Emergency Eyewash & Shower Testing Program

Similar documents
EMERGENCY EYEWASH & SHOWERS

Laboratory Safety Guideline Emergency Eyewash and Safety Showers

Cal Poly Eye Wash and Safety Shower Inspection Program June 20, 2018

1.0 PURPOSE 2.0 SCOPE 3.0 DEFINITIONS. ANSI: American National Standards Institute. CCC: Chemical Control Centre

Design Requirements for Eyewash and Safety Shower Units

Environmental Health & Safety Policy & Procedure #35

EMERGENCY WALL MOUNTED HAND OPERATED DELUGE SHOWER

Emergency Shower & Eyewash. Training Guide

EMERGENCY EYEWASH STATIONS & SAFETY SHOWERS GUIDELINES

Standards of Practice Emergency Shower/Eyewash Installation, Use, Testing & Maintenance

ENVIRONMENTAL HEALTH AND SAFETY STANDARD OPERATING PROCEDURES

PEDESTAL MOUNTED EMERGENCY EYE & EYE/FACE WASH

EYE WASH STATIONS & SAFETY SHOWERS GUIDELINES

EMERGENCY EYEWASH & SHOWER STATION TRAINING AND MAINTENANCE REQUIREMENTS

GUARDIAN EQUIPMENT Emergency Eye Wash and Shower Equipment. ANSI Z358.1 Compliance Checklist

ANSI Z Compliance Checklist

ANSI / ISEA Z Compliance Checklist

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

ANSI / ISEA Z Compliance Checklist

WALL MOUNTED EMERGENCY EYE & EYE/FACE WASH HAND OPERATED

Compressed Gases Safety Program

BY ORDER OF THE SECRETARY OF THE AIR FORCE AIR FORCE OCCUPATIONAL SAFETY AND HEALTH STANDARD SEPTEMBER Safety

Model Portable Eyewash

Installation. Heat Trace Combination Drench Shower and Eyewash Unit (includes 120 V and 208/240 V versions) S19-304GA

Installation. S19-300T (top supply) S19-300B (bottom supply)

8320 AXION MSR COMBINATION EYE / FACE WASH & DRENCH SHOWER

Control of Hazardous Energy Lockout / Tagout Program

(g)(1) Space about electric equipment.

TEMPLE UNIVERSITY ENVIRONMENTAL HEALTH AND RADIATION SAFETY

Common Discrepancies Uncovered on ADCI Diving Contractor & Training Program Audits

Hazardous Energies Control and Lockout/Tagout Program

Hazard Communication Program

CONTROL OF HAZARDOUS ENERGY LOCKOUT/TAGOUT PROGRAM

Hazardous Materials Management. Presented by. James E. Roughton, MS, CSP, CRSP, CHMM.

Environmental Health & Safety

Installation S Gallon Tank (ASME rated) with Eyewash and Hose Spray

SOP #: Pressure Vessels

TEMPLE UNIVERSITY ENVIRONMENTAL HEALTH AND RADIATION SAFETY

Installation S S19-788LHS

This guidance applies to those individuals who perform acid cleaning or chemical treatment aboard Marine Depot Maintenance Command Yermo CA.

SAFETY POLICY AND PROCEDURE MANUAL All Euramax Subsidiaries. Number K-3.0 Welding Safety Procedures

MARIPOSA COUNTY LOCKOUT/TAGOUT PROGRAM

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

Pipe Thread Connection 1/2 inch NPT. Friction Loss Refer to Figure 3

SAFETY EMERGENCY SAFETY SHOWERS AND EYEWASH STATIONS TABLE OF CONTENTS 1. INTRODUCTION SCOPE & PURPOSE DEFINITIONS...

LOCKOUT/TAGOUT PLAN August 2015

AED Program 2017 January 2017

TECHNICAL DATA Q= C. Table 1 - Specifications

CONFINED SPACE ENTRY PROGRAM

HYDROGEN PEROXIDE Railcar Unloading by Self-Priming Pump Technical Data Sheet

The University of Georgia Automated External Defibrillator (AED) Program Guidelines

6A.004 SCBA MAINTENANCE. Policy Number. Page 1 of 5 SCOPE

Compressed Gas Cylinders - Guideline

EmErgEncy EquipmEnt EyE and skin rinsing

"SAFETY SHOWERS AND EYE WASHES"

Lockout Tagout Policy

THE OSHA LOCK-OUT/TAG-OUT STANDARD

Energy Control Procedures Lockout/Tagout 29 CFR

8122H AXION Drench / Safety Shower

HYDROVEX TTT Membrane Flow Regulator

Bermad Pressure Reducing. Model: 42T

UC Irvine Environmental Health & Safety

WORKPLACE SAFETY INSPECTIONS TABLE OF CONTENTS INTRODUCTION...2 OBJECTIVE...2 REFERENCES...2 PREREQUISITES...2 PRECAUTIONS...2 CHECKLISTS...

1.0 Scope and Application. 2.0 Definitions. Cal Poly Risk Management Confined Space Program Page 1

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124

PROCEDURE NUMBER: PRC-SAF-16 (Preparation of Piping and Equipment for Repair) Page 1 of 10 Rev. 1.4 Date: 10/17/2016 Rev. 2.

TECHNICAL DATA. Q= Cv S

Welding & Cutting Written Program

LOCKOUT/TAGOUT PROGRAM

Central Washington University

Model: 43T. Bermad Pressure Relief Valve

HYDRANT/WATER POINT INSPECTION AND MAINTENANCE

Lockout/Tagout Program

WARNING: FOR OUTDOOR USE ONLY

Environmental Standard Operating Procedure Originating Office: MCAS Yuma Environment Department

SECTION BUTTERFLY VALVES

SPECIFICATIONS - DETAILED PROVISIONS Section Butterfly Valves C O N T E N T S

Compressed Gases and Cryogens

GREIG FILTERS, INC. OPERATION MANUAL

INSTALLATION MANUAL Matheson Tri-Gas Cabinet Enclosures

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT

HIGH-IMPACT. Leader s Guide

Page: 7/15/2009. Energy control procedures Use of lockout/tagout equipment to ensure safe work practices.

CHAPTER 9 GENERAL WORKPLACE SAFETY

THE TLC COMPANIES. Self Inspection Program. Self Inspection. Program. Revised 12/13/2002 DC00026

Fire Apparatus Operator: Pumper

Isolation Lockout and Tagging

Lockout/Tagout - Control of Hazardous Energy Program

Hydrogen Cyanide (HCN)

TECHNICAL DATA. Q = C v P S

Title: Swimming Pool Chlorination Operations

A Guide to Eyewash and Safety Shower Facilities

Standards of Practice Personal Protective Equipment

Lockout / Tag out Program

Carter Option X Valve connector assembly. Maintenance manual

HEALTH AND SAFETY PROGRAM 201 HOT TAP PERMIT/FILLET WELD REPAIRS

LABORATORY HAZARD AWARENESS TRAINING

Title: Recreational Facilities 3 - Athletic Facilities

Laboratory Inspection Checklist

Operating Manual CBA Series Cascade Breathing Air Assemblies

Transcription:

Emergency Eyewash & Shower Testing Program Summary: The purpose of this program is to ensure that safety eyewashes and showers supply clean, potable water and are in proper working order. This program applies to all emergency eyewash and shower units in university buildings. Annual flow rate testing and monthly sanitation testing of the emergency equipment will be documented. 1. Program Description 2. Scope 3. Definitions 4. Responsibilities 5. Program Components 6. Reporting Requirements 7. Training Requirements and Competency Assessment 8. Information and External References 1. Program Description The purpose of this program is to ensure that safety eyewashes and showers supply clean, potable water and are in proper working order. This program defines guidelines for inspection, testing and maintenance of emergency eyewash and shower equipment. 2. Scope This program applies to all emergency eyewash and shower units in university buildings. Annual flow rate testing and monthly sanitation testing of the emergency equipment will be documented. 3. Definitions American National Standards Institute (ANSI) : is a non-profit organization that coordinates the standardization and conformity assessment systems in the United States. Emergency Shower : a unit that cascades water over the whole body. Emergency Units or Equipment : general term for emergency eyewash, eye/face wash, shower, drench hose and combination units. Eyewash : a unit that flushes water specifically to the eyes. Eye/Face Wash : device that flushes both eyes and face. Combination Units : or Safety Stations, units that consist of both the emergency shower and an eye/face wash. Drench Hose Units : are hand-held units that reach to areas of the face and body that are inaccessible to fixed emergency units. Stay-Open Valve : a valve that manually opens and closes the emergency units. 4. Responsibilities 4.1 FACILITIES MANAGEMENT (FM) Provide program support for FM maintained facilities and assist EH&S in identifying units in non-fm support buildings. Perform monthly flush and verify proper operation of emergency eyewash and shower units throughout the university. Conduct annual flow rate testing and compliance assessment for each emergency unit on campus. Strive to ensure that each unit is appropriately tagged for documentation of location and testing requirements. Documentation of all testing will be maintained by Facilities Management. Work with EH&S to maintain an accurate inventory of these units. 4.2 ENVIRONMENTAL HEALTH AND SAFETY 4.3 USERS 5. Program Components Provide general oversight of this program. Work with Facilities Management to maintain an accurate inventory of these units. Know the location of the emergency units in the building and ensure that the emergency units are clear of obstructions. Check that emergency units are being flushed monthly by reviewing the unit tag. Contact Facilities Management if monthly flush tests are not documented on the tags. 5.1 General Requirements 5.1.1 Application: Emergency eyewash and shower units must be installed in work areas where there is high potential for accidents involving corrosive, irritant or toxic substance absorption through skin and eyes. 5.1.2 Location and Placement: The emergency eyewash and shower unit must be placed in a location no more than a maximum of 10 seconds travel time for an injured person through an unobstructed pathway. Specific placement requirements are listed below: Eyewash and eye/face wash units: Nozzles must be positioned between 33-45 inches from the floor. Also, a minimum distance of 6 inches from the nearest obstruction is required.

Drench hose units: The head of the hose must be placed 33-45 inches from the floor with a clearance of 6 inches from the wall. Emergency Showers: The distance of showerhead to the floor must be between 82-96 inches. Actuator height must be no higher than 69 inches from the floor. Also showers must have a clearance of 48 inches along the side and 30 inches across (creating a surface area of 10 square feet around the shower unit). Combination Units or Safety Stations: Refer to the dimensions above for distance and clearance of the eye/face wash and shower units. 5.1.3 Correction of Deficiencies. If the emergency unit is not operating to specifications, employees in the area must initiate appropriate action. Notify your supervisor to implement appropriate tagging of unit as DO NOT USE, if applicable. The supervisor must notify Facilities Management for repair or replacement. 5.2 Inventory and Equipment Identification: A tag with identification must be placed on or near the emergency unit at all times. Facilities Management testers must sign their initials and date on tags (indicate monthly testing dates with a black marker and annual testing date with a red marker). These tags will inform users of the most recent inspection and testing of the emergency units. Also, the tags will assure the user that the unit is safe and ready to use. Facilities Management should replace missing tags as soon as possible. Location of units will be identified with a highly visible sign. Failed tests will be corrected immediately. Immediate corrective action must be performed when deficiencies are noted. If deficiencies cannot be immediately corrected, FM must tag the unit DO NOT USE, if applicable. 5.3 Testing by Facilities Management 5.3.1 Eyewash and Eye/Face wash units Monthly Flush Test Visual inspection of the unit. Look for leaks or pipe damage and proper placement of protective covers. This should be done prior to testing in order to avoid further damage to the unit and risk of injury to users. Ensure that the unit is free of any obstructions. Activate unit. Ensure that the water flow is continuous, evaluate that the unit can maintain flow for 15 minutes, and is not injurious to the user's eye or face. Valve actuator must activate water flow in one second or less. Valve actuator must stay on unless manually turned off and must activate water flow in one second or less. Controlled flow of flushing fluid must be provided to both eyes simultaneously. The unit must be capable of delivering not less than 0.4 gallons per minute of flushing fluid for 15 minutes. Sanitize water supply through monthly flushing. In order to relieve the unit of any rust and other pipe buildup, flush the unit until the water runs clear. Annual Flow Test 5.3.2 Drench Hose Units Flow rate of the device will be conducted annually. Following established procedures let the water run for one minute to collect at least 1.5 liters (0.4 gallon) of water for eyewash alone and 11.4 liters (3.0 gallons) for an eye/face wash unit. Monthly Flush Test Visual inspection of the unit. Look for leaks, hose damage, and proper placement of protective covers. Ensure that the unit is free of any obstructions. Activate unit. Ensure that the water flow is continuous, evaluate that the unit can maintain flow for 15 minutes, and is not injurious to the user's eye or face. Valve actuator must activate water flow in one second or less. Valve actuator must stay on unless manually turned off and must activate water flow in one second or less. Controlled flow of flushing fluid must be provided to both eyes simultaneously. The unit must be capable of delivering not less than 0.4 gallons per minute of flushing fluid for15 minutes. Sanitize water supply through monthly flushing. In order to relieve the unit of any rust and other pipe buildup, flush the unit until the water runs clear. Annual Flow Test Flow rate of the device will be conducted annually. Following established procedures let the water run for one minute to collect at least 1.5 liters

5.3.3 Emergency Showers (0.4 gallon) of water for eyewash alone and 11.4 liters (3.0 gallons) for an eye/face wash unit. Document test with dates and initials on unit tag. Facilities Management is responsible to ensure an Monthly Flush Test Visual inspection of the unit. Look for leaks, pipe damage, and proper placement of protective covers. This should be done prior to testing in order to avoid further damage to the unit and risk of injury to users and yourself. Also inspect each shower if they are in compliance with the ANSI Z358.1 requirements. Ensure that the unit is free of any obstructions. Activate unit. Ensure that the water flow is continuous, evaluate that the unit can maintain flow for 15 minutes. Valve actuator must stay on unless manually turned off and must activate water flow in one second or less. Controlled flow of flushing fluid must be provided to both eyes simultaneously. The unit must be capable of delivering not less than 20 gallons per minute of flushing fluid. Sanitize water supply through monthly flushing. In order to relieve the unit of any rust and other pipe buildup, flush the unit until the water runs clear. Annual Flow Test Flow rate of the device will be conducted annually. Let the water run for one minute to collect at least 75.7 liters (20 gallons) of water. 5.3.4 Combination Units (Safety Stations) 6. Reporting Requirements Conduct a separate inspection of the emergency shower and the eye/face wash units. Apply procedures for each unit in testing safety stations (Sections 5.2.1 and 5.2.3). Single documentation will apply to the eyewash and shower combination units. Emergency eyewash and shower testing log must be maintained by Facilities Management and kept at a central location, i.e. Facilities Management Administration, for a period of three years. 7. Training Requirements and Competency Assessment Facilities Management employees will receive work unit specific training on the proper procedure for maintaining minimum performance requirements for eyewash and shower equipments. 8. Information and External References The California Code of Regulations (CCR) Title 8, Section 5162 ANSI Standards Z358.1 1998 Document Initiator: Belinda Manalac Rev.: 1/2004 University of California, Irvine Environmental Health & Safety 4600 Bison Avenue, Irvine, CA 92697-2725 (949) 824-6200, Fax (949) 824-8539 Copyright@2003