Date f Issue: 06/01/2015 Page 1 f 5 PA-65-x Multi-Range Air Differential Pressure Transmitter Features: Benefits: Field selectable multi-ranges Field selectable multi-utput Simple 5 step set-up LCD Display Duct fixing kit included IP65 Husing Lng term stability Technical Overview The PA-65-x range f multi-cnfigurable pressure sensrs are designed fr differential pressure measurements f air and ther neutral gases. The unit is especially suited fr measurement and cntrl in HVAC applicatins. The PA-65-x pressure transducers sense differential r gauge static) pressure and cnvert this pressure difference t a prprtinal electrical utput fr either field selectable unidirectinal r bidirectinal pressure ranges. The PA-65-x series is ffered with field selectable ranges and analg utputs f 0-5Vdc, 0-10Vdc, r 4-20mA. The measurement cell uses an advanced design f capacitive element t ensure excellent linearity and zer stability. The differential pressure t be measured induces a mvement f the stainless steel diaphragm which is cnverted t an electrnic utput signal by a capacitance measurement and a unique electrnic circuit. Tel: +44 0) 1732 861200 - E-mail: sales@sntay.cm - Web: www.sntay.cm 2012 Sntay Limited. All rights reserved
Date f Issue: 06/01/2015 Page 2 f 5 Specificatin: Accuracy RSS* at cnstant temp) ± 1.00% fsd Linearity BFSL) ± 0.98% fsd Hysteresis ± 0.20% fsd Repeatability ± 0.10% fsd Thermal effects** Cmp. range 0 t 50 C 32 t 122 F) Zer/span shift 0.054%FS/ C 0.03%FS/ F) Overpressure 68kPa 10 psi) Lng term stability 2% FS/yr max. Pressure cnnectins Push fit fr 6mm tube Output: Current 4-20mA, lad = 0 t 800 Vltage 0-10Vdc /p impedance 300 ) Pwer supply: Current utput 13-30Vdc Vltage utput 13-30Vdc r 18-24Vac Speed f reactin selectable): Slw 6 sec. Off 0.3 sec. Fast 1.5 sec. Nrmal 3 sec. Electrical Cnnectins Screw terminals fr 1.5mm² max. Optinal static prbe 196 Diaphragm Stainless steel 304 Husing: Material ABS flame retardant type VO) Dimensins 116 x 106 x 52mm Ambient: Temp RH Prtectin: Snap-shut lid Cuntry f rigin 0-50 C 32-122 F) 0-85% nn-cndensing IP54 IP65 see page 3 nte 7) UK Part Cdes: PA-65-0 Uni-directinal 0-50, 0-100, 0-150, 0-200Pa 0-0.2, 0-0.4, 0-0.6 & 0-0.8 Bi-directinal ±50, ±100, ±150, ±200Pa Selectable utput 0-5Vdc, 0-10Vdc r 4-20mA PA-65-1 PA-65-2 Uni-directinal 0-250, 0-500, 0-750, 0-1000 0-1, 0-2, 0-3 & 0-4 Bi-directinal ±250, ±500, ±750, ±1000Pa Selectable utput 0-5Vdc, 0-10Vdc r 4-20mA Uni-directinal 0-750, 0-1500, 0-2250, 0-3000 0-3, 0-6, 0-9 & 0-12 Bi-directinal ±750, ±1500, ±2250, ±3000Pa Selectable utput 0-5Vdc, 0-10Vdc r 4-20mA Fr ptins add suffix t the partcde at extra cst): -S Static pressure prbe Accessries DFK Additinal duct fixing kit TEE Tee piece pack f 10) PA-TUBE-8MM PVC tube, 30m 98.5 ft) reel A 'duct fixing kit' is supplied with the PA-65x cnsisting f 2m f 6mm i/d plastic tubing, 2 x pitt tubes, 4 x fixing screws. * RSS f Nn-linarity, nn-repeatility & hysteresis ** Units calibrated at nminal 21 C 70 F) The prducts referred t in this data sheet meet the requirements f EU Directive 2004/108/EC & RHs directive 2011/65/EU Tel: +44 0) 1732 861200 - E-mail: sales@sntay.cm - Web: www.sntay.cm 2012 Sntay Limited. All rights reserved
Date f Issue: 06/01/2015 Page 3 f 5 Cnnectins: Antistatic precautins must be bserved when handling these sensrs. The PCB cntains circuitry that can be damaged by static discharge. 1. If the sensr is t be munted utside, it is recmmended that the unit be munted with the cable entry at the bttm. If the cable is fed frm abve then int the cable gland at the bttm, it is recmmended that a rain lp be placed in the cable befre entry int the sensr. 2. In a suitable lcatin, drill tw hles at 92mm and fix the husing with apprpriate screws. 3. Release the snap-fit lid by gently squeezing the lcking tab and feed the cable thrugh the waterprf gland & terminate the cres at the terminal blck see belw fr details). Leaving sme slack inside the unit, tighten the cable gland nt the cable t ensure water tightness. 4. Pwer the unit, depending utput signal type. a) 4-20mA; +EXC 13-30Vdc nly COM 4-20mA utput +OUT N cnnectin b) 0-5Vdc r 0-10Vdc; +EXC 13-30Vdc r 18-24Vac COM Cmmn 0V +OUT 0-5Vdc r 0-10Vdc utput ZERO / CONFIG +EXC COM +OUT 5. Select the pressure type, pressure range, utput type and respnse time, see page 4 fr detailed infrmatin. 6. Push the pressure tubing nt the pressure prts n the unit. Ensure that the Hi and L prts have been crrectly identified. 7. Snap shut the lid after the cnnectins have been made if IP65 prtectin is required, secure the lid with tw screws prvided. 8. It is recmmended that screened cable be used and that the screen shuld be earthed at the cntrller nly. Care shuld be taken nt t lay cntrl signal wiring in clse prximity t pwer r ther cables which may prduce significant electrmagnetic nise. CAUTION The PA-65x will be damaged if subjected t excessive pressure. D NOT test the unit by blwing int the inlet prts. Zer & Span Adjustment: Hlding the Zer /Cnfig buttn dwn fr 2 secnds will d a zer r span peratin depending n the differential pressure being at zer pressure r if the diff pressure is near full range pressure it will d a span adjust. If the buttn is held dwn fr 5 sec the menu will be entered. Tel: +44 0) 1732 861200 - E-mail: sales@sntay.cm - Web: www.sntay.cm 2012 Sntay Limited. All rights reserved
Date f Issue: 06/01/2015 Page 4 f 5 Prgramming Quick-start Guide: When the unit is first pwered up unit will tggle thrugh the fllwing: Pressure range setting Analg utput setting Unit will then revert back t nrmal perating mde. All parameters are set in the fllwing sequence; Uni r Bi directinal setting dlr) Pressure range setting SPan) Analg utput setting OUP) Respnse time setting FILt) Unit will then revert back t nrmal perating mde. P buttn fr apprx. 5 sec. the display will blink until CONF appears. After blinking the unit will stp n dlr which prmpts yu t set the directinal range f the unit. Hld the ZERO/CONFIG buttn dwn fr and the display will blink after blinking-unit will stp n previusly selected directin range Push the ZERO/CONFIG buttn dwn quickly t tggle between BI and UnI Determine if yu want Uni r bidirectinal settings - after the determinatin is been made hld the ZERO/CONFIG buttn dwn fr - until the display blinks BI r UnI will nw blink verifying which mde was chsen dlr will reappear n the display signifying that the unit has been set fr that parameter Push the ZERO/CONFIG buttn quickly. SPAn will appear which prmpts yu t set the pressure range f the unit. Hld the ZERO/CONFIG buttn dwn fr and the display will blink after blinking-unit will stp n the previusly selected pressure range Push the ZERO/CONFIG buttn dwn quickly t tggle between fur different ranges available n the prduct Determine what pressure range is required- after the determinatin is been made hld the ZERO/CONFIG buttn dwn fr The pressure range will nw blink verifying which mde was chsen SPAn will reappear n the display signifying that the unit has been set fr that parameter Push the ZERO/CONFIG buttn quickly OUP will appear which prmpts yu t set the analg utput f the unit. Hld the ZERO/CONFIG buttn dwn fr and the display will blink after blinking-unit will stp n the previusly selected analg utput Push the ZERO/CONFIG buttn dwn quickly t tggle between three different utput ranges available n the prduct Determine what analg utput is required- after the determinatin is been made hld the ZERO/GONFIG buttn dwn fr The utput chsen will nw blink verifying which mde was chsen OUP will reappear n the display signifying that the unit has been set fr that parameter Push the ZERO/CONFIG buttn quickly. FILt will appear which prmpts yu t set the respnse time f the prduct. Hld the ZERO/CONFIG buttn dwn fr and the display will blink after blinking-unit will stp n the previusly selected respnse time Push the ZERO/CONFIG buttn dwn quickly t tggle between fur different respnse ranges available n the prduct Determine what respnsiveness is required- after the determinatin is been made hld the ZERO/CONFIG buttn dwn fr The respnse time will nw blink verifying which mde was chsen FILt will reappear n the display signifying that the unit has been set fr that parameter At this time, yu have cmpleted the selectin f all settings fr the prduct. Push the ZERO/CONFIG buttn quickly. dne will appear which prmpts yu t set the cmpleted settings Hld the ZERO/CONFIG buttn dwn fr and the display will blink after blinking-unit will tggle thrugh all the selectins that have been made in sequence and will then revert back t nrmal peratin. Tel: +44 0) 1732 861200 - E-mail: sales@sntay.cm - Web: www.sntay.cm 2012 Sntay Limited. All rights reserved
Date f Issue: 06/01/2015 Page 5 f 5 -S Static Prbe Optin: 1. Screw the ptinal static prbe int the base f the husing see fig.1) and release the snap-fit lid, by gently squeezing the lcking tab. 2. Carefully remve the red pressure hse frm the prt marked BASE PORT and place n the DUCT PROBE pressure nipple see fig. 2). 3. Fix the husing t the duct in a suitable lcatin with apprpriate screws then prceed with installatin instructins frm 4 frm sectin Cnnectins n previus page. Fig. 1 Fig. 2 Duct Fixing Kit: -65-x, i/d plastic tubing, 2 x pitt tubes and 4 x fixing screws. Pitt tube dimensins; 6.3mm 0.25") Ø 25.5mm 1") Ø3mm 0.12") 78mm 3.07") Ø 3.3mm 0.13") 59mm 2.32") 45 Tubing: It is recmmended fr best results shrtest respnse times) 6mm i/d tubing lengths up t 30.5m 100 ft) 7mm i/d tubing lengths up t 91.5m 300 ft) 9.5mm i/d fr tubing lengths up t 274m 900 ft) Whilst every effrt has been made t ensure the accuracy f this specificatin, Sntay cannt accept respnsibility fr damage, injury, lss r expense frm errrs r missins. In the interest f technical imprvement, this specificatin may be altered withut ntice. Tel: +44 0) 1732 861200 - E-mail: sales@sntay.cm - Web: www.sntay.cm 2012 Sntay Limited. All rights reserved