Tanker Fill Tests. Evaluating Direct Fill Lines DeKalb County, Alabama. November 16, Tests DeKalb County, AL

Similar documents
Evaluating 2-1/2 Direct Fill Lines Colton, New York

Chapter 14 Water Shuttle Operations

PROPERTY INSURANCE ASSOCIATION OF LOUISIANA

TurboDraft Fire Eductor

TurboDraft. Fire Eductor Operating Instructions.

Essentials of Fire Fighting

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised

Developed by Engineer Ben Wynkoop, Lieutenant Randy Stuart, and Firefighter Alex Klinger September 2011

Varying pump capacity affects the required hoseline diameter

The Evaluator shall ask the Apparatus Driver/Operator questions regarding the mechanical systems and size of the apparatus.

then the work done is, if the force and the displacement are in opposite directions, then the work done is.

Essentials of Fire Fighting 6 th Edition Firefighter I

MANUAL FLOW CONTROL 2-1/2" - 18" QUICKSET FLOW CHART

Cozumel Turbodraft. Operational Considerations

Des Plaines Fire Dept. Engineer Program

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2014 Edition)

PHILADELPHIA FIRE DEPARTMENT HIGH PRESSURE FIRE HYDRANT SYSTEM PFD TRAINING MANUAL SUPPLEMENT ENGINE PRACTICES SUPPLEMENT 101 PAGE 1

INSTRUCTOR GUIDE REFERENCES: PUMPING APPARATUS DRIVER/OPERATOR HANDBOOK, FIRST EDITION, IFSTA

Air Eliminators and Combination Air Eliminators Strainers

FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program

Flow Material Length. Weight GPM LPM. Style 3095

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions

Developed by Lt. Randy Stuart Eng. Ben Wynkoop, and FF. Alex Klinger in Sept 2011

Apparatus Driver/Operator Evaluation Form Rosenbauer Tanker:

PRODUCT INFORMATIONAL BULLETIN

KILGORE FIRE DEPARTMENT

SKYBOX USER GUIDE EMERGENCY ULTRAFILTRATION PACKAGE. The trusted choice for rapid response potable water solu4ons SKYBOX

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller.

Pumping Systems for Landscaping Pumps, Controls and Accessories. Mark Snyder, PE

USER GUIDE EMERGENCY PUMP KIT ULTRAFILTRATION ULTRAFILTRATION SYSTEMS. safe drinking water ULTRAFILTRATION UNIT FOR USE WITH:

Apparatus Operator Refresher Training Program

CONTINENTAL NH3 PRODUCTS PRODUCT CATALOG

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

The most common terms rating air flow capacity are ICFM, FAD, ANR, SCFM or nl/min

FIREGROUND HYDRAULICS

Pumping Apparatus Driver/Operator Apparatus Testing. Chapter Test. Directions: Write the correct letter on the blank before each question.

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out

Driver Operator Pumps: Basic Pump Operations

Atlantic County Tender Task Force B Bravo Division When Atlantic County Tender Task Force B is required the following procedure should be followed:

DW Module 8: Distribution Answer Key

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2009 Edition)

Galva Fire Department SOP

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

III. Identify the initial installation requirements for standpipe systems

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

HYDROVEX TTT Membrane Flow Regulator

CHAPTER 3 : AIR COMPRESSOR

OBSOLETE DESIGN DATA FOAM MAKER APPLICATION

A T JUNIPER (LIVERPOOL) Ltd. Juniper 2x25 Gallon Multi-Engine Compressor Washing Rig Part No. JMP/CFM56/D/4777/C400

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

ABRASIVE REGULATOR II

Irrigation System Winterization and Pressurization Procedures

Upon completion of this unit of study, the student should be able to: 1. Identify the parts of a water distribution system.

ABRASIVE REGULATOR II

Idaho Fire Service Technology Pumping Apparatus Driver/Operator Skill Sheet: 1

OPERATING MANUAL LO-CROSS-FLOW CF M

Water Hammer In Irrigation Systems 1

CASH VALVE TYPE KP BACK PRESSURE VALVES

Model 420-HY Pressure Regulating Hydrant Valve

Type , , S2.20 Specialized test procedure Procedure for testing LPG bulk meters using a vapour displacement prover

STIH) Technical Information Accessories for STIHL cut-off machines / drills. 1. New pressurized water tank

1 Exam Prep. Tabs and Highlights

Geotech 1.66 Reclaimer Installation and Operation Manual

Chapter 9 System Design Procedures

Geotech 3.5 Reclaimer Installation and Operation Manual

Water Supply for Suburban and Rural Firefighting

MEDICAL EQUIPMENT CATALOG

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company

Calculations of hydraulic resistance of simple pipelines for liquid viscous and non-newtonian products.

AirCannonPlans.Com. High Powered Water Cannon

User Manual for the Mars Calibration Bench

Chapter 16 Test. Directions: Write the correct letter on the blank before each question.

Driver Operator Pumps: Water Supplies. 2 Skills Total. NFPA 1002, Standard for Driver Operator Professional Qualifications, 2014 Edition

Pump Stages. By Tom Murray

Water Thiefs APPLIANCES APPLIANCES WATER THIEFS

VT-0017 CWH OVERVIEW. intended provide PARTS NEEDED. a cryogenic tank. avoid gas from. proper PPE tanks & testing. LNG. Review.

Dry Hydrants. The installation of a non-pressurized pipe system into local water sources provides a ready means of supplying water to fire engines.

Air Amplifiers & SYSTEMS

Chapter 10 Fluid Power Pneumatics (gas) & Hydraulics (liquid)

SEMI FIXED/PORTABLE LINE PROPORTIONERS SLP NPR270

Models 106-RF / 206-RF Rate of Flow Control Valve

STREAMLINE SHOP SERIES MODEL 30040V OPERATION & PARTS MANUAL

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes.

WLPGA East African Summit

Livewell/Baitwell Pumps. Livewell/Aerator

CRYOGENICS & LNG Application Guide

Apparatus Operator/Pumper

KJ4000 Operating Instructions & Parts Manual NSN

Storage and Pre-planning Considerations

Vertical and Horizontal Bladder Tanks

Geotech 1.66 Auto-Reclaimer Installation and Operation

Geotech 1.66 Auto-Reclaimer

WaterSense Specification for Spray Sprinkler Bodies. Version 1.0

SECRETARY OF THE AIR FORCE 17 APRIL 2000 LOADMASTER MAFFS CHECKLIST. Summary of Revisions: Redundant pages removed.

All information correct as of 25 th September 2013 and subject to change without notice. 6 inch HURRICANE modular dredge equipment operations manual.

DESIGN DATA. Dry 105a. September 5, 2008

vanishing water how to use the table: Choose the stream width Choose the stream length based on the gravel depth

2.5 & 5.0 GALLON PRESSURE TANKS

Gas Absorption Draft Standard Operating Procedure

Transcription:

www.gotbigwater.com Tanker Fill Tests Evaluating Direct Fill Lines DeKalb County, Alabama November 16, 2008

Overview On November 15 th and 16 th, 2008, the DeKalb County (AL) Association of Fire Departments hosted a Rural Water Supply Operations Seminar and Drill presented by GBW Associates, LLC of Westminster, Maryland. During the drill, it became obvious that all of the tankers were hampered in their fill times when using their 2-1/2- inch direct fill lines. After the water shuttle drill on second day of the seminar was over, five tankers were tested using various fill methods in an effort to show which methods worked best in reducing fill times. The results of those tests are documented in this presentation.

The Tankers Adamsburg Tanker 1 2007 Southern Fire tanker 2,500 gallon tank Waterous 1,250 gpm pump Three, 10-inch square dumps (rear and two sides) Two, 3-inch direct fill lines on rear of tank. Each equipped with a ¼-turn ball valve as the control mechanism.

The Tankers Aroney Engine 3 2007 Blue Grass tanker 3,000 gallon elliptical tank Darley 1,250 gpm pump 10-inch square dump (rear) One, 2-1/2-inch direct fill line with a ¼-turn ball control valve and one, 4- inch direct fill line with a gate vale. Both fills are on the rear of the tank.

The Tankers Dogtown Tanker 1 Converted fuel truck 1,400 gallon tank 250 gpm pump 10-inch square dump (rear) One, 2-1/2-inch, over-thetop, direct fill line on the rear of the tank. The fill line is equipped with a ¼- turn ball valve as the control mechanism.

The Tankers Fyffe Engine 4 2008 KME 1,800 gallon tank Hale 1,250 gpm pump 10-inch square dump (rear) Two, 2-1/2-inch direct fills on the rear of the tank each are outfitted with ¼-turn ball valves as its control mechanism.

The Tankers Hammondville Truck 1 1998 KME 1,500 gallon tank Hale 250 gpm pump 10-inch square dump (rear) Two, 3-inch direct fills on the rear of tank each equipped with a ¼-turn ball valve as its control mechanism.

The Problem All five of the tankers had small, 2-1/2inch direct fill lines with a 2-1/2-inch, ¼-turn ball valve as their control mechanism. Fortunately, one of the tankers (Aroney E3) had a 4-inch direct fill line in addition to a 2-1/2-inch direct fill. The small, direct fill lines seemed to result in personnel wanting to connect 2-1/2-inch hose to the inlets. During the course of the water supply drill, the use of 2-1/2-inch hose to fill the tankers resulted in very slow fill times when compared with how fast the tankers could dump.

2-1/2-inch Direct Fills Hammondville Truck 1 Tanker 4 Fyffe Engine 4 Tanker 35 Aroney Engine 3 Tanker 88 Dogtown Tanker 1 When used with 2-1/2-inch hose, these direct fills hampered fill times during the water supply drill. Engine/Tanker 44 Adamsburg Tanker 1

The Hypothesis Using 4-inch hose instead of 2-1/2-inch hose to fill a tanker will improve the rate at which that tanker can be filled even when using a 2-1/2- inch direct fill line.

The Test Set-up Fyffe Engine 2 (2,000 gpm) was used to pump the water needed for the tests. The engine was connected to a fire hydrant and a 5-inch supply line was taken into the pump from the hydrant s steamer outlet. Because the hydrant was limited in its operating pressure, a 3-inch line was run from one of the hydrant s 2-1/2-inch outlet to an intake on the pump. This improved the overall available water.

The Test Set-up Fyffe Engine 2 discharged water to a 100-ft section of 5-inch hose finished off with a 5 x 2-1/2 x 2-1/2 gated wye. Three tests were run with each tanker using a 50-ft length of 2-1/2-inch, a 50-ft length of 3-inch, or a 100-ft length of 4-inch hose to fill through the direct fills.

Establishing Constants In order to collect comparable data, a few constants had to be established. When pumping to the gated wye, Fyffe E2 would always maintain a discharge pressure reading of 75 psi with water flowing. When connecting the 4-inch hose to the 2-1/2 direct fills, a 4 x2-1/2 adaptor would always be used. The hose lines used for filling would always be 50-ft in length from the wye to the direct fill inlet except when using 4-inch hose those would always be 100-ft in length. All tankers were completely empty before being filled each time.

Test Results: Adamsburg Tanker 1 Dual, 2-1/2 fill hoses connected to the 2-1/2 direct fills 3 minutes, 2 seconds 824 gpm Dual, 3 fill hoses connected to the 2-1/2 direct fills 2 minutes, 32 seconds 987 gpm Single, 4 fill hose connected to the 2-1/2 direct fill 2 minutes, 29 seconds 1007 gpm A 22% improvement over dual, 2-1/2 hoses! 2-1/2-inch hose 4-inch hose

Test Results: Aroney Engine 3 Single, 2-1/2 fill hose connected to the 2-1/2 direct fill 3 minutes, 41 seconds 814 gpm Single, 3 fill hose connected to the 2-1/2 direct fill 3 minutes, 31 seconds 853 gpm Single, 4 fill hose connected to the 2-1/2 direct fill 2 minutes, 57 seconds 1017 gpm A 25% improvement over a single, 2-1/2 hose! 3-inch hose 2-1/2-inch hose 4-inch hose

Test Results: Dogtown Tanker 1 Single, 2-1/2 fill hose connected to the 2-1/2 direct fill 2 minutes, 51 seconds 491 gpm Single, 3 fill hose connected to the 2-1/2 direct fill 1 minutes, 55 seconds 730 gpm Single, 4 fill hose connected to the 2-1/2 direct fill 1 minutes, 20 seconds 1050 gpm A 113% improvement over a single, 2-1/2 hose! 3-inch hose 4-inch hose

Test Results: Fyffe Engine 4 Dual, 2-1/2 fill hoses connected to the 2-1/2 direct fills 1 minutes, 49 seconds 991 gpm Dual, 3 fill hoses connected to the 2-1/2 direct fills 1 minutes, 31 seconds 1187 gpm Single, 4 fill hose connected to the 2-1/2 direct fill 1 minutes, 25 seconds 1271 gpm A 28% improvement over dual, 2-1/2 hoses! 3-inch hose 2-1/2-inch hose 4-inch hose

Test Results: Hammondville Truck1 Dual, 2-1/2 fill hoses connected to the 2-1/2 direct fills 1 minutes, 30 seconds 1000 gpm Dual, 3 fill hoses connected to the 2-1/2 direct fills 1 minutes, 27 seconds 1034 gpm Single, 4 fill hose connected to the 2-1/2 direct fill 1 minutes, 11 seconds 1268 gpm A 27% improvement over dual, 2-1/2 hoses! 3-inch hose 2-1/2-inch hose 4-inch hose

Summary It was demonstrated with all five tankers that 4 hose is clearly a better choice to use for filling tankers when given the choice between using 2-1/2, 3, or 4 hose. Even when the direct fill piping is 2-1/2, 4-inch hose is still a better choice.

Summary While it may appear that only a minute or so was shaved off of each fill time during these tests, in a tanker shuttle operation, this shaved time means more trips can be made thus more water hauled and thus a higher, total delivery rate.

This program was developed by GBW Associates, LLC 2008 No part may be used or copied without expressed written consent. For more information contact us at thebigcamel@gotbigwater.com