Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels

Similar documents
Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel

Installation, Operation and Maintenance Instructions Buffer Vessel OM006

Installation, Operation and Maintenance Instructions for Pacific PA Non-Storage Heat Exchanger

Installation, Operation and Maintenance Instructions for Chemical Dosing Pots

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Vertical Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks

Horizontal Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks

Model MTB-ASME Horizontal Bladder Tanks

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

Cast iron swing check valve. BS EN 12334:2001 PN16

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

ENERGY BLADE 3K4. Energy Blade Installation Instructions

Eaton Filtration, LLC

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

SCA Series Inverted Bucket Steam Traps

TSS21 Sealed Thermostatic Steam Tracer Trap

TITAN FLOW CONTROL, INC.

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

TP1 and TP2 Temporary Cone Shaped Strainers

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

Engineering Data Sheet

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

UNVENTED HOT WATER SYSTEMS HAVE BECOME EXTREMELY POPULAR FOR BUILDING APPLICATIONS. WITH ALL THE MANDATORY

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

FV Flash Vessel Installation and Maintenance Instructions

Eaton Filtration, LLC

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

Pilot Operated Pressure Reducing Valve

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

Spirax Compact FREME Flash Recovery Energy Management Equipment

AVM7 Stainless Steel Thermostatic Air Vent

Installation / Operation / Maintenance Manual KLINGER Reflex Level Gauge Type R 25

Ductile iron gate valve PN16. BS EN 1171:2002 PN16

WORCESTER GREENSTORE. Indirect Unvented Cylinder with Solar Coil FOR USE WITH WORCESTER GREENSTORE SYSTEM HEATPUMP ONLY GB/IE

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

ST 18 Aluminium Gas Model

Size : Ends : Min Temperature : Max Temperature : Materials : Cast iron body

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

WHEATLEY Series 500 Swing Check Valve

ST 18 Aluminium Gas Model

BUTTERFLY VALVES Series 800

553 Series.

GESTRA Steam Systems AK 45. Installation Instructions Condensate Drain Valve AK 45

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

MEGAFLO Eco. Technical data FOR THE ULTIMATE IN HOT WATER PERFORMANCE AND COMFORT

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

INSTALLATION, MAINTENANCE & OPERATING INSTRUCTIONS 2-4 REDUCED PORT/ FULL PORT (5700/6700) ANSI CLASS 150/300/600/900/1500/2500 TRUNNION BALL VALVES

AVC32 Carbon Steel Air Vent for Steam Systems

SRV66 Sanitary Pressure Reducing Valve

Dri-Line Mk3 Monnier Compressed Air Drain Trap

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems.

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

Renewables. Tribune HE Unvented Hot Water Cylinders Installation and Maintenance Instructions. Issue 17 July 2012

Atmospheric relief valve type 1100 Installation and maintenance instructions

M03 WUNDATRADE. Heat Pump Manifold. Before you start: Check the contents. Optional. ...a division of WUNDA GROUP PLC

WKM Model 320F Floating Ball Valve

CA10S, CA14 and CA14S Air and Gas Traps

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

DF1 and DF2 Diffusers

MODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL

776 Cryogenic Safety Valve

Manual Actuated Boiler Blowdown Valves

GUIDELINES. Systems. Pressure. Guidelines Acceptance of equipment, establishment of safe operating limits and fitness for service

Spilt body Flange ball valve. TC-205MFF-PN1640 User Manual English Version. Document No: TC-205MFF-PN1640.Ur-manual. Date: 2007/04/2617. Version: 1.

Installation and commissioning instructions 255 series and 256 series

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual

Speed control assembly model A-1

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

VAD Variable Area Desuperheaters

DCV6 Disc Check Valve

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

Deluge Optimo Shower valve and kit 10032CP

SRV2S Pressure Reducing Valve

Transcription:

OM003 Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels The operating and maintenance instructions contained within this package are for standard storage vessels (vessels for use in a secondary system with a separate heat supply). Please refer to separate instructions for calorifiers and indirect cylinders. Rev Date By Details A 20/11/12 SR Revision Details

Contents 1.0 Standard Unit Information and Description 3 2.0 PED Information. 4 3.0 Installation 5 4.0 Commissioning and Operation. 6 5.0 Maintenance 7 6.0 Recommended Spares.. 8 [T:\gms\Word\GMSO&M\Word Format\OM003.doc] Page 2

1.0 Standard Unit Information & Description Standard sizes range from 230 litres to 9000 litres, with other sizes available to order. These are used to store water which has been heated externally to the vessel. The vessel may include an internal electric heater for backup purposes. These vessels are not suitable for storage of gases and appropriate arrangements must be made by the installer to ensure venting (via pipework or other means) of any air or other gases from the vessel. The vessels are designed for the storage of Domestic Hot Water but other applications, with different water temperatures, may also be permitted if specifically agreed by us for a given vessel. A choice of materials of construction is available. This manual covers types CS, CL, GS, SS, PL & VL vessels. Standard Material Options Schedule Shell Copper (CS) Copper-Lined Steel (CL) Galvanised Steel (GS) Stainless Steel (SS) Poly-Glass-Lined Steel (PL) Vitreous-Enamel-Lined (VL) (Other materials on request) Design Data Design Pressure Test Pressure Design Temperature Design Code Shell Side Refer to Vessel Nameplate Refer to Vessel Nameplate Refer to Vessel Nameplate Refer to Vessel Nameplate Please refer to our brochure for standard connection and dimensional data. [T:\gms\Word\GMSO&M\Word Format\OM003.doc] Page 3

2.0 PED Information The standard range of storage vessels are designed in accordance with the requirements of the Pressure Equipment Directive 97/23/EC. Units classed as SEP in the PED category are not supplied with a CE mark. Units in category I, II, III, IV are CE marked and appropriate markings and certification is supplied with each unit. It is the responsibility of the user and/or installer to ensure that the vessel is installed and operated safely, within its pressure and temperature limitations, and in accordance with these instructions. [T:\gms\Word\GMSO&M\Word Format\OM003.doc] Page 4

3.0 Installation Lifting & Handling: Use lifting eyes where fitted. Do not lift a vessel using the insulation (if fitted). Straps may crush the insulation. The shell of the vessel may be made of relatively light gauge metal and care should be exercised when handling and moving the unit not to damage the shell. Do not lift the vessel using chains directly in contact with the shell. Do not allow operatives to stand on the vessel Siting: Unless specifically ordered for outside siting, the vessel must be sited indoors. Foundations must be firm and level to prevent settling, pipe strain or distortion of the vessel. Unless specifically ordered differently, the vessel should be installed in a level position. For vessels with inspection openings ensure enough room exists to gain access to the opening. Protective covers/plugs may be fitted to connections to protect them in transit. These must be removed prior to use. If a connection is not required seal it appropriately. Check for and remove any foreign material, which may have got into the vessel. Pipe-work connected to the calorifier should be supported to prevent loads being transmitted to the vessel. Provide for thermal expansion with bends and expansion joints. To avoid corrosion do not use copper pipework with galvanised steel vessel or vice-versa. Fit isolation valves prior to vessel connections (NOT TO THE VENT) to facilitate servicing. For flanged connections tighten bolts in a diametrically opposite sequence to load the flanges evenly onto the gasket. For screwed connections use a thread sealant approved for use with potable water by the local water authority. The vent must not be blocked so, if the unit may need to be isolated from the vent, fit a 3-way vent valve. Ensure adequate venting for air removal during filling and operation. Fit a suitable Pressure Relief Valve ( Safety Valve ) to prevent overpressure. It is recommended to fit suitable pressure and temperature gauges. Destratification Pumpset To avoid damage in transit the pipe-work and pump of a de-stratification set (if included) may be supplied loose for fitting on site. The pump should be installed to circulate water from the top of the cylinder to the bottom. To ensure that the anti-stratification pump does not adversely affect performance of the calorifier during peak demand periods the power supply to the pump should be timed to come on during periods of low demand if possible, but often enough to guarantee heating the calorifier contents fully for a period of at least 1 hour per day. The unit should be flushed thoroughly with clean water prior to operation. Vessels on Unvented Systems. Special arrangements are required to prevent excessive pressure and temperature and formation of vacuum. This will include supplying and fitting suitable Pressure Relief Valve, Temperature Relief Valve, Expansion Vessel, Anti-Vacuum Valve, Control Thermostat, High Temperature Cut-Out and associated equuipment and also other equipment, if required such as a pressure regulating valve. The arrangements required are detailed in UK building and water regulations. Please see our separate leaflet on unvented systems for details. [T:\gms\Word\GMSO&M\Word Format\OM003.doc] Page 5

4.0 Commissioning and Operation Do not operate the equipment at pressures or temperatures in excess of those specified on the nameplate of the vessel marking. Do not subject the equipment to conditions of vacuum or partial vacuum. This is particularly vital for copper-lined steel vessels, which are supplied complete with anti-vacuum valve - which must not be removed. For example partial vacuum can be caused if the system connections or the vent are restricted during draw off or drain down. Open the system isolation valves carefully to avoid pressure surges Check that all gaskets are effective when the unit is operating - some bolt tightening may be necessary after the unit has been first pressurised and subsequently from time to time. Following installation and commissioning it is advisable to remove, clean and re-assemble any strainers. All fluids must be drained when the unit is out of operation to prevent freezing or possible corrosion. [T:\gms\Word\GMSO&M\Word Format\OM003.doc] Page 6

5.0 Maintenance Annual maintenance should include cleaning debris from the base of the calorifier to comply with guidelines on prevention of legionella bacteria proliferation. Also the site insurers may require annual inspection of shell condition. To drain the vessel down Obtain a complete set of replacement gaskets from GMS Thermal Products Ltd. It is assumed here that all isolation valves (except drain) are open at the start. For copper-lined steel vessels, ensure that the anti-vacuum valve is not stuck shut - also ensure that a vent is available at the top of the calorifier of flow area at least one half the flow area of the drain connection. Partial vacuum, caused by inadequate venting of copper-lined calorifiers during drain-down, will cause damage to the thin copper lining. If the vessel is open vented and shares a vent with other calorifiers, isolate it from the common vent using the 3-way valve (it will now vent to atmosphere). Isolate power to any backup immersion heater. Pipe the drain to a drain point and open the drain valve to fully drain the unit. Some vessels have a drain connection a short distance up the side and a small volume of water may need to be pumped out through the inspection opening. The shells internal condition can be inspected by removing the inspection cover to allow visual examination. The vessel is a confined space take suitable precautions if working inside it. Re-fit new gaskets and re-fill the calorifier according to the commissioning instructions above. Sacrificial Anodes Some vessels are fitted with sacrificial anodes to reduce corrosion. The anode corrodes instead of the vessel metal. The anodes need to be replaced periodically to ensure protection is continuous. Some enamel lined vessels have an anode condition meter on the top for easy checking. This should be checked by pressing the test button when the vessel is full of water. If the gauge shows goes to green then the anode is in good condition. When there is no test meter the anode should be checked after 6 months operation then periodically depending on rate of corrosion. It should be replaced when thickness has been reduced by 40% from the original. [T:\gms\Word\GMSO&M\Word Format\OM003.doc] Page 7

6.0 Recommended Spares Please contact our sales department for recommended spares prices and availability. The recommended quantities given are per unit supplied. Description Quantity Part Ref. Inspection Gasket 1 Contact us, quoting vessel serial number from data plate Sacrificial Anode 1 Contact us, quoting vessel serial number from data plate [T:\gms\Word\GMSO&M\Word Format\OM003.doc] Page 8

OM003 ` Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail: sales@gmsthermal.co.uk Riverside Works, Egmont Street, Mossley [T:\gms\Word\GMSO&M\Word Format\OM003.doc] Ashton-Under-Lyne, Page OL5 9NE