.1 19.1 31.6 38.6 47.8 57.0 107 166 83 544 99 145 668 300 160.8 3.9 6. 8. 1.1 15.4 5.6 31.3 38.9 46.4 87.7 137 37 463 80 146 379 300 50. 3. 5.0 6.6 9.8 1.5 0.8 5.5 31.6 37.9 7.0 113 197 389 68 1071 080 Notes: 1. To convert psig to kpa gauge, multiply psig by 6.895.. To convert feet to meters, multiply feet by 0.3048. 3. To convert lb air/min to grams air/sec, multiply lb air/min by 7.559. 4. To convert inches to millimeters, multiply inches by 5.4. Table 5 is reprinted by permission from ANSI/ASHRAE Standard 15-004: Safety Standard for Refrigeration Systems. Copyright 004, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. www.ashrae.orghydrostatic Pressure Relief of ASME Pressure Vessels

Appendix A: Remove Figures A-1 (page 38) and A- (page39) as an editorial change

Add new Appendix F: An informative appendix regarding hydrostatic pressure relief Appendix F (Informative Hydrostatic Pressure Relief Background Hydrostatic pressures can occur when liquids become confined within enclosed volumes with no gases present. For this to occur, the temperatures of such liquids must be below their boiling points. Liquids such as oil, secondary refrigerants, and subcooled primary refrigerants can become entrapped when certain components of a refrigerating system are isolated from other parts of the system by valves or other means. If there is an increase in temperature in such confined liquids, rapidly rising pressures can occur that are functions of the bulk moduli of elasticity of the liquids. While such increases in temperature and pressure can be very rapid, the corresponding rates of volume increase of the liquids are relatively low. Therefore, relief devices installed to preclude this phenomenon need not be nearly as large in flow capacity as similar devices used to protect components containing boiling liquids where mass relief is in the form of vapor. Practitioners have found that very small relief devices satisfy most requirements for hydrostatic relief found in refrigeration service. The technical literature available that quantifies such requirements, based on empirical test data, is found almost exclusively in areas of practice that are much more severe than refrigeration service. However, many authorities having jurisdiction require calculations or other evidence to justify selection and sizing of hydrostatic relief devices. In those cases, it is acceptable good engineering practice to demonstrate that a relief device having adequate capacity for an extremely severe application will certainly be adequate for less severe circumstances typically encountered in refrigeration applications. To that end, applicable methodology borrowed from more severe applications such as those found in the oil and gas industries provide a safe and conservative basis for hydrostatic relief protection in refrigeration applications. The objective is to provide adequate relief, not necessarily to determine exactly how much liquid expansion will occur. In most, if not all cases, the smallest relief valves manufactured for such purposes will have greater flow capacities than the requirements found by calculation for extremely severe circumstances. The American Petroleum Institute (API) addresses the sizing of orifices needed to relieve hydrostatic pressure as defined above in its standard, API Practice 50. This standard contains an equation for determining the areas of such orifices as stated below: where Q A 38 K d K w K v G P 1 P A = required effective discharge area, in square inches Q = flow rate, in US gallons per minute Kd = effective coefficient of discharge (0.65 for hydrostatic relief purposes) Kw = correction factor due to back pressure (1.0 if back pressure is atmosphere or valve responds only to pressure differential across its seat) Kv = correction factor due to viscosity G = specific gravity of the liquid at the flowing temperature P1 = upstream relieving pressure in psig P = total back pressure in psig (zero for discharge to atmosphere)

Q is determined by the relation: where BH Q 500 GC B = cubical expansion coefficient per degree Fahrenheit for the liquid at the expected temperature H = total heat of absorption to the wetted bare surface of a vessel, pipe or container in BTU per hour (H = 1,000 A 0.8, where A = total wetted surface in square feet) G = specific gravity of the liquid at the flowing temperature C = specific heat of the trapped fluid in BTU per lb- F Kv is determined as follows: Refer to Figure Fl below to find Kv as a function of the Reynolds number (R), which is defined by the following equation: where: 1,700 Q R U A Q = flow rate at the flowing temperature in US GPM U = viscosity at the flowing temperature in Saybolt Universal Seconds A = effective discharge area, in square inches (from manufacturers standard orifice areas) Figure F1 was reprinted by permission from Oil and Gas Journal, November 0, 1978 edition. Copyright 1978, Oil and Gas Journal. http://ogj.pennnet.com/home.cfm. Hydrostatic Pressure Relief of ASME Pressure Vessels This section pertains to vessels covered by Section VIII, Division 1, of the ASME Boiler and Pressure Vessel Code, herein referred to as ASME pressure vessels. When ASME pressure vessels contain liquid refrigerant and can be isolated from the other parts of a refrigerating system, the rules of ANSI/IIAR, paragraph 5.14 apply. However, when ASME pressure vessels contain a nonboiling liquid (i.e., a liquid whose vapor pressure at maximum normal operational, maintenance or standby conditions is less than the relief valve setting), specific requirements of the ASME Boiler and Pressure Vessel Code for hydrostatic relief valves apply: Hydrostatic relief valves protecting ASME pressure vessels must bear an ASME UV Code Symbol Stamp. (Code Case BC94-60) Hydrostatic relief valves protecting ASME pressure vessels must be certified and rated for liquid flow. (Code Case BC94-60) Any liquid pressure relief valve used shall be at least NPS 1/. (UG-18)

The opening through all pipe, fittings, and nonreclosing pressure relief devices (if installed) between a pressure vessel and its pressure relief valve shall have at least the area of the pressure relief valve inlet. In this upstream system, the pressure drop shall not reduce the relieving capacity below that required or adversely affect the proper operation of the pressure relief valve. (UG-135 (b) (1)) The size of the discharge lines leaving a hydrostatic relief valve shall be such that any pressure that may exist or develop will not reduce the relieving capacity of the pressure relief valve below that required to properly protect the vessel. (UG-135 (f)) The hydrostatic relief valve shall be capable of preventing the pressure from rising more than 10% above the maximum allowable working pressure during normal service or standby conditions. Sample calculations To illustrate how to apply these concepts and requirements, two examples of sizing hydrostatic relief valves for pressure-containing components are provided below. Example 1: Sizing a Hydrostatic Relief Valve for an ASME Pressure Vessel Determine the hydrostatic relief valve required to protect an oil cooler 10" in diameter and 1' long with 400 psig Maximum Allowable Working Pressure (MAWP). Assume oil temperature is 100 F and oil viscosity (U) is 300 Saybolt Universal Seconds at 100 F. From the oil manufacturer's data, the cubical expansion coefficient (B) is 0.00043/ F, specific gravity (G) is 0.87 and specific heat (C) is 0.5. First, determine the bare wetted external area (A) of the oil cooler, in square feet: 10.75 A dl 1 1 33.9 ft Next, determine total heat absorption (H) of the wetted bare surface of the oil cooler when exposed to maximum normal conditions: H = 1,000 A 0.8 H = 1,000 (33.8) 0.8 = 376,644 Btu/Hr. Next, determine rate of increase of the oil volume from the relation below: BH Q 500 GC 0.00043 376,644 Q 500 0.87 0.5 0.74 gpm Assume the relief valve will discharge into another part of the system having relief protection set at 300 psig. To prevent the pressure in the oil cooler from exceeding 400 psig under all conditions, the hydrostatic relief valve must be selected for 100 psi differential. A liquid-rated ASME certified relief valve is commercially available with 1/" NPT inlet and 3/4" NPT outlet. The valve s capacity at 100 psi Δp is 5.9 gpm, 35 times the oil volume rate of increase. The valve meets all ASME requirements. Per the ASME code, total inlet and outlet pressure losses may total 40 psi and still meet code requirements. Example : Sizing a Hydrostatic Relief Valve for a non-asme component Determine the orifice area required to protect an oil cooler 5" in diameter and 1' long with 400 psig MAWP. Assume oil temperature is 100 F and oil viscosity (U) is 300 Saybolt Universal Seconds at 100 F. From the oil manufacturer's data, the cubical expansion coefficient (B) is 0.00043/ F, specific gravity (G) is 0.87 and specific heat (C) is 0.5.

First, determine the bare wetted external area of the oil cooler, in square feet: 5.563 A dl 1 17.48 ft 1 Next, determine total heat absorption of the wetted bare surface of the oil cooler when exposed to maximum normal conditions from the relation: H = 1,000 A 0.8, outlined above. H = 1,000 (17.48) 0.8 = 19,98 Btu/hr. Next, determine rate of increase of the oil volume from the relation: BH Q 500 GC 0.00043 19,98 Q 0.433 gpm 500 0.87 0.5 Next, determine the viscosity correction factor (Kv) from Figure 1 and the Reynolds number (R) from the formula below: R 1,700Q U A To calculate R in this equation requires a value for A, which represents the orifice area. Interestingly, to calculate A using the primary equation requires a value for R. To solve this problem, an iterative method (trial and error) must be used. First, a starting value of A must be approximated to obtain an initial estimate of R, which can then be used in the primary equation to calculate a new value for A. Comparing this calculated value of A to the initial approximation for A will enable a even better approximation for A for the next iteration. This iterative process will quickly converge on a calculated value for A that is reasonably close to the final approximation for A. Try a 1/16" orifice having an area of 0.003068 in. 1,700 0.433 R 331 300 0.003068 From Figure Fl, Kv = 0.85 Assume Δp to another part of the system is 100 psi. The required flow area is much smaller (0.00198 in ) than the area assumed in estimating the Reynolds number (0.003068 in ). Therefore, a relief valve having a 1/16" diameter orifice is more than adequate. For a second iteration, assume a 3/64" orifice with 0.0017 in cross-sectional area. R would then become 1,700 0.433 R 445 300 0.0017 Kv = 0.85 Q A 38 K d K w K 0.433 A 38 0.65 1 0.85 v G P1 P 0.87 100 0.433 A 38 0.65 1 0.85 0.00198 0.87 100 in 0.0019 in

This area requirement is approximately 13% greater than that of the 3/64" orifice. Therefore, we can conclude that an orifice between 1/16" diameter and 3/64" would be ideal. A 1/16" orifice will be more than adequate. Inlet and Outlet Piping The ASME Boiler and Pressure Vessel (B & PV) Code requires that hydrostatic relief valve inlet piping for ASME pressure vessels must have at least the area of the pressure relief valve inlet. Since the same code requires a minimum NPS 1/" valve, the minimum inlet piping is established. Inlet piping requirements on larger hydrostatic relief valves would follow suit. On outlet piping, the B & PV Code simply requires that the relief valve discharge lines are large enough to avoid reducing the relieving capacity of the pressure relief device below that required to properly protect the vessel. For normal over-pressure protection, ASME permits overpressurization of a vessel to 10% above its MAWP. In the previous examples, the flows of liquid created by thermal expansion were very low. Consequently, outlet piping from commercially available certified ASME liquid relief valves could usually be much smaller than the nominal outlets of the valves themselves. For instance, consider the ASME vessel example with a 0.74 gpm relief requirement. The relief valve suggested for this application has a 3/4" NPT connection on the outlet. If, for example, the discharge piping is reduced to 1/" stainless steel tubing, the Reynolds number for oil having a nominal viscosity of 68 centistokes at 100 F. is less than 60 (57.9). In laminar flow, which by definition is flow at or below Reynolds numbers of 000, pressure loss to friction in psi per 100 ft of smooth pipe is given as: h f 43.3V G RD where V G R D = fluid velocity in ft/sec = specific gravity of fluid = Reynolds Number of fluid = I.D. of pipe in ft From the previous example, oil flow due to thermal expansion is 0.74 gpm or 0.1 cfm. The 1/" stainless steel tubing has a cross-sectional flow area of 1.0085 x 10-3 ft. Fluid velocity is therefore: cfm 0.1 V ft/sec 60A 601.008510-3 1.65 ft/sec Discharge piping pressure drop through the 1/" stainless tubing would therefore be: h f 43.3 V G 43.31.65 0.867 RD 57.9 0.0358 For a typical relief valve discharge pipe run of 6 ft., pressure drop due to friction would be less than 3 psi. Because ASME permits overpressurization of 10% above the MAWP of a pressure vessel, inlet and outlet losses could total 40 psi and meet ASME requirements. Therefore, hydrostatic relief valve outlet piping can be greatly reduced below the nominal outlet size of the relief valve selected in many cases. Inlet and outlet piping for hydrostatic relief valves protecting non-asme components containing incompressible non-refrigerants can be sized using identical techniques. In providing hydrostatic protection against ambient warming, 10% overpressurization above MAWP is permitted, providing the relief valve is selected at MAWP. Hydrostatic relief devices may be located anywhere on the protected component. When used to protect an ASME vessel, they must bear a UV Code Symbol. When used to protect a non-asme component, they must be listed by an approved nationally recognized testing laboratory or bear a UV Code Symbol. 49.3 psi / 100 ft

Add new Appendix G: An informative appendix on duplicate nameplates on pressure vessels

Appendix G (Informative) Duplicate Nameplates on Pressure Vessels The ASME Boiler and Pressure Vessel Code permits duplicate (or secondary) nameplates on pressure vessels. Duplicate nameplates may be desirable in certain circumstances, especially where the original nameplate may be obscured by insulation. Experience has shown that attempting to access the original nameplate for inspection through windows, removable insulation sections, stanchion mounting, etc. tends to compromise the integrity of the insulation system. Moisture ingress into the insulation system follows, with possible damage to the pressure vessel. The use of duplicate nameplates helps prevent vessel damage from inspection ports and other deliberate damage to insulation. Unfortunately, using duplicate nameplates creates the possibility that the wrong (duplicate) nameplate will be applied to a vessel. The ASME Boiler and Pressure Vessel Code specifies that the vessel manufacturer must ensure that the duplicate nameplate is properly applied. While the easiest way to accomplish this is for the manufacturer to weld the nameplate to a support or other permanent vessel appurtenance that will not be insulated, field installation is also permitted. (Some inspection authorities consider the insulation jacket as a permanent attachment to the vessel, and therefore the duplicate nameplate may be applied to the jacket.) The manufacturer s procedures for ensuring a proper match of duplicate to original must be rigorously followed. It is advisable to record the location of the original nameplate should inspection be necessary. Various inspection authorities such as State vessel inspectors may demand to inspect and/or approve the duplicate and original nameplates before insulation is applied. While many inspection bodies will accept a duplicate nameplate as evidence of ASME Code compliance for an insulated vessel, authorized inspectors may always demand to inspect the original vessel, including its nameplate. In particular, when the inspector is concerned about the physical condition of the vessel or questions the provenance of the duplicate nameplate, he or she may require the entire insulation system or any part to be removed to permit inspection. Damage to the insulation system must be promptly and professionally repaired, and due allowance should be made for the shorter service life of the repaired insulation system.

Add new Appendix H: A normative appendix based on the Appendix H from ANSI/ASHRAE 15-004 Appendix H (Normative) Allowable Equivalent Length of Discharge Piping The design back pressure due to flow in the discharge piping at the outlet of pressure relief devices and fusible plugs, discharging to atmosphere, shall be limited by the allowable equivalent length of piping determined by equations (1) or (). See Table 5 for the flow capacity of various equivalent lengths of discharge piping for conventional relief valves. where L Cr f 0.146 d ( L P fc -15 7.438110 d L fcr r P ) d 5 0 5 ln(p0 /P ) 6f ( P0 P ) d ln(p /P ) 0 500f = equivalent length of discharge piping, ft (m); = rated capacity as stamped on the relief device in lb/min (kg/s), or in SCFM multiplied by 0.0764, or as calculated in 9.7.7 for a rupture member or fusible plug, or as adjusted for reduced capacity due to piping as specified by the manufacturer of the device, or as adjusted for reduced capacity due to piping as estimated by an approved method; = Moody friction factor in fully turbulent flow (see typical values below); d ln P P0 = inside diameter of pipe or tube, in (mm); = natural logarithm; = absolute pressure at outlet of discharge piping, psi (kpa); = allowed back pressure (absolute) at the outlet of pressure relief device, psi (kpa). For the allowed back pressure (P0), use the percent of set pressure specified by the manufacturer, or, when the allowed back pressure is not specified, use the following values, where P is the set pressure: * for conventional relief valves, 15% of set pressure, P0 = (0.15 P) + atmospheric pressure; * for balanced relief valves, 5% of set pressure, P0 = (0.5 P) + atmospheric pressure; * for rupture members, fusible plugs, and pilot operated relief valves, 50% of set pressure, P0 = (0.50 P) + atmospheric pressure. Note: For fusible plugs, P is the saturated absolute pressure for the stamped temperature melting point of the fusible plug or the critical pressure of the refrigerant used, whichever is smaller, psi (kpa) and atmospheric pressure is at the elevation of the installation above sea level. A default value is the atmospheric pressure at sea level, 14.7 psi (101.35 kpa). Typical Moody friction factors (f) for fully turbulent flow: Tubing OD (in.) DN ID (in.) f 3/8 8 0.315 0.0136 ½ 10 0.430 0.018 5/8 13 0.545 0.01 ¾ 16 0.666 0.0117 7/8 0 0.785 0.0114 1 1/8 5 1.05 0.0108 1 3/8 3 1.65 0.0104 1 5/8 40 1.505 0.0101 Piping NPS DN ID (in.) f 1/ 15 0.6 0.059 3/4 0 0.84 0.040 1 5 1.049 0.05 1 1/4 3 1.380 0.009 1 1/ 40 1.610 0.00 50.067 0.0190 1/ 65.469 0.018 3 80 3.068 0.0173 4 100 4.06 0.0163 5 15 5.047 0.0155 6 150 6.065 0.0149 Appendix H is reprinted by permission from ANSI/ASHRAE Standard 15-004: Safety Standard for Refrigeration Systems. Copyright 004, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. www.ashrae.org.

1001 North Fairfax Street Suite 503 Alexandria, VA 314 (703) 31-400 Fax: (703) 31-0065 www.iiar.org